This m anual is provided for informational purposes only. Although the information contained in this
manual is believed to be accurate, it could include technical inaccuracies or typographical errors.
Changes are, therefore, periodically made to the information within this document and
incorporated without notice into subsequent revisions of the manual. Net Safety Monitoring Inc.
assum es no responsibility for any errors that m ay be contained within this manual.
This manual is a guide for the use of a 1, 2 and 4 Channel Field Mount Controller and the data
and procedures contained within this document have been verified and are believed to be
adequate for the intended use of the controller. If the controller or procedures are used for
purposes other than as described in the manual without receiving prior confirmation of validity or
suitability, Net Safety Monitoring Inc. does not guarantee the results and assumes no obligation or
liability.
No part of this manual may be copied, disseminated or distributed without the express written
consent of N et Safety Monitoring Inc.
Net Safety Monitoring Inc. products, are carefully designed and m anufactured from high quality
components and can be expected to provide many years of trouble free service. Each product is
thoroughly tested, inspected and calibrated prior to shipment. Failures can occur which are
beyond the control of the manufacturer. Failures can be minimized by adhering to the operating
and maintenance instructions herein. Where the absolute greatest of reliability is required,
redundancy should be designed into the system.
Net Safety Monitoring Inc., warrants its sensors and detectors against defective parts and
workmanship for a period of 24 months from date of purchase and other electronic assemblies for
36 months from date of purchase.
No other warranties or liability, expressed or implied, will be honoured by Net Safety Monitoring
Inc.
Contact Net Safety Monitoring Inc. or an authorized distributor for details.
Table of Contents
Unit I GENERAL INFORMATION ................................... 1
The UVC120 Flame Detectors combined with the U1F, U2F or U4F-UV Fire Controller provide
fast, reliable flame detection in a wide variety of applications. The microprocessor based
controllers sim ultaneously monitor up to four ultraviolet (UV) detectors to provide maximum
operating flexibility at minimum expense. The Automatic Visual Integrity (vi) feature provides a
continuous check of optical surfaces, sensitivity and electronic circuitry of the detector/controller
system. Automatic fault identification monitors system operation and provides a digital display of
system status using a numerical code. Controller response includes actuation of relays for direct
control of field response devices and a full array of faceplate indicators. Other features include
individual channel and area identification, "voting" capability and manual vi testing.
FEATURES
<Non-Intrusive testing activated by magnets
<Instantaneous response to ultraviolet radiation
<Automatic and manual Visual Integrity (vi) testing
<Adjustable sensitivity and time delay
<All automatic test functions performed with the system on line
<Automatic fault identification
<Individual channel identification with voting options
<Latching Area LEDs identify the area responding to fire
<Microprocessor-based controller is easily field-programmable.
<Two digital displays, one bar graph display and high intensity LEDs indicate
system status information
<Relay outputs are field adjustable as latching or non-latching
<Alarm relays are programmable for normally energized or de-energized operation
<Individual detector output (count rate) can be visually monitored on the digital
display
<Two 4-20mA current outputs (U2F and U4F). One 4-20mA output on U1F
<Conduit seals recommended to prevent moisture damage but not required
CONTROLLER SPECIFICATIONS
<Operating Voltage:
24 Volts DC nominal. 18 to 32Vdc.
<Power Consumption (controller only):
2.4 watts nom inal, 4.4 watts m aximum.
100 mA nominal, 180 mA maximum at 24 Volts DC.
Maximum startup current is 1.5 Amperes for 10 milliseconds. Power supplies
with fold back current limiting are not recom mended.
<Maximum Ripple:
Ripple should not exceed 5 Volts peak-to-peak. The sum of DC plus ripple must
be $18 Vdc and #32 Vdc
<Temperature Range:
Operating:-40ºC to +85ºC(-40ºF to +185ºF)
Storage:-55ºC to +150ºC(-65ºF to +302ºF)
- 1 -
<Relay Contacts:
Normally open/normally closed contacts rated for 5 Amperes at 30 Volts DC/ 250
Volts AC
<Current Outputs:
4-20mA DC into a maximum external loop resistance of 600 Ohms at 18-32
Volts DC
<Dimensions:
Refer to Figure 1
<Shipping Weight (approximate):
2 lbs (0.9 kilograms)
<Certification:
CSA, NRTL/C, NEMA 4X certified for hazardous locations
Class 1, Division 1, Groups B, C and D
IEC approval (Class 1, Zone 1 Groups IIB+H2 T5)
<System Sensitivity:
Sensitivity for the standard controller is field adjustable over a range of 8 through
120 counts per second (cps) in increments of 8 cps. The maximum response
distance is achieved at an 8 cps sensitivity setting. For applications involving high
background radiation potential, the system can be de-sensitized by increasing the
count rate required to actuate alarms. The 120 cps setting is the lowest
sensitivity.
