WARNING! The enclosure should
never be opened. Warranty void if
seal is tampered with or removed.
FCC COMPLIANCE NOTICE
This device complies with Part 15 of the FCC Rules Class A. Operation is subject to
the following two conditions: (1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may
cause undesired operation.
CE COMPLIANCE NOTICE
Class A Product Information for Supervisory Controllers:
The Emerson Supervisory Controllers are Class A products. In a domestic
environment this product may cause radio interference in which case the user may be
required to take adequate measures.
ULE211299
ELECTROSTATIC DISCHARGE CAUTION
This integrated circuit can be damaged by ESD. Failure to observe proper handling and
installation procedures can cause damage. ESD damage can range from subtle
performance degradation to complete device failure. Precision integrated circuits may
be more susceptible to damage because very small parametric changes may cause the
device to not meet its published specifications.
CONTENTS
1 BASIC SETUP INFORMATION ............................................................................................................................. 1-1
2.2.1.1 User View Details.................................................................................................................................................... 2-2
2.3 BASIC SCREEN ELEMENTS ......................................................................................................................................... 2-2
2.6.2 Site Aggregation ................................................................................................................................................. 2-4
2.6.3 Control Inventory ............................................................................................................................................... 2-5
SINGTHE HELP MENU ............................................................................................................................................. 2-7
2.10 I
CONSOR BUTTONS APPEARINGONTHE HOME SCREEN ........................................................................................ 2-8
5 RS485 I/O NETWORK BOARDS AND PERIPHERALS ..................................................................................... 5-1
5.1 T
HE I/O NETWORK..................................................................................................................................................... 5-1
5.2.3 MultiFlex RTU Support ...................................................................................................................................... 5-3
5.2.3.1 I/O Network and MultiFlex RTU Setup on Serial Port........................................................................................... 5-3
5.2.3.2 Creating an Instance of RTU Application...............................................................................................................
5.2.3.3 Deleting/Checking Status of RTU Board................................................................................................................
5.2.3.4 Zone Management...................................................................................................................................................
5.2.3.7 Real Time Clock Updates .......................................................................................................................................
5.2.4 MultiFlex RCB Support ...................................................................................................................................... 5-4
5.2.4.1 I/O Network and MultiFlex RCB Setup on Serial Port........................................................................................... 5-4
5.2.4.2 Creating an Instance of RCB Application...............................................................................................................
5.2.4.3 Deleting/Checking Status of RCB Board................................................................................................................
5.2.4.4 Zone Management...................................................................................................................................................
5.2.4.7 Real Time Clock Updates .......................................................................................................................................
5.2.9 The 8RO and 8ROSMT Relay Boards ................................................................................................................ 5-8
5.2.10 4AO Analog Output Board ............................................................................................................................... 5-9
5.2.11 8DO Digital Output Board ............................................................................................................................... 5-9
5.
2.12 XM Series of Case Controllers ......................................................................................................................... 5-9
5.2.12.2 XM679K v3.4 and v4.2.........................................................................................................................................
5.2.12.3 XM678D v2.5 and v2.8.......................................................................................................................................
5-9
5-10
5.2.13 XEV22 v1.1 and v1.5 ...................................................................................................................................... 5-10
7.1.4 Direct Connect to Site Supervisor...................................................................................................................... 7-3
7.2.4 Direct Connect to Site Supervisor...................................................................................................................... 7-5
7.3.4 Direct Connect to Site Supervisor...................................................................................................................... 7-8
7.4 S
ITE SUPERVISOR TOUCHSCREEN DISPLAY VERSION COMPATIBILITY..................................................................... 7-9
MERSON SUPERVISORY CONTROL NEW FEATURES .............................................................................................. 8-11
8.7 S
UCTION GROUPS .................................................................................................................................................... 8-12
8.7.2 The (Standard) Suction Group Application ..................................................................................................... 8-12
8.7.2.1 Overview of PID Control Strategy ........................................................................................................................ 8-12
8.7.3 The Enhanced Suction Group Application....................................................................................................... 8-12
8.7.3.3 The Control/Cycles Parameter............................................................................................................................... 8-13
8.7.3.4 Variable-Speed, Digital Scroll, and Digital Discus Compressor Support ............................................................. 8-13
NALOG SENSOR CONTROL .................................................................................................................................... 8-14
8.8.1 Control Strategy............................................................................................................................................... 8-14
8.8.2 Control Alarming ............................................................................................................................................. 8-15
8.8.3 Alarm Output When On/Off Parameters.......................................................................................................... 8-15
8.8.4 Control Bypass................................................................................................................................................. 8-15
