Emerson Rosemountl, 0085 Quick Start Manual

Quick Start Guide
00825-0100-4952, Rev DC
Rosemount™ 0085 Pipe Clamp Sensor Assembly
August 2017
Quick Start Guide
NOTICE
This guide provides basic guidelines for Rosemount 0085 Pipe Clamp Sensor. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 0085 Pipe Clamp Sensor Reference Manual instruction. The manual and guide are also available electronically on Emerson.com/Rosemount
If the Rosemount 0085 Sensor was ordered assembled to a temperature transmitter, see the appropriate Quick Start Guide for information on configuration and hazardous locations certifications.
Figure 1. Rosemount 0085 Pipe Clamp Sensor Assembly Exploded View
A
B
for more
.
C
D
E
F
G
H
A. Transmitter B. Sensor with spring loaded adapter C. Nipple union of the extension D. Nut
E. O-ring F. Mounting hardware G. Corrosion protection inlay (optional) H. Pipe clamp
Contents
Location and orientation . . . . . . . . . . . . . . . . . . 3
Install pipe clamp sensor . . . . . . . . . . . . . . . . . . 6
Installing optional accessories . . . . . . . . . . . . . . 7
2
Rosemount X-well™ Technology considerations . 9
Product Certifications . . . . . . . . . . . . . . . . . . . . . . . 11
August 2017
360°
Recommended
Zone
1.0 Location and orientation
The pipe clamp sensor should be mounted on the outside section of the pipe where the process medium is in contact of the inside of the pipe wall. Ensure that the pipe surface is clean of debris. The pipe clamp sensor should be mounted in a secure position to ensure there is no rotational movement after installation. To ensure ingress protection, the nut of the Rosemount 0085 Pipe Clamp sensor can be tightened to compress the O-ring to form a seal. The nut can be accessed and tightened by removing the sensor and the nipple union of the extension. Refer to “Location and orientation” on page 3 for the location of each part.
1.1 Horizontal orientation
Though the Rosemount 0085 Pipe Clamp sensor can be mounted in any orientation for full pipe flow applications, the best practice is to mount the pipe clamp sensor on the upper half of the pipe. Refer to Figure 2 for more information.
Quick Start Guide
Figure 2. Horizontal Orientation
Full pipe flow Partial pipe flow
1.2 Vertical orientation
The pipe clamp sensor can be installed in any position around the circumference of the pipe.
3
Quick Start Guide
Figure 3. Vertical Orientation
360°
1.3 Special considerations
Under most circumstances, the Rosemount 0085 Pipe Clamp Sensor can be mounted in a direct mount configuration. Since heat from the process is transferred from the pipe clamp sensor to the transmitter housing, if the expected process temperature is near or beyond specification limits, consider using a remote mount configuration to isolate the transmitter from the process. Refer to the appropriate transmitter reference manual for temperature effects.
Figure 4 displays a pipe clamp sensor assembly in remote mount configuration.
4
August 2017
Figure 4. Pipe Clamp Sensor Assembly in Remote Mount Configuration
Quick Start Guide
Wireless transmitters with external antennas allow for multiple antenna configurations. All wireless transmitter should be appropriately 3 ft. (1 m) from any large structure or building to allow clear communication to other devices. Wireless transmitters with external antennas should be positioned vertically, either straight up or straight down.
Figure 5. Wireless Transmitter Orientation
5
Quick Start Guide
A
D
B
C
2.0 Install pipe clamp sensor
Select the area for pipe clamp sensor installation with the recommendations outlined in “Horizontal orientation” on page 3. Mount the pipe clamp sensor on the pipe and snug tighten the bolts. Ensure the sensor passes through the hole of the pipe clamp and has direct contact between the sensor tip and pipe. Refer to Figure 4 on page 5 for more information. Tighten the bolts to secure the pipe clamp sensor to the pipe.
Figure 6. Sensor Tip and Pipe Contact
CorrectIncorrect
A
C
B
D
A. Sensor B. Extension of pipe clamp C. Pipe clamp D. Pipe
6
Loading...
+ 12 hidden pages