Emerson Sempell Series, STE 4 Operating Instructions Manual

SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
Before installation these instructions must be fully read and understood
Series
STE 4 Control device for safety valves with
pneumatic actuator.
1 DANGER AND WARNING INDICATIONS
The construction of the Sempell safety valves and control devices corresponds to the standard technology and the valid safety regulations. Nevertheless, improper use or improper installation may cause risks for personnel or can lead to restrictions in regard of the operational safety. Therefore Sempell GmbH recommends the operator of the valves to take appropriate measures and make sure that the present operating instruction is read and understood by the assigned personnel.
Please observe the following points besides the notes given in the text
• Danger of burning when in contact with safety valves and connecting pipes while operating
at increased temperature.
• Disassembly of the safety valve only in case
of pressureless system and after cooling
down. Wait for official permission. Disconnect
electrical supply.
• Protection against risks caused by
evaporation also in case of pressureless system; for information please contact the responsible safety inspector.
• After assembly check all sealing points in
regard of tightness.
• Carry ear protection during adjustment,
ifnecessary.
• Danger of burning by discharge of small
amounts of possibly hot medium in case
of safety valves with open spring bonnet
(typeSO..., VSE 1, VSR 1, VSE 8).
• Danger of injury while discharging in case of
open discharge line.
• Extreme vibrations (chatter) can lead to an
inadmissible increase of operating pressure
with possibly destruction of the safety valve or to destruction of the balanced bellows with
unintentional escape of medium.
Exclusion of liability
Sempell GmbH cannot be held liable in case
of improper maintenance and adjustment of
a Sempell valve, use of inadmissible spare parts or utilities and in case of temporary or
permanent connection of equipment with the safety valve which is not approved by us.
Application limits
It is only allowed to use the safety valves and the control device according to the details of this operating instruction and/or according to the parameters and application data agreed in the delivery contract (see nameplate). The application of the valve has to take place adequate to the medium tolerances of the used materials.
Warnings for the operating and maintenance personnel
Before commissioning and maintenance works familiarise yourself with the legal accident prevention regulations, the local safety instructions and this operating instruction and observe them. Use safety valve, control device and their individual parts and accessories only for the purpose intended by us. Work on the electrical systems or equipment must only be carried out by an electrician or instructed personnel under control and supervision of an electrician according to the electrotechnical regulations.
www.valves.emerson.com © 2017 Emerson. All rights reserved.
MA.330.02.0505.E
VCIOM-02238-EN 15/01
SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
2 DESCRIPTION OF COMPONENTS
For the following sections the connection
diagram section 9.2 is valid unless other provided.
2.1 Description of the function
The type-tested control device STE 4 pilots
the on- and off-switch of the loading air or lifting air of the spring-loaded safety valve with
pneumatic actuator.
Under power the 2/2 way solenoid valves (Y1,Y2, Y3) are closed and the 3/2 way solenoid
valve (Y4) connects de-energized the pressure space (H) of the pneumatic actuator for lifting
air with the atmosphere.
Via pressure regulator (R1), filter (F) and throttle (D), the loading air is on the loading cavity (B) of the pneumatic actuator. It causes an additional closing force to the spindle of the spring-loaded
safety valve with pneumatic actuator.
The pressure gauge MB in the control unit
shows the loading pressure, the control lamps
(Y1, Y2, Y3, B) shine.
D2D1
A2A1 G2 D3 A3 G3G1
Opening
The pressure switches (D1, D2, D3) inserted into the impulse unit are adjusted to the desired set pressure. In case of exceeding set pressure,
the solenoid valves (Y1, Y2, Y3) installed into the control unit become de-energized. These
solenoid valves (Y1, Y2, Y3) switch by means of
the contacts of the relay and are assigned to
the corresponding pressure switch
Additionally, each of the three solenoid valves become simultaneous de-energized by means of a relay contact released by each of the three
pressure switches (D1, D2, D3). The solenoid
valve (Y4) is energized. The loading air is relieved through the solenoid valves (Y1, Y2, Y3). The lifting air is built up by the solenoid valve (Y4). The controlled safety valve opens. The relief of the loading air also occurs if only one of the three solenoid valves (Y1, Y2, Y3) opens.
If the lifting air is not switched on, the
controlled safety valve opens after the reduction of the loading air like a spring-loaded safety valve.
