Emerson Adapt, iTrust Adapt, UHA1R-0050, UHA1R-0050L User Manual

iTrust Adapt 6kVA UPS
User Manual
Version V1.0 Revision date BOM
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Copyright © 2009 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Safety Guidelines
Prohibitions
1. Non-professionals are prohibited to install or commission the UPS alone.
2. As hazardous voltages are present within the UPS, only an Emerson technician or an Emerson-authorized technician is permitted to open it. Failure to observe this could result in electric shock risk and invalidation of any implied warranty.
3. Never dispose of the battery in a fire, as it may explode and jeopardize personnel safety when exposed to flame.
Matters needing attention
1. The standard UPS has its own energy source, external battery, therefore, the output terminal of the UPS may carry live voltage even when the UPS is not connected to the AC mains.
2. Before moving or re-wiring the UPS, please disconnect the mains source and make sure the UPS is completely shut down. Or else, the output terminal may carry live voltage, thus presenting electric shock risk.
3. To ensure human safety and normal operation, the UPS must be solidly and adequately grounded before use.
4. The operating environment and save method affect the UPS lifetime and reliability. It is advisable not to use the UPS for long in the following environments:
Places where the temperature and relative humidity are outside the specifications (temperature:
0°C ~ 40°C, relative humidity: 5% ~ 95%)
Places in direct sunlight or near heat source
Places subject to vibrations or shocks
Places which are dusty, strewn with corrosive substances or salts, or where flammable gases
are present
5. Please keep the air inlet and outlet unobstructed. Poor ventilation will increase the internal temperature, which will shorten the lifetime of the UPS components, hence that of the UPS.
6. Liquid and other irrelevant objects are strictly prohibited inside the UPS.
7. In case of fire, use dry chemical fire extinguisher to put out the fire. Using foam fire extinguisher may cause electric shock.
8. High ambient temperature shortens the battery lifetime. To ensure normal UPS operation and adequate autonomy time, the battery should be replaced periodically. Only Emerson-authorized technicians are permitted to replace the battery.
9. If the UPS will remain idle for a long period, it must be stored in a dry environment. The storage temperature should range between -20°C and +55°C for standard UPS (with internal battery), between -40°C and +70°C for extended UPS (with no internal battery.)
10. This equipment complies with IEC 61000-3-12 provided that the short-circuit ratio Rsce is greater than or equal to 250 at the interface point between the user’s supply and the public systerm. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit ratio Rsce greater than or equal to 250.
11. The UPS output cable must be less than 10m.
Others
When the UPS is purchased to deliver power to the equipment listed below, please discuss with the distributor in advance about the applicability, settings, management and maintenance of the UPS, as these need special considerations during design and development.
Life-supporting medical apparatus
Facilities such as lifts/elevators where adequate care has to be taken to avoid any fatal
eventuality endangering human life
Any other mission-critical equipment like the above
Contents
Chapter 1 Product Description .......................................................................................................................... 1
1.1 Features.............................................................................................................................................. 1
1.2 Model Configuration............................................................................................................................ 1
1.3 Appearance And Components............................................................................................................ 2
1.3.1 Appearance ............................................................................................................................. 2
1.3.2 Components ............................................................................................................................ 2
1.4 Operating Principle ............................................................................................................................. 3
1.5 UPS State And Operation Mode ......................................................................................................... 3
1.5.1 Normal Mode ........................................................................................................................... 3
1.5.2 Bypass Mode........................................................................................................................... 3
1.5.3 Battery Mode ........................................................................................................................... 4
1.5.4 ECO Mode............................................................................................................................... 4
1.5.5 Fault State ............................................................................................................................... 4
1.6 Specifications...................................................................................................................................... 5
Chapter 2 Installation ........................................................................................................................................ 6
2.1 Unpacking Inspection.......................................................................................................................... 6
2.2 Installation Preliminaries ..................................................................................................................... 6
2.3 Mechanical Installation........................................................................................................................ 6
2.3.1 Tower Installation .................................................................................................................... 7
2.3.2 Rack Installation ...................................................................................................................... 8
2.4 Connecting Cables.............................................................................................................................. 9
2.4.1 I/O Terminal Block ................................................................................................................... 9
2.4.2 Connecting Input And Output Cables ...................................................................................... 9
2.4.3 Connecting Battery Cables .................................................................................................... 10
