Emerson Rosemount 5900S Quick Start Guide

Page 1
Quick Start Guide
00825-0100-5900, Rev AA
March 2020
Rosemount™ 5900S Radar Level Gauge
Parabolic antenna
Page 2
Contents
Page 3

1 About This Guide

This Quick Start Guide provides basic guidelines for installation and configuration of the Rosemount 5900S Radar Level Gauge with Parabolic antenna.
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For equipment service or support needs, contact your local Emerson Automation Solutions/Rosemount Tank Gauging representative.
Spare Parts
Any substitution of non-recognized spare parts may jeopardize safety. Repair, e.g. substitution of components etc, may also jeopardize safety and is under no circumstances allowed.
Rosemount Tank Radar AB will not take any responsibility for faults, accidents, etc caused by non-recognized spare parts or any repair which is not made by Rosemount Tank Radar AB.
Specific ETSI Requirements (Europe)
The Rosemount 5900S is required to be installed at a permanent fixed position at a closed (not open) metallic tank or reinforced concrete tank, or similar enclosure structure made of comparable attenuating material. Flanges and attachments of the Rosemount 5900S equipment shall provide the necessary microwave sealing by design.
Manholes or connection flanges at the tank shall be closed to ensure a low­level leakage of the signal into the air outside the tank.
Installation and maintenance of the Rosemount 5900S equipment shall be performed by professionally trained individuals only.
Specific FCC Requirements (USA)
Rosemount 5900S generates and uses radio frequency energy. If it is not installed and used properly, that is, in strict accordance with the manufacturer´s instructions, it may violate FCC regulations on radio frequency emission.
Rosemount TankRadar 5900S has been FCC certified under test conditions which assume a metallic tank.
Page 4
Specific IC Requirements (Canada)
Radio approvals for this device apply for installation in complete enclosed container to prevent unwanted RF emission. In open air application site license is required. Installation shall be done by trained installers, in compliance with the manufacturer's instructions.
The use of this device is on a "no-interference, no-protection" basis. That is, the user shall accept operations of high-powered radar in the same frequency band which may interfere with or damage this device. Devices found to interfere with primary licensing operations will be required to be removed at the user's expense.
Low Emission of Microwave Radiation
The microwave radiation emitted by a Rosemount 5900S radar level gauge is very low compared to limits given by the Rec. 1999/519/EC (much less than
0.1 mW). No additional safety measures are needed.
CAUTION
The products described in this document are NOT designed for nuclear­qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
NOTICE
The device is designed for installation in complete enclosed container to prevent unwanted RF emission. Installation must be in accordance with local regulations and may require local radio approvals.
Installation in open air applications may be subject for site license approval.
Installation shall be done by trained installers, in compliance with the manufacturer's instructions.
Page 5
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
Use the equipment only as specified in this manual. Failure to do so may
impair the protection provided by the equipment.
Do not perform any service other than those contained in this manual
unless you are qualified.
To prevent ignition of flammable or combustible atmospheres,
disconnect power before servicing.
Substitution of components may impair Intrinsic Safety.
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent
with the appropriate hazardous locations certifications.
Before connecting a handheld communicator in an explosive
atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Do not remove the gauge cover in explosive atmospheres when the
circuit is alive.
High voltage that may be present on leads could cause electrical shock.
Avoid contact with the leads and terminals.
Ensure the main power to the transmitter is off and the lines to any other
external power source are disconnected or not powered while wiring the gauge.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
Page 6
WARNING
WARNING - Substitution of components may impair Intrinsic Safety.
AVERTISSEMENT - La substitution de composants peut compromettre la sécurité intrinsèque.
WARNING - To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
AVERTISSEMENT - Ne pas ouvrir en cas de presence d'atmosphere explosive.
Page 7

2 General information

2.1 Symbols

Table 2-1: Symbols
The CE marking symbolizes the conformity of the product with the applicable European Community Directives.
The EU-Type Examination Certificate is a statement of a Notified Certification Body declaring that this product meets the Essential Health and Safety Requirements of the ATEX directive
The FM APPROVED Mark indicates that the equipment is approved by FM Approvals according to applicable Approval Standards and is applicable for installation in hazardous locations
Protective Earth
Ground
External cabling must be approved for use in min. 81°C

2.2 Service support

For service support contact the nearest Emerson Automation Solutions / Rosemount Tank Gauging representative. Contact information can be found on the web site www.Emerson.com.

