Emerson Copeland Scroll, XJAM-002, XJAL-002, XJAM-012, XJAL-012 Installation And Reference Manual

...
Copeland Scroll® Outdoor Condensing Unit
Installation and reference manual
Application Engineering
BULLETIN
Application Engineering
AE5-1377 R2
BULLETIN
®
Copeland Scroll
Introduction .........................................................................................................2
Nomenclature/Features......................................................................................2
Performance Data ...............................................................................................2
Electrical/Physical Data/Sound Data/BOM Details ..........................................2
Generator Requirements ...............................................................................2
Physical Dimensions..........................................................................................2
Installation/Piping Instructions .........................................................................2
Condensing Unit Operational Control ..............................................................3
Control Features .................................................................................................3
Fresh Start Program ......................................................................................3
Stop Program .................................................................................................3
Automatic Liquid Injection ..............................................................................3
Compressor Phase Reversal .........................................................................3
Loss of Phase Protection ...............................................................................3
Motor Current Overload .................................................................................4
Non-Adjustable High and Low Pressure Switches ........................................4
Non-Adjustable High Pressure Control .......................................................4
Non-Adjustable Low Pressure Control ........................................................4
Adjustable Low Pressure Switch ...................................................................4
Liquid Floodback Protection ...........................................................................4
Crankcase Heater ..........................................................................................4
Condenser Fan Speed Control ......................................................................4
Enhanced Vapor Injection (EVI) Control ..........................................................4
Electronic Expansion Value (EXV) .................................................................4
TXV selection .................................................................................................5
Other Inputs to the Control Board ....................................................................5
Customer Supplied Control (Thermostat) ......................................................5
Other Outputs from the Control Board .............................................................5
Defrost Control Board ....................................................................................5
Evaporator Fan Control ..................................................................................5
Diagnostic Display Board ..................................................................................5
Short Cycle Protection Option ..........................................................................8
System Diagnostics/Troubleshooting Information (Table 9) ........................15
Sensor Information (Table 10)..........................................................................18
Wiring Diagrams
XJAM/XJAL Single Fan CFV-002 and -012 Models ........................................... 21
XJAM/XJAL Single and Dual Fan TFC-002 and -012 Models ...........................22
XJAM/XJAL Dual Fan CFV-002 and -012 Models ............................................23
XJAM/XJAL Single Fan CFV-022 Models .......................................................... 24
XJAM/XJAL Single and Dual Fan TFC-022 Models ........................................... 25
XJAM/XJAL Dual Fan CFV-022 Models ............................................................. 26
On Board -022 Bom Defrost Schematic ..........................................................27
APPENDIX:
One Way Communication Board Installation Details (RS Form 026-4909) ........28
Outdoor Condensing Unit
TABLE OF CONTENTS
October 2011
© 2011 Emerson Climate Technologies Printed in the U.S.A.
1
Application Engineering
BULLETIN
Introduction
Copeland Scroll many benefi ts of scroll compressor technology, coupled with advanced diagnostic controls, to ensure reliable performance and operation in foodservice applications. Electronics are used extensively in its protection and diagnostic features. These features are controlled by an electronic integrated control board. The control board provides base control functions related to temperature controller, defrost, evaporator fan control, compressor protection e.g. current overload, phase reversal, liquid/ vapor injection control, self diagnostics and warnings. These error codes can be seen by an LED display for easy and rapid troubleshooting and maintenance.
A complete product offering for medium and low temperature HFC-404A units is being offered in single and three phase 208/230 volts. The -002 and -012 BOM product is approved for operation in ambients from 120°F to -10°F. The -022 BOM is featured with the required components to operate in colder climates. See Figure 1 for details. For applications outside these guidelines, please contact Application Engineering.
Nomenclature/Features See Figure 1 (page 6).
Understanding Actual vs. Standard Airfl ow
T o choose the proper coil for your application, the density of the incoming air needs to be known to calculate the actual capacity and performance of the system.
A coil’s required capacity can be calculated using the thermodynamic equation
Q = M x Delta hr
Q = Heat transfer to or from the air (Btuh) M = Mass fl ow rate of air (lb/hr) Delta h = Difference between the entering and leaving
air enthalpy or total heat (Btu/lb)
The mass fl ow rate is equal to the density of air times the face area of the coil times the velocity of the air at the coil or face velocity.
