Emerson Rosemount 3051S MultiVariable, Rosemount 3051SF series MultiVariable Quick Start Manual

Page 1
Quick Start Guide
00825-0100-4853, Rev AD
August 2016
Rosemount™ 3051S MultiVariable™ Transmitter Rosemount 3051SF Series MultiVariable Flowmeter
with FOUNDATION™ Fieldbus Protocol
Page 2
Quick Start Guide
August 2016
NOTICE
This guide provides basic guidelines for Rosemount 3051SMV FOUNDATION Fieldbus Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051SMV F
Reference Manual EmersonProcess.com/Rosemount
Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated with a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 3051SMV F
Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the
segment are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
marked “M20” are M20 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, adapters, or
glands in cable/conduit entries.
for more instruction. This manual is also available electronically on
.
OUNDATION Fieldbus Reference Manual for any restrictions associated with a safe installation.
1
/2–14 NPT thread form. Entries
OUNDATION Fieldbus
Contents
Mount the transmitter. . . . . . . . . . . . . . . . . . . . . 3
Tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Consider housing rotation . . . . . . . . . . . . . . . . . 6
Set the switches . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2
Wire, ground, and power . . . . . . . . . . . . . . . . . . 9
System readiness . . . . . . . . . . . . . . . . . . . . . . . . 14
Zero trim the transmitter. . . . . . . . . . . . . . . . . 14
Product Certifications. . . . . . . . . . . . . . . . . . . . 15
Page 3
August 2016
Flow
1.0 Mount the transmitter
1.1 Liquid flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
1.2 Gas flow applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Quick Start Guide
Flow
1.3 Steam flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
1.4 Mounting brackets
Coplanar flange
Panel mount Pipe mount
Flow
Flow
3
Page 4
Quick Start Guide
Traditional flange
Panel mount Pipe mount
1.5 Bolting considerations
If the transmitter installation requires assembly of a process flange, manifold, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter. Only use bolts supplied
with the transmitter or sold by Emerson
Figure 1 illustrates common transmitter assemblies with the bolt length required
for proper transmitter assembly.
Process Management as spare parts.
August 2016
Figure 1. Common Transmitter Assemblies
A
4 × 1.75-in.
(44 mm)
B
4 × 2.88-in.
(73 mm)
A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adapters C. Transmitter with traditional flange and optional flange adapters D. Transmitter with coplanar flange and optional manifold and flange adapters
C
4 × 1.75-in.
(44 mm)
D
4 × 2.25-in.
(57 mm)
4 × 1.50-in.
(38 mm)
4 × 1.75-in.
(44 mm)
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1. If bolt material is not shown in Table 1, contact a local Emerson Process Management representative for more information.
4
Page 5
August 2016
316
316
316
SW
316
STM
316
R
B8M
A
B
C D
Quick Start Guide
Use the following bolt installation procedure:
Note
Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
1. Finger tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern. See Ta b le 1 for initial torque value.
3. Torque the bolts to the final torque value using the same crossing pattern. See Ta b le 1 for final torque value.
4. Verify the flange bolts are protruding through the sensor module bolt holes before applying pressure.
Table 1. Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markings Initial torque Final torque
Carbon Steel (CS) 300 in-lb 650 in-lb
Stainless Steel (SST) 150 in-lb 300 in-lb
1.6 O-rings with flange adapters
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring designed for its specific flange adapter, as shown below.
Whenever the flanges or adapters are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the O-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE O-ring.
Flange adapter O-ring location
B7M
A. Flange adapter B. O-ring C. PTFE-based profile (square) D. Elastomer profile (round)
5
Page 6
Quick Start Guide
Commissioning Tag
DEVICE ID:
001151AB00010001440-121698091725
DEVICE REVISION: 1.0
PHYSICAL DEVICE TAG
DEVICE ID:
001151AB00010001440-121698091725
DEVICE REVISION: 1.0
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A
2.0 Tagging
2.1 Commissioning (paper) tag
To identify which device is at a particular location use the removable tag provided with the transmitter. Ensure the physical device tag (PD Tag field) is properly entered in both places on the removable commissioning tag and tear off the bottom portion for each transmitter.