2.3 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/ regulations.
Page 8

3 Installation considerations

3.1 General considerations

When finding an appropriate location on the tank for a Rosemount 5900S Radar Level Gauge, the conditions of the tank must be carefully considered. The gauge should be installed so that the influence of disturbing objects is kept to a minimum, preferably outside the radar signal beam.
Ensure that the Rosemount 5900S is installed such that it is not exposed to higher pressure and temperature than specified.
It is the responsibility of the user to ensure that the device meets the specific inside tank installation requirements such as:
chemical compatibility of wetted materials
design/operation pressure and temperature
For a complete specification of the 5900S device to be installed, you can identify the model code on the attached antenna label and match with ordering information data.
Ensure that environmental conditions are within specified limits.
Do not install the Rosemount 5900S in non-intended applications, for example environments where it may be exposed to extremely intense magnetic fields or extreme weather conditions.
Antennas with plastic surfaces and painted surface, may under certain extreme conditions generate an ignition-capable level of electrostatic charge. When installing in hazardous areas ensure using tools, cleaning material etc. which can not generate electrostatic charge.
See the Rosemount 5900S Reference Manual for more information.
Page 9

3.2 Parabolic antenna requirements

3.2.1 Inclination

The inclination of the Rosemount 5900S with Parabolic Antenna should not exceed 1.5 ° towards the center of the tank. For products with high condensation such as bitumen/asphalt applications, the radar beam should be directed vertically without any inclination.
Figure 3-1: Maximum Inclination with Parabolic Antenna
A. Maximum inclination 1.5°

3.2.2 Flange requirements

The tank flange has to meet the following inclination requirements (see
Figure 3-2) in order to allow proper adjustment of the antenna:
maximum 4.5° away from the tank wall
maximum of 2° towards the tank wall
in case the nozzle inclination exceeds the recommended values, you may
use the welded flange ball which can be mounted at a maximum angle of 17°
Page 10
60 mm (2.4 in.)
< 17°
Figure 3-2: Maximum Inclination of Tank Flange
A. 4.5° max B. 2.0° max
Figure 3-3: Maximum Inclination with Welded Flange

3.2.3 Nozzle and free space requirements

When installing the Rosemount 5900S with parabolic antenna on a Ø 20" nozzle, consider the following recommendations.
Obstacles (construction bars, pipes larger than Ø 2", etc.) within the 10° wide radar beam are generally not accepted, as these may result in disturbing echoes. However, in most cases a smooth tank wall or small objects will not have any significant influence.
Page 11
C
E
B
F
F
G
A
D
D
Figure 3-4: Nozzle and Free Space Requirements for Parabolic Antenna
A. Minimum 800 mm (31 in.) for highest accuracy. Minimum 500 mm (20
in.) with reduced accuracy.
B. Recommended height: 400 mm (16 in.). Maximum height: 600 mm (24
in.).
C. Minimum nozzle diameter: 500 mm (20 inch.)
E. Ø 440 mm (17.3 in.)
Vertical plumb line
D.
F. 5° minimum
G. > 800 mm (31.5 in.)
Page 12
$

3.3 Electrical requirements

3.3.1 Cable/conduit entries

The electronics housing has two entries for ½ - 14 NPT. Optional M20×1.5, minifast and eurofast adapters are also available. The connections must be made in accordance with local or plant electrical codes.
Make sure that unused ports are properly sealed to prevent moisture or other contamination from entering the terminal block compartment of the electronics housing.
Note
Use the enclosed metal plugs to seal unused ports. The plastic plugs mounted at delivery are not sufficient as seal!
Note
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and to meet the required degree of ingress protection as well as to enable future removal of the plug/gland.
NPT is a standard for tapered threads. Engage the gland with 5 to 6 threads. Note that there will be a number of threads left outside the housing as illustrated below.
Figure 3-5: Cable Entry with NPT Threaded Gland
A. The NPT threaded gland leaves a number of threads outside the housing
Ensure that glands for the cable entries meet requirements for IP class 66 and 67.

3.3.2 Grounding

The housing should always be grounded in accordance with national and local electrical codes. Failure to do so may impair the protection provided by the equipment. The most effective grounding method is direct connection to earth ground with minimal impedance.
There are three grounding screw connections provided. Two are located inside the terminal compartment of the housing and the third is located on
Page 13
the housing. The internal ground screws are identified by a ground symbol:
.
Note
Grounding the transmitter via threaded conduit connection may not provide sufficient ground.
Grounding - FOUNDATION™ Fieldbus
Signal wiring of the fieldbus segment can not be grounded. Grounding out one of the signal wires may shut down the entire fieldbus segment.
Shield wire ground
To protect the fieldbus segment from noise, grounding techniques for shield wire usually require a single grounding point for shield wire to avoid creating a ground loop. The ground point shall be located at the power supply.
The devices designed for “daisy-chain” connection offer an isolated shield loop-through terminal in order to enable a continuous shield throughout the Tankbus network.
In order to avoid unintentional grounding points, the cable shield inside the terminal compartment must be isolated.

