Emerson TS1-A1A, TS1-A2P, TS1-A3P, TS1-A2A, TS1-A3A Datasheet

...
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 1 / 8 10.08.2011
Adjustable temperature controls for refrigeration applications.
Features
Flush mounted version
Adjustable temperatures and differentials
Range and differential pointer in units °C and °F
Range and differential individually lockable by wire seal
High rated SPDT contacts for all versions
Captive terminal and cover screws
Manual toggle for system checkout and override
Vapour and x-ambient charges
Sensor shapes for various applications
Bellows heater for thermostats with vapour charge (not for
frost monitors)
Room thermostats with insulation console
Versions with and without manual override
Options
Gold plated contacts for electronic applications
(PLC, low voltage/current)
Factory set to customer specification
Different types of mounting brackets
Sensor bulb wells and capillary tube holders
Special approvals
Introduction
The TS1 Series is ALCO’s range of adjustable thermostats for application in refrigeration and heat pump systems.
In these systems, thermostats serve control and monitoring functions, such as space temperature control, high/low temperature alarming or defrost termination. By operating a set of electrical contacts, a temperature value is kept inside a certain limit.
Several housing variants and sensors are provided in order to suit a control to a specific application.
Housing variants
TS1 controls can be delivered in three main housing variants, top operated, front operated and flush mounted.
Top operated controls have adjustment spindles at the top and a display scale, indicating temperature setpoint and differential, at the front. A knob which may be permanently plugged onto one of the adjustment spindles comes with every control. Frost monitors and room thermostats are derivatives of top operated thermostats. They differ by their sensors and other features to suit their particular target applications.
Front operated controls have an adjustment knob at the front for the temperature setpoint with an approximate scale imprinted on
the knob. In order to adjust the temperature differential, the cover of the control must be removed.
Flush mounted controls are designed in a way that they can be integrated into a panel or housing, for example into display cases.
All of these three variants are available either with or without off-switch, which cuts off power supply to the thermostat in off position
Temperature sensing
TS1 thermostats sense temperature by means of a thermal system, consisting of temperature charge, bulb, capillary and bellows. The temperature charge changes its pressure based on the refrigerant temperature to be sensed. The sensor is the portion of the system which is in thermal contact with the refrigerant, the capillary connects the sensor with the bellows and the bellows contracts or expands depending on the temperature, causing the thermostat to operate the electrical contacts. An exception are capillary type of sensors, which do not have a bulb, instead, their capillary serves as the bulb directly.
TS1 Flush Mounted
TS1 FrontOperated
TS1 Top Operated
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 2 / 8 10.08.2011
Charges and sensor types are matched to temperature ranges and other application specific characteristics. TS1 thermostats come with two charge types: vapour and adsorption charges. The application temperature range covered by each charge type is shown below:
Vapour charge – Sensor type A, E, P
These sensing elements always sense from the coldest point on the capillary, coil, bulb or power element head. For proper operation it must be ensured that this coldest point is at the sensor portion which is exposed to the medium tempereature to be sensed. The sensing location should be at least 2K colder than the other parts of the thermal system.
In order to avoid unwanted effects of heat transfer, e.g. from a cold wall, ALCO vapour charged thermostats come with an integrated bellows heater (not for frost monitors), which is rated for 230V applications. For other applications the heater must be disabled, alternatively, a bellows heater with a different rating may be available.
In addition to the bellows heater, room thermostats are supplied with an insulation console for the same reason.
Sensor type ‘A’ is a coiled bulb sensor with two meter capillary, which may be used with or without a bulb well. Style ‘E’ is a coil sensor for space temperature sensing, and type ‘P’ is a capillary type of sensor which can be wrapped around a heat heat exchanger’s surface in order to sense the coldest point on the heat exchanger for frost protection applications.
Vapour charges respond faster to temperature changes than adsorption and liquid charges.
Adsorption charge – sensor type F
Adsorption charged sensor types operate on the basis of a temperature dependent adsorption material, which is located inside the bulb only. Therefore these sensor types always respond to temperature changes at the bulb only. This makes them suitable to applications where it is not always defined which part of the thermal system the coldest point is (cross ambient applications). An example for such applications is defrost control.
