Emerson SL-22075 User Manual

Page 1
Liebert SH Series Surge Protection
Installation, Operation and Maintenance Manual
Surge Protection For Business-Critical Continuity
Page 2
Surge Protective Devices
LIEBERT SURGE PROTECTIVE DEVICE
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE OF CONTENTS
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Handling Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LOCATION CONSIDERATIONS
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Audible Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings Defined . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ELECTRICAL CONNECTIONS
Voltage Ratings and Power Source Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Voltage Ratings and Power Source Configurations (Chart) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wire Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Over Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
NEC Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Voltage Protection Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Circuit Ampacity Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Grounding and Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Parallel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Grounding Electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Neutral Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION INSTRUCTIONS
Product Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensional Information (Chart) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Suggested Breaker and Wire Size (Chart) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MONITORING FEATURES
External Status Indicators (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Audible Alarm (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Summary Alarm Contact (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Transient Counter (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Swell Counter (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TROUBLESHOOTING/SERVICING/MAINTENANCE
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Corrective Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
WARRANTY INFORMATION
10-Year Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation, Operation and Maintenance Manual 1 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 3
Surge Protective Devices
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damages.
3. If any damage as a result of shipping is observed, immediately file a claim with the shipping agency and forward a copy to your local Liebert Sales Representative.
Handling Considerations
Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack. Check the size and weight. Refer to the cabinet data furnished with the unit.
Storage
The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care should be taken to avoid condensation. All packing and shipping materials should be left intact until the unit is ready for final installation. If the unit has been stored for an extended period of time, the unit should be cleaned and carefully inspected before placing into service.
LOCATION CONSIDERATIONS
For optimum transient surge protection, coordinated surge suppression should be applied at the service entrance and all other electrical connections to the building (telephone, CATV, etc.), at known surge generating loads within the building (large motors, arc welders, switched capacitors, etc.), as well as at sensitive electronic loads (such as computers, electronic appliances, solid state motor drives, etc.). For interconnected electronic loads (such as by way of data cabling), transient surge suppression should also be applied to the interconnecting wiring (data cables).
Environment — Unit is designed for operation indoors in ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (non-condensing).
The unit is provided in an industrial use enclosure, which is dust-tight and drip-tight and should not be installed in areas with excessive dust, corrosive vapors, flammable materials or explosive atmospheres.
Audible Noise — The audible noise of the unit is less than 40 dB at 5 feet, which allows its placement within almost any room if desired.
Service Clearances — Service clearance is needed for units with hinged doors on the front that are capable of being opened. Thirty-six inches (36 in/914 mm) minimum is recommended.
Mounting — Unit is intended to be wall mounted. Refer to installation instructions for mounting dimensions and weight.
Warnings Defined —
Danger: Indicates an imminently
hazardous situation that, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations.
Warning: Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
Caution: Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Installation, Operation and Maintenance Manual 2 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 4
ELECTRICAL CONNECTIONS
Surge Protective Devices
All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.
VERIFY THAT ALL POWER CIRCUITS ARE
DE-ENERGIZED AND LOCKED OUT BEFORE MAKING
ELECTRICAL CONNECTIONS.
Voltage Ratings and Power Source Configurations —
Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See the chart on page 4 for voltage rating applications with typical power source configurations.
Wire Connections — With parallel connection, the size of the wiring to the SPD unit is independent of the protected circuit’s ampacity. NEC Article 285-21(B) requires surge suppressor connecting conductors to be at least #14 copper or #12 aluminum. To reduce the wiring impedance to surge currents, it is recommended that the phase, neutral (if required), and ground conductors are twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors.
Overcurrent Protection — The SPD unit conducts practically no current under normal operation and only conducts very short duration transient surge currents.
NEC Considerations — The following is from the National Electric Code 2008 Edition.
NEC 285.21 Connections
NEC 285.23 Type 1 SPDs. Shall be installed in accordance with
285.35(A) and (B).
(A) Installation. Type 1 SPDs shall be installed as follows:
(1) Type 1 SPDs shall be permitted to be connected to the supply side of the service disconnect as permitted in
230.82(4) or
(2) Type 1 SPDs shall be permitted to be connected in Type 2 locations as specified in 285.24.