M = P x A x V P = Density (lb/ cubic ft.) A = Face area of coil (square ft.) ~ Fin height x fi n length V = Air Velocity (ft./min.)
For temperature conversions
®
outdoor condensing units provide the
( )=
+
Temperature Conversion Factors
Temp
(degrees F)
0 1.15 60 1.02 10 1.13 70 1.00 20 1.10 80 .98 30 1.08 90 .96 40 1.06 100 .95 50 1.04 110 .93
Altitude Conversion Factors (A2)
Alt.- Ft. Factor- A2 Alt.- Ft Factor- A2
0 1.00 3000 .895 500 .982 4000 .864 1000 .965 5000 .832 1500 .947 6000 .802 2000 .930 7000 .771 2500 .912 8000 .743
SCFM= CFM X A1 X A2 Note: all calculations and ratings are based on standard
air at 70°F dry bulb temp and 29.92 Hg atmospheric pressure (sea level). These tables convert non standard cfm to standard cfm.
Performance Data See Tables 1 and 2 (page 10).
Electrical / Physical Data
See
Table 3
Generator Requirements
In situations or locations were an electrical power generator could be applied in the event of a power outage, the Copeland Scroll® outdoor condensing unit will operate providing the generator will provide a supply voltage range of 180-260 VAC along with a frequency of 47-63 Hz. The electronics control along with the power board will function properly providing the range of operating limits is in compliance!
Physical Dimensions See Figure 2 (page 7).
Installation / Piping Instructions
See Figure 2 for overall dimensions of the units. It is recommended that a clearance of 8 inches from the
Factor A1
(page 11).
Temp
(degrees F)
Factor A1
© 2011 Emerson Climate Technologies Printed in the U.S.A.
2
Application Engineering
BULLETIN
wall (or the next unit) be maintained from the unit’s left and rear panel whereas a clearance of 20 inches is to be maintained from the unit's right, top and front panels. Both service access and airfl ow have been considered in making these recommendations. Where multiple units are to be installed in the same location, careful consideration for proper clearance needs to be given to each individual unit.
Ideally, the unit should be mounted level on a solid concrete slab with rubber strips between unit feet and concrete. However, these units have been designed for mounting on suitable brackets for wall mounting. In this case it is equally important that the spatial guidelines given above are followed, and additional consideration needs to be given for possible air recycling if units are stacked above and below each other. In general terms, air by-pass around each condenser and between each unit should be avoided at all times.
Pipe sizing should not only be of suffi cient size to ensure optimum performance and good oil return, but it also needs to take into account the full capacity range through which this particular unit will need to operate. Follow the ASHRAE guidelines for proper piping practices.
Condensing Unit Operational Control
The Digital Control electronic control board controls the operation of the condensing unit. Whenever there is a control input asking to start or stop the condensing unit, the control board will execute a set of pre-programmed procedures to do so. It also monitors the compressor operating parameters, so as to protect the system from unsafe operating parameters. See Figure 3 (page 8).
For example, when the low temperature unit experiences an extreme temperature day , the control board decides to switch from vapor-injection-optimization to discharge gas temperature control to allow the compressor to run safely and pass the extreme weather hours.
Control Features
The base control function is for the following standard features. See Figure 3 for additional input options and output options of the control board.
Fresh Start Program
This Fresh Start Program is a bump start procedure that will energize and start the compressor for 3 seconds and then will be followed by a 20 second off cycle time. This will occur for 3 cycles, and then continuous power will be supplied to the compressor for normal operation.
The Fresh Start Program will be executed on initial start up or any time power is reapplied when the ambient
temperature is lower than 95°F. In addition, the Fresh Start Program will be executed for any start when the unit has been cycled off for more than an hour when the ambient temperature is lower than 95°F.
Stop Program
When the unit is satisfi ed, or there is any error which requires the unit to be shut down, the controller will execute a Stop Program. The compressor and the condenser fans will cycle off and the injection valves will close.
For low temperature units only, when the unit is satisfi ed the EXV will start closing immediately, but the compressor will delay 5 seconds before shut down to prevent reverse rotation of the compressor.
