Emerson Rosemount 3144P Quick Start Guide

Quick Start Guide
00825-0100-4021, Rev PB
Rosemount™ 3144P Temperature Transmitter
with HART® Protocol and Rosemount X-well™ Technology
March 2021
Quick Start Guide March 2021
Contents
About this guide...........................................................................................................................3
System readiness......................................................................................................................... 5
Verify configuration..................................................................................................................... 6
Set the switches......................................................................................................................... 10
Mount the transmitter................................................................................................................11
Wire and apply power................................................................................................................ 13
Perform a loop test.....................................................................................................................18
Safety Instrumented Systems (SIS)............................................................................................. 19
Product certifications................................................................................................................. 20
2 Rosemount 3144P
March 2021 Quick Start Guide

1 About this guide

This guide provides basic guidelines for installing the Rosemount 3144P Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3144P Transmitter Reference Manual for more instructions. The manual and this guide are also available electronically on Emerson.com/Rosemount.
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
Review the Product Certifications section of this document for any restrictions associated with a safe installation.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten thermowells and sensors before applying pressure. Do not remove the thermowell while in operation.
Conduit/cable entries
The conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads could cause electrical shock.
Quick Start Guide 3
Quick Start Guide March 2021
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
4 Rosemount 3144P
March 2021 Quick Start Guide

2 System readiness

2.1 Confirm HART revision capability

If using HART based control or asset management systems, confirm the HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 Protocol. You can configure the transmitter for either HART Revision 5 or 7.
For instructions on how to change the HART revision of your transmitter, refer to Switch HART revision mode.
Quick Start Guide 5
Quick Start Guide March 2021

3 Verify configuration

The Rosemount 3144P Transmitter communicates using a Field Communicator (communication requires a loop resistance between 250 and 1100 ohms) or AMS Device Manager.
Do not operate when power is below 12 Vdc at the transmitter terminal. Refer to the Rosemount 3144P Transmitter Reference Manual and Field Communicator Reference Manual.

3.1 Update the Field Communicator software

To fully communicate with the Rosemount 3144P Transmitter, you need the latest Field Communicator Field Device Revision Dev v5 or v7, DD v1 or greater. Transmitters equipped with Rosemount X-well Technology require DD revision 3144P Dev. 7 Rev. 1 or greater to view this functionality.
The Device Descriptors are available with new communicators at
Emerson.com/Rosemount, or you can download them into existing
communicators at any Emerson Service Center.
The device descriptors are as follows:
Device in HART 5 mode: Device v5 DDv1
Device in HART 7 mode: Device v7 DDv1
Complete the following steps to determine if you need to upgrade your device. Refer to Figure 3-1.
6 Rosemount 3144P
March 2021 Quick Start Guide
Figure 3-1: Connecting a Communicator to a Bench Loop
A. Power/signal terminals B. 250 Ω ≤ RL ≤ 1100 Ω C. Power supply
Procedure
1. Connect the sensor. See the wiring diagram located on the inside of the housing cover.
2. Connect the bench power supply to the power terminals ("+" or "-").
3. Connect a Field Communicator to the loop across a loop resistor or at the power/signal terminals on the transmitter.
The following message will appear if the communicator has a previous version of the device descriptors (DDs):
NOTICE: Upgrade the communicator software to access new XMTR functions. Continue with old description?
Note
If this notice does not appear, the latest DD is installed.
If the latest version is not available, the communicator will communicate properly, but when the transmitter is configured some new capabilities may not be visible.
To prevent this from happening, upgrade to the latest DD or answer NO to the question and default to the generic transmitter functionality.
Quick Start Guide 7
Quick Start Guide March 2021