8.9.1 Control Strategy............................................................................................................................................... 8-16
8.9.3 Alarm Output When On/Off Parameters.......................................................................................................... 8-16
Supervisory Controller 2.13 Installation and Operation Manual Table of Contents • vii
8.9.4 Control Bypass ................................................................................................................................................. 8-16
8.10 L
IGHTING CONTROL .............................................................................................................................................. 8-17
8.10.1 Lighting Control Logic................................................................................................................................... 8-17
8.10.3 Solar Calculation ........................................................................................................................................... 8-17
8.10.4 Digital Lighting Output.................................................................................................................................. 8-18
8.12.4 Heating and Cooling Control......................................................................................................................... 8-21
8.12.5 Control Logic ................................................................................................................................................. 8-21
8.12.6 Heat/Cool Lockout Based on Outside Air Temperature ................................................................................ 8-22
8.12.7 System Shutdown............................................................................................................................................ 8-22
8.12.8 Fan Control.................................................................................................................................................... 8-22
8.12.9 Fan Mode ....................................................................................................................................................... 8-22
8.12.11 Fan Proof Failure ........................................................................................................................................ 8-22
8.12.12 System Shutdown.......................................................................................................................................... 8-22
8.12.14 Determine the Analog Damper Position ...................................................................................................... 8-23
8.12.15 Determine the Digital Damper Position ...................................................................................................... 8-24
8.12.16 Heat Pump Control ...................................................................................................................................... 8-24
IME SCHEDULE APPLICATION.............................................................................................................................. 8-24
8.13.1 Time Schedule Method ................................................................................................................................... 8-24
8.13.2 Standard Schedule.......................................................................................................................................... 8-25
8.13.8 Control Override............................................................................................................................................ 8-28
8.13.9 Control Bypass ............................................................................................................................................... 8-28
8.13.10 Control Override.......................................................................................................................................... 8-28
8.13.11 Special Conditions........................................................................................................................................ 8-28
8.13.12 Priority of Services....................................................................................................................................... 8-28
8.13.13 Control Alarming ......................................................................................................................................... 8-29
8.15.1.2 Analog Input ........................................................................................................................................................ 8-31
8.15.1.3 Digital Pulse Input ............................................................................................................................................... 8-31
8.15.2.2 Fixed Period Totalizers........................................................................................................................................ 8-31
8.15.3.2 Average Rate of Consumption Output................................................................................................................. 8-32
8.15.3.4 Time In Shed Output............................................................................................................................................ 8-32
8.15.4 Application Specific Logs............................................................................................................................... 8-32
8.15.5 Units of Measurement .................................................................................................................................... 8-32
8.16.2.1 Power Monitoring Input....................................................................................................................................... 8-33
8.17.2 Adding and Deleting Onboard I/O Application............................................................................................. 8-34
8.17.3 Status and Detail Screen ................................................................................................................................ 8-35
AND 2.6............................................................................................................................................ 8-36
ASE DISPLAY....................................................................................................................................... 8-42
8.23.1 General Control ............................................................................................................................................. 8-45
ATA LOGGINGAND GRAPH................................................................................................................................. 8-46
8.28.1 Communication .............................................................................................................................................. 8-47
8.32.1 How It Works.................................................................................................................................................. 8-49
8.32.2 Compatible Applications to be Connected to HVAC Zones........................................................................... 8-49
8.32.3 Temperature Control...................................................................................................................................... 8-50
8.32.4 HVAC Zone Temperature............................................................................................................................... 8-50
8.32.5 Economizer Control ....................................................................................................................................... 8-50
8.32.7 The Effect of Enabling Economization........................................................................................................... 8-51
8.32.8 Dehumidification Control .............................................................................................................................. 8-51
