Emerson XCM25D User Manual

CC7.8.17/0220/E 1/22
Date of last update: Feb-20
Application Engineering Europe
COPELAND EAZYCOOL ZX CONDENSING UNITS
XCM25D CONTROLLER PARAMETER LIST
Copeland EazyCool ZX Condensing Units are equipped with an XCM25D electronic controller from Dixell. The controller design allows the installer to start and operate the system with minimum effort in terms of controller adjustments. The most important controller settings are described in the application guidelines and most likely there is no need to change those settings.
In case of special applications additional parameters might have to be adjusted according to those special needs. This document contains the full list of available parameters in the XCM25D controller. It is not a user’s manual. For questions about how to handle the controller and for functionality description please refer to the dedicated documentation available at www.climate.emerson.com/en-gb.
Legend L1 = Parameter in level 1 (without password) L2 = Parameter in level 2 (with password = 3 2 1) N.V. = Parameter not accessible
NOTE: When changing parameters C01 (Cin), C02 (CoU) and C05 (CPb) a reset of the controller (interruption of power supply) is required.
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
A01
Probe P1 configuration
Not used (0-NU) Suction pressure (0-5V)(1-SUP)
Suction pressure (0-5V)
L2
L2
L2
A02
Start of scaling for probe 1 (0-5V)
0-5V: -1.5 bar to P1E; -21 PSI to P1E
0
L2
L2
L2
A03
End of scaling for probe 1 (0-5V)
0-5V: P1i to 99.9 bar; P1i to 999 PSI
15
L2
L2
L2
A04
Probe P1 calibration
0-5V: -12.0 to 12.0 bar; -12.0 to12.0 PSI
0
L2
L2
L2
A05
Probe P1 reading error delay (P1C = 0-5V)
0 to 255 min
5
L2
L2
L2
A06
Probe P2 configuration
Not used (0-NU) Mid-coil temperature (NTC10K)(1-MCT) Mid-coil pressure (0-5V)(2-MCP)
Mid-coil pressure (0-5V)
L2
L2
L2
CC7.8.17/0220/E 2/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
A07
Start of scaling for probe 2
0-5V: -1.5 bar to P2E; -21 PSI to P2E NTC10K: -40°C to P2E
0
L2
L2
L2
A08
End of scaling for probe 2
0-5V: P2i to 99.9 bar; P2i to 999 PSI NTC10K: P2i to 110°C
35
L2
L2
L2
A09
Probe P2 calibration
0-5V: -12.0 to 12.0 bar; -12.0 to 12.0 PSI NTC10K: -12°C to 12°C
0
L2
L2
L2
A10
Probe P2 reading error delay (P2C=0-5V)
0 to 255 min
0
L2
L2
L2
A11
Probe P3 configuration
Not used (0-NU) Discharge line temperature (1-DLT)
Discharge line temperature
L2
L2
L2
A12
Probe P3 calibration
-12°C to 12°C
0
L2
L2
L2
A13
Probe P4 configuration
Not used (0-NU) Ambient temperature (NTC10K)(1-AMT) Thermostat temperature (NTC10K)(2-TMT) Vapour inlet temperature (NTC10K)(3-UIT) Vapour outlet temperature (NTC10K)(4-UOT) Evaporator temperature (NTC10K)(5-EPT) Liquid temperature (NTC10K)(6-LLT) Suction line temperature (7-SLT) Coil temperature (8-COT)
Not used
L2
L2
L2
A14
Probe P4 calibration
-12°C to 12°C
0
L2
L2
L2
A15
Probe P5 configuration
Not used (0-NU) Ambient temperature (NTC10K)(1-AMT) Thermostat temperature (NTC10K)(2-TMT) Vapour inlet temperature (NTC10K)(3-UIT) Vapour outlet temperature (NTC10K)(4-UOT) Evaporator temperature (NTC10K)(5-EPT) Liquid temperature (NTC10K)(6-LLT) Suction line temperature (7-SLT) Coil temperature (8-COT)
