Edco SRA64 Series
1 Pair Data/Signal
Surge Protection
For Business-Critical Continuity
TM
The Edco SRA64 Series surge suppressor is a single pair cube implementing three-stage
hybrid technology. This cube addresses over voltage transients with gas tubes and
silicon avalanche components. In addition, sneak and fault currents are mitigated with
resettable fuses (PTCs). The PTCs increase resistance several orders of magnitude when
over-currents exceed safe levels. A normal state resumes when over-currents are
removed. The ability to self restore in this manner significantly increases suppressor
performance and survivability.
The standard Edco SRA64 second stage clamps are placed from each signal line-toground. In certain cases, where ground potentials vary from site-to-site, a line-to-line
only second stage clamp may be preferred. This variation is specified by a suffix “D”
on the part number. In other cases, line-to-line and line-to-ground second stage clamps
may be preferred. This variation uses an “X” suffix on the part number.
A variety of clamping voltages are available as standard. Reference the “How to
Specify the Appropriate Model” section to insure that a complete part number
description is obtained.
Features
Lightning protection for balanced low
voltage signal lines
Multi-stage protection
Sneak/fault current protection
Differential and common
mode protection
Automatic recovery
Fast response time
Flame retardant epoxy encapsulated
5 year warranty
Part Number Edco SRA64 Series
Total Peak Surge Current 10kA (8 x 20 µs)
Response Time <1 nanosecond
Voltage Clamp 8, 15, 20, 30, 36, 43, 50, 60, or 270
Resistance 5! (typical)
Temperature -40°C to+85°C
Weight 2 oz.
Dimensions 1.15" Cube
Mounting Stud (standard) No.10-32 x 1/2"
Warranty 5 years
General Technical Specifications
Caution
The hybrid design of this product includes series resistance. Do not place this product in service on
any signal lines capable of supplying more than 150?milliamperes continuously