(B) At the service. When installed at the services, the grounding conductor of a Type 1 SPD shall be connected to one of the following:
(1) Grounded service conductor
(2) Grounded electrode conductor
(3) Grounding electrode for service
(4)Equipment grounding terminal in the service equipment
Voltage Protection Ratings — To obtain the voltage protection ratings (VPRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with the Standard
for Safety, Surge Protective Devices (SPDs), Standard 1449, Third Edition, released (2009), marked on this product, the wire size
listed for each product must be utilized to connect the unit to your facilities’ power grid. Connections made with conductors other than the wire size listed may result in different VPRs.
Circuit Ampacity Limitations — Representative samples of these products have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents up to 200,000 AIC, as described in the Standard for
Safety, Surge Protective Devices (SPDs), Standard 1449, Third Edition, released (2009).
System Grounding and Bonding — The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD’s operation.
All electrical circuits to the SPD must include an equipment-
grounding conductor as required by the NEC and local codes.
UNGROUNDED POWER SYSTEMS ARE INHERENTLY UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH LINE-TO­GROUND VOLTAGES DURING CERTAIN FAULT CONDITIONS. DURING THESE FAULT CONDITIONS ANY ELECTRICAL EQUIPMENT, INCLUDING AN SPD, MAY BE SUBJECTED TO VOLTAGES WHICH EXCEED THEIR DESIGNED RATINGS. THIS INFORMATION IS BEING PROVIDED TO THE USER SO THAT AN INFORMED DECISION CAN BE MADE BEFORE INSTALLING ANY ELECTRICAL EQUIPMENT ON AN UNGROUNDED POWER SYSTEM. CONTACT FACTORY FOR UNGROUNDED APPLICATIONS.
An insulated grounding conductor is required in addition to any metallic raceway, which may be used as a grounding conductor. For parallel-connected SPDs, the grounding conductor should be the same wire size as the associated power conductors.
(continued on page 5)
Installation, Operation and Maintenance Manual 3 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 5
Source Configurations
L
N
G
L
N
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
B
A
G
N
C
A
N
B C
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
B
A
G
N
C
A
N
B C G
A
B C G
Single Phase L-N, 2 W + G
VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS
Nominal Operating Voltage
L-N L-G L-L
120 120 N/A
Maximum Continuous
Operating Voltage
150 L-N
Model Voltage Code
(Found in part number)
120 N
Single Phase L-L, 2 W + G
Single Phase, 3 W + G
Three Phase Delta, 3 W + G
Three Phase Wye, 4 W + G
Three Phase Wye, 3 W + G No Neutral
Installation, Operation and Maintenance Manual 4 Liebert SPDs SL-22075 Rev 0, 9/2010
230 230 N/A
277 277 N/A
320 L-N
320 L-N
230 N
277 N
N/A 208 208
N/A 240 240
N/A 400 400
N/A 480 480
120 120 208, 240
240, 277 240, 277 480
N/A 208 208
N/A 240 240
N/A 380-415 380-415
N/A 480 480
120 120 208
220-240 220-240 380-415
277 277 480
N/A 120 208
N/A 220-240 380-415
N/A 277 480
300 L-L
320 L-L
580 L-L
580 L-L
150 L-N
320 L-N
300 L-L 208D
320 L-L
580 L-L
580 L-L
150 L-N
320 L-N
320 L-N
150 L-G
320 L-G
320 L-G
208L
240L
400L
480L
120S
240S
240D
400D
480D
120Y
230Y
277Y
120X
230X
277X
Note 1: For other voltages or source configurations, consult factory.