Not used
L2
L2
L2
A16
Probe P5 calibration
-12°C to 12°C
0
L2
L2
L2
CC7.8.17/0220/E 3/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
A17
Probe P6 configuration
Not used (0-NU) Ambient temperature (NTC10K)(1-AMT) Thermostat temperature (NTC10K)(2-TMT) Vapour inlet temperature (NTC10K)(3-UIT) Vapour outlet temperature (NTC10K)(4-UOT) Evaporator temperature (NTC10K)(5-EPT) Liquid temperature (NTC10K)(6-LLT) Suction line temperature (7-SLT) Coil temperature (8-COT)
Ambient temperature (NTC10K)
L2
L2
L2
A18
Probe P6 calibration
-12°C to 12°C
0.0
L2
L2
L2
A19
Probe P7 configuration
Not used (0-NU) Ambient temperature (NTC10K)(1-AMT) Thermostat temperature (NTC10K)(2-TMT) Vapour inlet temperature (NTC10K)(3-UIT) Vapour outlet temperature (NTC10K)(4-UOT) Evaporator temperature (NTC10K)(5-EPT) Liquid temperature (NTC10K)(6-LLT) Suction line temperature (7-SLT) Coil temperature (8-COT)
Not used
L2
L2
L2
A20
Probe P7 calibration
-12°C to 12°C
0
L2
L2
L2
A21
Delay before activating probe error
0 to 255 sec
0
L2
L2
L2
B01
Measurement unit for pressure
Bar (0-BAR) – PSI (1-PSI) – KPA (2-TPA)
bar
L2
L2
L2
B02
Measurement unit for temperature
°C (0-C)
°C
L2
L2
L2
B03
Remote display visualization
P1 (0-P1) - P2 (1-P2) - P3 (2-P3) ­P4 (3-P4) - P5 (4-P5) - P6 (5-P6) ­P7 (6-P7) – Per (7-PER) – Aou (8-AOU)
P1
L2
L2
L2
B04
Filter enabling for probe reading
n (0-NO) - Y (1-YES)
YES
N.V.
N.V.
N.V.
B05
Coefficient for probe reading filter (0 = max,100 = disable)
0 to 100, mEd (101)
50
N.V.
N.V.
N.V.
C01
Compressor cut-in pressure setpoint
CoU to US
4
N.V.
L1
L1
C02
Compressor cut-out pressure setpoint
LS to Cin
2
L2
L1
L1
C03
Minimum setpoint for suction pressure/temperature
P1i to US; -50.0°C to US
0.6
L2
L2
L2
CC7.8.17/0220/E 4/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
C04
Maximum setpoint for suction pressure/temperature
LS to P1E; LS to 60.0°C
7.2
L2
L2
L2
C05
Compressor regulation probe selection
NU (0-NU) Suction pressure probe (1-SUP) Case temperature (2-CST) Suction pressure switch (3-dIS)
Suction pressure probe
L2
L2
L2
C06
EXV closing time before compressor off
0 to 999 sec
0
L2
L2
L2
C07
Refrigerant selection for regulation
R404A (0-404) - R507 (1-507) R134a (2-134) - R22 (3-R22) R407C (4-07C) - R407A (5-07A) R407F (6-07F) - R448A (7-48A) R449A (8-49A)
R404A
L1
L1
L1
C08
Setpoint offset
NU (0-NU) Small offset (1-SOF) Medium offset (2-MOF) Large offset (3-LOF) LAO (4-FOF)
Not used
L2
L2
L2
C09
Ambient temperature operation setpoint
-40°C to 110°C
-20
L2
L2
L2
C10
Pressure/Temperature operation for ambient differential
0.0 to 9.9 bar; 0.0 PSI to 99.9 PSI
0.0°C to 25.5°C
1
L2
L2
L2
C11
Ambient temperature recover differential
0.1°C to 25.5°C
5
L2
L2
L2
C12
Ambient temperature threshold for low ambient operation
-40°C to 110°C
-10
L2
L2
L2
C13
Temperature/Pressure to end low ambient timer and resume normal operation
-40°C to 110°C
-1.5 to 99.9 bar; -21 to 999 PSI
10
L2
L2
L2
C14
Compressor minimum on time in low ambient operation
0 to 255 sec
10
L2
L2
L2
C15
Pressure to end low ambient timer and shut off the compressor
-1.5 to 99.9 bar; -21.0 to 999 PSI
0.5
L2
L2
L2
C16
Digital compressor setpoint
LS to US
3.3
L1
N.V.