8.32.9 HVAC Zone Humidity Input ........................................................................................................................... 8-51
8.33 AHU ...................................................................................................................................................................... 8-53
8.34 A
8.35 A
8.36 C
NALOGAND DIGITAL COMBINER ........................................................................................................................ 8-53
NTI-SWEAT CONTROL ......................................................................................................................................... 8-54
8.36.3 Fan Control.................................................................................................................................................... 8-55
8.36.5 Fast Recovery................................................................................................................................................. 8-55
ASE CONTROL CIRCUITS ..................................................................................................................................... 8-57
8.38.2 Case Circuit Control Software Overview....................................................................................................... 8-57
8.38.4 Defrost Control ............................................................................................................................................. 8-59
8.39 IRRIGATION CONTROL ........................................................................................................................................... 8-60
8.40.2 Temperature Differential (TD) Strategy ........................................................................................................ 8-61
8.40.3 TD Control Fail-Safes.................................................................................................................................... 8-61
OOP/SEQUENCE CONTROL ................................................................................................................................... 8-62
x • Table of Contents026-1800 Rev 18
8.42 MODULAR CHILLER CONTROL .............................................................................................................................. 8-63
8.42.3.1 Digital Scroll Compressor.................................................................................................................................... 8-64
8.42.3.2 Variable Frequency Drive Compressor ............................................................................................................... 8-65
IRCUIT CONTROL ......................................................................................................................................... 8-65
8.43.1.1 Case Circuit Association Support ........................................................................................................................ 8-65
8.43.1.2 Dual Association Not Supported ......................................................................................................................... 8-66
8.43.1.4 Visibility of Associated Parameters..................................................................................................................... 8-66
8.43.2 Suction Group Interaction ............................................................................................................................. 8-66
8.43.2.1 Standard Suction .................................................................................................................................................. 8-66
8.43.3 Supervisory Control Functions ...................................................................................................................... 8-66
8.43.3.1 Dewpoint Value ................................................................................................................................................... 8-66
8.43.3.5 Case States ........................................................................................................................................................... 8-67
8.43.3.6 Case Type............................................................................................................................................................. 8-67
ASE DISPLAY....................................................................................................................................... 8-68
APPENDIX E: PEER TO PEER NETWORK SETUP FOR MIXED SITES (2 SUPERVISORS AND 1 E2) .. E-1
Supervisory Controller 2.13 Installation and Operation Manual Table of Contents • xi
1Basic Setup
Information
1.1Ethernet Connection
1.ETH1 is designed to be used for directly
connecting to laptop, PC, or optional touchscreen
with a CAT5 network cable.
2.The default IP for ETH1 is 192.168.1.250.
3.The optional touchscreen default IP is
192.168.1.200 and will connect automatically to
the Supervisory Controller when plugged into
ETH1. It is recommended that you do not change these defaults.
4.ETH0 should be reserved for the secure network
connections: store or corporate networks. Ask
your network administrator for the correct
network IP address for ETH0.
5.ETH0 and ETH1 are physically separated for
added security. Directly connecting to ETH1 will
not access the secure network connection on
ETH0.
Figure 1-2 - Supervisory Controller ETH0 Port
1.2Direct Connect
Instructions - Connect
your laptop to
Supervisory
Figure 1-1
Controller’s Ethernet
Port ETH1
1.Under Control Panel - Network and Sharing
Center, select Change adapter settings.
2.Select the Local Area Connection port being
used.
3.Select Properties.
- Supervisory Controller ETH1 Ports
Figure 1-3 - Change Adapter Settings
Ethernet ConnectionBasic Setup Information • 1-1
4.Highlight the section Internet Protocol Version
4 (TCP/IPv4) and click Properties:
1.3Logging Into the
Supervisory
Controller
1.Launch a preferred Web browser: IE 9 and above,
Firefox 13 and above, Chrome (all versions), and
Safari (all versions) are the supported browsers.
2.Enter the IP Address of the device.
3.Enter the Username/Password (default user/pass)
and click Login. Update the password to the
minimum complexity requirements and click
Save. Note that after the first login using the
default user/pass, the password must be updated.
NOTE: When directly connecting your laptop
or PC to ETH1, enter the default IP into the
browser address bar: ETH1 Default IP
Address is 192.168.1.250.
Figure 1-4
- Highlight Internet Protocol Version 4 (TCP/IPv4)
5.Click Use the following IP address: and enter
the IP address 192.168.1.251 and the Subnet mask 255.255.255.0 of the PC being used on the
Local Area Network or direct connection and
click OK:
Figure 1-6
To ensure the highest level of protection and security,
Emerson requires users to create passwords for logging
into Supervisor controllers that meet certain criteria and
National Institute of Standards and Technology (NIST)
recommendations.
•Passwords must contain 8 to 24 characters.
•Passwords cannot be composed of all the same
•Passwords cannot contain a commonly-used phrase.
- Login Screen at Controller Startup
characters (for example, “aaaaaaaa” or
“&&&&&&&&”).
If your unit has been received directly from the Emerson factory, the Setup Wizard will open and take you through the
following setup screens:
1.4.1Localization Screen
Figure 1-7
Set the Supervisory Controller’s localization data such as language, date and time formats, and engineering units from the
Localization screen.
Language: The default for the language selection is American English (United States). The system stores a setting for the
preferred system language (internal language code). The default language is used when no user is currently logged into the
Supervisor or when the currently active preferred language does not have a translation for a given label, prompt, or
display text.
Date: The Date format can be set to either Day, Month, and full Year (D-M-YR) or Month-Day and full Year (M-D-YR)
format. The day, month, and year values are separated by either a forward slash or a dash line depending on user selection.