2.4.4 Connecting Communication Cables ...................................................................................... 11
2.5 N + 1 Parallel System (Optional)....................................................................................................... 12
2.5.1 Mechanical Installation .......................................................................................................... 12
2.5.2 Setting Parallel Addresses..................................................................................................... 14
2.5.3 Connecting Parallel Cables ................................................................................................... 15
2.5.4 Connecting POD Cables ....................................................................................................... 15
Chapter 3 Operation And Display Panel ......................................................................................................... 17
3.1 Control Keys ..................................................................................................................................... 17
3.2 Indicators .......................................................................................................................................... 17
3.2.1 UPS State Indicators ............................................................................................................. 18
3.2.2 UPS Load Battery Capacity And Fault Orientation Indicator.................................................. 18
Chapter 4 Operation Instructions .................................................................................................................... 19
4.1 Check Before Power-On ................................................................................................................... 19
4.2 UPS Power-On ................................................................................................................................. 19
4.3 Turning On UPS................................................................................................................................ 19
4.4 Battery Self-Test ............................................................................................................................... 20
4.4.1 Battery Power-On Self-Test................................................................................................... 20
4.4.2 Battery Manual Self-Test ....................................................................................................... 20
4.4.3 Battery Periodic Self-Test...................................................................................................... 21
4.5 Turning Off UPS................................................................................................................................ 21
4.6 UPS Power-Off ................................................................................................................................. 22
4.7 Transferring UPS Between Operation Modes................................................................................... 22
4.7.1 Transferring UPS From Overload Protection To Bypass Mode ............................................. 22
4.7.2 Transferring UPS From Mains Failure To Battery mode........................................................ 22
4.7.3 Transferring UPS From Inner Overheating Protection To Bypass Mode ............................... 23
4.7.4 Transferring UPS From Output Short Protection To Fault State............................................ 23
4.8 UPS Monitoring................................................................................................................................. 23
Chapter 5 Maintenance And Troubleshooting ................................................................................................. 24
5.1 Fan Maintenance .............................................................................................................................. 24
5.2 Battery Maintenance ......................................................................................................................... 24
5.3 Cleaning UPS ................................................................................................................................... 24
5.4 Checking UPS State ......................................................................................................................... 24
5.5 Checking UPS Functions .................................................................................................................. 24
5.6 Troubleshooting ................................................................................................................................ 25
5.7 Technical Support ............................................................................................................................. 26
Appendix 1 Battery Module ............................................................................................................................. 27
Appendix 2 Communication Function.............................................................................................................. 29
Appendix 3 LCD Operation And Display Panel ............................................................................................... 30
1. Brief Introduction................................................................................................................................. 30
2. LCD Operation And Display Interface ................................................................................................. 31
Appendix 4 POD ............................................................................................................................................. 35
1. Single-Phase Input Single-Phase Output 1 + 1 POD.......................................................................... 35
2. Single-Phase Input Single-Phase Output 3 + 1 POD.......................................................................... 35
3. 3-Phase Input Single-Phase Output 3 + 1 POD.................................................................................. 36
Appendix 5 Optional Part List.......................................................................................................................... 38
Chapter 1 Product Description 1
iTrust Adapt 6kVA UPS User Manual
Chapter 1 Product Description
iTrust Adapt 6kVA UPS (UPS for short) is an intelligent online UPS system with sine wave output developed by Emerson Network Power Co., Ltd. The UPS provides reliable and high quality AC power to your sophisticated equipment. The UPS adopts modular design, and rack/tower installation can be used depending on your requirements. It is applicable to supplying AC power to small scale computer center, network, communication system, automatic control system and precision instrument.