Adsorption charges are slower in response to temperature changes than vapour charges.
Setpoints
TS1 are adjustable controls with adjustment spindles for range and differential*. By turning the range spindle, the upper setpoint is defined and by adjusting the differential spindle, the differential and hence the lower setpoint is defined.
The dependency between upper and lower setpoint is always as follows:
lower setpoint = upper setpoint – differential
The following two rules should be kept in mind:
an adjustment of the range spindle always affects both,
upper and
lower setpoint.
an adjustment of the differential spindle affects the lower
setpoint, only.
The following diagrammes depict this dependency:
Effect of turning range spindle
Effect of turning differential spindle
The controls are equipped with display scale and pointers to indicate the approximate settings. Top operated controls have display scales in units °C and °F, front operated controls have a display scale in units °C.
For precise setting of the controls, external thermometers must be used.
*) Manual reset controls and some other controls have a fixed differential and no differential spindle
 = constant
= variable
-100 -50 0 50 100 150 200
Adsorption Charge
Vapour Charge
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 3 / 8 10.08.2011
Electrical contacts
TS1 temperature controls are equipped with high rated double snap action contacts for shatter-free and reliable operation.
All contacts throughout this range of controls are designed as Single Pole Double Throw (SPDT) contacts. One contact may be used for control and the other contact for alarm/status indication or auxilliary control.
Gold plated contacts are available on request for low electrical loads, for example in electronic signalling applications.
For applications using a supply voltage other than 230V and for applications using gold plated contacts, the bellows heater of vapour charged thermostats (sensor style A, E or P – not for frost monitors function C or D) must be disabled.
Contact function
Thermostat contacts TS1 are labelled 1-2-4 where ‘1’ refers to the common pole, ‘2’ refers to the lower setpoint and ‘4’ refers to the upper setpoint.
The contact function for automatic and manual reset versions is as described below.
Automatic reset
On temperature rise above the upper setpoint, contacts 1-2 open and contacts 1-4 close. On decreasing temperature lower setpoint contacts 1-4 open and contacts 1-2 close.
Automatic reset contact function
Manual reset low temperature
On decreasing temperature below the lower setpoint, contacts 1-4 open, contacts 1-2 close and latch. Only on pressure rise above upper setpoint and after pressing the manual reset button contacts 1-2 will open and contacts 1-4 will close again.
Manual reset low pressure contact function
Manual reset high temperature
On increasing temperature above the upper setpoint, contacts 1-2 open, contacts 1-4 close and latch. Only on falling temperature below lower setpoint and
after pressing the manual reset button, contacts 1-4 will open and contacts 1-2 will close again.
Manual reset high temperature contact function
For operational safety, all TS1 with manual reset are designed as trip-free controls, i.e. pressing the manual reset button while the temperature has not reached its reset treshold will not operate the electrical contacts.
Off-switch
TS1-B/F/H with an off-switch (TS1-B/F/H) cut off the line to terminal 1 when in Position “STOP”.
Off-switch interrupting line to terminal 1
Bellows heater
TS1 with vapour charges, ie. sensor types A, E, P (not frost monitors function C or D) have a bellows heater wired across the contacts in the following way.
Bellows heater
Installation and maintenance
Controls come with an adjustment knob and a lockplate which may be used to protect the settings by wire-seal if desired. Range and differential spindle may be sealed independent from each other.
A front access manual toggle is provided for checking out control operation. All TS1 controls come with heavy duty terminal blocks which are finger-proof and feature wire clamps plus non-loosable terminal screws for ease of wiring.
Available accessories include mounting brackets of various types, sensor bulb wells and capillary tube holders.
The standard mounting holes for mounting brackets are equipped with a universal thread to fit both, M4 and UNC 8-32 screws. The standard wholesale package includes two mounting screws.
In addition, further hole patterns for surface mounting are provided.
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 4 / 8 10.08.2011
Nomenclature
The following chart explains the nomenclature of the TS1 controls for ease of reference. The basic structure is that of a three digit Product Name followed by a three digit code, describing Function, Temperature Range and Temperature
Sensor.
Customised versions, which deviate from standard catalogue products are available on request and use a different Product Name. They are called TSA followed by the three digit code to indicate function, temperature range and temperature sensor.