Page 6
E
F
(4X)
B
A
D
C
Service Panel for
Loads to be Protected
Phase L1/A
Phase L2/B Phase L3/C
Disconnect/Main Breaker for Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Recommended Wire
Entrance
Summary Alarm Contacts (X2)
Pin 1 = Normally Open
Pin 2 = Common
Pin 3 = Normally Closed
TB1 TB2
1 2 3 1 2 3
Liebert SH Series (Without Disconnect)
Model
#
Dimensions (Inches)
Weight
(lbs)
A B C D E F
SH025 SH032 SH040 SH075
16 16 16 20
8 8 8 8
17.25
17.25
17.25
21.25
9.5 10 10 14
0.44
0.44
0.44
0.44
35 49 49 85
16 16 16 20
Liebert SH Series (With Disconnect)
Model
#
Dimensions (Inches)
Weight
(lbs)
A B C D E F
SH025 SH032 SH040 SH075
16 16 16 24
8 8 8 8
21.25
21.25
21.25
21.25
10 10 10 18
0.44
0.44
0.44
0.44
45 58 58 95
20 20 20 20
To
Protected
Loads
Liebert
Surge
Protective
Device
Protected
Panel
Wire should be less than 5 feet
and straight
as possible
Neutral
Phase(s)
Transient
Ground
Safety
Ground
Neutral
Phases
Ground
To
Protected
Loads
Liebert
Surge
Protective
Device
Protected
Panel
Wire should be less than 5 feet
and straight
as possible
Neutral
Phase(s)
Transient
Ground
Safety
Ground
Neutral
Phases
Ground
To
Protected
Loads
Liebert
Surge
Protective
Device
Protected
Panel
Wire should be less than 5 feet
and straight
as possible
Neutral
Phase(s)
Transient
Ground
Safety
Ground
Neutral
Phases
Ground
Rotary
Disconnect
PARALLEL CONNECTIONS
Surge Protective Devices
Typical Parallel Connections
(without Internal Rotary Disconnect)
Grounding conductors must be routed with the associated power conductors in the same raceway (conduit). When metallic raceways are used, adequate electrical continuity must be maintained at all raceway connections, particularly raceway terminations to the electrical enclosures.
The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended.
Grounding Electrode — Surge protective devices do not discharge all surges to ground (earth). Surge protective devices can also divert the surge current back to its source to complete the electrical circuit.
In the case of lightning whose potential is developed with respect to the earth, the SPD diverts the surge current to the grounding electrode (earth connection). However, for most transient surges that are developed by switching loads, the SPD diverts the surge current back to its source without involving the grounding electrode.
Installation, Operation and Maintenance Manual 5 Liebert SPDs SL-22075 Rev 0, 9/2010
ELECTRICAL CONNECTIONS
Typical Parallel Connections
(with Internal Rotary Disconnect)
(continued from page 3)
For proper SPD performance, the service entrance grounding electrode system must comply with the NEC by having all available electrodes (building steel, metal water pipe, driven rods, concrete encased electrodes, etc.) properly bonded together and connected to the power system grounding.
The use of a separate grounding electrode to ground the SPD defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended.
Neutral Connection –
FOR PROPER AND SAFE OPERATION, THE SPD’s
NEUTRAL, MUST BE RELIABLY CONNECTED TO THE NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLE NEUTRAL CONNECTION MAY RESULT IN FAILURE!
Page 7
E
F
(4X)
B
A
D
C
Service Panel for
Loads to be Protected
Phase L1/A
Phase L2/B Phase L3/C
Disconnect/Main Breaker for Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Recommended Wire
Entrance
Summary Alarm Contacts (X2)
Pin 1 = Normally Open
Pin 2 = Common
Pin 3 = Normally Closed
TB1 TB2
1 2 3 1 2 3
Liebert SH Series (Without Disconnect)
Model
#
Dimensions (Inches)
Weight
(lbs)
A B C D E F
SH025 SH032 SH040 SH075
16 16 16 20
8 8 8 8
17.25
17.25
17.25
21.25
9.5 10 10 14
0.44
0.44
0.44
0.44
35 49 49 85
16 16 16 20
Liebert SH Series (With Disconnect)
Model
#
Dimensions (Inches)
Weight
(lbs)
A B C D E F
SH025 SH032 SH040 SH075
16 16 16 24
8 8 8 8
21.25
21.25
21.25
21.25
10 10 10 18
0.44
0.44
0.44
0.44
45 58 58 95
20 20 20 20
INSTALLATION INSTRUCTIONS
The Liebert SH Series Hybrid Surge Protective Devices (SPDs) are high quality, high energy surge current diversion systems designed to protect sensitive equipment from damaging transient voltage surges. Proper installation is required for maximum system performance.
The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert SPD system should only be performed by qualified personnel.
1. Insure that all power is removed before beginning installation. A qualified licensed electrician shall install all electrical connections.
Dimensional Information
Liebert SH Series
Surge Protective Devices
2. The SPD is provided in NEMA 4 enclosures which are suitable for use in indoor or outdoor installations.
3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and the input power terminals of the service panel. Punch or cut the proper hole size in the side of the SPD closest to the knockout to be utilized in the service panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the table below. Mount surge suppressor to wall using 3/8” mounting hardware.