This chapter gives a brief description of the UPS, including the UPS features, model configuration, appearance, components, operating principle, state, operation mode and specifications.
1.1 Features
Compatible with two input modes: 3-phase and single-phase input mode, with automatic input recognition
function
Capable of parallel connection to achieve up to 3 + 1 redundant power supply
High-frequency double conversion topology structure, with high input power factor, wide input voltage range, and
output immune to grid interference, thus adaptable to areas with unstable mains supply
High power density
Full digital control technology based on digital signal processor (DSP) to achieve high system reliability with
self-protection and fault diagnosis
Intelligent battery management to extend the battery life
Operation and display panel with both LCD and LED indication to help you learn about the system operation
status and operating parameters
2U thick. Tower installation and rack installation are optional to meet different installation requirements
Capable of ECO mode, which saves energy to the maximum extent
Flexible network management with Emerson monitoring software
Fan fault self-inspection and automated diagnosing function
SNMP card optional, providing network communication function
Capable of connecting multiple battery strings, extending the power supply time of Battery mode
1.2 Model Configuration
As shown in Table 1-1, two models are available: standard model and extended model.
Table 1-1 Model configuration
Model Type Remarks
Standard model UHA1R-0050
Configured with battery module. See Appendix 1 Battery Module for the structure and connection of battery module
Extended model UHA1R-0050L No battery module is configured. You need to use external battery
2 Chapter 1 Product Description
iTrust Adapt 6kVA UPS User Manual
1.3 Appearance And Components
1.3.1 Appearance
The UPS appearance is shown in Figure 1-1.
Operation and display panel Ventilation holes
B
A
T
T
E
R
Y
L
O
A
D
F
A
U
L
T
U
T
I
L
I
T
Y
I
N
V
E
R
T
E
R
B
Y
P
A
S
S
B
A
T
T
E
R
Y
O
F
F
O
N
/
S
I
L
E
N
C
E
Figure 1-1 UPS appearance
Note
Non-professionals are prohibited from opening the chassis cover. Failure to observe this could result in electric shock.
1.3.2 Components
Operation and display panel
The UPS provides an operation and display panel on the front panel. The operation and display panel provides LED indicators and control keys. For details, refer to Chapter 3 Operation And Display Panel.
Rear panel
As shown in Figure 1-2, the UPS rear panel provides parallel port, DIP switch, bypass switch, battery port, USB port, ventilation holes, SNMP card slot and I/O terminal block.
PE
-
+
192Vdc 27A
Battery port
230/400Vac-40A
Input switch
Parallel port (with
protective cover)
Ventilation hole
DIP switch (with
protective cover) Battery port
I/O terminal block
(with protective cover)
SNMP card solt (with
protective cover)
Bypass switch
USB port
Figure 1-2 UPS rear panel
Chapter 1 Product Description 3
iTrust Adapt 6kVA UPS User Manual
1.4 Operating Principle
The operating principle of the UPS is shown in Figure 1-3.
I/O filter
Rectifier /
PFC
Inverter
DC/DC
Battery
input
Internal charger
Mains power
GND GND
Bypass
Output
Figure 1-3 Operating principle diagram
1. The UPS is composed of mains input, I/O filter, rectifier/PFC, DC/DC boost, inverter, bypass, internal charger, battery input and UPS output.
2. When the mains is normal, close the bypass switch, and the internal charger will charge the battery. Before turning on the UPS, the output voltage is zero. After turning on the UPS, the electronic transfer switch connects the inverter to the load, the rectifier/PFC circuit rectifiers the mains power into DC power and feeds the DC power to the inverter. The inverter then inverts the DC power to pure sine wave AC power and feeds the AC power to the load through electronic transfer switch.
