Emerson XCM25D User Manual

Emerson XCM25D User Manual

Date of last update: Feb-20

Ref: CC7.8.17/0220/E

Application Engineering Europe

COPELAND EAZYCOOL™ ZX CONDENSING UNITS

XCM25D CONTROLLER PARAMETER LIST

Copeland EazyCool™ ZX Condensing Units are equipped with an XCM25D electronic controller from Dixell. The controller design allows the installer to start and operate the system with minimum effort in terms of controller adjustments. The most important controller settings are described in the application guidelines and most likely there is no need to change those settings.

In case of special applications additional parameters might have to be adjusted according to those special needs. This document contains the full list of available parameters in the XCM25D controller. It is not a user’s manual. For questions about how to handle the controller and for functionality description please refer to the dedicated documentation available at www.climate.emerson.com/en-gb.

Legend

L1 = Parameter in level 1 (without password)

L2 = Parameter in level 2 (with password = 3 2 1)

N.V. = Parameter not accessible

NOTE: When changing parameters C01 (Cin), C02 (CoU) and C05 (CPb) a reset of the controller (interruption of power supply) is required.

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

 

ZXME

 

 

ZXLE

 

 

 

A01

Probe P1 configuration

 

Not used (0-NU)

 

Suction pressure

L2

 

 

L2

 

 

L2

 

 

 

 

Suction pressure (0-5V)(1-SUP)

 

(0-5V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A02

 

 

Start of scaling for probe 1 (0-5V)

 

 

0-5V: -1.5 bar to P1E; -21 PSI to P1E

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

 

A03

End of scaling for probe 1 (0-5V)

 

0-5V: P1i to 99.9 bar; P1i to 999 PSI

15

 

L2

 

 

L2

 

 

L2

 

 

 

A04

 

 

Probe P1 calibration

 

 

0-5V: -12.0 to 12.0 bar; -12.0 to12.0 PSI

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

 

A05

Probe P1 reading error delay (P1C = 0-5V)

 

0 to 255 min

5

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

Mid-coil pressure

 

 

 

 

 

 

 

 

 

 

 

A06

 

 

Probe P2 configuration

 

 

Mid-coil temperature (NTC10K)(1-MCT)

 

 

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

(0-5V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mid-coil pressure (0-5V)(2-MCP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

 

1/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

 

ZXME

 

 

ZXLE

 

 

A07

Start of scaling for probe 2

 

0-5V: -1.5 bar to P2E; -21 PSI to P2E

0

 

L2

 

 

L2

 

 

L2

 

 

 

NTC10K: -40°C to P2E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A08

 

 

End of scaling for probe 2

 

 

0-5V: P2i to 99.9 bar; P2i to 999 PSI

 

 

35

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

NTC10K: P2i to 110°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A09

Probe P2 calibration

 

0-5V: -12.0 to 12.0 bar; -12.0 to 12.0 PSI

0

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

NTC10K: -12°C to 12°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A10

 

 

Probe P2 reading error delay (P2C=0-5V)

 

 

0 to 255 min

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

A11

Probe P3 configuration

 

Not used (0-NU)

 

Discharge line

L2

 

 

L2

 

 

L2

 

 

 

Discharge line temperature (1-DLT)

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A12

 

 

Probe P3 calibration

 

 

-12°C to 12°C

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (NTC10K)(1-AMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat temperature (NTC10K)(2-TMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vapour inlet temperature (NTC10K)(3-UIT)

 

 

 

 

 

 

 

 

 

 

 

 

A13

Probe P4 configuration

 

Vapour outlet temperature (NTC10K)(4-UOT)

 

Not used

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

Evaporator temperature (NTC10K)(5-EPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid temperature (NTC10K)(6-LLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction line temperature (7-SLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil temperature (8-COT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A14

 

 

Probe P4 calibration

 

 

-12°C to 12°C

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (NTC10K)(1-AMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat temperature (NTC10K)(2-TMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vapour inlet temperature (NTC10K)(3-UIT)

 

 

 

 

 

 

 

 

 

 

 

 

A15

Probe P5 configuration

 

Vapour outlet temperature (NTC10K)(4-UOT)

 