Closing
If the system pressure drops below the reseat pressure of the pressure switches (D1, D2, D3), the solenoid valves (Y1, Y2, Y3, Y4) switch back.
The supply of lifting air stops. The pressure space (H) of the pneumatic actuator relieves to atmosphere and the loading air in the loading cavity (B) builds up again. The controlled safety valve closes.
P1 E1 P2E2 P3E3
room. Incase of higher control air pressures (lifting air) a second pressure regulator R2
will be used toreduce the loading air pressure (accessory, see system circuit diagram with
pressure regulator R2).
2.2 Description of the construction
According to the specification, there are three separated control lines in the control device STE 4, that means three pulse generators
(pressure switches) and three control units (solenoid valves) with each an independent
pressure sense connection. For testing and/or repair purpose it is possible to temporarily put one of the three control lines out of operation by means of the valve interlock(G). The control device STE 4 consists of the functional groups:
impulse unit A161, electric switch unit A162 and
pneumatic control unit A163. The impulse unit is composed of the connections for the pressure sense lines (E1,
E2, E3), the shut-off valves with interlock (A1, A2, A3) and the pressure switches (D1, D2, D3).
The test connections (P1, P2, P3) are located between the shut-off valves and the pressure switches. The pressure switches contain two micro switches so that opening and closing
pressure can be set independent from each
other (P-min, P-max).
Sliding pressure operation
Open the safety valve below the set pressure
by an electrical impulse from the control
ATTENTION!
The components of the impulse unit A161 are under system pressure!
2
SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
The electric switch unit includes the equipment
for signal treatment and control. At the bottom
side is the connection for the power supply. Protected by an inspection window, control lamps and manual switches for working and testing are on the front panel. Pressing the switch “Lamp Test” en ergizes all control
lamps.
The pneumatic control unit contains the connections for the compressed-air supply of the pneumatic section through pressure regulator (R1) and air filter (F) to three closed-
circuit 2/2 way solenoid valves (Y1, Y2, Y3); one open-circuit 3/2 way solenoid valve (Y4) and
the pressure gauges for loading and lifting air (MB,MH). At the upper side are the connections of the control lines to the pneumatic actuator.
P4 MHY4
P5R1
Y1 Y2 Y3 F
3
SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
3 TECHNICAL DATA SAFETY VALVE CONTROL
Manufacturer Sempell GmbH Name Control Device Series STE 4 Compressed-air supply Max. 8 bar, 12 bar as option Operating pressure for the pneumatic actuator Max. 8 bar
Max. 12 bar for lifting air (accessory with pressure regulator R2)
Air consumption at opening About 26 Nm3 at 5 bar Ambient temperature Max. 60 °C
Protection class IP 55 Weight About 78 kg
Type tested approval mark no. TÜV.SV ...-846
Electric connections:
Control device: Input voltage 230 V, 50 Hz - 24 V DC or 48 V DC as option Solenoid valve coils: Connecting voltage 230 V, 50 Hz - 24 V DC or 48 V DC as option
4 OPERATING INSTRUCTIONS
Switch on the control device STE 4 by the key operated switch at the electric switch unit. The white control lamp “Operation” shows the
operating state. The pointer of the measuring
instrument in the “Test” field is in the black area “Operation”.
ATTENTION!
A change of the lead sealed pressure switch adjustment must take place inthe presence of the independent TÜVinspector (TRD 601, sheet 2, section4.2.1).
4.1 Adjustment after installation
Before delivery the pressure switches are
pre-set to the desired set pressure and closing pressure (see section 2.1). After the installation of the system a resetting of the pressure
switches (D1, D2, D3) may be necessary
under operating conditions (e.g. because of temperature changes or after maintenance
works). Therefore connect a spindle pump with
calibrated pressure gauge (accessory) at one
of the test connections (P1, P2, P3). Apply the desired set pressure to the pressure switch.
Because of the closed pertaining shut-off valve (A1, A2, A3) the system pressure has no influence. In doing so, temporarily prevent the response of the safety valve by the pneumatic actuator.
Procedures
• Open the front door of the electric switch unit. Set test switch in the “Test” field into position“Test 1”.
Indicator: yellow control lamp in the “Test”
field blinks.
The lifting air to the pneumatic actuator is
temporarily switched off. The safety valve
remains fully operational.
Unlock and close the corresponding shut-off valve (A1, A2 or A3) by means of interlock key.