3.2 Switch HART revision mode

If the HART Protocol configuration tool is not capable of communicating with HART Revision 7, the transmitter will load a generic menu with limited capability. The following procedure will switch the HART Revision mode from the generic menu.
Procedure
Select Manual Setup Device Information Identification Message.
a) To change to HART Revision 5, enter HART5 in the Message field.
b) To change to HART Revision 7, enter HART7 in the Message field.
Function HART 5 Fast Keys HART 7 Fast Keys
2-wire offset sensor 1 2, 2, 1, 5 2, 2, 1, 6
2-wire offset sensor 2 2, 2, 2, 5 2, 2, 2, 6
Alarm values 2, 2, 5, 6 2, 2, 5, 6
Analog calibration 3, 4, 5 3, 4, 5
Analog output 2, 2, 5 2, 2, 5
Average temperature setup 2, 2, 3, 3 2, 2, 3, 3
Burst mode N/A 2, 2, 8, 4
Comm status N/A 1, 2
Configure additional messages N/A 2, 2, 8, 7
Configure Hot Backup
Date 2, 2, 7, 1, 2 2, 2, 7, 1, 3
Descriptor 2, 2, 7, 1, 3 2, 2, 7, 1, 4
Device information 2, 2, 7, 1 2, 2, 7, 1
Differential temperature setup 2, 2, 3, 1 2, 2, 3, 1
Filter 50/60 Hz 2, 2, 7, 5, 1 2, 2, 7, 5, 1
Find device N/A 3, 4, 6, 2
First good temperature setup 2, 2, 3, 2 2, 2, 3, 2
Hardware revision 1, 8, 2, 3 1, 11, 2, 3
HART lock N/A 2, 2, 9, 2
Intermittent sensor detect 2, 2, 7, 5, 2 2, 2, 7, 5, 2
Lock status N/A 1, 11, 3, 7
Long tag N/A 2, 2, 7, 2
2, 2, 4, 1, 3 2, 2, 4, 1, 3
8 Rosemount 3144P
March 2021 Quick Start Guide
Function HART 5 Fast Keys HART 7 Fast Keys
Loop test 3, 5, 1 3, 5, 1
LRV (lower range value) 2, 2, 5, 5, 3 2, 2, 5, 5, 3
Message 2, 2, 7, 1, 4 2, 2, 7, 1, 5
Open sensor holdoff 2, 2, 7, 4 2, 2, 7, 4
Percent range 2, 2, 5, 4 2, 2, 5, 4
Sensor 1 configuration 2, 2, 1 2, 2, 1
Sensor 1 serial number 2, 2, 1, 7 2, 2, 1, 8
Sensor 1 setup 2, 2, 1 2, 2, 2
Sensor 1 status N/A 2, 2, 1, 2
Sensor 1 type 2, 2, 1, 2 2, 2, 1, 3
Sensor 1 unit 2, 2, 1, 4 2, 2, 1, 5
Sensor 2 configuration 2, 2, 2 2, 2, 2
Sensor 2 serial number 2, 2, 2, 7 2, 2, 2, 8
Sensor 2 setup 2, 2, 2 2, 2, 2
Sensor 2 status N/A 2, 2, 2, 2
Sensor 2 type 2, 2, 2, 2 2, 2, 2, 3
Sensor 2 unit 2, 2, 2, 4 2, 2, 2, 5
Sensor drift alert 2, 2, 4, 2 2, 2, 4, 2
Simulate device variables N/A 3, 5, 2
Software revision 1, 8, 2, 4 1, 11, 2, 4
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Terminal temperature units 2, 2, 7, 3 2, 2, 7, 3
URV (upper range value) 2, 2, 7, 3 2, 2, 7, 3
Variable mapping 2, 2, 8, 5 2, 2, 8, 5
Thermocouple diagnostic 2, 1, 7, 1 2, 1, 7, 2
Min/max tracking 2, 1, 7, 2 2, 1, 7, 2
Rosemount X-well configuration N/A 2, 2, 1, 11
Quick Start Guide 9
Quick Start Guide March 2021

4 Set the switches

The Rosemount 3144P Transmitter comes with hardware switches to configure alarms and lock the device. Use the following procedures to set the switches.
WARNING
Enclosure
Enclosure covers must be fully engaged to meet explosion-proof requirements.

4.1 Set the switches with an LCD display

Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Unscrew the LCD display screws and gently slide the meter straight off.
4. Set the alarm and security switches to the desired position.
5. Gently slide the LCD display back into place.
6. Replace and tighten the LCD display screws to secure the LCD display.
7. Reattach housing cover.
8. Apply power and set the loop to automatic control.
4.2
10 Rosemount 3144P

Set the switches without an LCD display

Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the alarm and security switches to the desired position.
4. Reattach housing cover.
5. Apply power and set the loop to automatic control.
March 2021 Quick Start Guide

5 Mount the transmitter

Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing.

5.1 Typical North American installation

Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach any necessary unions, couplings, and extension fittings. Seal the fitting threads with an approved thread sealant, such as silicone or PTFE tape (if required).
5. Screw the sensor into the thermowell or directly into the process (depending on installation requirements).
6. Verify all sealing requirements.
7. Attach the transmitter to the thermowell/sensor assembly. Seal all threads with an approved thread sealant, such as silicone or PTFE tape (if required).
8. Install field wiring conduit into the open transmitter conduit entry (for remote mounting) and feed wires into the transmitter housing.
9. Pull the field wiring leads into the terminal side of the housing.
10. Attach the sensor leads to the transmitter sensor terminals. The wiring diagram is located inside the housing cover.
11. Attach and tighten both transmitter covers.
5.2
Quick Start Guide 11

Typical European installation

Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach a connection head to the thermowell.
5. Insert sensor into the thermowell and wire the sensor to the connection head.
The wiring diagram is located inside the connection head.
6. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of the optional mounting brackets.
Quick Start Guide March 2021
7. Attach cable glands to the shielded cable running from the connection head to the transmitter conduit entry.
8. Run the shielded cable from the opposite conduit entry on the transmitter back to the control room.
9. Insert shielded cable leads through the cable entries into the connection head/transmitter. Connect and tighten cable glands.
10. Connect the shielded cable leads to the connection head terminals (located inside the connection head) and to the sensor wiring terminals (located inside the transmitter housing).
12 Rosemount 3144P
Loading...
+ 28 hidden pages