3.3.3 Hazardous areas

When the Rosemount 5900S level gauge is installed in hazardous areas, local regulations and specifications in applicable certificates must be observed.
Certificates for Rosemount Tank Gauging products, such as the Rosemount 5900, are available on Emerson.com/Rosemount Tank Gauging.

3.3.4 Power requirements

The Rosemount 5900S is powered over the intrinsically safe Tankbus by the Rosemount 2410 Tank Hub. The 2410 feeds the intrinsically safe fieldbus segment by acting as a FISCO power supply on the Tankbus.
When installed in a FOUNDATION Fieldbus system without a Rosemount 2410 Tank Hub, the Rosemount 5900S is powered by the FF segment.
Page 14

4 Mechanical installation

4.1 Parabolic antenna

4.1.1 Mounting the clamped Flange Ball

Follow this instruction when installing the clamped Flange Ball on a flange.
Prerequisites
1.
Use a flange of thickness 6 - 30 mm.
Make sure that the diameter of the hole is 96 mm. Make a small
2. recess at one side of the flange hole.
Figure 4-1: Flange Requirements
A. Recess
Page 15
$
%
Procedure
1. Put the O-ring on the flange and insert the Flange Ball into the hole. Make sure that the guide pin on the side of the Flange Ball fits into the recess on the flange.
A. Flange Ball B. Nut
2. Tighten the nut so that the Flange Ball fits tightly to the flange (torque 50 Nm).

4.1.2 Mounting the welded Flange Ball

Follow this instruction when installing the welded Flange Ball on a flange.
Prerequisites
For horizontal mounting according to requirements in chapter Parabolic
antenna requirements, make sure that the diameter of the hole is 116 ± 2
mm.
Page 16
$
%
%
$
Figure 4-2: Flange Requirements
A. 116±2 mm B. 6-38 mm
In case the flange requirements in chapter Parabolic antenna requirements are not met, the hole needs to be machined to an oval shape prepared for inclined welding of the Flange Ball.
Procedure
1.
Let the protection plates remain on the Flange Ball until welding is finished. These plates protect the surface of the Flange Ball from welding sparks.
A. Protection plate B. Flange Ball
Page 17
$
60 mm (2.4 in.)
< 17°
2. Make sure that the Flange Ball is mounted in such a way that the grove is directed upwards when the flange is mounted on the tank nozzle.
A. Groove
3. If the tank flange is inclined, make sure that the Flange Ball is welded so that the Flange Ball is horizontal when it is mounted on the tank.
The tank flange inclination should not exceed 17 degrees.
Page 18
$
$
4. Remove the protection plates when the Flange Ball is welded to the flange.
A. Protection plate

4.1.3 Mounting the parabolic antenna

This section describes how to install the Rosemount 5900S with Parabolic antenna.
Follow this instruction to install the Parabolic antenna and transmitter head assembly on a tank.
Prerequisites
See Parabolic antenna requirements for considerations before installing
the gauge on the tank.
Check that all parts and tools are available before carrying them up to
the tank top.
Page 19
$
%
&
Procedure
1. Fit the Parabolic Reflector onto the Antenna Feeder and tighten the five M5 screws.
A. M5x5 B. Parabolic Reflector C. Antenna Feeder
2. Check that all parts are properly mounted.
Page 20
&
$
%
'
3. Put the two O-rings in the grooves on the upper surface of the Flange Ball.
A. 2 O-rings B. Grooves C. Flange Ball
D.
Flange
Page 21
$
%
&
'
(
*
+
)
4. Turn the flange around and insert the Antenna Waveguide into the flange hole.
A. Nut B. Tab Washer C. Antenna label plate
Finger Nut
D.
E. Washer Ball
F. Stop Washer G. Flange H. Antenna Waveguide
5. Mount the washers and nuts. Note that the purpose of the Stop Washer is to prevent the antenna
from falling down into the tank. Therefore it fits tightly to the Antenna Waveguide.
Page 22
$
%
C
B
A
D
6. Tighten the finger nut and the upper nut by hand.
A. Finger Nut B. Upper Nut
7. Place the antenna and flange assembly on the tank nozzle and tighten the flange screws.
A. Antenna Waveguide B. Flange C. Antenna
D.
Nozzle
Page 23
&
%
$
8. Put the level gauge on the Antenna Waveguide. Ensure that the guide pin inside the transmitter head fits into the groove on the Antenna Waveguide.
A. Nut B. Antenna Waveguide C. Finger Nut
9. Tighten the nut that connects the transmitter head to the antenna.
10.
Loosen the finger nut slightly.
Page 24
$
&
%
r
r
11. Align the level gauge by using the cross hairs on top of the transmitter head.
In case the weather protection hood is attached, the gauge can be aligned by using a line of sight along the screws on top of the head.
A. Tank B. Tank center C. Line of sight
12. Ensure that the gauge is directed at an angle of 45° to the line of sight from the center of the tank to the wall.
Page 25
13. Use the marks on the Washer Ball to adjust the gauge so the antenna is inclined roughly 1.5° towards the center of the tank.
Note
For products with high condensation, such as bitumen, the gauge should be mounted with 0° inclination in order to achieve maximum signal strength.
A. Marks B. Plumb line C. Tank center
D. Incline antenna 1.5° towards tank center
14. Tighten the finger nut.
Page 26
15. You may use a level (optional) to verify correct inclination of 1.5° towards the tank center. Ensure that the level is put on a flat and steady surface on top of the transmitter head. If needed, loosen the finger nut and adjust the gauge.
Note
Make sure the air bubble touches, but doesn't overlap the 1.5° mark.
A. Finger Nut
16. Tighten the finger nut firmly.
Page 27
17. In case the Weather Protection Hood was removed, put it back on top of the transmitter head and tighten the screw.
A. Weather Protection Hood B. Finger Nut
Page 28
18. Tighten the upper nut to lock the finger nut (you may temporarily remove the transmitter head to make room for tools if needed), and secure by folding the tab washer over the nut.
A. Upper Nut
19. Wire the gauge and configure by using the RosemountTankMaster WinSetup software (see the Rosemount Tank Gauging System
Configuration Manual).
Page 29