The Date Format can be changed based on user preference and saved to user profiles. On initial Supervisor startup, the
Date format defaults to the format of the language selected. For example, en-US will default to D-M-YR and all others
will default to M-D-YR.
Time: The Time format can be set to either a 12-hour (12-hr) format or 24-hour (24-hr) format. The hour, minute, and
second values are separated by either a colon or a period depending on user selection.The Time format can be changed
based on user preference and saved to user profiles. On initial Supervisor startup, the Time format defaults to the format of
the language selected. Date and Time delimiters default to forward slashes and colons.
Engineering Units: The default engineering units are based on the assigned units for the chosen preferred language.
Users can choose or change their preferred set of engineering units and save them to their user profiles. The default
engineering units are based on the International System of Units (SI System) format.
Set the system language type in the Language drop-down menu. Click the right arrow > to save and proceed to the
System Values screen.
- Localization Screen
Setup WizardBasic Setup Information • 1-3
1.4.2System Values Screen
From the System Values screen, name the unit by entering it in the Site Name field. The Confirmation window will slide
open. Click OK. Then click the right arrow > to proceed to the Network Settings Screen.
Figure 1-8
- System Values Screen
1.4.3Network Settings Screen
Configure the settings on the Internet TCP/IP screen such as host name, text, and email settings. If you have Internet
access, enter the IP Subnet Mask and Default Gateway settings (see your IT Administrator). If connecting directly to a
laptop, use the Default IP and leave the DHCP set to Disable. For text messaging, enable the SMS setting and use the
SMTP address (see your IT Administrator).Click the arrow > to save and finish the Setup Wizard.
•Site Supervisor IONet connections must be wired reverse polarity.
•For Site Supervisor Serial IONet connections, connect the white wire to the negative terminal and the black wire to
the positive terminal.
•For 8RO and MultiFlex RS485 IONet connections, connect the white wire to the positive terminal and the black
wire to the negative terminal.
•Connect the shield wire to earth/chassis at the Site Supervisor end of the IONet network segment. DO NOT
connect the shield wire to any connector on the Site Supervisor.
•For daisy-chain configurations, terminate devices at the beginning and the end of the network segment. All other
devices in the network segment are not terminated (termination jumpers in the not-terminated position).
Figure 1-10
Site Supervisor RS485 Wiring Guide ExamplesBasic Setup Information • 1-5
- Site Supervisor and MultiFlex Wiring Layout
•Site Supervisor and XR75CX share the same MODBUS network polarity. Do not reverse polarity.
•Connect the shield wire to earth/chassis at the Site Supervisor end of the MODBUS network segment. Do not
con-
nect the shield wire to any connector on the Site Supervisor or XR75CX.
•For daisy-chain configurations, terminate devices at the beginning and the end of the network segment. Set the dip
switch position 1 and 2 to the ON position on Site Supervisor. For XR75CX end of network, terminate with a 150ohm resistor or 535-2711 termination block. All other devices in the network segment are not terminated
Log into Site Supervisor by clicking the Login icon in the
upper right part of the screen. For the Main Menu, click
the gear icon and the panel will slide open. Click the gear
icon again or to the right of the panel to close.
Six icons at the first row along the top of the screen are the
Back Arrow, Main Menu, Home, Refresh, Control
Inventory, and Schedule and Events. Refer to (Table 2-1)
for icon descriptions.
2.1Menus and Submenus
1.Login - Logs you into the Supervisory controller.
Click and enter your username and password.
Once logged in, clicking Logout will log you
back out of the system. (You will automatically
be logged out of the system after a specified
period of idle time.)
Enter your Username/Password (default user/pass) and
click Login. Then update your password to the minimum
complexity requirements and click Save.
2.Home - Returns you to the set Home screen.
Click the Home icon to return to the Home screen
from anywhere in the system.
3.Summaries - Three submenus will display: Case
Defrost Schedule Summary, Network Summary,
and System Summary. Click each selection or
drop-down arrow (caret) to expand. Note that if
Peer Network is set up, the area controllers will
display under the Summaries menu under Area
Controllers.
• Case Defrost Schedule Summary- Takes you to
the Case Defrost Schedule Summary page where
edits to case defrost schedules can be managed.
• Network Summary - The network summary shows
the status of all network devices associated with
this Site Supervisor.