Figure 2. Commissioning Tag
August 2016
3.0 Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw to 30 in-lb.
Figure 3. Transmitter Housing Set Screw
A. Housing rotation set screw (3/32-in.)
6
Page 7
August 2016
A
B
Quick Start Guide
Note
Do not rotate the housing more than 180° without first performing a disassembly procedure. See the Rosemount 3051SMV F
Manual for more information. Over-rotation may sever the electrical connection between
the sensor module and the electronics.
OUNDATION Fieldbus Transmitter Reference
3.1 Rotate the LCD display
Transmitters ordered with the LCD display will be shipped with the display installed.
In addition to housing rotation, the optional LCD display can be rotated in 90-degree increments by squeezing the two tabs, pulling out, rotating and snapping back into place.
If LCD display pins are inadvertently removed from the interface board, carefully re-insert the pins before snapping the LCD display back into place.
Use the following procedure and Figure 4 to install the LCD display:
1. If the transmitter is installed in a segment, then secure the segment and disconnect power.
2. Remove the transmitter cover opposite the field terminal side. Do not remove the instrument covers in explosive environments when the circuit is live.
3. Engage the four-pin connector into the LCD display and snap into place.
4. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.
5. If the transmitter was installed, reapply power.
Figure 4. Optional LCD Display
A. LCD display B. Meter cover
7
Page 8
Quick Start Guide
4.0 Set the switches
Set Simulate and Security switch position before installation (location of switches shown in Figure 5), as desired.
The Simulate switch enables or disables the ability to set simulated alerts or
simulated measured value and status.
The Security switch allows (unlocked symbol) or prevents (locked symbol) any
configuration of the transmitter.
Further security settings are available in the software, including settings which use a software lock. Additionally, these settings can be used to disable both hardware and software locks.
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the segment, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and simulate switches into the preferred position.
August 2016
4. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.
5. If the transmitter was installed, reapply power.
Figure 5. Simulate and Security Switches
A
SECURITY
B
C
SIMULATE
ENABLE
DISABLE
D
E
F
A. Security unlocked position B. Security switch C. Security locked position
8
D. Simulate disabled position E. Simulate switch F. Simulate enabled position
Page 9
August 2016
DP
B
A
D
C
C
E
Quick Start Guide
5.0 Wire, ground, and power
Use a copper wire of sufficient size to ensure the voltage across the transmitter power terminals does not drop below 9 Vdc. Power supply voltage can be variable, especially under abnormal conditions such as when operating on battery backup. A minimum of 12 Vdc under normal operating conditions is recommended. Shielded twisted pair Type A cable is recommended.
Figure 6. Wiring Terminals with RTD
A
B
C
DP
D
E
C
A. Protective grounding terminal
(do not ground cable shield at the transmitter)
B. Trim shield and insulate
D. Insulate shield E. Connect shield back to the power
supply ground
C. Minimize distance
Figure 7. Wiring Terminals without RTD
A. Protective grounding terminal
(do not ground cable shield at the transmitter) B. Trim shield and insulate C. Minimize distance
D. Insulate shield E. Connect shield back to the power
supply ground
9
Page 10
Quick Start Guide
Note
The power terminals are polarity insensitive, which means the electrical polarity of the power leads does not matter when connecting to the power terminals. If polarity sensitive devices are connected to the segment, terminal polarity should be followed.
5.1 Signal wiring and shield grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations.
1. Remove the field terminals housing cover.
2. To power the transmitter, connect the power leads to the terminals indicated on the terminal block label.
3. Tighten the terminal screws to ensure adequate contact.
4. Trim the cable shield as short as practical and insulate from touching the transmitter housing as indicated in Figure 6 and Figure 7.
August 2016
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches the transmitter housing, it can create ground loops and interfere with communications. To protect the fieldbus segment from noise, grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop.
a. The cable shield should maintain a continuous connection to the power
supply ground.
b. Connect the cable shields for the entire segment to a single good earth
ground at the power supply.
Note
Improper grounding is the most frequent cause of poor segment communications.
5. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.
6. Plug and seal unused conduit connections.
NOTICE
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged.
5.2 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety, and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide complete functionality.