5 Electrical installation

5.1 Wiring

To connect the Rosemount 5900S level gauge:
Procedure
Ensure that the power supply is switched off.
1.
2. Remove the cover on the terminal compartment.
3. Run the wires through the appropriate cable gland/conduits. Install cables with a drip loop in such a way that the lower part of the loop is under the cable/conduit entry.
4.
Connect wires as described in Terminal blocks.
5. Ensure that the positive lead is connected to the terminal marked FB + and the negative lead to the terminal marked FB-.
6. Use metal plugs to seal unused ports.
The cover on the terminal compartment should be tightened to
7. mechanical stop (metal to metal). Make sure the cover is fully engaged to meet explosion-proof requirements and to prevent water from entering the terminal compartment.
8. Tighten the cable gland/conduit. Note that adapters are required for M20 glands.
Note
Ensure that O-rings and seats are in good condition prior to mounting the cover in order to maintain the specified level of ingress protection. The same requirements apply for cable inlets and outlets (or plugs). Cables must be properly attached to the cable glands.
Page 30
AA
B
D
E
C
F
Figure 5-1: Terminal Compartment
A. Cable glands B. Internal Ground screws C. Terminals for signal and power supply
Locking screw (Unscrew to lock)
D.
E. External Ground screw F. Cover
Page 31
B
A A
C
+
-
+
-
C

5.2 Terminal blocks

Figure 5-2: Rosemount 5900S Terminal Compartment
A. Test terminals B. Ground terminals, internal C. Field bus
Table 5-1: Terminal Block Connections for the Rosemount 5900S
Connection Description
X1: Tankbus in Intrinsically safe Tankbus input, power and communication
X2: Terminate on The integrated line terminator is connected over the Tankbus
X3: Shield loop through
X4: Tankbus out Tankbus output connected to X1 for optional daisy-chain
Test terminals Test terminals for temporary connection of a Field
(spur in FOUNDATION Fieldbus system)
when a jumper is placed in the terminal block
Cable shield daisy-chain connector (not grounded)
connection to other devices
Communicator
Page 32
A
FB +
FB -
B
C

5.2.1 Terminal block two-in-one single bus

Figure 5-3: Terminal Compartment 2-in-1 Version
A. Test terminals
B. Ground terminals, internal
C. Jumpers between X3 and X4
FB. Field Bus
Table 5-2: Rosemount 5900S Two-in-One with Single Tankbus
Connection Two-in-One / Single tankbus
X1: Primary Tankbus in
X2: Primary Terminate on
X3: Primary Tankbus out
X4: Secondary Tankbus in
Test terminals Test terminals for temporary connection of a field
Intrinsically safe Tankbus input, power and communication
Termination for primary tankbus. The integrated line terminator is connected over the Tankbus when a jumper is placed in the terminal block.
Jumpers between X3 and X4
communicator
Page 33