<Response Time:
Response to a saturating (high intensity) UV source is typically 10 milliseconds for
the instant alarm outputs and 0.5 seconds for the area alarm outputs when
sensitivity is set for 8 cps and time delay is set for 0.5 seconds (minimum
settings).
Figure 1 - Controller Dimensions
DETECTOR SPECIFICATIONS
<Operating Voltage:
290Vdc ± 3Vdc (provided for controller)
- 2 -
<Power Consumption (each detector):
0.29 Watts nominal, 0.5 Watts maximum
1 mA nominal, 1.7 mA maximum
<Temperature Range:
Operating:-40ºC to +125ºC(-40ºF to +257ºF)
Storage:-55ºC to +150ºC(-65ºF to +302ºF)
<Dimensions:
Refer to Figures 2a and 2b
<Detector Enclosure Materials:
Available in anodized copper-free aluminum or optional stainless steel
<Shipping Weight (approximate):
2 lbs (0.9 kilograms)
<Certification:
CSA, NRTL/C, NEMA 4X certified for hazardous locations
Class 1, Division 1, Groups B, C and D
IEC approval (Class 1, Zone 1 Groups IIB+H2 T5)
<Spectral Sensitivity Range:
The detector responds to UV radiation over the range of 185 to 260 nanometres
(1850 to 2600 angstroms)
<Cone of Vision:
The Detector has a nominal 120 degree cone of vision
Figure 2a - Detector Dimensions
Figure 2b - Swivel Mount
Dimensions
- 3 -
BASIC OPERATION - CONTROLLER
CONTROLLER FACEPLATE DESCRIPTION
The controller faceplate provides LEDs and two digital displays for identifying status conditions, a
bar graph display for indicating an alarm condition and MENU/SET and SELECT/RESET push-
button switches (See appendix for instructions on activation) for testing and resetting the system.
Refer to Figure 3.
Figure 3 - Controller Face-Plate
<Digital Displays - The left side of the digital display is normally off. If a fire alarm
or visual integrity fault is detected, it indicates the channel number of the alarm or
fault. The digital displays indicate system status including system error codes,
visual integrity (vi) faults, system faults or fire alarms. The right side of the
display shows ‘nor’ in normal operating mode. If more than one channel is in an
alarm or fault condition the digital displays will cycle through these channels.
Since at least one side of the display is always lit they also function as a power
indicator.
<Bar Graph Display - Normally off. Flashing when fire detected in any area.
<Instant LED - (no time delay) Flashes when any detector signal exceeds the fire
sensitivity setting.
<Area 1 & 2 LEDs - (Area 1 only for U1F) If the selected “voting” criteria of the
area and the preset time delay has elapsed the corresponding LED starts
flashing.
<Fault LED - flashes upon detection of an overall system fault or vi fault.
<Channel LEDs - (1, 2 or 4 depending on m odel) flash to indicate detector in
alarm and remain illuminated until reset after an alarm condition has returned to
normal.
<MENU/SET Reed Switch - is used to enter the main menu, to toggle through
menu selections and in conjunction with the SELECT/RESET Reed Sw itch to
enter the special functions menu.
<SELECT/RESET Reed Switch - is used for a basic system reset, menu selection
and with the MENU/SET Reed Sw itch to enter the special functions m enu. This
switch is also used during the m anual vi test.
- 4 -
OUTPUTS
Relay Outputs:
The Instant, Area and Fault relays have SPDT contacts rated 5 Amps at 30 Volts DC or 250 Volts
AC.
The Instant and Area alarm relays are programmable for either normally energized or norm ally
de-energized operation and for latching or non-latching (programmable as a group not
individually). The fault relay is only normally energized. The relays can be configured with jumpers
for normally open or normally closed contacts.
RECOMMENDATION
The fault relay output should not be used to activate an automatic shutdown procedure.
The fault output indicates a potential problem with the controller, not an alarm condition.
Refer to Table 1 for a summary of the relay programming options.
Selectable Normally
OUTPUT
1
AREAYYY
Open/Closed
Selectable Normally
Energized/De-Energized
Selectable
Latching/Non-Latching
INSTANTYYY
FAULTYNN
23
Table 1 - Selectable Output Options
1
2
3
Area alarms are programmed together, not individually.
