This guide provides basic guidelines for Rosemount Smart Pressure Gauges. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, or intrinsically safe
(I.S.) installations. Refer to the Rosemount Smart Pressure Gauge Reference Manual for more
instruction. The manual and this guide are also available electronically.
NOTICE
Shipping considerations
The device is shipped with the battery installed.
Each device contains one “D” size primary lithium-thionyl chloride battery. Primary lithium
batteries are regulated in transportation by the U.S. Department of Transportation, and are also
covered by IATA (International Air Transport Association), ICAO (International Civil Aviation
Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the
responsibility of the shipper to ensure compliance with these or any other local requirements.
Consult current regulations and requirements before shipping.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local,
national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field practices.
Electrical shock could cause death or serious injury.
Device must be installed to ensure a minimum antenna separation distance of 8 in. (20 cm) from
all persons.
Care must be taken during transportation of device to prevent electrostatic charge build-up.
Process leaks could result in death or serious injury.
Handle the device carefully.
Failure to follow these installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
Q4: Calibration Cert
QG: Calibration Cert and GOST
Verification Cert
QP: Calibration Cert and Tamper Evident
Seal
Q8: Material Traceability cert per EN
102043.1
Q15: Cert of Compliance to NACE
MR0175/ISO 15156 for wetted materials
Q25: Cert of Compliance to NACE
MR00103 for wetted materials
Normal range Indication (model code LK) Product Certification model codes
Quick Start Guide5
Quick Start GuideFebruary 2019
3Optional: Power/device check
The device is designed to be installation-ready.
Procedure
1. To check device battery prior to installation, perform Turn on device
2. Slide the ON/OFF switch to the OFF position until ready for use.
6Emerson.com/Rosemount
February 2019Quick Start Guide
4Optional: Normal range indication option
Important
• The stickers are intended to be installed on the dial only and should not be
applied on the inside or outside of the housing cover.
• Stickers should be applied in an environment where the ambient
temperature is above 50°F (10°C)
Procedure
1. Modify each of the stickers to desired size.
2. Remove housing cover.
3. Slide ON/OFF switch to the OFF position and wait for the LED to stop
flashing.
4. Gently move the needle in the clockwise direction until it is pointing at
the red X.
NOTICE
Equipment Damage
Use caution as the electronics assembly is connected to the needle.
5. Remove any debris on the dial, so it does not become trapped under
the sticker.
6. Peel back the white paper backing of the sticker.
7. Slowly lower the sticker onto the surface of the dial in the desired
location and rub it in place firmly. Repeat steps Step 6 and Step 7 until
desired indication locations are set.
Moving the sticker after initial contact is not recommended as this
decreases the amount of adhesive on the back of the sticker.
8. Slide ON/OFF switch to the ON position.
9. Replace housing cover.
Quick Start Guide7
OR
Quick Start GuideFebruary 2019
5Installation Procedure
Procedure
1. Seal and protect threads
2. Mount device
Note
Use wrench on flats, not on housing.
5.1
Mounting orientation
The low side pressure port (atmospheric reference) is located in the neck of
the device behind the housing.
The vent path is between the housing and sensor.
CAUTION
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the device so the process can drain away.
8Emerson.com/Rosemount
A
February 2019Quick Start Guide
Figure 5-1: Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
5.2Turn on device
Check to ensure the device and battery are working properly.
Procedure
1. Twist the cover counterclockwise to remove it.
2. Slide the OFF/ON switch to the ON position to initiate the power
sequence.
Note
During the power sequence, the dial tests full range of motion and LED
flashes amber.
3. Once the power sequence ends, verify that the LED flashes green.
The LED may display several colors; see Device status indicator .
Quick Start Guide9
1 2 3
64 5
8 709
A
B
C
Quick Start GuideFebruary 2019
5.3Connect to the device
Image displaying the device connection diagram
A. Field Communicator
B. HART® Modem
C. AMS Configurator
5.3.1 AMS Configurator
Procedure to connect the AMS Configurator to the smart pressure gauge.
Procedure
1. Start AMS Configurator.
2. From the View menu, select Device Connection View.
3. Double-click the device under the HART modem.
5.3.2 Field communicator
Procedure to connect the smart pressure gauge to the field communicator.
Procedure
1. Turn on the Field Communicator.
2. From the Main menu, select the HART symbol.
5.4
Eliminate mounting effects
Devices are factory-calibrated. Once installed, it is recommended to perform
this step to eliminate potential error caused by mounting position or static
pressure.
10Emerson.com/Rosemount
February 2019Quick Start Guide
Note
See the Rosemount Smart Pressure Gauge Reference Manual for the
following:
• Using AMS Configurator
• Sensor trim function on absolute gauge
Procedure
1. Vent the device.
2. Connect the Field Communicator.
3. From the HOME screen, enter the HART Fast Key sequence.
Device dashboard Fast Keys2, 1, 1
4. Follow the commands to perform the procedure.
Quick Start Guide11
Quick Start GuideFebruary 2019
6Troubleshooting
6.1Device status indicator
Table 6-1: Status Descriptions
LED colorDevice status
GreenFunctioning properly
AmberBattery is low, battery replacement
RedBattery replacement required OR
No colorNo power, verify ON/OFF switch is in
6.2Pressure measurement
If the mounting effects have not been eliminated after completing, perform
this alternative procedure for verifying the pressure value.
Procedure
1. From the HOME screen, enter the HART Fast Key sequence.
recommended
Device is malfunctioning
the on position
Device dashboard Fast
Keys
2, 2, 1, 1, 1
2. Follow the commands to perform the procedure.
12Emerson.com/Rosemount
February 2019Quick Start Guide
7Product Certifications
Rev: 2.0
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification from CSA
The product has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by
CSA, a nationally recognized test laboratory (NRTL) as accredited by the
Federal Occupational Safety and Health Administration (OSHA).