Automatic Liquid Injection (Medium temperature units only)
Automatic Liquid Injection ensures that the scroll compressor operates within a safe temperature limit. This unit employs a patented liquid injection system which injects a saturated refrigerant into the suction line at the compressor. Activation of the liquid injection valve is in response to a thermistor which is attached to the compressor discharge line. A signal is sent to the stepper motor of the injection valve, opening the valve in response to increasing discharge temperatures and injecting saturated refrigerant to reduce the discharge temperature.
Compressor Phase Reversal
Compressor Phase Reversal senses for the correct phase sequence on three phase applications. Reset is automatic once the correct phase sequence is sensed. An error message will be shown on the diagnostic LED.
Loss of Phase Protection
If three phase supply is incorrectly connected to the contactor terminals, or if a missing phase is sensed, an error message will be shown on the diagnostic LED. Reset is automatic once the correct phasing is sensed.
Motor Current Overload
All scroll compressors used in these condensing
units have an internal inherit motor protector.
The Copeland Scroll Outdoor Condensing Unit is
also equipped with two current sensors (CT1, CT2) to monitor the electrical current of the condensing unit. If the condensing unit current exceeds a pre­defi ned current limit, the controller will take the following actions:
Stop the compressor for 3 minutes
© 2011 Emerson Climate Technologies Printed in the U.S.A.
3
Application Engineering
BULLETIN
LED signal will display an Over Current Error
for 3 minutes
After a 3 minute delay the compressor will go
through a normal start
The system will lock out after 6 over current
trips within an hour
For this function to operate, two of the power leads are routed through the current sensing coils (CT1, CT2), prior to the contactor, from the factory. See Figure 3.
Non-Adjustable High Pressure Control
This pressure sensing device is a nonadjustable, low voltage pressure switch that will open at 435psig and reset at 348psig in the event of high discharge pressure. Its signal is monitored by the control board.
In the event of a high pressure trip, the unit will stop
and then restart after a 3-minute delay.
After 6 successive HP cut-outs within 1 hour, the
unit will lock-out.
The lockout feature can be reset by disconnecting
the power source and then cycling power to the unit.
Adjustable Low Pressure Switch
An adjustable low pressure switch is provided as standard equipment on both the medium and low temperature condensing units. This control can be used for a pump-down cycle if so desired. See T able 8, Low Pressure Control Settings (page 13). No error message will be shown for this adjustable control.
Liquid Floodback Protection
Liquid refrigerant entering the compressor during
the run cycle, in excessive quantities, can damage the compressor by diluting the lubricant, as well as excessive stress on several components in the compressor. Proper control of liquid refrigerant within the system is an application issue and is beyond control of this controller. However, the controller can perform checks and alert the user that liquid refrigerant fl oodback may be occurring and immediate fi eld service is required. This is only a warning signal and will not terminate the operation of the unit. See Tables 6 and 6a (page
13).
Liquid Floodback Protection is acquired by
monitoring the compressor discharge temperature. When the discharge line temperature falls below a specifi ed point, low suction line superheat may be the cause.
Crankcase Heater
The crankcase heater is wired through a normally closed
contact of the compressor contactor which is energized whenever the compressor cycles off.
Condenser Fan Speed Control
The Condenser Fan Speed Control will vary the speed of the condenser fan motor for head pressure control under low ambient conditions. There are two thermistor type sensors that are connected to the control board. These sensors monitor the condenser mid coil temperatures and ambient air temperatures to control the fan speed.
Enhanced Vapor Injection (EVI) Control (Low temperature units only)
The EVI system improves low temperature operational effi ciency and provides a reliable low temperature envelope. It is used to optimize performance and to prevent the scroll set from overheating. This is done by controlling the discharge line temperature (DLT) and vapor injection superheat (VISH).
Enhanced vapor injection is accomplished by utilizing a subcooling circuit. A heat exchanger is used to subcool the liquid refrigerant before it enters the evaporator. As a result of the subcooling done by the heat exchanger, refrigerant will also be evaporated. This evaporated refrigerant is then injected into the mid compression cycle of the scroll compressor for overheat temperature control.