Technical data
Environmental conditions Electrical contacts
Ambient temperatures Type of contacts 1 x SPDT contact
storage and transportation:
operation:
-50 °C to +70 °C
-50 °C to +70 °C
Contact material - standard:
- options:
CuAg
3
gold plated contacts
Maximum temperature at sensor bulb depending on bulb Heating load (AC1): 24A / 230 V AC
Locked rotor / Startup (AC3): 144A / 230 V AC
type and charge Inductive load (AC15): 10A / 230 V AC
Dust and water protection
EN 60529 / IEC 529: Control mounted flush against wall!
IP44 (w/o off-switch) IP30 (with off-switch)
Inductive load (DC13):
0.1A / 230 V DC 3A / 24 V DC 6A / 12 V DC
Vibration resistance: 4 g @ 10 … 1000 Hz Motor rating UL (FLA): 24A / 120/240V AC
Approvals
Locked rotor UL (LRA): 144A / 120/240V AC
Low Voltage Directive all models Bellows heater (sensor types A, E, P -
73/23/EWG 93/68/EWG; EN 60947-1 / 60947-5-1 / 60730-2-9
(CE-Label) not for frost monitors function C or D):
- option:
82 k, 230V AC, DC 12V, 24V rating
Germanic Lloyd: standard models
Materials
when used with marine cable glands (accessory) Housing materials
cover:
Polycarbonate (PC)
UL / CSA:
all models (pending)
frame: Steel, yellow chromated
Type code
TS1
-
Function / housing variant
A = Wall mounting, top adjustment
B = Wall mouting, top adjustment, off-switch
C = Frost monitor, auto reset
D = Frost monitor, manual reset
E = Wall mounting, front adjustment
F = Wall mounting, front adjustment, off-switch
G = Flush mounting
H = Flush mounting, off-switch
R = Wall mounting, top adjustment, manual reset*
*temp. ranges 0 – 4: manual reset for falling temperature
temp. ranges 5 – 9: manual reset for rising temperature
Temperature Sensor Type
A = Vapour charge, 2 m, bulb
E = Vapour charge, 0 m, coil
F = Adsorption charge, 2 m, bulb
P = Vapour charge, 2 m, capillary
function „C“ and „D“: 6 m capillary
Tempera
ture range
0 = +4.5 … + 20 °C
1 = -45 … -10 °C
2 = -30 … +15 °C (-30 … +10 °C)
3 = -10 … +35 °C (-10 … +25 °C)
4 = -25 … +30 °C (-30 … +35 °C)
5 = +20 … +60 °C (+25 … +75 °C)
6 = +50 … +100 °C
7 = 0 … +10 °C
() = dep. on exact version
Product Name
TS1 = Adjustable thermostat
TSA = Customised version
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 5 / 8 10.08.2011
Physical dimensions and drawings
TS1-Axx / Bxx / Cxx / Dxx TS1-Exx / Fxx
TS1-Gxx / Hxx
Sensor type A
Vapour charge
2 m capillary
with bulb
Sensor type P
Vapour charge
2 m capillary
(6m with function C
or D)
Sensor type E
Vapour charge
coil, 0 m
Sensor type F
Adsorption charge
2 m capillary
with bulb
54
70
Ø 9
2
2,5
Ø 9,5
70
Ø 22
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 6 / 8 10.08.2011
Standard Temperature Controls
Temperature controls should be selected such, that the target upper and lower setpoints fall well inside the adjustment range and not at the end of the specified range.
Type
Part Adjustment
Range Lowest Factory Max. Temp. Sensor
No.
Upper
Setpoint
°C
Differential
Setpoint
K
Setpoint
°C
Setting
°C
Bulb
Temp.