Connect spindle pump with pressure gauge at the test connection (P1 or P2 or P3) of the
previously closed shut-off valve (connections see section 4.7.1).
4.2 Pre-setting
In case of a new adjustment or of great deviations pre-set both micro switches of the pressure switch (D1, D2, D3) approximately at
their set value first.
The precision pressure switches
Manocomb-Sem-2K have calibrated
nominal value scales for P-max and P-min with an accuracy of ≤ 1%. By means of the corresponding knurled-head screws pre-set the switch points quite precise.
4.3 Set pressure control
Increase pressure with the spindle pump
connected to the test connection until the
control lamp P-max (red) flashes up. This is the switch point. Register pressure reading on the
test gauge.
To change the switch point, turn the higher knurled-head screw. Turn the adjusting screw only a little when you are close to the switch point. Lower excess pressure up to about 0bar
and then increase again until the pressure
switch actuates. Register pressure indicator of the gauge again and correct switch point if
necessary.
Repeat procedures until the desired switch
pressure is reached.
In case of pressure decrease, the switching band of the pressure switch with micro switches can be determined. This is the pressure difference between switch-on point (flash up of the control lamp P-max) and switch-back point (darken of the control lamp P-max).
4
SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
4.4 Reseat pressure
Increase pressure with the spindle pump
connected at the test connection beyond the desired closing pressure until the control
lamp P-min (yellow) shines. Slowly decrease pressure until the control lamp P-min (yellow) goes out. This is the switch point. Register
pressure reading of the gauge.
To change the switch point, turn the corresponding adjusting screw. Turn adjusting screw a little when approaching the switch point. Lower excess pressure up to about 0 bar
and then increase again beyond the closing
pressure (control lamp P-min (yellow) shines). Slowly decrease pressure until the pressure switch actuates. Register pressure reading of the gauge again and correct switch point if
necessary.
Repeat procedures until the desired switch
point is reached.
In case of pressure decrease the switching band of the pressure switch with micro switch
can be determined. This is the pressure
difference between switch-on point (lighting up of the control lamp P-min) and back switch point (darken of the control lamp P-min). After adjustment open the corresponding
shut-off valve again and lock it by means of the
interlock key. Put the cover on the pressure switch and lead seal. Close front door again. Switch back test switch of the electric switch unit in the “Test” field. Indicator: yellow control lamp in the field “Test”
does not signal.
4.5 Monitoring
Check daily the actual status of the control device by visual check.
The actual function will be shown as follows:
• The safety valve is closed and loading air is
applied:
Electric switch unit: white control lamp “Operation” shines. Gauge
reading is in the black area “Operation”.
Green lamps Y1, Y2, Y3 and B shine.
Pneumatic control unit: gauge reading present at “Load” (MB).
Inspection window “Load” is green.
• The safety valve is opened and lifting air is
applied:
Electric switch unit: white control lamp “Operation” shines. Gauge
reading is in the black area “Lifting”. Yellow lamps Y4 and H shine. Red and yellow lamps
(P-min/P-max) 1 and/or 2 and/or 3 shine. Pneumatic control unit: gauge reading present at “Lifting” (MH).
Inspection window “Lifting” is green.
4.7 Testing
4.7.1 Check of pressure switch and operation of the solenoid valves
For testing, one of the three pressure
switches (D1, D2, D3) can be separated from
the system by closing the unlocked shut-off valve (A1,A2,A3) in the pressure sense line (E1,E2,E3) by means of the valve interlock (G).
With a spindle pump with test gauge
(accessory) the desired set pressure can be applied through the respective connection
(P1, P2, P3). Therefore connect the spindle pump with a pressure hose and vice coupling
(Minimess Fa. Hydrotechnik) after removing the knurled protective cap.
The control lamps P-min or P-max show the
gain of set and closing pressure (also see sections4.3, 3.4).
If the safety valve shall not open during the
tests, set the test switch at field “Test” of the control device in position “Test 1” to prevent the opening of the 3/2 way solenoid valve (Y4) and
so the charge of the lifting air. At the same time
this switch position leads to the opening of only
the solenoid valve (Y1, Y2, Y3) assigned to the
specific pressure switch.
Have the set and closing pressure adjustment
checked once a year by an inspector.
ATTENTION!
A change of the lead sealed pressure switch adjustment must take place inthe presence of the independent TÜVinspector (TRD 601, sheet 2, section4.2.1).