There are two thermistors sensing the discharge line temperature, one is located at the discharge line of the compressor and the second one is placed at the inlet of the condenser coil. In order to have a higher temperature resolution, the discharge line thermistor and condenser coil inlet sensor cooperate to sense a temperature range from 50°F to 329°F . The discharge line thermistor has a sensing range from 163°F to 329°F and the condenser coil will sense temperature from 50°F to 176°F . The EVI system will keep the discharge line temperature below 230°F to ensure the safety of the compressor.
It is important to insulate the system liquid line from the condensing unit to the evaporator. The recommended insulation thickness is a minimum of ½ inch. Also the lower liquid temperature can increase the evaporator expansion valve capacities. Please follow the valve manufactures recommended liquid temperature correction factors for proper selection of the evaporator expansion valve.
Electronic Expansion Value (EXV)
The Electronic Expansion Value (EXV) is a key part of the EVI system. It will regulate vapor injection fl ow to optimize the performance of system and cool the scroll set. Every second, the control chip will collect the
© 2011 Emerson Climate Technologies Printed in the U.S.A.
4
Application Engineering
BULLETIN
thermistors reading and do a four second averaging. The EXV opening will be changed every 20 seconds and the variation is calculated by different ways based on different purposes.
TXV selection
For EVI, Emerson recommends a balanced port TXV because it offers a wider operating range for fl oating liquid temperatures.
See Table 7 (page 14) for specifi cs regarding balanced port sizing recommendations. Applied with the low temp units it is recommended that a balanced port expansion valve be used along with a complete review of the the distributor & nozzle (orifi ce) that is supplied with the Evaporator coil being matched with the applicable condensing unit. Typically nozzles are selected for standard TXV sizing using 100°F liquid, with the XJAL those typical selections could be grossly oversized. See
Table 7 for the liquid correction safety factors when
selecting those components.
Other Inputs to the Control Board Customer Supplied Control (Thermostat)
The control board will accept a normal 220 volt AC input ON/OFF signal such as the switching action of a normal commercial thermostat and relay. If the system is controlled by low pressure control for a multiple evaporator system and/or pump down system, the control board will accept the signal directly from the control. See Wiring Diagrams, pages 21-24, for proper installation.
Other Outputs from the Control Board Defrost Control Board
The defrost control board is a basic time initiated module which is standard on the low temperature units and is an add on feature for the medium temperature units. The defrost control board can control either off-cycle or electric defrost.
The defrost control board will control the liquid line solenoid valve. When defrost is initiated the liquid line solenoid valve will close and the unit will go into a pumpdown cycle. When the suction pressure equals the setting of the low pressure control, the compressor will cycle off. After the defrost time has expired, the liquid line solenoid valve opens and then the low pressure control will allow the compressor to restart.
Due to heater amperage loads, electric defrost requires an additional relay or contactor to energize the defrost heater.
The defrost cycle can be executed either automatically or manually . There are two rotary dip switches by which the user can set up the defrost cycle, see Figure 4. One rotary dipswitch sets the defrost duration (SW1) and the second rotary dipswitch sets the time interval between defrost cycles (SW2). For automatic defrost set SW1 and SW2 as desired. See Table 4 (page 11) for time settings. The defrost control board also incorporates a manual defrost button that enables a manual defrost as an override to the rotary switch setting the defrost interval. Upon the completion of a manual defrost, the system will reset to the refrigeration cycle with the same procedures as automatic defrost and then the automatic defrost timer will reset.
For setting manual defrost only set SW1 as desired and set SW2 to “0”. Whenever the manual defrost button is pressed, one defrost cycle will be executed and the duration of defrost will be determined by the setting of the rotary dipswitch SW1.
Note: There is no method to terminate a defrost cycle without resetting the control board.
Table 4 lists rotary dip switch settings for the Defrost Control Board.
An ON/OFF output connection is provided on the control board (JP10) for direct connection of a customer supplied contactor coil/relay when the defrost option is used. T erminals are male spade type. Coil voltage rating should be 220V AC and current ratings, 30V A (hold) and 330VA (inrush). See Figure 6 (page 9).
For customers using their existing defrost timer, remove the defrost cable connecting the defrost control board to the unit control board. Also on the unit control board change the mode setting dip-switch bit 2 to ON and proceed to standard defrost wiring. See Table 5 (page 12)
Evaporator Fan Control An ON/OFF output connection is also provided on the
control board (JP9) for direct connection of a customer supplied contactor coil controlling the evaporator fans. Terminals are the male spade type. Coil voltage rating is to be 220VAC and a maximum power rating of 30VA (hold) and 330VA (inrush). See Figure 6.