3. During mains failure, the rectifier/PFC circuit boosts the battery voltage and feeds it to the inverter. The inverter then converts it into pure sine wave AC power, and feeds the AC power to the load through electronic transfer switch.
4. After the mains recovers, the UPS will switch to Normal mode from Battery mode, the rectifier/PFC circuit rectifiers the mains power into DC power and feeds the DC power to the inverter, then electronic transfer switch feeds the DC power to the load.
1.5 UPS State And Operation Mode
The UPS state and operation modes include: Normal mode, Bypass mode, Battery mode, ECO mode and Fault state.
For the descriptions of indicators and control keys in this section, refer to Chapter 3 Operation And Display Panel.
1.5.1 Normal Mode
After installing the UPS, press and hold the ON/SILENCE key for over one second until a beep sound is heard. The UPS is started and then enters Normal mode or Battery mode.
When the mains input and output load are normal, the load is powered by the mains after processing of the inverter and the rectifier; meanwhile, the internal charger charges the battery. When the UPS is in Normal mode, the UTILITY indicator and INVERTER indicator are on.
1.5.2 Bypass Mode
Upon output overload or faults during the UPS operation, the UPS will switch to Bypass mode, the load is powered by the bypass AC source, which comes directly from the AC mains input; meanwhile, the internal charger charges the battery. When the UPS is in Bypass mode, the BYPASS indicator is on.
Note
In the event of a mains failure or mains voltage outside the specifications (120Vac ~ 253Vac) when the UPS is in Bypass mode, the UPS will cease power for the load.
4 Chapter 1 Product Description
iTrust Adapt 6kVA UPS User Manual
1.5.3 Battery Mode
Upon mains failure, rectifier overload or mains voltage outside the specifications, the rectifier and internal charger will become inoperative, and the battery will power the load through the inverter. When the UPS is in Battery mode, the BATTERY indicator and INVERTER indicator are on, and the buzzer beeps every 3.3 seconds, notifying the user that the battery is powering the load.
Note
1. In Battery mode, when the battery voltage is low, the buzzer beeps rapidly (once per second), and the corresponding measures must be done in time.
2. The battery had been fully charged before delivery. However, storage and transportation will inevitably cause some charge loss. Therefore, it is required to charge the battery for eight hours before putting the UPS into operation, so as to ensure adequate battery autonomy.
1.5.4 ECO Mode
In ECO mode, when the bypass voltage is 220Vac ±10% and the frequency is within 50Hz ± 2Hz, the load is supplied by the bypass AC source and the bypass indicator is on. You can use the ECO mode to power through bypass those loads that are insensitive to power supply quality, so as to reduce the power loss.
When the bypass voltage is normal, and the inverter is in no-load state, the load is supplied by the bypass AC source and the BYPASS indicator is on.
Note
1. In ECO mode, if the bypass fails or bypass voltage is abnormal when the output is NOT overloaded, the UPS will switch to the Normal mode. However, if the bypass fails or bypass voltage is abnormal when the output IS overloaded, the UPS swill not switch to the Normal mode, but shut down the bypass.
2. In ECO mode, the efficiency of the UPS is up to 97%.
1.5.5 Fault State
Upon inverter failure or UPS over-temperature, the UPS will switch to Bypass mode when the UPS is in Normal mode, or shut down and stop the output when the UPS is in battery state. In UPS Fault state, the FAULT indicator will turn on, the buzzer will keep beeping and the corresponding indicator will blink.
Note
In Fault state, if the bypass fails or bypass voltage is abnormal when the output is NOT overloaded, the UPS will shut down and be powered by the inverter, such as radiator over-hot. However, if the bypass fails or bypass voltage is abnormal when the output IS overloaded, the UPS will not switch to the inverter, but shut down the bypass.
Chapter 1 Product Description 5
iTrust Adapt 6kVA UPS User Manual
1.6 Specifications
The UPS specifications are listed in Table 1-2.