(continued on page 7)
Installation, Operation and Maintenance Manual 6 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 8
Surge Protective Devices
L
N
G
L
N
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
B
A
G
N
C
A
N
B C
G
L
N
G
L
N
G
L1
L2
G
L1
L2
G
L1
N
G
L2
L1
N
G
L2
A
B
C
GG
B
A
G
N
C
A
N
B C G
A
B C G
Model #
Allowable Range
Factory Suggested Size
Circuit Breaker Size
Connection Wire Size
Circuit Breaker
Size
Connection
Wire Size
With Disconnect Without Disconnect With Disconnect Without Disconnect
SH025 SH032 SH040 SH075
15A – 150A 15A – 175 A 15A – 175A 15A – 175A
15A – 175A
#8 – 1/O AWG #8 – 1/O AWG #8 – 1/O AWG #8 – 1/O AWG
60 Amp 80 Amp 80 Amp
100 Amp
#6 AWG #4 AWG #4 AWG #2 AWG
#14 – 2/O AWG
INSTALLATION INSTRUCTIONS
4. Connect black wires (line or phase) marked L1/A, L2/B or
L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical distribution system, keep all conductors as short as possible and avoid sharp bends.
5. Connection to the unit’s summary alarm contacts shall be with #18 – 22 AWG. The ratings of the Form ‘C’ contacts are 5 amps at 250 VAC maximum with a power factor of 1.0. For additional information, see “Monitoring” section.
6. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or a RED
7. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or
1-607-721-8840.
8. The protection modules in these SPDs may be replaceable,
contact Liebert/Emerson Network Power Surge Protection for replacement.
(continued from page 6)
LED is illuminated, check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-721-8840.
Installation, Operation and Maintenance Manual 7 Liebert SPDs SL-22075 Rev 0, 9/2010
If the SPD model is a Wye configured unit (4W+G), and a Neutral connection is not available, please contact factory.
SUGGESTED BREAKER AND WIRE SIZE
Page 9
Surge Protective Devices
MONITORING FEATURES
External Status Indicators (Standard) — These indicators
provide a summary of the status of the surge SPD module. For normal conditions, the green “OK” LED is illuminated and the red “Service” LED is extinguished. If the surge SPD module requires replacement, the green “OK” LED is turned off and the red “Service” LED illuminated.
Audible Alarm (Standard) — If the surge SPD module requires replacement, an audible alarm is activated to draw attention to the fact that repair service is required to restore the system to normal operation. An audible alarm disable is provided to silence the alarm. The system will automatically reset itself after repair. The audible alarm switch and “Service” LED can be tested by activating the “Test” switch on the system monitor panel.
Summary Alarm Contact (Standard) — Two sets of summary alarm Form C relay contacts (2 N.O. and 2 N.C.) are provided for remote indication of the failed surge SPD module. Contacts are rated 5 amps at 250 VAC maximum with a power factor of
1.0. Access to the contacts is provided via contact terminals located on the printed circuit board mounted on the inside of the unit’s cover.
Surge Counter (Optional) – The surge counter is provided for transient voltage surge monitoring. The counter totalizes line surges monitored since the last time the counter was reset. The circuit counts all surges that deviate from the line sine wave. The factory setting is 30% over nominal line voltage. Other settings include 50%, 70%, and 100%.
TROUBLESHOOTING/ SERVICING/
MAINTENANCE
Troubleshooting
If status failure indication occurs or summary alarm contacts has changed states, a qualified electrician shall first determine if the systems voltage and proper phasing exists.
If the SPD remains in an alarm condition once the electrician is satisfied that the electrical system and its connections are normal, the unit should be repaired.
At this point consult the factory, having available the following information:
• Unit identification number – (refers to the model and serial numbers detailed on the data label and is located on the front of the enclosure.)
• Nature of problem – (including status of all status indicators and alarms).
Servicing
The Liebert SH Series comes with a ten year parts and five year labor warranty (see Warranty Information). For servicing assistance, contact your local Liebert Sales Representative or Emerson Network Power, Surge Protection at 800-288-6169
or 607-721-8840.
ONLY QUALIFIED PERSONNEL SHOULD PERFORM MAINTENANCE ON THE SYSTEM.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS.
ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS UNIT.
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT.
