Emerson Rosemount 3095FB MultiVariable MODBUS Quick Installation Manual

Page 1
www.rosemount.com
¢00825-0100-4738i¤
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
MODBUS
Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Connect the Wiring and Power Up Step 4: Verify Configuration Step 5: Trim the Transmitter Product Certifications
Rosemount 3095FB MultiVariable™ Transmitter with MODBUS
®
Protocol
Page 2
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
2
© 2009 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Rosemount Inc.
8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307, F (952) 94 9- 7001 T (Intnl) (952) 906-8888
Emerson Process Management GmbH & Co. OHG
Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211, F (65) 6777 0947/(65) 6777 0743
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233, F (86) (10) 6422 8586
IMPORTANT NOTICE
This installation guide provides basic guidelines for the Rosemount 3095FB MultiVariable Transmitter with MODBUS Protocol (reference manual document number 00809-0100-4738). It does not provide instructions for configuration, diagnostics, maintenance, service, or troubleshooting. Refer to the appropriate reference manual for more instruction. These manuals are also available electronically on www.rosemount.com.
WARNING
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
• Before connecting communications in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-Proof/Flame-Proof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• To avoid process leaks, only use the o-ring designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
Page 3
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
3
STEP 1: MOUNT THE TRANSMITTER
Figure 1. Using a Mounting Bracket
Liquid Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
Gas Flow Applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Steam Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Panel Mount
(1)
(1) Panel bolts are customer supplied.
Pipe Mount
Flow
Flow
Flow
Flow
Page 4
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
4
STEP 2: CONSIDER HOUSING ROTATION
Consider Housing Rotation
To improve field access or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. Rotate the housing clockwise to the desired position – up to 180° from its original position. Over rotating will damage the transmitter.
3. If the desired position is attained, tighten the housing rotation set screw.
4. If the desired position cannot be reached because the housing will not rotate further, rotate the housing counterclockwise until in the desired position is attained (up to 180° from its original position).
5. Tighten the housing rotation set screw.
Field Installation
1. Mount the transmitter
a.Install the flange or flange/adapter bolt finger-tight. b.Torque bolts to initial torque value using a cross pattern (see Table 1). When
installing to a mounting bracket, torque bolts to 125 in./lb (169 N/m)
2. If security jumpers are not installed, the transmitter will operate normally with the default security off. Verify baud rate. Default baud rate is 9600 with switch S1 and S2 in on position. Verify AC termination, pull down (B), and pull up (A) switches; default is in the off position.
Figure 2. Transmitter Ele ct r onics Board and Optional LCD Display
Table 1. Torque Cross Pattern
Bolt Material Initial Value Final Value
Carbon Steel (CS) 300 in./lb (34 N/m) 650 in./lb (73 N/m) Stainless Steel (SST) 150 in./lb (17 N/m) 300 in./lb (34 N/m)
Housing Rotation Set Screw (9/64-inch)
OFF
ON
< <
SECURITY
S1 S2
ON OFF
AC (B) (A )
ON OFF
Electronics Board
Optional LCD Display
Page 5
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
5
STEP 2 CONTINUED...
3. Connect the transmitter to the process.
4. Install the RTD Cable Assembly (optional). All RTD 3095 Cable Assemblies use the 3095 RTD Cable Connector. Identify the cable type being installed and follow the steps below.
• Installing an Armored Shielded RTD Cable (See Figure 3) a.Fully engage the black cable connector to the 3095 RTD connector. b.Tighten the cable adapter until metal contacts metal. c.Install the compression fitting. d.Tighten the cap onto the compression fitting.
Figure 3. Armored Shielded RTD Cable
Washer
Cap
Black Cable Connector
RTD Cap
Conductive Bushing
Connect to RTD
Compression Fitting
Compression Fitting
Cable Adapter
3
/4 to 1/2-14 NPTAdapter
Bushing
Page 6
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
6
STEP 2 CONTINUED...
• Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit.
a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter until metal contacts metal.
Figure 4. Shielded RTD Cable
• Installing a ATEX/IECEx Flameproof 3095 RTD Cable (See Figure 5) a.Fully engage the black cable connector to the 3095 RTD Connector. b.Tighten the cable adapter and cable gland until metal contacts metal.
Figure 5. ATEX/IECEx Flameproof RTD Cable
5. Check all process connections for leaks.
6. Connect the appropriate wiring (see Step 5). Ground the transmitter according to national and local electrical codes. Install field wiring grounding (optional).