6 Configuration

6.1 Tank geometry parabolic antenna

The following parameters are used for tank geometry configuration of a Rosemount 5900S Radar Level Gauge with parabolic antenna:
Figure 6-1: Tank Geometry Parameters for the Rosemount 5900S
A. Tank Reference Point B. Tank Ullage C. Minimum Level Offset (C); distance from Zero Level to tank bottom
Ullage
D.
E. Product level F. Zero Level (Dipping Datum Point)
G. Gauge Reference Distance (G); distance from Tank Reference Point to the
Gauge Reference Point
H. Gauge Reference Point
I. Hold Off Distance; defines how close to the Gauge Reference Point levels
can be measured
J. Measuring range
K. Tank Reference Height (R); distance from Tank Reference Point to Zero
level
Page 34
1. Communication
2. Preferences
3. Rosemount 2460 System Hub
4. Rosemount 2410 Tank Hub
6. Tanks
7. Calibration
5. Rosemount 5900 and other field devices
Rosemount 2460
Rosemount TankMaster
Rosemount 2410
Rosemount 2230
Rosemount 2240S
Rosemount 5900S

6.2 Configuration using WinSetup

A Rosemount 5900S is typically installed by using the installation wizard in TankMaster WinSetup configuration software. It is recommended that the Rosemount 2460 System Hub and Rosemount 2410 Tank Hub are installed and configured prior to field devices such as level gauges, temperature, and pressure transmitters as illustrated in Figure 6-2.
It is important that the tank database of the Rosemount 2410 Tank Hub has all the information that is stored in the Rosemount 2460 System Hub’s database. This ensures that new devices are mapped to the correct tanks, and that all tank variables are properly updated and distributed.
See the System Configuration Manual (Document no. 00809-0300-5100) for more information.
Figure 6-2: Installation Procedure
Page 35
Configuration in TankMaster WinSetup
A field device such as the Rosemount 5900S level gauge is typically installed as part of the Rosemount 2410 Tank Hub installation procedure in TankMaster.
Once the gauge is installed, click the Properties option to configure the device.
Figure 6-3: TankMaster WinSetup Workspace with Installed Devices
Page 36
A
B D E
F
G
H
C
The Properties window includes tabs for basic and advanced configuration.
Figure 6-4: Properties Window
A. Tabs for basic and advanced configuration B. Tank hub that the radar level gauge is connected to C. Position in the tank hub's database
Communication channel
D.
E. Modbus address
F. Unit Id G. Application and boot firmware versions H. Red icon means that the device is not configured
See the System Configuration Manual (Document no. 00809-0300-5100) for more information.
Page 37
Basic configuration
The Properties window has a number of tabs that lets you configure the device for optimum performance. The Communication, Antenna, and Geometry tabs cover basic configuration of the Rosemount 5900S.
Figure 6-5: Antenna Configuration
Figure 6-6: Tank Geometry Configuration
Page 38

A Product Certifications

Rev 7.15

A.1 European directive information

The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.

A.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). Complies with FM 3810:2005 and CSA: C22.2 No. 1010.1.

A.3 Telecommunication compliance

A.3.1 FCC

This device complies with Part 15C of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Certificate: K8C5900

A.3.2 IC

This device complies with RSS210-7.
Certificate: 2827A-5900

A.3.3 Radio Equipment Directive (RED)

This device complies with ETSI EN 302 372 and EN 62479. EU directive 2014/53/EU. The device shall be installed according to requrements ETSI EN
302372.

A.4 CE-mark

The product complies with applicable EU directives (EMC, ATEX, LVD, and RED). Based on the low emitted effects from the gauges (below 0.1 mW) compared to limits given by the Rec. 1999/519/EC, no additional measures are needed.
Page 39

A.5 Installing Equipment in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.

A.6 North America

A.6.1 I5 USA Intrinsic Safety

Certificate
Standards
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Specific Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. When installed as EPL Ga, care must be taken during installation and use to prevent impact or friction.
FM 17US0030X
FM Class 3600:2018, FM Class 3610:2018, FM Class 3810:2005, ANSI/ISA 61010-1:2004, ANSI/NEMA 250:2003, ANSI/IEC 60529:2004, ANSI/UL 60079-0:2013 Ed 6, ANSI/UL 60079-11:2014 Ed 6.3, ANSI/UL 60079-26:2017 Ed 3
IS/I,II,III/1/ABCDEFG/T4 DIP/II,III/1/EFG/T5 CL 1 ZN 0 AEx ia IIC T4 Ga CL 1 ZN 0/1 AEx ib IIC T4 Ga/Gb Ta = -50°C to 80°C - 9240040-917; Type 4X; IP66; IP67
Ii (lmax) Pi Ci Li
(Vmax)
2. Non-metallic surfaces and the surface of the painted housing may, under certain extreme conditions, generate an ignition-capable level of electrostatic. Appropriate measures must be taken to prevent electrostatic discharge.
3. Using the box provided on the nameplate, the User shall permanently mark the type of protection chosen for the specific
Page 40
installation. Once the type of protection has been marked it shall not be changed.
4.
When installed as Ex ib Ga/Gb, the partition wall materials separating EPL Ga from EPL Gb are constructed of different materials depending on the antenna option. Please refer to Control Drawing D9240040-917 for the material type of each antenna. The material shall not be subject to environmental conditions which might adversely affect the partition wall.
Maximum Process Temperatures are as follows:
5.
When option n=Tank Seal
PV or QV Viton -15°C to +180°C
PK, FK, HK or QK Kalrez -20°C to +230°C
PE or QE EPDM -40°C to +110°C
PB or QB BUNA-N -35°C to +90°C
PM, FF, HH or QM FVMQ -60°C to +155°C
PF or QF FEP -60°C to +180°C