• Online - The device is online and communicating
normally
• Offline - The device is not communicating
(dropped off the network, has not been
commissioned, is not functional, or is not
powered up)
• Unknown - Unable to communicate with the
device
• This Supvr - Represents the current Supervisory
controller you are using; therefore, only one entry
in the list can show this status
• System Summary - Returns you to the home
screen
4.System Logs & Statistics - Contains controller
system information for technical personnel-level
users. Setpoint files can now be printed. Select
Setpoint Report. This report can be downloaded,
saved, or printed. Select Service Log for Clean Out and Reset buttons. Clean Out will return the
controller to factory defaults. The controller will
reboot after a clean out with all programmed
applications, logs, and other data erased.
CAUTION: A clean out will erase all
programmed parameters from memory. The
Reset button only restarts and reboots the
controller.
5.Configure System- Contains navigation to
Logging Groups, Alarm Communications, File
Management & Licensing, General System
Properties, Manage Users (performs account
creation and role assignment for system users,
view, edit, and remove users) and My Profile
(allows you to create or edit your personal profile
page, create keyboard shortcuts, set localization
and engineering unit settings and more). Click
the drop-down arrow (caret) to expand.
• Logging Groups - Allows you to view log
parameters, add new logging groups, edit
parameters of existing logging groups, and delete
logging groups.
• Alarm Communications - View, edit, or delete
alarm notices from this page. Enable All to view all
notices in the system.
• File Management& Licensing - File Management
opens the File Management screen where you can
install and delete application description (ADF)
files, backup and restore system configuration,
install and delete floorplans, add/delete a license,
view application licenses in the system, add a
Feature Set, and upgrade firmware.
• General System Properties - Contains a
drop-down menu that includes these submenus:
COM Ports (COM Ports and baud rate settings),
Network Settings (Internet, subnet mask, DNS,
MAC Address, Email (SMTP), Text messaging
(SMS) and more), Localization (language and
engineering unit settings), and System Values
(general setup parameters, Web server and UI
setup).
Menus and SubmenusBasic Navigation • 2-1
2.2Overview
2.2.1Conditional Visibility
Conditional Visibility allows points to be viewed that are
applicable to the defined view level (Basic or Advanced equivalent to “Full Options” in previous generation
controllers) for certain (not all) applications.
NOTE: The mobile Supervisory Controller
view does not support conditional visibility.
2.2.1.1User View Details
mark.
• Control Inventory (box) - Select this
box to access the Control Inventory
screen where applications can managed.
• Time Schedules (calendar) - Select to
access the Schedules and Events screen
where Schedules, Events, Inputs/Outputs,
Alarms, and System information is located.
• Refresh - Select to return to the Home
screen and log out.
NOTE: When you navigate to a specified
screen, you will see the points equal to or less
than your View Level available on the
Supervisory Controller’s rule. The basic user
level does not see the Advanced view level point.
Some screen information and contents are editable, which
when clicked can either display additional or related
information or move to another screen.
NOTE: The screen will only display applicable
points according to your view level and the
Supervisory Controller’s rules.
2.3Basic Screen Elements
• Main display - This is the main section of the
screen, which contains and displays the content of
the chosen selection such as reports, device
information, configuration settings, and more.
• Main Menu (gear) - When clicked, the
Main Menu panel will slide open
containing the menus and submenus of
the controller.
• Home button - Returns you to the
default Home screen of the controller.
• Back button - This button will return
you to the previous screen. The Back
button is indicated by a left arrow icon.
• Active Alarms (red circle with excla-
mation mark) - When this icon is clicked,
the screen will display the
current active alarms. The number of alarms is
displayed in parentheses next to the exclamation
• Send To- Changes to multiple
applications at the same time
using the Send To button.
Changes to summary parameters, setpoints, log points, and
other parameters can now be
sent to multiple, user-selected
“like” applications. A single change or multiple
changes can be sent to all “like” applications using
the Save and Send To buttons, eliminating making
a change individually to each application one at a
time. For example, updates to a temperature setpoint can be sent with a single click to all controllers that you wish to update. The save confirmation
will confirm all changes made
NOTE: When some screen information and
contents are clicked, additional or related
information can be displayed or additional
screens accessed.
2.4Language Settings
The default for the language selection is English (United
States). The system will store a setting for the preferred
system language (internal language code). This is used
when no authorized user is logged in. The default
language is used as a fall back when the currently active
preferred language doesn’t contain a translation for the
given label, prompt, or display text.
3.Click Configure System> General System Properties.
Figure 2-3 - Language Settings Set Up
7.The Confirmation pop-up box will appear on the
screen showing the summary of changes, click
OK or Cancel button.
Figure 2-2 - Language Settings Set Up
4.On the General System Properties page, click the
Localization tab.
5.Choose the preferred language on the Language
drop-down menu.
6.Click the Save button.
NOTE: English is the only language available.
Changing this setting will only change the
engineering units appropriate to the region
selected.