Not used

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

Evaporator temperature (NTC10K)(5-EPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid temperature (NTC10K)(6-LLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction line temperature (7-SLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil temperature (8-COT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A16

 

 

Probe P5 calibration

 

 

-12°C to 12°C

 

 

0

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

2/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

ZXME

 

 

ZXLE

 

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (NTC10K)(1-AMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat temperature (NTC10K)(2-TMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vapour inlet temperature (NTC10K)(3-UIT)

 

Ambient temperature

 

 

 

 

 

 

 

 

 

A17

Probe P6 configuration

 

Vapour outlet temperature (NTC10K)(4-UOT)

 

L2

 

L2

 

 

L2

 

 

 

 

 

(NTC10K)

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator temperature (NTC10K)(5-EPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid temperature (NTC10K)(6-LLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction line temperature (7-SLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil temperature (8-COT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A18

 

 

Probe P6 calibration

 

 

-12°C to 12°C

 

 

0.0

 

L2

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (NTC10K)(1-AMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat temperature (NTC10K)(2-TMT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vapour inlet temperature (NTC10K)(3-UIT)

 

 

 

 

 

 

 

 

 

 

 

 

A19

Probe P7 configuration

 

Vapour outlet temperature (NTC10K)(4-UOT)

 

Not used

L2

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

Evaporator temperature (NTC10K)(5-EPT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid temperature (NTC10K)(6-LLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction line temperature (7-SLT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil temperature (8-COT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A20

 

 

Probe P7 calibration

 

 

-12°C to 12°C

 

 

0

 

L2

 

L2

 

 

L2

 

 

 

A21

Delay before activating probe error

 

0 to 255 sec

0

 

L2

 

L2

 

 

L2

 

 

 

B01

 

 

Measurement unit for pressure

 

 

Bar (0-BAR) – PSI (1-PSI) – KPA (2-TPA)

 

 

bar

 

L2

 

L2

 

 

L2

 

 

 

B02

Measurement unit for temperature

 

°C (0-C)

 

°C

L2

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

P1 (0-P1) - P2 (1-P2) - P3 (2-P3) -

 

 

 

 

 

 

 

 

 

 

 

 

 

B03

 

 

Remote display visualization

 

 

P4 (3-P4) - P5 (4-P5) - P6 (5-P6) -

 

 

P1

 

L2

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

P7 (6-P7) – Per (7-PER) – Aou (8-AOU)

 

 

 

 

 

 

 

 

 

 

 

 

 

B04

Filter enabling for probe reading

 

n (0-NO) - Y (1-YES)

 

YES

N.V.

 

N.V.

 

 

N.V.

 

 

 

B05

 

 

Coefficient for probe reading filter (0 =

 

 

0 to 100, mEd (101)

 

 

50

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

 

 

max,100 = disable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C01

Compressor cut-in pressure setpoint

 

CoU to US

4

 

N.V.

 

L1

 

 

L1

 

 

 

C02

 

 

Compressor cut-out pressure setpoint

 

 

LS to Cin

 

 

2

 

L2

 

L1

 

 

L1

 

 

 

C03

Minimum setpoint for suction

 

P1i to US; -50.0°C to US

0.6

 

L2

 

L2

 

 

L2

 

 

 

pressure/temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

3/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

ZXME

 

ZXLE

 

 

 

C04

 

 

Maximum setpoint for suction

 

 

LS to P1E; LS to 60.0°C

 

 

7.2

 

L2

 

L2

 

L2

 

 

 

 

 

pressure/temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NU (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C05

Compressor regulation probe selection

 

Suction pressure probe (1-SUP)

 

Suction pressure

L2

 

L2

 

L2

 

 

 

 

Case temperature (2-CST)

 

probe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction pressure switch (3-dIS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C06

 

 

EXV closing time before compressor off

 

 

0 to 999 sec

 

 

0

 

L2

 

L2

 

L2

 

 

 

 

 

 

 

 

 

R404A (0-404) - R507 (1-507)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R134a (2-134) - R22 (3-R22)

 

 

 

 

 

 

 

 

 

 

 

C07

Refrigerant selection for regulation

 

R407C (4-07C) - R407A (5-07A)