10
Page 11
August 2016
A
B
Quick Start Guide
5.3 Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply, filter, and decouple the segment from other segments attached to the same power supply.
5.4 Grounding
Signal wiring of the fieldbus segment can not be grounded. Grounding one of the signal wires will shut down the entire fieldbus segment.
Transmitter case grounding
Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case are listed below.
Internal ground connection
The internal ground connection screw is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ). The ground connection screw is standard on all Rosemount 3051SMV Transmitters (see
Figure 8).
Figure 8. Internal Ground Connection
A. Ground lug
External ground connection
The external ground connection is located on the exterior of the transmitter housing (see Figure 9). This connection is only available with option D4 and T1.
Figure 9. External Ground Connection
A
A. External ground lug B. External ground assembly (03151-9060-0001)
11
Page 12
Quick Start Guide
A
A
Note
Grounding the transmitter case via threaded conduit connection may not provide sufficient ground continuity.
Transient protection terminal block grounding
The transmitter can withstand electrical transients of the energy level usually encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
The transient protection terminal block can be ordered as an installed option (option code T1) or as a spare part to retrofit existing Rosemount 3051SMV Transmitters in the field. The lightning bolt symbol shown in Figure 10 identifies the transient protection terminal block.
Figure 10. Transient Protection Terminal Block
with RTD without RTD
August 2016
A. Lightning bolt symbol location
Note
The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case (see “Grounding” on page 11).
5.5 Signal termination
A terminator should be installed at the beginning and end of every fieldbus segment.
12
Page 13
August 2016
C
B
Red
Red
White
White
A
Quick Start Guide
5.6 Install optional process temperature input (Pt 100 RTD Sensor)
Note
To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof cables
(temperature input code C30, C32, C33, or C34) may be used.
1. Mount the Pt 100 RTD Sensor in the appropriate location.
Note
Use shielded four-wire cable for the process temperature connection.
2. Connect the RTD cable to the Rosemount 3051S MultiVariable Transmitter by
inserting the cable wires through the unused housing conduit and connect to the four screws on the transmitter terminal block. An appropriate cable gland should be used to seal the conduit opening around the cable.
3. Connect the RTD cable shield wire to the ground lug in the housing.
Figure 11. Transmitter RTD Wiring Connection
A. Ground lug B. RTD cable assembly wires C. Pt 100 RTD sensor
13
Page 14
Quick Start Guide
6.0 System readiness
6.1 Confirm correct device driver
Verify the correct device driver (DD) is loaded on your systems to ensure
proper communications.
Download the correct device driver at your host vendor download site,
EmersonProcess.com/Rosemount by selecting Download Device Drivers
under Related Resources or FieldCommGroup.org End User Resources.
and select
7.0 Zero trim the transmitter
Transmitters are shipped fully calibrated per request or by the factory default of full scale.
A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. Use the steps below if zero offset is less than 5% of URL.
1. When performing a zero trim, ensure the equalizing valve is open and all wet
legs are filled to the correct level. Make sure the transmitter is connected to the host system.
August 2016
2. Zero the differential pressure sensor by using the “Zero Differential Pressure”
method in the host system.
3. Follow the zero DP trim procedure.
4. Zero the static pressure sensor by using the “Zero Static Pressure” or the
“Lower Static Pressure Trim” method in the host system. a. Use the “Zero Static Pressure” for a transmitter equipped with a gage static
pressure sensor and the “Lower Static Pressure Trim” for a transmitter equipped with an absolute static pressure sensor.
Note
When performing a lower sensor trim on a pressure sensor, it is possible to degrade the performance of the sensor if inaccurate calibration equipment is used. Use calibration equipment that is at least three times as accurate as the pressure sensor of the Rosemount 3051SMV FOUNDATION Fieldbus Transmitter.
5. Follow the static pressure trim procedure.
14
Page 15
August 2016
Quick Start Guide
8.0 Product Certifications
Rev 1.14
8.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at EmersonProcess.com/Rosemount
8.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
8.3 Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
.