A.6.2 I6 Canada Intrinsic Safety

Certificate
Standards
Markings
FM17CA0016X
CSA-C22.2 No. 25-2017 CSA-C22.2 No. 94-M91:1991 (R2011) CSA-C22.2 No. 1010-1:2004 (R2009) CSA-C22.2 No. 60529:2016 CSA-C22.2 No. 60079-0:2015 CSA-C22.2 No. 60079-11:2014 CSA-C22.2 No. 60079-26:2016
IS/I,II,III/1/ABCDEFG/T4 Ex ia IIC T4 Ga Ex ib IIC T4 Ga/Gb DIP/II,III/1/EFG/T5 Ta = -50°C to 80°C 9240040-917 Type 4X; IP66; IP67
O-ring Type Min/Max Process
Temperature Range
Page 41
Ui
(Vmax)
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Ii (lmax) Pi Ci Li
Specific Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. When installed as EPL Ga, care must be taken during installation and use to prevent impact or friction.
2. Non-metallic surfaces and the surface of the painted housing may, under certain extreme conditions, generate an ignition-capable level of electrostatic. Appropriate measures must be taken to prevent electrostatic discharge.
3. Using the box provided on the nameplate, the User shall permanently mark the type of protection chosen for the specific installation. Once the type of protection has been marked it shall not be changed.
4. When installed as Ex ib Ga/Gb, the partition wall materials separating EPL Ga from EPL Gb are constructed of different materials depending on the antenna option. Please refer to Control Drawing D9240040-917 for the material type of each antenna. The material shall not be subject to environmental conditions which might adversely affect the partition wall.
5. Maximum Process Temperatures are as follows:
When option n=Tank Seal
PV or QV Viton -15°C to +180°C
PK, FK, HK or QK Kalrez -20°C to +230°C
PE or QE EPDM -40°C to +110°C
PB or QB BUNA-N -35°C to +90°C
PM, FF, HH or QM FVMQ -60°C to +155°C
PF or QF FEP -60°C to +180°C
O-ring Type Min/Max Process
Temperature Range

A.7 Europe

A.7.1 I1 ATEX Intrinsic Safety

Certificate
FM09ATEX0057X
Page 42
Standards
EN IEC 60079-0:2018, EN 60079-11:2012, EN 60079-26:2015, EN 60529:1991+A1(2000)+A2(2013)
Markings
II 1 G Ex ia IIC T4 Ga II 1/2 G Ex ib IIC T4 Ga/Gb Ta = -50°C to 80°C; IP66, IP67
Ui
(Vmax)
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Ii (lmax) Pi Ci Li
Specific Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. When installed as EPL Ga, care must be taken during installation and use to prevent impact or friction.
2. Non-metallic surfaces and the surface of the painted housing may, under certain extreme conditions, generate an ignition-capable level of electrostatic. Appropriate measures must be taken to prevent electrostatic discharge.
3.
Using the box provided on the nameplate, the User shall permanently mark the type of protection chosen for the specific installation. Once the type of protection has been marked it shall not be changed.
4. When installed as Ex ib Ga/Gb, the partition wall materials separating EPL Ga from EPL Gb are constructed of different materials depending on the antenna option. Please refer to Control Drawing D9240040-917 for the material type of each antenna. The material shall not be subject to environmental conditions which might adversely affect the partition wall.
5. Maximum Process Temperatures are as follows:
When option n=Tank Seal
PV or QV Viton -15°C to +180°C
PK, FK, HK or QK Kalrez -20°C to +230°C
PE or QE EPDM -40°C to +110°C
PB or QB BUNA-N -35°C to +90°C
O-ring Type Min/Max Process
Temperature Range
Page 43
When option n=Tank Seal
PM, FF, HH or QM FVMQ -60°C to +155°C
PF or QF FEP -60°C to +180°C