 

R404A

L1

 

L1

 

L1

 

 

 

 

 

 

 

 

 

R407F (6-07F) - R448A (7-48A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R449A (8-49A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NU (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Small offset (1-SOF)

 

 

 

 

 

 

 

 

 

 

 

 

C08

 

 

Setpoint offset

 

 

Medium offset (2-MOF)

 

 

Not used

 

L2

 

L2

 

L2

 

 

 

 

 

 

 

 

 

Large offset (3-LOF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAO (4-FOF)

 

 

 

 

 

 

 

 

 

 

 

 

C09

Ambient temperature operation setpoint

 

-40°C to 110°C

-20

 

L2

 

L2

 

L2

 

 

 

C10

 

 

Pressure/Temperature operation for ambient

 

 

0.0 to 9.9 bar; 0.0 PSI to 99.9 PSI

 

 

1

 

L2

 

L2

 

L2

 

 

 

 

 

differential

 

 

0.0°C to 25.5°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C11

Ambient temperature recover differential

 

0.1°C to 25.5°C

5

 

L2

 

L2

 

L2

 

 

 

C12

 

 

Ambient temperature threshold for low

 

 

-40°C to 110°C

 

 

-10

 

L2

 

L2

 

L2

 

 

 

 

 

ambient operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C13

Temperature/Pressure to end low ambient

 

-40°C to 110°C

10

 

L2

 

L2

 

L2

 

 

 

 

 

 

 

 

 

 

timer and resume normal operation

 

-1.5 to 99.9 bar; -21 to 999 PSI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C14

 

 

Compressor minimum on time in low ambient

 

 

0 to 255 sec

 

 

10

 

L2

 

L2

 

L2

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C15

Pressure to end low ambient timer and shut

 

-1.5 to 99.9 bar; -21.0 to 999 PSI

0.5

 

L2

 

L2

 

L2

 

 

 

off the compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C16

 

 

Digital compressor setpoint

 

 

LS to US

 

 

3.3

 

L1

 

N.V.

 

N.V.

 

 

 

C17

Proportional band for compressor regulation

 

0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to 25.5°C

2

 

L1

 

N.V.

 

N.V.

 

 

 

C18

 

 

Band offset for compressor regulation

 

 

0 to 9.9 bar; 0 to 99.9 PSI; 0.0°C to 25.5°C

 

 

0

 

L2

 

N.V.

 

N.V.

 

 

 

C19

Integral time

 

0 to 999 sec

250

 

L2

 

L2

 

N.V.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

4/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

ZXME

 

ZXLE

 

 

 

C20

 

 

Start-up time: interval time with digital valve

 

 

0.0 to 10.0 sec

 

 

10

 

L2

 

N.V.

 

N.V.

 

 

 

 

 

energized before regulation starts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C21

Cycle time for digital compressor

 

10 to 40 sec

20

 

L1

 

N.V.

 

N.V.

 

 

 

C22

 

 

Safety value for PI regulator (in case of probe

 

 

0 to 100%

 

 

50

 

L2

 

N.V.

 

N.V.

 

 

 

 

 

error)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C23

Number of active compressor when probe

 

0 (0) – 1 (1) – 2 (2)

0

 

L2

 

N.V.

 

N.V.

 

 

 

 

 

 

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C24

 

 

Minimum capacity for digital compressor

 

 

0 to PMA

 

 

20

 

L1

 

N.V.

 

N.V.

 

 

 

C25

Maximum capacity for digital compressor

 

PMi to 100

100

 

L1

 

N.V.

 

N.V.

 

 

 

C26

 

 

Time with DGS at PMA before starting another

 

 

0 to 255 sec

 

 

0

 

L2

 

N.V.

 

N.V.

 

 

 

 

 

load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C27

Time with DGS at PMi before switching off

 

0 to 255 sec

0

 

L2

 

N.V.

 

N.V.

 

 

 

another load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C28

 

 

R404A Enable function

 

 

Disable (0-NO) - Enable (1-YES)

 

 

Enable

 

N.V.

 

N.V.

 

N.V.

 

 

 

C29

R507 Enable function

 

Disable (0-NO) - Enable (1-YES)

 

Enable

N.V.