Diagnostic Display Board
Each condensing unit is supplied with a diagnostic display board, see Figure 5 (page 13). A two character display will make up the diagnostic/error code. The fi rst character will display the unit status as shown in Table
6. The second character will display the error/warning
© 2011 Emerson Climate Technologies Printed in the U.S.A.
5
Application Engineering
BULLETIN
XJAM XJAL XJAM XJAL XJAM XJAL
-002 -002 -012 -012 -022 -022
Fan Motor Variable Variable Variable Variable Variable Variable
Head Pressure Control VS VS VS VS VS VS
Service Valves Brass Brass Brass Brass Brass Brass
Receiver X X XXXX
Liquid Shut O X X XXXX
Filter Dryer X X XXXX
Fixed HP X X XXXX
Adjustable LP X X XXXX
Diagnoscs X X XXXX
Accumulator X X X
Oil Seperator X X X
3 Minute An-Short Cycling X X XXXX
Low Pressure Bypass Time Delay X X
Over Current
X X XXXX
Incorrect Phase Rotaon
X X XXXX
"Smart" CCH
X X XXXX
Compressor Overheang
X X XXXX
Remote Alarming
code as shown in T able 6a. See Figure 5 for a detailed view of the diagnostics board assembly.
The Main Board Connector terminal will accept the cable connecting the display board to the main control board.
Family X-Line
J = R404A
A = Air-Cooled
M = Medium Temp L = Low temp
Z = Scroll
X J A M - 0 2 0 Z - T F C - 0 0 2
1.5 to 6.0 = Nominal Hp
BOM
Hood X X XXXX
The Reset Button will reset the diagnostic display board only. The Message Recall Button will display the last error signal received by the display board. See Figure 5.
CFV = 208/230V-1ph-60Hz TFC = 208/230V-3ph-60Hz
0 = UL Listed Product
Model Variation 0 Base Unit 1 Communication/ Defrost Module 2 Low Ambient / On Board Defrost Relays
Moisture Indicator X X X X X X
CCH X X X X X X
FeaturesDiagnoscs
Defrost mer X X X One Way Communicaon XXXX
20 Second An-Short Cycling Opon X X X X Defrost mer w/ Relays X X Heated Insulated Receiver X X
Liquid Flood-Back Predicon "Fresh" Start Logic
Compressor Short Cycle Fault Code History
X X XXXX X X XXXX
X X XXXX X X XXXX X X XXXX
Figure 1 – Nomenclature and Features
© 2011 Emerson Climate Technologies Printed in the U.S.A.
6
Application Engineering
BULLETIN
MODEL
SINGLE FAN UNIT 40.51" 33.07" 16.69" 22.84" 15.28" 3/4" 1/2" 12" 20" 8" 20" 20"
DUAL FAN UNIT 40.51" 48.90" 16.69" 22.84" 15.28" 7/8" 1/2" 12" 20" 8" 20" 20"
WIDTH HEIGHT DEPTH MTG. CENTERS CONN. SIZE INSTALLATION CLEARANCES
W H D X Y Suction Liquid a b c d e
Figure 2 – Physical and Installation Requirements
© 2011 Emerson Climate Technologies Printed in the U.S.A.
PHYSICAL DATA
7
Application Engineering
BULLETIN
3-Phase Power
Supply Input
3-Phase Detect
Module
Compressor Current Sensing
(Hi/Lo) Setting Dip-Switch
Current Transformers
MCU
Temperature Sensors
Compressor Type Setting Rotary-Switch
High Pressure Switch Connector
Short Cycle Protection Option
*See Note
Defrost Module Connector
EXV Driver
Diagnosis Module Connector
Switch Mode
Power Supply
1-Phase Power
Supply Input
High Voltage
Outputs
Figure 3 – Power Board / Control Board
* Note: Short Cycle Protection Option
a) Factory Jumper Installed Three Minute Time Delay b) Remove Jumper Twenty Second Time Delay
Mode Setting
Dip-Switch
© 2011 Emerson Climate Technologies Printed in the U.S.A.