A.8 International

A.8.1 I7 IECEx Intrinsic Safety

Certificate
Standards
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Specific Conditions for Safe Use (X):
1. The enclosure contains aluminum and is considered to present a potential risk of ignition by impact or friction. When installed as EPL Ga, care must be taken during installation and use to prevent impact or friction.
IECEx FMG 09.0009X
IEC 60079-0:2017, IEC 60079-11:2011, IEC 60079-26:2014
Ex ia IIC T4 Ga Ex ib IIC T4 Ga/Gb Ta = -50°C to +80°C; IP66, IP67
(Vmax)
O-ring Type Min/Max Process
Temperature Range
Ii (lmax) Pi Ci Li
2. Non-metallic surfaces and the surface of the painted housing may, under certain extreme conditions, generate an ignition-capable level of electrostatic. Appropriate measures must be taken to prevent electrostatic discharge.
3. Using the box provided on the nameplate, the User shall permanently mark the type of protection chosen for the specific installation. Once the type of protection has been marked it shall not be changed.
4. When installed as Ex ib Ga/Gb, the partition wall materials separating EPL Ga from EPL Gb are constructed of different materials depending on the antenna option. Please refer to Control Drawing D9240040-917 for the material type of each antenna. The material shall not be subject to environmental conditions which might adversely affect the partition wall.
Page 44
5. Maximum Process Temperatures are as follows:
When option n=Tank Seal
PV or QV Viton -15°C to +180°C
PK, FK, HK or QK Kalrez -20°C to +230°C
PE or QE EPDM -40°C to +110°C
PB or QB BUNA-N -35°C to +90°C
PM, FF, HH or QM FVMQ -60°C to +155°C
PF or QF FEP -60°C to +180°C

A.9 Brazil

A.9.1 I2 INMETRO Intrinsic Safety

Certificate
Standards
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
UL-BR 17.0982X
ABNT NBR IEC 60079-0:2013, 60079-11:2013, 60079-26:2016
Ex ia IIC T4 Ga/Gb Tamb: -50 °C to + 80 °C IP66/IP67
(Vmax)
O-ring Type Min/Max Process
Temperature Range
Ii (lmax) Pi Ci Li
Special Conditions for Safe Use (X):
1. See certificate for special conditions.

A.10 China

A.10.1
I3 China Intrinsic Safety
Certificate
Standards
Markings
GYJ16.1251X
GB 3836.1 - 2010, GB 3836.4 - 2010, GB 3836.20 - 2010
Ex ia IIC T4 Ga
Page 45
Ui
(Vmax)
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Ii (lmax) Pi Ci Li
Special Conditions for Safe Use (X):
1. See certificate for special conditions.

A.11 Technical Regulations Customs Union (EAC)

A.11.1 IM EAC Intrinsic Safety

Certificate
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
RU C-SE.AA87.B.00346
Ga/Gb Ex ia IIC T4 X Tamb: -50 °C to + 80 °C IP66/IP67
Ii (lmax) Pi Ci Li
(Vmax)

A.12 Japan

A.12.1 I4 Japan Intrinsic Safety

Certificate
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
CML 17JPN2301X
Ex ia IIC T4 Ga/Gb
-50 °C ≤ Ta ≤ +80 °C
Ii (lmax) Pi Ci Li
(Vmax)
Page 46

A.13 Republic of Korea

A.13.1 IP Korea Intrinsic Safety

Certificate
Markings
Ui
Entity parameters 30 V 300 mA 1.3 W 1.1 nF 1.5 µH
FISCO parameters 17.5V 380 mA 5.32 W 1.1 nF 1.5 µH
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
14-KB4BO-0573X
Ex ia IIC T4 Ga/Gb (-50 °C ≤ Ta ≤ +80 °C)
Ii (lmax) Pi Ci Li
(Vmax)

A.14 Additional certifications

A.14.1 Functional Safety Certification (SIS)

3 Functional Safety
Certificate
Standards
S Functional Safety
Certificate
Standards
Certificate
Standards
ROS 1312032 C001 SIL 3 2-in-1 (1oo2) option (SIS-relays)
IEC 61508:2010 Parts 1-7
ROS 1312032 C004 SIL 2 1-in-1 (1oo1) option, with 4-20mA or K1/K2 relay
IEC 61508:2010 Parts 1-7
ROS 1312032 C005 SIL 2 2-in-1 (1oo1) option, with 4-20mA or K1/K2 relay
IEC 61508:2010 Parts 1-7

A.14.2 Germany WHG Certification (DIBt)

Certificate
Z-65.16-500

A.14.3 Belgium Overfill Certification (Vlarem)