8.4 USA
E5 US Explosionproof (XP) and Dust Ignition-proof (DIP)
Certificate: 3008216 Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011,
FM Class 3810 – 2005, ANSI/NEMA
Markings: XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(-50 °C ≤ T
I5 US Intrinsically Safe (IS) and Nonincendive (NI)
Certificate: 3031960 Standards: FM Class 3600 –2011, FM Class 3610 – 2007, FM Class 3611 – 2004,
FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III;
Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C ≤ T 03151-1206; Type 4X
+85 °C); Factory Sealed; Type 4X
a
+70 °C); when connected per Rosemount drawing
a
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See drawing 03151-1206.
IE US FISCO Intrinsically Safe
Certificate: 3031960 Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991
Markings: IS CL I, DIV 1, GP A, B, C, D; T4(-50 °C ≤ T
Rosemount drawing 03151-1006; Type 4X
®
250 – 2003
+70 °C); when connected per
a
15
Page 16
Quick Start Guide
8.5 Canada
E6 Canada Explosionproof, Dust Ignition-proof, Division 2
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966,
CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings: Explosionproof Class I, Division 1, Groups B, C, D; Dust-Ignitionproof Class II,
Division 1, Groups E, F, G; Class III; suitable for Class I, Division 2, Groups A, B, C, D; Type 4X
I6 Canada Intrinsically Safe
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966,
CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings: Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1,
Zone 0, IIC, T3C, T 03151-1207; Type 4X
= 70 °C; when connected per Rosemount drawing
a
August 2016
IF Canada FISCO Intrinsically Safe
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966,
CSA Std C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2 No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2 No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05 (R2010)
Markings: FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for
Class I, Zone 0; T3C, T 03151-1207; Type 4X
8.6 Europe
E1 ATEX Flameproof
Certificate: KEMA 00ATEX2143X Standards: EN 60079-0:2012, EN 60079-1:2007, EN 60079-26:2007
(3051SFx models with RTD are certified to EN 60079-0:2006)
Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(-60 °C ≤ T
T5/T4 (-60 °C ≤ T
Temperatu re clas s Process temperature
T6 -60 °C to +70 °C
T5 -60 °C to +80 °C
T4 -60 °C to +120 °C
= 70 °C; when installed per Rosemount drawing
a
+70 °C),
a
+80 °C)
a
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
16
Page 17
August 2016
Quick Start Guide
2. For information on the dimensions of the flameproof joints the manufacturer shall be
contacted.
I1 ATE X Int r insic Safet y
Certificate: Baseefa08ATEX0064X Standards: EN 60079-0:2012, EN 60079-11:2012 Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C ≤ T
+70 °C)
a
Parameters HART
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
30 V 30 V 7.14 V 30 V 30 V
300 mA 300 mA 300 mA 2.31 mA 18.24 mA
1 W 1.3 W 887 mW 17.32 mW 137 mW
14.8 nF 0 0.11 uF 0 0.8 nF
i
0 0 0 0 1.33 mH
®
FOUNDATION
Fieldbus
SuperModule™
only
RTD (for 3051SFx)
HART Fieldbus
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of
withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IA ATE X FISCO
Certificate: Baseefa08ATEX0064X Standards: EN 60079-0:2012, EN 60079-11:2012 Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C ≤ T
Parameters FISCO
+70 °C)
a
Volta ge U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
17.5 V
380 mA
5.32 W
0
0
ND ATE X Dus t
Certificate: BAS01ATEX1374X Standards: EN 60079-0:2012, EN 60079-31:2009 Markings: II 1 D Ex ta IIIC T105 °C T
95 °C Da, (-20 °C ≤ Ta +85 °C), V
500
= 42.4 V
max
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at
least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of
the apparatus and capable of withstanding a 7 J impact test.
4. The SuperModule(s) must be securely screwed in place to maintain the ingress
protection of the enclosure(s).
17
Page 18
Quick Start Guide
N1 ATEX Type n
Certificate: Baseefa08ATEX0065X Standards: EN 60079-0: 2012, EN 60079-15: 2010 Markings: II 3 G Ex nA IIC T4 Gc, (-40 °C ≤ T
+70 °C), V
a
max
= 45 V
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding
the 500 V electrical strength test as defined in Clause 6.5.1 of EN 60079-15:2010. This must be taken into account during installation.