8
Application Engineering
BULLETIN
Manual Defrost
Button
Remote Manual
Defrost Button
Connector
Defrost Control Module
Defrost Duration
Switch SW1
Main Board
Connector
Figure 4
2 Digit LED display
Defrost Duration
Switch SW2
Reset Button
Message Recall Button
Main Board Connector
Emerson-Supplied Defrost Module Requirements Utilized on Bom's -002/-012
Defrost Wiring
Figure 5
Diagnostics Module
Figure 6
Emerson Supplied Defrost
© 2011 Emerson Climate Technologies Printed in the U.S.A.
9
Application Engineering
BULLETIN
Table 1
Medium Temp Performance Criteria
H.P.
1.5 XJAM-015Z-CFV 14600 13600 R404A / POE
H.P.
Medium Temperature
Model Number
2 XJAM-020Z-CFV 19600 17900 R404A / POE 2 XJAM-020Z-TFC 19600 17900 R404A / POE 3 XJAM-030Z-CFV 28500 25900 R404A / POE 3 XJAM-030Z-TFC 28500 25900 R404A / POE 4 XJAM-040Z-CFV 38600 35300 R404A / POE 4 XJAM-040Z-TFC 38600 35300 R404A / POE 5 XJAM-050Z-CFV 47100 43800 R404A / POE 5 XJAM-050Z-TFC 47100 43800 R404A / POE 6 XJAM-060Z-TFC 54600 50200 R404A / POE
Low Temperature
Model Number
Btu/hr @ +25°F Sat. Suction
Temp / 90°F Ambient
Table 2
Low Temp Performance Criteria
Btu/hr @ +25°F Sat. Suction
Temp / 90°F Ambient
Btu/hr @ +25°F Sat. Suction
Temp / 100°F Ambient
Btu/hr @ -10°F Sat. Suction
Temp / 100°F Ambient
Refrigerant/
Oil Type
Refrigerant/
Oil Type
2 XJAL-020Z-CFV 13100 12700 R404A / POE 2 XJAL-020Z-TFC 13100 12700 R404A / POE 3 XJAL-030Z- TFC 17200 16400 R404A / POE 3 XJAL-035Z- CFV 19700 18100 R404A / POE 4 XJAL-040Z-CFV 24700 23700 R404A / POE 4 XJAL-040Z-TFC 24700 23700 R404A / POE 5 XJAL-050Z-CFV 27600 25700 R404A / POE 5 XJAL-050Z-TFC 27600 25700 R404A / POE 6 XJAL-060Z-TFC 34700 32700 R404A / POE
© 2011 Emerson Climate Technologies Printed in the U.S.A.
10
Application Engineering
BULLETIN
Table 3
Mechanical / Electrical Specifi cations
Dimensions
(in)
Unit Model Compressor H.P.
L W H Suction Liquid
XJAM-015Z ZB11KCE 1.5 16.7 40.5 33 3/4 " 1/2 " 1 12.3 / 20 N/A 7.5 180 55 XJAM-020Z ZX15KCE 2 16.7 40.5 33 3/4 " 1/2 " 1 18.7 / 30 11.1 / 15 7.5 182 55 XJAM-030Z ZX21KCE 3 16.7 40.5 33 3/4 " 1/2 " 1 24.3 / 40 14.7 / 25 7.5 194 55 XJAM-040Z ZX30KCE 4 16.7 40.5 49 7/8 " 1/2 " 2 32.1 / 50 19.7 / 30 11 250 56 XJAM-050Z ZX38KCE 5 16.7 40.5 49 7/8 " 1/2 " 2 36.6 / 60 29.0 / 50 11 258 56 XJAM-060Z ZX45KCE 6 16.7 40.5 49 7/8 " 1/2 " 2 N/A 28.1 / 45 11 270 56
XJAL-020Z ZXI06KCE 2 16.7 40.5 33 3/4 " 1/2 " 1 19.4 / 30 14.7 / 25 7.5 188 50 XJAL-030Z ZXI09KCE 3 16.7 40.5 33 3/4 " 1/2 " 1 N/A 15.4 / 25 7.5 192 50 XJAL-035Z ZXI11KCE 3.5 16.7 40.5 33 7/8 " 1/2 " 1 30.7 / 50 N/A 7.5 213 50 XJAL-040Z ZXI14KCE 4 16.7 40.5 49 7/8 " 1/2 " 2 36.1 / 60 24.5 / 40 11 251 58 XJAL-050Z ZXI15KCE 5 16.7 40.5 49 7/8 " 1/2 " 2 N/A 26.1 / 45 11 267 58 XJAL-050Z ZXI16KCE 5 16.7 40.5 49 7/8 " 1/2 " 2 40.4 / 70 N/A 11 287 58 XJAL-060Z ZXI18KCE 6 16.7 40.5 49 7/8 " 1/2 " 2 N/A 30.7 / 50 11 291 58