N.V.
C17
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to 25.5°C
2
L1
N.V.
N.V.
C18
Band offset for compressor regulation
0 to 9.9 bar; 0 to 99.9 PSI; 0.0°C to 25.5°C
0
L2
N.V.
N.V.
C19
Integral time
0 to 999 sec
250
L2
L2
N.V.
CC7.8.17/0220/E 5/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
C20
Start-up time: interval time with digital valve energized before regulation starts
0.0 to 10.0 sec
10
L2
N.V.
N.V.
C21
Cycle time for digital compressor
10 to 40 sec
20
L1
N.V.
N.V.
C22
Safety value for PI regulator (in case of probe error)
0 to 100%
50
L2
N.V.
N.V.
C23
Number of active compressor when probe error
0 (0) – 1 (1) – 2 (2)
0
L2
N.V.
N.V.
C24
Minimum capacity for digital compressor
0 to PMA
20
L1
N.V.
N.V.
C25
Maximum capacity for digital compressor
PMi to 100
100
L1
N.V.
N.V.
C26
Time with DGS at PMA before starting another load
0 to 255 sec
0
L2
N.V.
N.V.
C27
Time with DGS at PMi before switching off another load
0 to 255 sec
0
L2
N.V.
N.V.
C28
R404A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C29
R507 Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C30
R134a Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C31
R22 Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C32
R407C Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C33
R407A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C34
R407F Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C35
R448A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C36
R449A Enable function
Disable (0-NO) - Enable (1-YES)
Enable
N.V.
N.V.
N.V.
C37
R410A Enable function
Disable (0-NO) - Enable (1-YES)
Disable
N.V.
N.V.
N.V.
C38
Compressor regulation control signal
Pressure (0-PRS) - temperature (1-TMP)
Pressure
L2
L2
L2
D01
Output delay at start-up
0 to 255 sec
5
L2
L2
L2
D02
Compressor On time with faulty probe
0 to 255 min
0
L2
L2
L2
D03
Compressor Off time with faulty probe
0 to 255 min
0
L2
L2
L2
D04
Minimum time between two starts (same compressor)
0 to 15 min
4
L2
L2
L2
CC7.8.17/0220/E 6/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
D05
Delay between compressor switch-off and start-up (same compressor)
1 to 900 sec
120
L2
L2
L2
D06
Delay between two different loads start-up
[0÷99.5] min, resolution 10 sec
10
N.V.
N.V.
N.V.
D07
Delay between two different loads switch-off
[0÷99.5] min, resolution 10 sec
10
N.V.
N.V.
N.V.
D08
Minimum time a stage stays switched on
[0÷99.5] min, resolution 10 sec
0
L2
L2
L2
D09
Maximum time a stage stays switched on
[0.00÷24.00] hours, resolution 10 min
0
L2
L2
L2
D10
don delay enabled also for the first request
No (0-NO) - Yes (1-YES)
NO
L2
N.V.
N.V.
D11
doF delay enable also for the first switching off
No (0-NO) - Yes (1-YES)
NO
L2
N.V.
N.V.
D12
Low suction pressure alarm delay
0 to 999 sec
0
L2
L2
L2
D13
Low suction pressure error signal enabling
No (0-NO) - Yes (1-YES)
YES
L2
L2
L2
D14
Compressor minimum off time for high­pressure switch protection
0 to 15 min
5
L2
L2
L2
D15
Number of high-pressure switch activations before compressor lockout
0 to 15
7
L2
L2
L2
D16
Bump start enable
No (0-NO) - Yes (1-YES)
NO
N.V.