Table 1-2 UPS specifications
Standard UPS Extended UPS
Product model
UHA1R-0050 UHA1R-0050L
Rated voltage Single-phase: 220Vac, 3-phase: 380Vac
Voltage range
176Vac ~ 276Vac, at full load 120Vac ~ 160Vac, linear derating 120Vac, at half load
Frequency 50Hz ± 5Hz
Input
Power factor Single-phase: ≥ 0.99, 3-phase: ≥ 0.95
Rated power 6kVA/4.2kW
Voltage 220Vac ± 3%
Frequency
In Normal mode: synchronizes with the bypass frequency when the bypass frequency is within 50Hz ± 5Hz In Battery mode is 50Hz ± 0.2Hz Bypass frequency track range is ±10%
Slew rate 0.2Hz/s (default), 1Hz/s
Power factor 0.7 (6kVA)
Crest factor 3:1
Voltage harmonic distortion ≤ 3% (linear load), ≤ 5% (non-linear load)
Load regulation rate 2%
Dynamic response recovery
time
60ms
Overload capacity 105% ~ 125% rated load for 1min, 125% ~ 150% rated load for 100ms
Bypass voltage 120Vac ~ 253Vac
Output
Mains efficiency 91%
Type Sealed, lead-acid, maintenance-free battery (12V/7Ah)
Cell No. 16
Rated voltage 192Vdc
Recharge duration (standard
UPS)
Fours hours to 90% rated capacity Depended on external battery capacity
Battery
Charge current 2A 4A
Normal←→Battery 0
Transfer time
Inverter←→Bypass ≤ 4ms
Noise (within 1m) ≤ 50dB
Display LED/LCD (optional)
Safety CCEE (GB4943-1995)/GB4943
Conduction emission IEC/EN 62040-2
Immunity I ≤ 16A, IEC/EN61000-3-3; 16A < I ≤ 75A, IEC/EN61000-3-11
EMC
Harmonic current
I ≤ 16A, IEC/EN61000-3-2; 16A < I ≤ 75A, IEC/EN61000-3-12 YD/T1095-2001 level 2 15%
Surge protection
IEC/EN-61000-4-5, endurance level 4 (4kV) (live line to earth), level 3 (2kV) (during live lines)
Protection level IP20
Operating temperature 0°C ~ +40°C
Storage temperature -40°C ~ +70°C (battery excluded); -20°C ~ +55°C (battery included)
Relative humidity 5% ~ 95%, non-condensing
Environmental
condition
Altitude < 1500m, derating in accordance with GB/T3859.2 when higher than 1500m
Size W × H × D (mm) 430 × 88 × 630
Standard UPS (kg) 23
Weight
Extended UPS (kg) 25
6 Chapter 2 Installation
iTrust Adapt 6kVA UPS User Manual
Chapter 2 Installation
This chapter expounds the UPS installation, including the unpacking inspection, installation notes, and installation procedures.
Note
The UPS installation must be carried out by professionals strictly.
2.1 Unpacking Inspection
Unpack the UPS and conduct the following checks:
1. Visually inspect the UPS appearance for shipping damage. If any shipping damage is founded, notify the carrier immediately.
2. Check the accessories against the delivery list. If there is any discrepancy, contact the distributor immediately.
2.2 Installation Preliminaries
Notes
The UPS is suitable for resistive-capacitive load (like computer), resistive load and micro-inductive load. It is not suitable for purely inductive load or purely capacitive load (like motor, air-conditioner and duplicator), nor can it be connected to half-wave rectifier load.
Installation environment
1. Do not install the UPS outdoors. The installation environment should meet the specifications (see Table 1-2).
2. Install the UPS in an environment with good ventilation and free of dust, volatile gas, salt, and corrosive materials. Keep the UPS far away from water, heat source, flammables and explosive substances. Avoid direct sunlight.