Corrective Maintenance - The Liebert SPD is designed for
years of trouble-free operation. However, even the most reliable equipment may fail under abnormal conditions. Diagnostic indicators are provided to indicate when the unit needs repair or replacement. To ensure continuity of surge protection, failed units should be repaired or replaced at the earliest convenient service opportunity. When replacing surge modules, other components should be inspected for damage and replaced if necessary. Standard electrical troubleshooting procedures should be used to isolate problems other than failed surge current diverter modules. When replacing components, for continued proper operation and safety, replace only with identically rated components. Please contact factory for information on replacement parts.
Preventative Maintenance (Inspection and Cleaning) - Periodic system inspections, cleaning, and connection checks are recommended to ensure reliable system performance and continued surge transient protection.
It is difficult to establish a schedule for preventative maintenance since conditions vary from site to site. Inspections for failed surge modules using available diagnostics should be done routinely (weekly or monthly).
Installation, Operation and Maintenance Manual 8 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 10
Surge Protective Devices
Limited Warranty
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business.
General: Liebert Corporation products and systems are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship.
Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty.
TEN YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
LIEBERT PRODUCTS COVERED:
Liebert SH Series (Interceptor®)
Terms of Warranty:
As provided herein, the Liebert product is warranted to be free of defects in material and workmanship for a period of ten (10) years from the date of product shipment from Liebert. The shipment date will be determined only from the Liebert bill of lading. If any part or portion of the Liebert product fails to conform to the warranty within the warranty period, Liebert, at its option, will furnish new or factory remanufactured parts for repair or replacement of that part or portion.
Warranty Extends to First Purchaser for Use, Non-transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the Liebert product specified herein is originally installed for use (the “User”) in the fift y United States (excluding territories) or Canada. This Warranty is not transferable or assignable without the prior written permission of Liebert.
Assignment of Warranties:
Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of the Liebert product and which are assignable, but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components.
Drawings, Descriptions:
Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the certified drawings, if any, applicable thereto, to Liebert’s final invoices, and to applicable Liebert product brochures and manuals current as of the date of product shipment (“Descriptions”). Liebert does not control the installation and use of any Liebert product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
Obtaining Performance Under This Warranty:
Within a reasonable time, but in no case to exceed thirty (30) days, after User’s discovery of a defect, User shall contact Liebert at 1-800-LIEBERT (543-2378) and request a return authorization number. User shall ship the product, with proof of purchase, to Liebert freight prepaid. Liebert products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User’s expense. Liebert products shipped by User to Liebert which have incurred freight damage due to User’s improper packaging of the product will not be covered by this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned freight collect to User.
Subject to the limitations specified herein, Liebert will repair or replace, at its option, without charge for Liebert labor or materials, subsequent to its inspection F.O.B. Liebert’s facility, the Liebert product warranted hereunder which does not conform to the Warranty. Replacement parts, components or products shipped to User prior to Liebert’s receipt and inspection of the product claimed to be defective shall be invoiced in the full current price amount and shipped freight collect F.O.B. Liebert’s facility. Warranty coverage will be extended only after Liebert’s receipt of the claimed defective product within thirty (30) days of shipment of any replacement parts, components or products, if applicable, and only if Liebert’s inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of this Warranty. All defective products and component parts replaced under this Warranty become the property of Liebert.
Warranty Performance of Component Manufacturers:
It is Liebert’s practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate with and utilize the services of component manufacturers and their authorized representatives in the per formance of work to correct defects in the product components. Accordingly, Liebert may utilize third parties in the performance of Warranty work, including repair or replacement hereunder, where, in Liebert’s opinion, such work can be performed in less time, with less expense, or in closer proximity to the Liebert product.
Installation, Operation and Maintenance Manual 9 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 11
Items Not Covered By Warranty:
Surge Protective Devices
Installation, Operation and Maintenance Manual 10 Liebert SPDs SL-22075 Rev 0, 9/2010
Page 12
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 800 877 9222 Phone (US & Canada Only) 614 888 0246 (Outside U.S.) 614 841 6022 FAX
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX
Liebert.com
Technical Support
607 721 8840 Phone 607 722 8713 FAX 800 288 6169 Toll-Free
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-22075 (9/10) Rev. 0 Printed in USA
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™. Emerson Network Power.com
AC Power Connectivity DC Power
Emerson Network Power, the Emerson Network Power logo and Business-Critical Continuity are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
Embedded Computing Embedded Power Monitoring
Outside Plant Power Switching & Controls Precision Cooling
Racks and Integrated Cabinets Services
Surge Protection
Loading...