4.6 TROUBLE SHOOTING
Malfunction Cause Remedies
Loading air is prematurely dropped
Pressure switch adjustment changed Pressure switch adjustment see chapter 4 Control line “Load” leaky Eliminate leaking point in the control line
Tube fittings leaky Retighten tube fittings Electric supply deactivated Check electric connections
5
SEMPELL SERIES STE 4 CONTROL DEVICE FOR SAFETY VALVES
Operating instructiOns
• Check of the control legs 1 to 3
- Adjustment of the control air pressure to
2bar
Check of the pressure gauge “Load”
- Test switch into position “Test 1”
Signal lamp (orange) lights up.
• Check of control leg 1 (pressure switch D1,
solenoid valve Y1)
- Unlock and close shut-off valve A1.
- Slowly apply pressure to test connection P1 up to the response of the pressure switch.
Read corresponding pressure P-max at the
test gauge. Solenoid valve Y1 powerless. Drop
of the loading air; indicator at the pressure
gauge “Load” < 0.2 bar; no lifting air. Indicator pressure gauge “Lifting” 0 bar, ampere meter in position “Test 1”.
- Slowly drop pressure until the pressure switch switches back.
Read corresponding pressure P-min at the
test gauge. Solenoid valve Y1 is energized and
closes. Loading air will be charged. Indicator pressure gauge “Load” 2 bar.
- Open and lock shut-off valve A1.
• Check of control leg 2 (pressure switch D2,
solenoid valve Y2)
- Unlock and close shut-off valve A2.
- Slowly apply pressure to test connection P2 up to the response of the pressure switch.
Read corresponding pressure P-max at the
test gauge. Solenoid valve Y2 powerless. Drop
of the loading air; indicator at the pressure
gauge “Load” < 0.2 bar; no lifting air. Indicator pressure gauge “Lifting” 0 bar, ampere meter in position “Test 1”.
- Slowly drop pressure until the pressure switch switches back.
Read corresponding pressure P-min at the
test gauge. Solenoid valve Y2 is energized and
closes. Loading air will be charged. Indicator pressure gauge “Load” 2 bar.
- Open and lock shut-off valve A2.
• Set back to working conditions
- Turn test switch into position “Operation”.
Set control air pressure at normal operating pressure.
Signal lamp (orange) goes out. Control at the
pressure gauge “Load”.
4.7.2 Check of the displacement force reserve of solenoid valves Y1, Y2 and Y3
The solenoid valves (Y1, Y2, Y3) consist of a electric actuated pilot valve and a pneumatic actuated control valve. At the electric actuated pilot valve, pressing the
respective push-button in the electric switch unit lowers the operating tension up to a value where a faultless solenoid has to switch. A
pressure drop of the loading air at the pressure
gauge (MB) shows the switching. The lifting air
is not actuated.
As the extent of the loading air pressure counteracts the switch safety of the solenoid valve check with the highest possible control
pressure. By means of the magnetic actuated pilot valve the pilot pressure is released. In case of the pneumatic actuated control valve the height of
the air pressure brings about the switch safety.
To prove the displacement force reserve on the
control valve check with the lowest possible
control pressure (operation test according to section 4.7.1). Control the displacement force reserve at the
solenoid valves by pressing the switches at a highest possible air pressure. Afterwards control according to section 4.7.1 at lowered air
pressure. The loading air pressure has to drop
top<0.2bar for all tests.
Once a year an inspector has to test the
displacement force reserves with the same
pressures.
Potentiometer Switch
• Check of control leg 3 (pressure switch D3,
solenoid valve Y3)
- Unlock and close shut-off valve A3.
- Slowly apply pressure to test connection P3 up to the response of the pressure switch.
Read corresponding pressure P-max at the
test gauge. Solenoid valve Y3 powerless. Drop
of the loading air; indicator at the pressure
gauge “Load” < 0.2 bar; no lifting air. Indicator pressure gauge “Lifting” 0 bar, ampere meter in position “Test 1”.
- Slowly drop pressure until the pressure switch switches back.
Read corresponding pressure P-min at the
test gauge. Solenoid valve Y3 is energized and
closes. Loading air will be charged. Indicator pressure gauge “Load” 2 bar.
- Open and lock shut-off valve A3.
6
Loading...
+ 14 hidden pages