Emerson SRA16C-1 Installation Manual

Edco™SRA16C-1
Vehicle Loop Detection
Surge Protection For Business-Critical Continuity
TM
The Edco SRA16C-1 is a three terminal device, two of which are connected across the signal inputs of the detector for differential mode protection, and the third is grounded to protect against common mode damage.
Differential mode surges (induced voltage across the loop detector input terminals) are instantly clamped by a semiconductor array. The array is designed to appear as very low capacitance to the detector.
Common mode surges (induced voltage between the loop leads & ground) are handled by a rugged three-element gas discharge tube which operates (fires) at 90 VDC and thereafter clamps the two loop leads to 30 volts in respect to ground. This design eliminates any ground noise from entering the loop detector and being amplified. The Edco SRA16C-1 is intended for all current detector models on the market.
Features
Rugged Gas Tube Protection
Compatible with Digital Detectors
5 Year Warranty
Maximum Operating Voltage 75 VDC
Clamping Voltage 90 VDC
Peak Surge Current 10 kA
Operating Frequency 47-63 Hz
SPD Technology GDT
Connection Type Wire Leads, #18 AWG, 8.0”, Minimum Out of Case
Operating Temperature -40˚C to + 85˚C
Dimensions (Inches) 1”Sq., Ht. 2” Max.
Mounting No. 10 - 32 x 3/8” Stud, (Standard Model Only)
Weight 3 oz.
General Technical Specifications
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Control
Racks and Integrated Cabinets
Services
Precision Cooling
Surge Protection
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
TM
.
IO-50155 5/11 Rev. 0
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2011 Emerson Electric Co.
www.emersonnetworkpower.com/surge
Emerson Network Power Contact information
Headquarters
Surge Protection 100 Emerson Parkway Binghamton, NY 13905 T: (607) 721-8840 T: (800) 288-6169 F: (607) 722-8713 E: contactsurge@emerson.com
Note:
The Edco SRA16C-1WLEADS (special order) is installed very similar to the standard unit except the common (bolt) is replaced with a green wire.
One Edco SRA16C-1 is used for each loop detector to be protected. Units are installed as close as practical to the point where the detector loop wires enter the controller cabinet. Connect one of
the flexible leads to each end of the loop. The common (bolt) connection on each Edco SRA16C-1 must be connected to earth ground.
Best performance is obtained by (1) shortening the flexible leads as much as possible, and (2) providing the lowest possible impedance to ground.
Installation
Edco SRA16C-1 Edco SRA16C-1WLEADS
Loading...