Connection
Lines
# of
Fans
Min Circuit
Ampacity/ Max Fuse
(Amps)
208/230V 1ph-60hz
208/230V 3ph-60hz
Pump Down
Capacity
(lbs)
Unit
Weight
(lbs)
dba *
Assume Each Fan @ .75 Amps
*Estimated sound pressure values are 10 feet from the unit at 25F evap for MT and -10 evap for LT at 90 ambient. A sound reduction of up to 3 dBA will occur in ambient temperatures below 70F. This data is typical of “free fi eld” conditions for horizontal air cooled condensing units and may vary depending on the condensing unit installation. There are many factors that affect the sound reading of a condensing unit such as unit mounting, refl ecting walls, background noise and operating condition.
Switch 1 Defrost duration (minutes)
0 No defrost (manual defrost only) 1 5 minutes 2 10 minutes 3 15 minutes 4 20 minutes 5 25 minutes 6 30 minutes 7 35 minutes
© 2011 Emerson Climate Technologies Printed in the U.S.A.
Table 4
Emerson Supplied Defrost Set Points
Switch 2 Time interval between defrost
0 No defrost (manual defrost only) 1 1 hour 2 2 hours 3 3 hours 4 4 hours 5 5 hours 6 6 hours 7 7 hours
11
Application Engineering
BULLETIN
Table 5
Main Control Board Setting For XJAM
Model Name**
Control Board
Default Setting ZB11KCE-PFV A ON/ON ZX15KCE-TF5 1 ON/ON ZX15KCE-PFV 2 ON/ON ZX21KCE-TF5 3 ON/ON ZX21KCE-PFV 4 OFF/OFF ZX30KCE-TF5 5 ON/ON ZX30KCE-PFV 6 OFF/OFF ZX38KCE-TF5 7 OFF/OFF ZX38KCE-PFV 8 OFF/OFF ZX45KCE-TF5 9 OFF/OFF
Rotary Switch
0 ON/ON
Main Control Board Setting For XJAL
2bit
Dip-Switch
3bit Dip-Switch
Bit 1: To set evaporator fan control mode
- “ON”: Evaporator fan will be ON all the time no matter whether compressor is ON/ OFF or defrosting
Bit 2: To set defrost mode
- “OFF”: Using Emerson defrost module
- “ON”: Using customer defrost module Bit 3: Not used yet.
Model Name**
Control Board
Default Setting
ZXI06KCE-TF5 1 ON/ON
ZXI06KCE-PFV 2 ON/ON
ZXI09KCE-TF5 3 ON/ON
ZXI11KCE-PFV 4 OFF/OFF
ZXI14KCE-TF5 5 OFF/OFF
ZXI14KCE-PFV 6 ON/ON
ZXI15KCE-TF5 7 OFF/OFF
ZXI16KCE-PFV 8 OFF/OFF
ZXI18KCE-TF5 9 OFF/OFF
** Please set the switches to the correct position according to compressor model.
Rotary Switch
0 ON/ON
2bit
Dip-Switch
3bit Dip-Switch
Bit 1: To set evaporator fan control mode
- “OFF”: Evaporator Fan On/Off Logic Same As Compressor
- “ON”: Evaporator fan will be ON all the time no mater whether compressor is ON/ OFF or defrosting
Bit 2: To set defrost mode
- “OFF”: Using Emerson defrost module
- “ON”: Using customer defrost module Bit 3: Not used yet.
© 2011 Emerson Climate Technologies Printed in the U.S.A.
12
Loading...
+ 28 hidden pages