Figure 2-4 - Language Settings Set Up
2.5Locating and Working
With Applications
Applications in the controller are located on the Home
screen and from individual application screens and are
easy to find.
Each of the five categories can be seen on the Home
screen and if applications have been set up, they will
display under the category to which they have been
assigned. For example, in Figure 2-6 all of the five
categories are displayed with Refrigeration containing two
applications that have been set up. Choose an application
and the categories will then be displayed as icons across
the top that are easily accessible. Click the icons to see the
Locating and Working With ApplicationsBasic Navigation • 2-3
applications.
conditions, which is an energy penalty and most often
goes undetected. Performance Meter gives the user a
graphical representation of performance data that shows
instances for performance that fall outside of the expected
normal performance band.
The Performance Meter tab will only be visible if licensed.
To display this tab, the user must click the Advanced
button, then click three-line menu as shown in Figure 2-7,
then click Performance.
Figure 2-5
The five categories are displayed on each application
screen. Click each icon to view applications that have been
set up for each category. For example, in Figure 6-2, the
Refrigeration icon has been clicked and the applications
for that category are displayed (Standard Circuits and
XR75CX). Click the application to go directly to that
screen.
Figure 2-6 - Application Screen Menus
- Home Screen Application Menus
2.6Application Tabs
2.6.1Performance Meter
Performance Meter gives the user a quick and simple
visual indication of system performance and early insight
that provides an opportunity to take corrective actions to
remedy conditions that may be reducing energy efficiency,
causing required service or ultimately leading to costly
failures. Performance Meter is a licensed application that
looks at the operational performance in relation to a
desired setpoint and calculates a “Figure of Merit” (FOM),
which takes into account deviations above and below
setpoints, but excluding defrosts. The overall FOM value
uses both high-temperature conditions that result in
product degradation as well as low-temperature
Figure 2-7 - Performance Meter Tab
2.6.2Site Aggregation
Site Aggregation brings together status and data from
multiple controllers into one convenient view. You can
drag and drop the summary information into the order that
is most important to you. This can be your preferred view
when you log in with your user name. You can also create
custom categories, and drag and drop Summary Tiles into
categories and in the order you prefer. Categories appear
collapsed by default on the System Summary screen. (This
feature is supported by all models and not limited to
having a Site Aggregator license.)
To create a new custom category, click Edit on the
upper-right corner of the screen, then click the plus sign
that appears opposite the application name. An open box
(Category Name) will appear. Enter the name of your
custom category and click Save.
The Site Aggregator floor plan now links to E2 peer
application status and overrides. The Site Aggregator can
now be used with an E2 peer network to render E2 status
and overrides on floor plans.
Control Inventory provides a centralized control list by
category. It allows you to view the network status of
controls, and perform the following functions: create and
duplicate one or more controls to a group quickly,
commission a device, associate controls to other controls,
edit the control name or commission information for
existing controls, and delete a control from existing
groups.
To duplicate an application, the appropriate user
privileges must be assigned. The user can specify the
number of duplicated instances for a device or application.
When a device or application is duplicated, the points
specified by the user or application type on the status tiles
is also duplicated. The name of each duplicated instance is
unique. The maximum total number of application
instances of a given type, including duplicated instances of
that type, will not exceed the license limit for that type.
Once the user has logged in, click the duplicate
button next to the application on the screen.
Select the count in Number of Duplicates.
2.6.3.1Adding Applications
1.Add an application to your Supervisor by first
going to the Control Inventory page.
2.After logging in, click the Control Inventory icon
at the top of the screen.
3.From the Control Inventory screen, select an
application to add from the drop-down list at the
bottom of each category.
4.Fill in the fields and click Save.
5.Go back to the Home screen to verify the
application appears under the category.
Application TabsBasic Navigation • 2-5
2.7ADFs
An ADF is an Application Description File. ADFs allow a
particular device to communicate on the Supervisor. An
ADF is required before connecting a non-native device on
the Supervisor. The ADF is not automatically activated on
the Supervisor after installation. A license key is required
to enable specified instances of the application/device.
Contact your Sales representative or Customer Service to
obtain an ADF. The ADF can be uploaded on the
Supervisor using the File Management screen. A license
key is required to active the application after the ADF has
been uploaded. A license key can be obtained from
Technical Support with necessary approval. Email
ColdChain.TechnicalServices@Emerson.com with the
below information to generate the required license:
1.Name of the application/device
2.Supervisor MAC address and Model Type
3.Number of instance of the application
2.8Creating a Backup and
Restore
Figure 2-13 - File Management & Licensing
3.Click Backup and select where to save the
Backup (Local PC or Other Devices; SD Card)
and enter a name for the Backup.