Certificate
99/H031/13072201
Page 47

A.14.4 India Intrinsic Safety

Certificate
Markings
P349859/1
Ex ia IIC Ga/Gb

A.15 Custody Transfer Certifications

Australia Custody Transfer
Certificate
Standards
Belgium Custody Transfer
BMS Certificate
Bulgaria Custody Transfer
Bulgaria Institute of Metrology
China Custody Transfer
CPA Pattern Approval
Certificate
Croatia Custody Transfer
Certificate
No 5/1/7
Regulation 60: National Measurement Regulations 1999
NR. P6.0.014.02-B-16
18.10.5106.1
2012-L134
558-02-01_01-15-2
Czech Republic Custody Transfer
Certificate
Estonia Custody Transfer
Certificate
France Custody Transfer
Certificate
Germany Custody Transfer
Certificate
0111-CS-C022-10
TJA 6.13-3_15.09.11
No. LNE-24609
PTB-1.5-4058175
Page 48
India Custody Transfer
Certificate
IND/13/12/191
Indonesia Custody Transfer
Certificate
DITJEN MIGAS CT approval 26.10.2010
Italy Custody Transfer
Certificate
183349 (Raptor system)
Kazakhstan Custody Transfer
GOST Pattern Approval:
Certificate
KZ.02.02.06177-2018 No.14983 (5900) KZ.02.02.04018-2014 No.10790 (System)
Malaysia Custody Transfer
Certificate
ATS 09-11
Netherlands Custody Transfer
NMI Certificate
TC7982
Norway Custody Transfer
Certificate
No. N-11-7146
Poland Custody Transfer
Certificate
ZT-7 2013
Portugal Custody Transfer
Certificate
P12_101.12_31
Russia Custody Transfer
GOST Pattern Approval:
Certificate
SE.C.29.639.A No. 66902 (5900)
Serbia Custody Transfer
Certificate
393-7_0-01-2088
Page 49
South Africa Custody Transfer
Certificate
Switzerland Custody Transfer
Certificate
OIML Custody Transfer
Certificate
SAEx S11-065
Zulassungszertifikat CH-L-11127-01
R85-2008-SE-11.01

A.16 Product Certifications Rosemount 2051

Extract from Rosemount 2051 Product Certifications Rev: 1.13

A.16.1 North America

IE USA FISCO
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
The Model 2051 transmitter housing contains aluminum and is
1. considered a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
FM16US0231X
FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class 3810 – 2005
IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 02051-1009 (-50°C ≤ Ta ≤ +60°C); Type 4x
IF Canada Intrinsic Safety
Certificate
Standards
Markings
2041384
CSA Std. C22.2 No. 142 - M1987, CSA Std. C22.2 No. 213 - M1987, CSA Std. C22.2 No. 157 - 92, ANSI/ISA
12.27.01 – 2003, CAN/CSA-E60079-0:07, CAN/CSA­E60079-11:02
Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawing 02051-1008. Ex ia IIC T3C. Single Seal. Enclosure Type 4X
Page 50

A.16.2 Europe

IA ATEX FISCO
A.16.3
Certificate
Standards
Markings
Ui Ii Pi Ci Li
FISCO parameters
Baseefa08ATEX0129X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (-60°C ≤ Ta ≤ +60°C)
17.5V 380 mA 5.32 W 0 µF 0 mH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it is incapable of withstanding the 500V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact and abrasion when located in Zone 0.
International IG IECEx FISCO
Certificate
Standards
Markings
IECExBAS08.0045X
IEC60079-0:2011, IEC60079-11:2011
Ex ia IIC T4 Ga (-60°C ≤ Ta ≤ +60°C)
Ui Ii Pi Ci Li
FISCO parameters
17.5V 380 mA 5.32 W 0 nF 0 µH
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it is incapable of withstanding the 500V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact and abrasion when located in Zone 0.
3.
The equipment contains thin wall diaphragms. The installation, maintenance and use shall take into account the environmental conditions to which the diaphragms will be subjected. The
Page 51
manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

A.17 Declaration of conformity

Emerson.com/Rosemount
Figure A-1: Rosemount 5900S EU Declaration of Conformity (page 1)
Page 52
Figure A-2: Rosemount 5900S EU Declaration of Conformity (page 2)
Page 53
Figure A-3: Rosemount 5900S EU Declaration of Conformity (page 3)
Page 54

A.18 China RoHS

Figure A-4: Rosemount 5900S China RoHS
Page 55
Page 56
Global Headquarters and Europe Regional Office Tank Gauging
Emerson Automation Solutions Box 150 (Visiting address: Layoutvägen 1) SE-435 23 Mölnlycke Sweden
+46 31 337 00 00 +46 31 25 30 22 Sales.RTG@Emerson.com
*00825-0100-5900*
Quick Start Guide
00825-0100-5900, Rev. AA
March 2020
North America Regional Office Tank Gauging
Emerson Automation Solutions 6005 Rogerdale Road Mail Stop NC 136 Houston, TX 77072, USA
+1 281 988 4000 or +1 800 722 2865 Sales.RTG.HOU@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RMTLAContactUS@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RTGMEA.Sales@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Specialist-OneLevel.RMT-
AP@Emerson.com
©
2020 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...