Cable Adapter 1/2–14 NPT
Black Cable Connector
Black Cable Connector/ RTD Connector
Cable Adapter
Cable Gland
RTD Cable Gland CM20
Page 7
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
7
STEP 2 CONTINUED...
Bolting Considerations
If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 6 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 6. Common Transmitter Assemblies
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Figure 7. If bolt material is not shown in Figure 7, contact the local Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Figure 7 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Figure 7 for final torque value.
5. Verify that the flange bolts are protruding through the isolator plate before applying pressure.
4 x 1.75-in. (44 mm)
4 x 2.88-in. (73 mm)
A. Transmitter with
Coplanar Flange
B. Transmitt er with Coplanar
Flange and Optional Flange Adapters
C. Transmitter with Traditional
Flange and Optional Flange Adapters
D. Transmitter with
Coplanar Flange and Optional Manifold and Flange Adapters
4 x 1.75-in. (44 mm)
4 x 1.50-in. (38 mm)
4 x 1.75-in. (44 mm)
4 x 2.25-in. (57 mm)
Page 8
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
8
STEP 2 CONTINUED...
Figure 7. Torque values for the flange and flange adapter bolts
O-rings with Flange Adapters
WARNING
Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the o-rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring.
Bolt Material Head Markings Initial Torque Final Torque
Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs.
Stainless Steel (SST) 150 in.-lbs. 300 in.-lbs.
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or
serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring
that is designed for its specific flange adapter, as shown below.
B7M
316
316
316
SW
316
STM
316
R
B8M
Rosemount 3051S / 3051 / 2051 / 3095
Rosemount 1151
Flange Adapter
O-ring
Flange Adapter
O-ring
PTFE Based
Elastomer
PTFE
Elastomer
Page 9
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
9
STEP 3: CONNECT THE WIRING AND POWER UP
Use the following steps to wire the transmitter:
1. Remove the housing cover on the side marked FIELD TERMINALS.
2. Connect the lead from the positive power supply terminal to the “+” terminal (PWR/COMM) and the lead from the negative power supply terminal to the “–” terminal.
3. Connect the transmitter to the RS-485 bus: Connect the A lead to the “A” terminal. Connect the B lead to the “B” terminal.
NOTE
Improper field wiring connections may damage the 3095FB. Do not connect power wiring to the RS-485 terminals. Twisted pairs should be used for best results. Twisted pair is required for RS-485 bus wiring. Runs under 1000 ft (305 m) should be AWG 22 or larger. Runs from 1000 to 4000 feet (305 to 1219 m) should be AWG 20 or larger. Wiring should not exceed AWG 16.
4. Plug and seal unused conduit connections.
5. Install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
Figure 8 shows wiring connections necessary to power a 3095 and enable communications. The 3095FB requires a power supply between 7.5 - 30 Vdc. RS-485 signal wiring requires 2-wire half duplex RS-485 Modbus with 8 data bits, one stop bit, and no parity.
Figure 8. Transmitter Wiring Di agram
NOTE
Installation of the transient protection terminal block does not provide transient protection unless the 3095 case is properly grounded. The converter cables may be connected directly to the RS-485 bus or the transmitter terminals. Be sure to observe proper polarity.
3095FB
+
Converter
RS-485 Bus
A
B
120
120
Twisted pair required
User-Provided Power Supply
-
A B RS-485
+
-
PWR
Page 10
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
10
STEP 4: VERIFY CONFIGURATION
To verify configuration, the user must first be connected to the Rosemount 3095FB using the Rosemount FB user interface software.
3095FB User Interface Software Packages
• Part Number 03095-5130-0003: Windows User Interface Software–Single PC License, Converter, and Cable.
• Part Number 03095-5125-0004: Windows User Interface Software–Single PC License.
• Part Number 03095-5125-0005: Windows User Interface Software– Site License.
• Part Number 03095-5106-0002: RS-485 Converter and Cable.