2.8.1Backup
Creating a backup is important if you are planning to
upgrade the Supervisor firmware. A Backup file does not
save properties such as Ethernet settings, loaded license
keys, firmware versions, alarm history, and logs.
If the Backup file is available, a Restoration can be
performed. To successfully Restore, the Supervisor used to
create the Backup and the Supervisor to be restored should
be the same model. The ADF and license keys must be
complete on the Supervisor to be restored, matching the
applications configured on the Backup file.
1.From the home page, click the gear icon and
choose Configure Settings> File Management &
Licensing.
6.Click Restore.
Figure 2-18 - Restore
7.Click OK or Cancel on the confirmation window.
The Site Supervisor provides a restore notice when
restoring backup files. The notice will list any applications
that did not restore and the reason why, such as number
application limits exceeded, or missing ADF files.
2.9Using the Help Menu
Figure 2-16
2.Click Restore.
Figure 2-17 - Restore
3.Select the source of the Backup file. Click Select.
4.Select the Backup file from its location.
5.Click Open.
- File Management & Licensing
This section contains instructions for using the help menu
on the Site Supervisor.
1.Log into the Site Supervisor and enter the
username and password.
Figure 2-19 - Logging into the Supervisory Controller
2.From anywhere in the controller, click the Help
Using the Help MenuBasic Navigation • 2-7
icon (question mark inside a circle):
2.10Icons or Buttons
Appearing on the
Home Screen
IconFunction
Figure 2-20 - Click Help Icon for Page Help
3.A search field is available at the top of each help
page. Enter a keyword into the search field and
the help page you are currently viewing will be
searched for the keyword.
NOTE: The HELP menu is context sensitive
and will display information about the
function, application, or device the user is
viewing.
4.Click the Main Menu button (three horizontal
lines) to show the complete menu. It will provide
links to the complete help menu with links per
topic on the table of contents.
5.Search key words on the search box to narrow
down topics to search.
Main Menu
Gear Icon
Found at the top left-hand
side of the page. When the
main menu gear icon is
clicked, the main menu
panel will slide open
containing the menus and
submenus of the
controller.
HomeOpens the main menu
panel when clicked. The
main menu panel contains
menus and submenus of
the controller.
Back Arrow The Back button will
return you to the previous
screen.
Active
Alarms
When the Active Alarm
icon is clicked, the screen
will display the current
active alarms.
FilterClicking the Filter icon
opens the Filter Alarms
screen which allows you
to choose or filter the type
of alarm you want to see
on your Active Alarms
screen.
Figure 2-21
- Click Help Icon for Page Help
Control
Inventory
Click to manage the
system-wide inventory of
applications. Edit, delete,
and add applications from
this screen.
Time
Schedules
Table 2-1 - Top Screen Icons and Buttons
Click to add and edit
schedules and events.
Screen Dropdown Menu
The screen drop-down
menu is activated when
the current screen is
active/online. This menu
contains other options
such as Download,
E-mail, Print, and View
History.
Refrigeration Displays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under
Refrigeration.
HVACDisplays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under HVAC.
LightingDisplays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under
Lighting.
Floor PlanClick to manage the
floorplans installed on
your controller (if
applicable)
Physical I/O
Status
Click to view and
configure all I/O boards
on your controller.
Table 2-1 - Top Screen Icons and Buttons
EnergyDisplays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under Energy.
OtherDisplays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under Other.
SystemDisplays on Home screen
and application screens.
Shows all applications in
the controller that are
categorized under System.
Table 2-1 - Top Screen Icons and Buttons
Icons or Buttons Appearing on the Home ScreenBasic Navigation • 2-9
3Alarm
Configuration
Alarms in the supervisory controller can be generated
from different sources including external networked
devices, applications, value-added applications, and subsystems. Alarm configuration, transmission, and history
settings can be defined by the user.
1.Log in to the Site Supervisor by clicking Login
on the Main Menu, located on upper right side of
the screen and enter your username/password.
to access the device status page.
Figure 7-3 - XR75CX Under Refrigeration
4.On the drop-down menu on the upper right of the
screen, click Edit and Advanced to access
configuration properties and alarms for the
XR75CX 5.6 device.
Figure 3-1
Figure 3-2 - Accessing Site Summary
- Site Supervisor Login
2.From the Home screen, navigate to Summaries>
System Summary.