°C
Charge Type
Thermostats TS1 Top Operated (with capillary type sensor)
Thermostats without Off-Switch
TS1-A2P 4 530 400 -30 … +15 1.5 … 16 -36 -1 / -6 +150 2m TS1-A3P 4 356 700 -10 … +35 1.5 … 16 -23 +3 / -2 Vapour capillary TS1-A1A 4 351 500 -45 … -10 -55 -18 / -20
TS1-A2A4 351 600
-30 … +15 1.5 … 16 -36 -1 / -6 +150 2m
TS1-A3A
4 352 500
-10 … +35 -23 +3 / -2 capillary
TS1-A4F
4 351 800
-30 … +35 2.8 … 20 -35 +5 / 0 and
Defrost- and Universal
Thermostat
+100 Adsorption bulb
TS1-A5F 4 458 400 +20 … +60 3 … 10 +10 +35 / +30
Thermostats with Off-Switch
TS1-B1A 4 366 700 -45 … -10 -55 -18 / -20 2 m TS1-B2A 4 366 800 -30 … +15 1.5 … 16 -36 -1 / -6 +150 Vapour capillary TS1-B3A 4 366 900 -10 … +35 -23 +3 / -2 and TS1-B4F 4 367 000 -30 … +35 2.8 … 20 -35 +5 / 0 +100 Adsorption bulb
Room Thermostats TS1 Top Operated (with coil type sensor)
Room Thermostats without Off-Switch, including insulation console
TS1-A1E 4 362 800 -45 … -10 -55 -18 / -20 0 m TS1-A2E 4 355 200 -30 … +15 1.5 … 16 -36 +4 / +2 +70 Vapour coil TS1-A3E 4 355 300 -10 … +35 -23 +20 / +18
Room Thermostats with Off-Switch, including insulation console
TS1-B2E 4 344 400 -30 … +15 1.5 … 16 -36 +4 / +2 +70 Vapour 0 m TS1-B3E 4 344 500 -10 … +35 -23 +20 / +18 coil
Frost Monitors TS1 Top Operated (with capillary type sensor)
Frost Monitors without Off-Switch
TS1-C0P 4 352 100 +4.5 … +20 2.5 fix +2 4.5 / +2 6 m TS1-D0P 4 352 200 +4.5 … +20 man. reset +2 +2 +150 Vapour capillary
Low temp. cut out
ca. 2.5 fix
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 7 / 8 10.08.2011
Type
Part Adjustment
Range Lowest Factory Max. Temp. Sensor
No.
Upper
Setpoint
°C
Differential
Setpoint
K
Setpoint
°C
Setting
°C
Bulb
Temp.
°C
Charge Type
Thermostats TS1 Front Operated (with capillary type sensor)
Thermostats without Off-Switch
TS1-E1A 4 361 000 -45 … -10 2 … 16 -55 -18 / -20 TS1-E2A 4 356 200 -30 … +10 1.5 … 15 -36 +4 / +2 +150 Vapour TS1-E3A 4 365 200 -10 … +25 1.5 … 15 -23 +3 / -2 2 m
TS1-E4F
4 367 500
-25 … +30 2.8 … 20 -30 +5 / 0 capillary
Defrost- and Universal Thermostat
and TS1-E5F 4 338 100 +20 … +60 3 … 10 +10 +35 / +30 +100 Adsorption bulb TS1-E7F 4 367 600 +0 … +10 2.5 fix -2.5 +5.5 / +3
Milk and beer Cooler Thermostat
Thermostats with Off-Switch
TS1-F1A 4 367 100 -45 … -10 2 … 16 -55 -18 / -20 2 m TS1-F2A 4 367 200 -30 … +10 1.5 … 15 -36 -1 / -6 +150 Vapour capillary TS1-F3A 4 367 400 -10 … +25 1.5 … 15 -23 +3 / -2 and bulb
Room Thermostats TS1 Front Operated (with coil type sensor)
Room Thermostats without Off-Switch, including insulation console
TS1-E1E 4 365 300 -45 … -10 2 … 16 -55 -18 / -20 0 m TS1-E2E 4 356 800 -30 … +10 1.5 … 15 -36 +4 / +2 +70 Vapour coil TS1-E3E 4 356 900 -10 … +25 1.5 … 15 -23 +20 / +18
Room Thermostats with Off-Switch, including insulation console
TS1-F1E 4 368 000 -45 … -10 2 … 16 -55 -18 / -20 TS1-F2E 4 368 100 -30 … +10 1.5 … 15 -36 +4 / +2 +70 Vapour 0 m TS1-F3E 4 368 200 -10 … +25 1.5 … 15 -23 +20 / +18 coil
Thermostats TS1 for Flush Mounting (with coil type sensor)