 

N.V.

 

N.V.

 

 

 

C30

 

 

R134a Enable function

 

 

Disable (0-NO) - Enable (1-YES)

 

 

Enable

 

N.V.

 

N.V.

 

N.V.

 

 

 

C31

R22 Enable function

 

Disable (0-NO) - Enable (1-YES)

 

Enable

N.V.

 

N.V.

 

N.V.

 

 

 

C32

 

 

R407C Enable function

 

 

Disable (0-NO) - Enable (1-YES)

 

 

Enable

 

N.V.

 

N.V.

 

N.V.

 

 

 

C33

R407A Enable function

 

Disable (0-NO) - Enable (1-YES)

 

Enable

N.V.

 

N.V.

 

N.V.

 

 

 

C34

 

 

R407F Enable function

 

 

Disable (0-NO) - Enable (1-YES)

 

 

Enable

 

N.V.

 

N.V.

 

N.V.

 

 

 

C35

R448A Enable function

 

Disable (0-NO) - Enable (1-YES)

 

Enable

N.V.

 

N.V.

 

N.V.

 

 

 

C36

 

 

R449A Enable function

 

 

Disable (0-NO) - Enable (1-YES)

 

 

Enable

 

N.V.

 

N.V.

 

N.V.

 

 

 

C37

R410A Enable function

 

Disable (0-NO) - Enable (1-YES)

 

Disable

N.V.

 

N.V.

 

N.V.

 

 

 

C38

 

 

Compressor regulation control signal

 

 

Pressure (0-PRS) - temperature (1-TMP)

 

 

Pressure

 

L2

 

L2

 

L2

 

 

 

D01

Output delay at start-up

 

0 to 255 sec

5

 

L2

 

L2

 

L2

 

 

 

D02

 

 

Compressor On time with faulty probe

 

 

0 to 255 min

 

 

0

 

L2

 

L2

 

L2

 

 

 

D03

Compressor Off time with faulty probe

 

0 to 255 min

0

 

L2

 

L2

 

L2

 

 

 

D04

 

 

Minimum time between two starts (same

 

 

0 to 15 min

 

 

4

 

L2

 

L2

 

L2

 

 

 

 

 

compressor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

5/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

ZXME

 

 

ZXLE

 

 

 

D05

Delay between compressor switch-off and

 

1 to 900 sec

120

 

L2

 

L2

 

 

L2

 

 

 

start-up (same compressor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D06

 

 

Delay between two different loads start-up

 

 

[0÷99.5] min, resolution 10 sec

 

 

10

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D07

Delay between two different loads switch-off

 

[0÷99.5] min, resolution 10 sec

10

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D08

 

 

Minimum time a stage stays switched on

 

 

[0÷99.5] min, resolution 10 sec

 

 

0

 

L2

 

L2

 

 

L2

 

 

 

D09

Maximum time a stage stays switched on

 

[0.00÷24.00] hours, resolution 10 min

0

 

L2

 

L2

 

 

L2

 

 

 

D10

 

 

don delay enabled also for the first request

 

 

No (0-NO) - Yes (1-YES)

 

 

NO

 

L2

 

N.V.

 

 

N.V.

 

 

 

D11

doF delay enable also for the first switching off

 

No (0-NO) - Yes (1-YES)

 

NO

L2

 

N.V.

 

 

N.V.

 

 

 

D12

 

 

Low suction pressure alarm delay

 

 

0 to 999 sec

 

 

0

 

L2

 

L2

 

 

L2

 

 

 

D13

Low suction pressure error signal enabling

 

No (0-NO) - Yes (1-YES)

 

YES

L2

 

L2

 

 

L2

 

 

 

D14

 

 

Compressor minimum off time for high-

 

 

0 to 15 min

 

 

5

 

L2

 

L2

 

 

L2

 

 

 

 

 

pressure switch protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D15

Number of high-pressure switch activations

 

0 to 15

7

 

L2

 

L2

 

 

L2

 

 

 

before compressor lockout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D16

 

 

Bump start enable

 

 

No (0-NO) - Yes (1-YES)

 

 

NO

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D17

Bump start ambient threshold

 

-40°C to 110°C

0

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D18

 

 

Compressor stop time for next bump start

 

 

0 hour to 23 hours and 50 minutes

 

 

1 hour

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D19

Compressor on time during bump function

 

1 to 15 sec

2

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D20

 

 

Compressor off time during bump function

 

 

1 to 15 sec

 

 

15

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D21

Number of cycles during bump start

 

1 to 15

3

 

N.V.