Installing in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions.The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined in
the respective codes.
USA
I5U.S.A. Intrinsically Safe (IS)
Certificate:
Standards:
Markings:
Special Conditions for Safe Use(X):
1. Do not replace battery when explosive atmosphere is present.
2. Use only 00G45-9000-0001 batteries.
3.
4. Substitution of components may impair intrinsic safety.
Quick Start Guide13
[CSA] 70047656
FM 3600 – 2011, FM 3610 – 2010, UL Standard 50 – Eleventh
IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0, AEx ia IIC T4 Ga;
T4 (–40 °C ≤ Ta ≤ +70 °C) when installed per Rosemount
drawing 00G45-1020; Type 4X; IP66/67;
The surface resistivity of the housing is greater than 1G. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with
solvents or a dry cloth.
Intrinsically Safe for Class I, Division 1, Groups A, B, C, D T4; Ex
ia IIC T4 Ga T4 (–50 °C ≤ Ta ≤ +70 °C) when installed per
Rosemount drawing 00G45-1020; Type 4X; IP66/67;
Special Conditions for Safe Use (X):
1. Do not replace battery when explosive atmosphere is present. Ne pas
remplacer les accumulateurs si une atmosphère explosive peut être
présente.
2. Use only 00G45-9000-0001 batteries. Utiliser uniquement des
accumulateurs 00G45-9000-0001.
3.
The surface resistivity of the housing is greater than 1G
. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with
solvents or a dry cloth. La résistivité de surface du boÎtier est
supérieure à un gigaohm. Pour éviter l’accumulation de charge
électrostatique, ne pas frotter ou nettoyer avec des produits solvants
ou un chiffon sec.
4. Substitution of components may impair intrinsic safety. La
substitution de composants peut compromettre la sécurité
intrinsèque.
Europe
I1
Certificate:
Standards:
Markings:
ATEX Intrinsic Safety
Baseefa16ATEX0005X
EN 60079-0: 2012 + A11: 2013, EN 60079-11: 2012
II 1 G Ex ia IIC T4 Ga, T4 (–40 °C ≤ Ta ≤ +70 °C) IP66/67;
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The measured capacitance between the equipment enclosure and
metallic inline sensor module is 4.7pF. This must be considered only
when the SPG is integrated into a system where the process
connection is not grounded.
14Emerson.com/Rosemount
February 2019Quick Start Guide
3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.
International
I7IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 16.0012X
IEC 60079-0: 2011, IEC 60079-11: 2011
Ex ia IIC T4 Ga, T4 (–40 °C ≤ Ta ≤ +70 °C) IP66/67;
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The measured capacitance between the equipment enclosure and
metallic inline sensor module is 4.7pF. This must be considered only
when the SPG is integrated into a system where the process
connection is not grounded.
3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.
Quick Start Guide15
EU Declaration of Conformity
No: RMD 1108 Rev. E
Page 1 of 3
We,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
declare under our sole responsibility that the product,
Models WPG & SPG:
Wireless Pressure Gauge & Smart Pressure Gauge
manufactured by,
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317-9685
USA
to which this declaration relates, is in conformity with the provisions of the European
Community Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when
applicable or required, a European Community notified body certification, as shown in the
attached schedule.
(signature)
Vice President of Global Quality
(function name - printed)
Chris LaPoint
(name - printed)
1-Feb-19
(date of issue)
Quick Start GuideFebruary 2019
Figure 7-1: Declaration of Conformity
16Emerson.com/Rosemount
EU Declaration of Conformity
No: RMD 1108 Rev. E
Page 2 of 3
EMC Directive (2014/30/EU)
Models WPG & SPG
Harmonized Standards:
EN 61326-1: 2013
Radio Equipment Directive (RED) (2014/53/EU)
Model WPG (Wireless Pressure Gauge only)
Harmonized Standards:
EN 300 328 V2.1.1
EN 301 489-1 V2.2.0
EN 301 489-17: V3.2.0
EN 61010-1: 2010
EN 62479: 2010
ATEX Directive (2014/34/EU)
Models WPG & SPG
Baseefa16ATEX0005X - Intrinsic Safety Certificate
Equipment Group II Category 1 G
Ex ia IIC T4 Ga, T4(-40°C ≤ Ta ≤ +70°C)
Harmonized Standards:
EN 60079-0: 2012 + A11: 2013
EN 60079-11: 2012
February 2019Quick Start Guide
Quick Start Guide17
EU Declaration of Conformity
No: RMD 1108 Rev. E
Page 3 of 3
ATEX Notified Bodies
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3)
00211 HELSINKI
Finland
Quick Start GuideFebruary 2019
18Emerson.com/Rosemount
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount SPG
List of Rosemount SPG Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
XOOOOO
༣փ㓴Ԧ
Housing
Assembly
OOOOOO
Րᝏಘ㓴Ԧ
Sensor
Assembly
XOOOOO
⭥⊐㓴Ԧ
Battery
Assembly
XOOOOO
ᵜ㺘Ṭ㌫ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ
This table is proposed in accordance with the provision of SJ/T11364.
O:
Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of
GB/T 26572.
X:
Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above
the limit requirement of GB/T 26572.
February 2019Quick Start Guide
Quick Start Guide19
*00825-0100-4145*
00825-0100-4145, Rev. BB
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo is a
trademark and service mark of Emerson Electric
Co. Rosemount is mark of one of the Emerson
family of companies. All other marks are the
property of their respective owners.