Thermostats for Flush Mounting without Off-Switch
TS1-G2A 4 355 400 -30 … +15 1.5 … 15 -36 +4 / +2 +150 Vapour 2 m TS1-G3A 4 364 800 -10 … +35 1.5 … 15 -23 +20 / +18 capillary TS1-G4F 4 355 600 -30 … +35 2.8 … 20 -35 +5 / 0 and
Defrost- and Universal Thermostat
+100 Adsorption bulb TS1-G7F 4 356 000 0 … +10 2.5 fix -2.5 +5.5 / +3
Milk and beer Cooler Thermostat
Thermostats for Flush Mounting with Off-Switch
TS1-H1A 4 364 600 -45 … -10 1.5 … 15 -55 -18 / -20 TS1-H2A 4 355 500 -30 … +15 1.5 … 15 -36 -1 / -6 +150 Vapour 2 m TS1-H3A 4 367 900 -10 … +35 1.5 … 15 -23 +3 / +2 capillary TS1-H4F 4 355 800 -30 … +35 2.8 … 20 -35 +5 / 0 and TS1-H7F 4 365 500 0 … +10 2.5 fix -2.5 +5.5 / 3 +100 Adsorption bulb
Milk and beer Cooler Thermostat
TS1 Series
Temperature Controls
Alco Controls
D A T A S H E E T
TS1__35038_EN_R05.doc 8 / 8 10.08.2011
Accessories
Universal mounting bracket
803 801 (incl. screws)
Mounting bracket angle
803 799 (incl. screws)
Extension bracket
803 800 (incl. screws)
Insulation console
803 777
room thermostats: standard
1
4
Ø 5,5
6
20
2
8
R1/2
19 27
SW 27
Ca
pillary tube holder,
5 pcs
803 778
frost monitors: standard
Capillary tube gland, brass,
For sensors A + C
803 807
Mounting angle for TS1
-
G, -H
803 805
ALCO CONTROLS is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information given herein is based on technical data and tests which ALCO CONTROLS believes to be reliable and which are in compliance with technical knowledge of today. It is intended only for use by persons having the appropriate technical knowledge and
skills, at their own discretion and risk. Our products are designed and adapted for fixed locations. For mobile applications failures may occur. The suitability for this has to be assured from the plant manufacturer which may include making appropriate tests. Since conditions of use are outside of ALCO'S control we can not assume any liability for results obtained or damages occurred due to improper application. This document replaces all earlier versions.
Emerson Electric GmbH & Co OHG
ALCO CONTROLS
Postfach 1251
Heerstraße 111
D-71332 Waiblingen
Germany
Phone ...49-7151-509-0
Fax ...49-7151-509-200
www.emersonclimate.eu
Benelux Germany, Austria & Switzerland France, Greece, Maghreb Italia Spain & Portugal UK & Ireland Sweden, Denmark, Norway & Finland Eastern Europe & Turkey Poland Russia & Cis Balkan Romania Ukraine
Phone:
+31 (0)77 324 0 234 +49 (0)6109 6059 -0 +33 (0)4 78 66 85 70 +39 02 961 781 +34 93 41 23 752 +44 (0) 1635 876 161 +49 (0)2408 929 0 +49 (0)2408 929 0 +48 (0)22 458 9205 +7 495 981 9811 +385 (0) 1560 38 75 +40 364 73 11 72 +38 44 4 92 99 24
Fax:
+31 (0)77 324 0 235 +49 (0)6109 6059 40 +33 (0)4 78 66 85 71 +39 02 961 788 888 +34 93 41 24 2 +44 (0) 1635 877 111 +49 (0)2408 929 528 +49 (0)2408 929 525 +48 (0)22 458 9255 +7 495 981 9816 +385 (0) 1 560 3879 +40 364 73 12 98 +38 44 4 92 99 28
12,625,212,6
82
65
50,5 25,2
25,225,212,6
5
120
41
4
0
1
8
2
5
12,5
Ø 4,5
25
30
2
5
2
5
25
M4
12,5
Ø 4,5
44
70 ±0,2
4,8
30
15,5
83
3011
48
Loading...