 

N.V.

 

 

N.V.

 

 

 

D22

 

 

DLT alarm temperature to stop compressor

 

 

-40°C to 180°C

 

 

140

 

L2

 

L2

 

 

L2

 

 

 

D23

DLT alarm recover temperature to turn on

 

-40°C to 180°C

90

 

L2

 

L2

 

 

L2

 

 

 

compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D24

 

 

DLT alarm activation delay

 

 

0 to 255 sec

 

 

30

 

L2

 

L2

 

 

L2

 

 

 

D25

Compressor minimum off time for DLT Alarm

 

0 to 255 min

5

 

L2

 

L2

 

 

L2

 

 

 

D26

 

 

Number of DLT alarm activations before

 

 

0 to 15

 

 

10

 

L2

 

L2

 

 

L2

 

 

 

 

 

compressor lockout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D27

Time to ignore low DLT sensor error at start-

 

0 to 255 min

5

 

L2

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

6/22

 

Code

 

 

Description

 

 

Range

 

 

Factory setting

 

ZXDE

 

 

ZXME

 

 

ZXLE

 

 

 

D28

 

 

Compressor minimum off time for low-

 

 

0 to 15 min

 

 

3

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

pressure switch protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D29

Low-pressure alarm value (from serial number

 

0 to 15 bar

0.5

 

L1

 

 

L1

 

 

L1

 

 

 

16EZ08855M onwards)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D30

 

 

Cold start enable

 

 

Disable (0) - Enable (1)

 

 

Disable

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

D31

DLT temperature threshold to trip during cold

 

-40 to 180°C

60

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

 

 

 

 

 

 

 

start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D32

 

 

Suction pressure threshold to trip during cold

 

 

-1.5 to 99.9 bar

 

 

0.5

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D33

Allowed number of cycles of DLT temperature

 

1 to 15

4

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

 

 

 

 

 

 

 

trips during cold start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D34

 

 

Allowed number of cycles of low-pressure trips

 

 

1 to 15

 

 

4

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

during cold start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D35

Compressor stop time during cold start

 

1 to 999 sec

180

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

 

 

 

 

Not used (0-NU)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

 

 

Condenser fan motor modulation type

 

 

Fan cycling (1-CYC)

 

 

Modulated fan

 

L2

 

 

L2

 

 

L2

 

 

 

 

 

 

 

 

 

Modulated fan (2-MOD)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E02

Low setpoint for condenser fan map 1 (for

 

-40°C to HT1

10

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

R404A, R507)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E03

 

 

Lower suction pressure point for condenser

 

 

-1.5 bar to HP1; -21 PSI to HP1

 

 

3.3

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

fan map 1 (for R404A, R507)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E04

High setpoint for condenser fan map 1 (for

 

LT1 to 110°C

30

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

R404)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E05

 

 

High suction pressure point for condenser fan

 

 

LP1 to 99.9 bar; LP1 to 999 PSI

 

 

7.2

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

map 1 (for R404A, R507)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E06

Low setpoint for condenser fan map 2 (for

 

-40°C to HT2

25

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

R134)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E07

 

 

Lower suction pressure point for condenser

 

 

-1.5 bar to HP2; -21 PSI to HP2

 

 

2.5

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

fan map 2 (for R404)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

High setpoint for condenser fan map 2 (for

 

LT2 to 110°C

40

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

R134)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E09

 

 

High suction pressure point for condenser fan

 

 

LP2 to 99.9 bar; LP2 to 999 PSI

 

 

3.9

 

N.V.

 

 

N.V.

 

 

N.V.

 

 

 

 

 

map 2 (for R404)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC7.8.17/0220/E

 

 

 

 

 

 

 

 

 

 

 

7/22

Loading...
+ 15 hidden pages