3.In this example, alarm configuration for
XR75CX 5.6 controller is used. Select the
XR75CX 5.6 device on the Site Summary screen
Figure 3-4 - Accessing the Configuration Properties of
XR75CX 5.6
Click each tab to see the XR75CX parameters:
Figure 3-5 - XR75CX 5.6 Tabs
In the Status tab, selecting properties for the Status tab list
is unlimited. The top 10 properties shown on the System
Summary tile will appear with a different color from the
rest of the items on the list. Properties can be dragged and
dropped into the list and color designations can be
changed. Note that under the Status tab on any device
application page, the wrench icon can be clicked for
customizing the summary tile information.
Alarm Configuration • 3-1
Users who are logged in with System Administrator
privileges can overwrite the default setting on the selected
point's section that will be synchronized with the tiles on
the System Summary page. New category icons are
located across the top and when clicked will go to those
application pages.
will go to the call center for monitoring) or OFF
(for no call center monitoring).
3.Once configurations have been set, select Save
on the upper right side of the screen.
3.2 Alarm
3.1 Alarm Configuration
1.For alarm configurations, scroll down to the
Alarm Cfg parameter section.
Figure 3-6
- Configuring Alarms
2.On the Alarm Cfg parameter section, click the
arrow beside the name of the parameter to
configure other settings for alarming.
• Alarm descriptions can be overridden from this
page. Enter the name of each application alarm you
wish to appear in the alarm log. If no name has been
entered, the default alarm message will display in
the alarm log.
• Each alarm type (urgency level) can be categorized
as Non-Critical, Critical, or Notice (the least
urgent).
• Each alarm category (where it is categorized in the
supervisory controller) can be set under the
Category field: Refrigeration, HVAC, Lighting,
Energy, or Other.
• Set the repeat time for the alarm on the Repeat
Rate field, which is the time the advisory is next
scheduled to repeat if not acknowledged. A
repeated advisory will re-queue to the system as if it
had just been generated. However, it will not create
a new instance; it will only update the existing
instance with the next repeat time. All other
processing and propagation will act as a new
instance of an advisory.
• Set the Monitor Alarm field to ON (if the alarm
Communications
Setting
Configure alarm communications setting on Alarm
Communications screen for SMTP (emailing), and texting
alarms.
1.From the Home screen, navigate to Main Menu>
Configure System> Alarm Communications and click Add
an Alarm Notice at the top.
Figure 3-7 - Alarm Comm Page - Create New Alarm Notice
The Alarm Communications screen creates a custom
notification of alarm conditions or set default values for as
many as 20 notifications for each device.
NOTE: This screen will not be accessible if you
are not logged into the controller.
When creating a new alarm notice, there are three steps
on the Alarm Communications page:
Step 1: Enter a unique name
• Click the wrench icon beside the alarm
notice to view the tabs then click Edit located on
the upper right side of the screen. Name the alarm
notice by entering a unique identifier under App
Name in the General tab.
Step 2: Select all of the desired options under each
tab
• Category – Select ON or OFF for the following
category menu options: Refrigeration, HVAC,
Lighting, Energy, Other, System, and ProAct.
• Alarm type – Select ON or OFF for the following
alarm-type menu options: Critical, Non-Critical,
and Notice (least urgent).
• Resolution – Select how the alarm notice should be
handled. Select ON or OFF for the following
resolution menu options: Acknowledge, Reset to
Normal, and Return to Normal.
• Schedule – Select an option from the drop-down
list.
• Outputs - The output menu options are the
following: Alarm Out 1 Config (Audio), Alarm Out
2 Config (Visual), Alarm Out 3 Config (3rd Party
A), and Alarm Out 4 Config (3rd Party B). Select
the desired value for each output menu option: Not
enabled, Active until acknowledged, Active until
muted, or Timed one-shot pulse.
Figure 3-10 - Input/Output Status Tab
• Input/Output Status - The Input/Output Status tab of
every application will appear as a new tab on the
details summary screen to view all the necessary
properties to troubleshoot any issues more
effectively.
Step 3: Click Save
• Click Save in the upper right side of the screen.
When all fields for the new alarm notice are
completed, a confirmation pop-up screen will
appear.
NOTE: Only 20 notices can be created. To edit
the current notice, a specific role is required in
this function.
Figure 3-9
- Recipients Tab
• Recipients - For each user, select how the alarm
will be communicated. The first column shows the
list of users while the second column shows the
combo box. The combo box will have 4 selections:
Disabled (blank), Email, SMS (Text), and Email +
SMS. The default value will be “Disabled”.
Select the Active Alarms icon to open the Alarm Log
screen and view the list of active alarms in the system:
Figure 3-11
The alarm name appearing in the Description column is
the default name or custom name assigned to the alarm.
Click View History to see the collection of alarms that
have been resolved.
Figure 3-12 - Alarm History
Active alarms also appear as default on the Home screen.