Installation clearances
Maintain a clearance of at least 200mm at both sides and back of the UPS. Keep the air inlets unobstructed on the front panel and rear panel of the UPS to facilitate ventilation and heat dissipation. Otherwise, the UPS internal temperature will rise, which will shorten the lifetime of the UPS.
Installation tools
Prepare installation tools according to Table 2-1. The tools must be insulated and ESD-proof processed before they are used.
Table 2-1 Installation tools
Installation tool Specification Application
Cross screwdriver EJ5100mm Remove the UPS top plate, or open the chassis
Wire-pressure plier YT-12 Press wires for I/O terminal block
Diagonal plier MTC3C Make input and output connection cables
Small slotted screwdriver EJ375mm Connect input and output cables
2.3 Mechanical Installation
Two installation modes are available: tower installation and rack installation. You can select an appropriate installation mode according to the actual conditions.
Chapter 2 Installation 7
iTrust Adapt 6kVA UPS User Manual
2.3.1 Tower Installation
Note
Various installation configurations are available: single UPS, single UPS with single- or multiple-battery. Their installation methods are all the same.
Installation method:
1. Take out support bases from the accessories, and snap them up in the direction shown in Figure 2-1, and then put the support bases down on the installation surface flatwise.
Figure 2-1 Installing support base (top view)
2. If battery module installation is necessary, take out a support base extension delivered with the battery module, and then assemble the support base extension and the support bases through fastenings, as shown in Figure 2-2.
Support base extensionFastening
Support base
Support base
Figure 2-2 Installing support base with support base extension (front view)
3. Place the UPS on the support bases. Each UPS needs four support bases to install, as shown in Figure 2-3.
Support base
UPS
B A T T E
R Y
L
O A D
F A U
L T
U
T I L
I T Y
I N VE
R T
E R
B
Y P A
S S
B A
T T E
R Y
O F F
O N
/ S I
L E N
C E
B
A T T
E R Y
L O A
D
F A U
L T
U
T I L
I T Y
I N V
E R T
E R
B Y
P A S
S
B A T
T E R
Y
O F F
O N /
S I L
E N C E
UPS
Battery module
Support base
Figure 2-3 Tower installation
8 Chapter 2 Installation
iTrust Adapt 6kVA UPS User Manual
2.3.2 Rack Installation
Note
1. Various installation configurations are available: single UPS, single UPS with single or multiple-battery. Their installation methods are all the same.
2. Because battery modules are too heavy, two or more installation personnel are required to install them at the same time. Please install them from bottom to top.
Rack installation: fix the UPS and battery module onto the rack through brackets.
Installation method:
1. Take out two brackets and six M4 * 10 screws from the accessories, and fix the brackets onto the battery module using the screws through installation holes, as shown in Figure 2-4.
Bracket (2 pcs)
Battery module
Installation hole (4 pcs)
screw (6 pcs)
Figure 2-4 Installing bracket
2. Place the battery module onto guide rail in the rack, and push it completely into the rack along the guide rail (it is prohibited to place the battery module through the brackets). Take out four M6 * 16 screws from accessories, and fix the battery module onto the rack using the screws through the installation holes on the racket, as shown in Figure 2-5.
Battery module
Guide
Installation hole (4 pcs)
Rack
Figure 2-5 Installing battery module
3. The installation method of the UPS is the same as that of the battery module. Install the UPS on top of the battery module. The rack installation method of standard UPS with single UPS and single battery module is shown in Figure 2-6.
UPS
Battery module
B
A
T
T
E
R
Y
L
O
A
D
F
A
U
L
T
U
Y
I
L
I
T
T
T
Y
B
A
T
E
R
B
Y
P
A
S
S
I
N
V
E
R
T
E
R
O
N
/
S
I
L
E
N
C
E
/
/
O
F
F
Figure 2-6 Rack installation of standard UPS with single UPS and single battery module
Loading...
+ 30 hidden pages