Verify Tag Information
1. Click Transmitter on the taskbar.
2. Click Device Info... from the drop-down menu.
3. Verify tag information.
4. Click OK to exit.
Verify Damping
1. Click Transmitter on the taskbar.
2. Click Damping... from the drop-down menu.
3. Verify damping settings for DP, SP, and PT.
4. Click OK to exit.
Verify Units of Measure
1. Click Transmitter on the taskbar.
2. Click on Units... from the drop-down menu.
3. Verify units of measure for DP, SP, and PT.
4. Click OK to exit.
Verify Sensor Range
1. Click Transmitter on the taskbar.
2. Click on Sensor Limits... from the drop-down menu.
3. Verify sensor limits.
4. Click Cancel to exit.
Page 11
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
11
STEP 5: TRIM THE TRANSMITTER
NOTE
Transmitters are shipped from Emerson Process Management, Rosemount Division fully calibrated per request or by the factory default of full scale.
Zero Offset Trim
A zero trim is a single-point adjustment used for compensating mounting position effects. When performing a zero trim, ensure the low side block valve is closed, the equalize valve is open, the high side block valve is open, and all wet legs are filled to the correct level.
If zero offset is less than 3% of true zero, follow the user interface software instructions below.
Trim DP Offset (Zero)
1. Click Maintenance, Sensor Trim on the taskbar.
2. Click DP option.
3. click Offset Trim option.
4. Enter the offset trim point to trim DP Offset (Zero)
5. Click Trim to complete the sensor trim
Trim SP Offset (Zero) (AP, GP)
1. When performing a offset or zero SP trim, ensure the low side block valve is closed, the equalize valve is open, and the high side block valve is closed. Then, open vent to atmosphere.
2. Click Maintenance, Sensor Trim on the taskbar.
3. Click SP option.
4. click Offset Trim option.
5. If using GP type sensor, enter zero. If using AP type sensor, do not zero. Instead, enter an Offset value based on a barometric pressure reading.
NOTE
For Absolute Pressure (AP) Sensor: If open to atmosphere, reading should be at atmospheric pressure (roughly 12 - 15 psi (0.8 – 1.0 bar), not zero. Use a barometer that is four times as accurate as the Rosemount 3095 AP sensor.
6. Click Trim to complete the sensor trim.
7. Once the offset or zero SP trim is complete, verify that vent is closed, the high side block valve is open, close the equalize valve tightly, then open the low side block valve.
Page 12
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
12
PRODUCT CERTIFICATIONS
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
European Directive Information
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directive (PED) (97/23/EC)
3095F_2/3,4/D Flow Transmitters
— QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity
Assessment
All other 3095_ Transmitters/Level Controller
— Sound Engineering Practice
Transmitter Attachments: Process Flange - Manifold
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (2004/108/EC)
3095F Flow Transmitters - EN 61326-1:1997 - A1, A2, and A3
Ordinary Location Certification for Factory Mutual
As standard, the Rosemount 3095FB transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Hazardous Locations Certifications
North American Certifications
FM Approvals
A Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for
Class II/III, Division 1, Groups E, F, and G, hazardous locations. Factory Sealed. Provides non-incendive RTD connections for Class I, Division 2, Groups A, B, C, and D. Install per Rosemount drawing 03095-1025. Enclosure Type 4X.
Page 13
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
13
Canadian Standards Association (CSA)
C Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for
Class II/III, Division 1, Groups E, F, and G, hazardous locations. CSA enclosure Type 4X. Factory Sealed. Provides a non-incendive RTD Connection for Class I, Division 2, Groups A, B, C, and D. Suitable for use in Class I, Division 2, Groups A, B, C, and D. Install in accordance with Rosemount Drawing 03095-1024. Single Seal.
European Certifications
H ATEX Flameproof
Certificate Number: KEMA02ATEX2320X II 1/2 G Ex d IIC T5 (-50°C  T
amb
80°C)
T6 (-50°C  T
amb
65°C)
V
max
= 55V dc
1180
Special Conditions for Safe Use (x):
The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
PATEX Dust
Certificate Number: KEMA02ATEX2321 II 1 D T90°C Ambient Temp (-50°C  T
amb
°C) V = 55 Vdc MAX I = 23 mA MAX IP66
1180
IECEx Certifications
7 IECEx Flameproof
Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C  T
a
65°C)
Zone 0/1 Ex d IIC T5 (-20°C  T
a
80°C)
V
max
= 55 Vdc
I
max
= 23 mAdc
8 IECEx Dust
Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP66
Page 14
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
14
Page 15
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
15
Page 16
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
16
Page 17
Quick Installation Guide
00825-0100-4738, Rev BA October 2009
Rosemount 3095FB
17
Page 18
Quick Installation Guide
00825-0100-4738, Rev BA
October 2009
Rosemount 3095FB
18
Loading...