Fault relay is normally energized.
Fault relay is non-latching.
Current Outputs:
4-20 mA DC current outputs transmit system inform ation to other devices. The current outputs
can be wired for isolated or non-isolated operation by changing the jumpers as shown in Figure 4.
Refer to Unit IV, System Operation for a description of the current output signal levels.
- 5 -
Figure 4 - Jumper Selection for Isolated or Non-Isolated Current Outputs
PROGRAMMING OPTIONS
DIP switches located on the circuit board are used to “program” various options including:
<channel selection,
<system sensitivity,
<fire area voting logic,
<time delay for fire area alarms,
<relay latching/non-latching selection, and
<relay energized/de-energized selection.
NOTE
Power to the controller must be cycled to make dip switch changes take effect.
EXTERNAL RESET
A normally open, momentary closure switch connected between the external reset terminal and
the negative power terminal provides remote reset.
AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION
The microprocessor-based controller features self-testing circuitry that continuously checks for
problems that could prevent proper system response. When power is applied, the microprocessor
autom atically tests memory. In the Norm al Operating Mode it continuously monitors the system to
ensure proper functioning. A "watchdog" timer is maintained to ensure that the program is running
correctly.
The main loop of the operating program continuously cycles through the Automatic Visual Integrity
test, checking each detector and its wiring. The microprocessor can be interrupted by
- 6 -
(Automatic Diagnostics and Fault Identification Cont)
any one of several status changes such as a fault or a "fire" signal from one of the detection areas
to take appropriate action.
If a system or vi fault is detected the Fault LED flashes, digital displays and current outputs
identify the nature of the fault and the fault relay is de-energized.
VOTING LOGIC (not applicable to U1F)
The controller can be DIP switch configured for either one or two monitoring areas. For a one
area configuration, all channels are considered as being in Area 1 and both Area alarm relays will
be activated together.
The dip switches can be set so that only one channel need be in alarm to activate the area alarm
or any two channels must ‘vote’ (see a fire at the same time) to activate the area alarm. The
instant alarm will be activated when any channel sees UV radiation exceeding the preset
sensitivity setting, no matter what voting option is being used.
For a two area configuration, channel one (one and two for U4F) make up Area 1 and channel
three (three and four for U4F) make up Area 2. With the U4F each Area alarm may be
programmed with different voting criteria (ie. Area 1 may be set so that either channel one OR
channel two may activate the area alarm, and Area 2 may be set so that both channels three AND
four must see the fire at the same time to activate the Area alarm).
DETECTOR
The detector responds to UV radiation over the range of 185 to 260 nanometers. It is not
sensitive to direct or reflected sunlight nor to normal artificial lighting.
The detector is housed in an explosion-proof enclosure that is designed to meet most national and
international standards. It is available in anodized alum inum or optional stainless steel.
The detector is typically mounted with a swivel mounting assembly which is recommended. Other
mounting arrangements are possible.
Unit II UV FIRE DETECTION
SYSTEM APPLICATION
The detector responds instantly to ultraviolet radiation emitted by a flame. It is designed for use in
hazardous locations and is suitable for use in outdoor applications.
Typical applications for UV detection systems are:
<around highly combustible m aterials
<if instantaneous response to flame is needed
<where automated fire protection is required
<to protect large capital investments
<butane and propane loading and storage
<pipeline compressor stations
<gas gathering facilities
<LNG loading, transfer and storage
<hydrogen
<gas turbines
Other Processes
<paint spray booths
<chemical and petrochemical production
<powder coating booths
Automated fire protection systems also have applications in any manufacturing or research
facility where the potential of fire may be low to moderate but the losses due to a fire would be
high.
DETECTOR SENSITIVITY
SPECTRAL SENSITIVITY RANGE
The UV fire detector responds to radiation wavelengths of 185 to 260 nanometres (1850 to 2600
angstroms). Figure 5 illustrates the range of sensitivity and compares this range to other forms of
radiation. Note that UV radiation reaching the earth from the sun does not extend into the
sensitivity range of the detector. Nor does radiation from normal artificial lighting, such as
fluorescent, mercury vapor and incandescent lamps.
Figure 5 - Various Spectral Distributions
NOTE
Some mercury vapor lamps can operate for extended periods with cracked or damaged
envelopes and will then emit UV radiation in the range of the detector. Remove defective
mercury vapor lamps from service.
- 8 -
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.