N.V.
N.V.
D17
Bump start ambient threshold
-40°C to 110°C
0
N.V.
N.V.
N.V.
D18
Compressor stop time for next bump start
0 hour to 23 hours and 50 minutes
1 hour
N.V.
N.V.
N.V.
D19
Compressor on time during bump function
1 to 15 sec
2
N.V.
N.V.
N.V.
D20
Compressor off time during bump function
1 to 15 sec
15
N.V.
N.V.
N.V.
D21
Number of cycles during bump start
1 to 15
3
N.V.
N.V.
N.V.
D22
DLT alarm temperature to stop compressor
-40°C to 180°C
140
L2
L2
L2
D23
DLT alarm recover temperature to turn on compressor
-40°C to 180°C
90
L2
L2
L2
D24
DLT alarm activation delay
0 to 255 sec
30
L2
L2
L2
D25
Compressor minimum off time for DLT Alarm
0 to 255 min
5
L2
L2
L2
D26
Number of DLT alarm activations before compressor lockout
0 to 15
10
L2
L2
L2
D27
Time to ignore low DLT sensor error at start­up
0 to 255 min
5
L2
L2
L2
CC7.8.17/0220/E 7/22
Code
Description
Range
Factory setting
ZXDE
ZXME
ZXLE
D28
Compressor minimum off time for low­pressure switch protection
0 to 15 min
3
L2
L2
L2
D29
Low-pressure alarm value (from serial number 16EZ08855M onwards)
0 to 15 bar
0.5
L1
L1
L1
D30
Cold start enable
Disable (0) - Enable (1)
Disable
N.V.
N.V.
N.V.
D31
DLT temperature threshold to trip during cold start
-40 to 180°C
60
N.V.
N.V.
N.V.
D32
Suction pressure threshold to trip during cold start
-1.5 to 99.9 bar
0.5
N.V.
N.V.
N.V.
D33
Allowed number of cycles of DLT temperature trips during cold start
1 to 15
4
N.V.
N.V.
N.V.
D34
Allowed number of cycles of low-pressure trips during cold start
1 to 15
4
N.V.
N.V.
N.V.
D35
Compressor stop time during cold start
1 to 999 sec
180
N.V.
N.V.
N.V.
E01
Condenser fan motor modulation type
Not used (0-NU) Fan cycling (1-CYC) Modulated fan (2-MOD)
Modulated fan
L2
L2
L2
E02
Low setpoint for condenser fan map 1 (for R404A, R507)
-40°C to HT1
10
N.V.
N.V.
N.V.
E03
Lower suction pressure point for condenser fan map 1 (for R404A, R507)
-1.5 bar to HP1; -21 PSI to HP1
3.3
N.V.
N.V.
N.V.
E04
High setpoint for condenser fan map 1 (for R404)
LT1 to 110°C
30
N.V.
N.V.
N.V.
E05
High suction pressure point for condenser fan map 1 (for R404A, R507)
LP1 to 99.9 bar; LP1 to 999 PSI
7.2
N.V.
N.V.
N.V.
E06
Low setpoint for condenser fan map 2 (for R134)
-40°C to HT2
25
N.V.
N.V.
N.V.
E07
Lower suction pressure point for condenser fan map 2 (for R404)
-1.5 bar to HP2; -21 PSI to HP2
2.5
N.V.
N.V.
N.V.
E08
High setpoint for condenser fan map 2 (for R134)
LT2 to 110°C
40
N.V.
N.V.
N.V.
E09
High suction pressure point for condenser fan map 2 (for R404)
LP2 to 99.9 bar; LP2 to 999 PSI
3.9
N.V.
N.V.
N.V.
Loading...
+ 15 hidden pages