8.7 International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 08.0010X (Flameproof) Standards: IEC 60079-0:2011, IEC 60079-1: 2007, IEC 60079-26:2006
(3051SFx models with RTD are certified to IEC 60079-0:2004)
Markings: Ex d IIC T6…T4 Ga/Gb, T6(-60 °C ≤ T
Temperature class Process temperature
T6 -60 °C to +70 °C
T5 -60 °C to +80 °C
+70 °C), T5/T4(-60 °C ≤ Ta +80 °C)
a
August 2016
T4 -60 °C to +120 °C
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be
contacted.
Certificate: IECEx BAS 09.0014X (Dust) Standards: IEC 60079-0:2011, IEC 60079-31:2008 Markings: Ex ta IIIC T105 °C T
95 °C Da, (-20 °C ≤ Ta +85 °C), V
500
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at
least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of
the apparatus and capable of withstanding a 7 J impact test.
4. The Rosemount 3051S- SuperModule must be securely screwed in place to maintain the
ingress protection of the enclosure.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 08.0025X Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: Ex ia IIC T4 Ga, T4(-60 °C ≤ T
+70 °C)
a
Parameters HART
Voltage U
Current I
i
i
18
FOUNDATION
Fieldbus
30 V 30 V 7.14 V 30 V 30 V
300 mA 300 mA 300 mA 2.31 mA 18.24 mA
SuperModule
only
RTD (for 3051SFx)
HART Fieldbus
Page 19
August 2016
Quick Start Guide
Parameters HART
Power P
Capacitance Ci14.8 nF 0 0.11 uF 0 0.8 nF
Inductance L
i
i
1 W 1.3 W 887 mW 17.32 mW 137 mW
0 0 0 0 1.33 mH
FOUNDATION
Fieldbus
SuperModule
only
RTD (for 3051SFx)
HART Fieldbus
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of
withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane
paint finish; however, care should be taken to protect it from impact or abrasion if located in a Zone 0 environment.
IG IECEx FISCO
Certificate: IECEx BAS 08.0025X Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: Ex ia IIC T4 Ga, T4(-60 °C ≤ T
Parameters FISCO
Volta ge U
Current I
Power P
Capacitance C
Inductance L
i
i
i
i
i
17.5 V
380 mA
5.32 W
0
0
+70 °C)
a
N7 IECEx Type n
Certificate: IECEx BAS 08.0026X Standards: IEC 60079-0: 2011, IEC 60079-15: 2010 Markings: Ex nA IIC T5 Gc, (-40 °C ≤ T
+70 °C)
a
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable of withstanding
the 500 V electrical strength test as defined in Clause 6.5.1 of IEC 60079-15:2010. This must be taken into account during installation.
8.8 Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 15.0393X Standards: ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011,
ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1: 2008
Markings: Ex d IIC T* Ga/Gb, T6(-60 °C ≤ T
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints, the manufacturer shall be
contacted.
+70 °C), T5/T4(-60 °C Ta +80 °C), IP66
a
19
Page 20
Quick Start Guide
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 15.0357X Standards: ABNT NBR IEC 60079-0:2008 + Addendum 1:2011,
ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga, T4(-60 °C ≤ T
+70 °C)
a
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V transient suppressor, it is incapable of
withstanding the 500 V isolation from earth test and this must be taken into account during installation.
2. For processes with temperatures above 135 °C, the user must assess whether the
SuperModule temperature class is suitable for such applications, because in this situation there is a risk of the SuperModule temperature being above T4.
August 2016
Parameters
Voltage U
Current I
Power P
Capacitance C
Inductance L
i
i
i
Input RTD Input RTD
30 V 30 V 30 V 30 V
300 mA 2.31 mA 300 mA 18.24 mA
1 W 17.32 mW 1.3 W 137 mW
i
i
14.8 nF 0 0 0.8 nF
HART Fieldbus
0 0 0 1.33 mH
8.9 China
E3 China Flameproof and Dust Ignition-proof
Certificate: 3051SMV: GYJ14.1039X [Mfg USA, China, Singapore]
3051SFx: GYJ11.1711X [Mfg USA, China, Singapore]
Standards: 3051SMV: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010
3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,
GB12476.1-2000
Markings: 3051SMV: Ex d IIC T6/T5 Ga/Gb
3051SFx: Ex d IIC T6/T5 Ga/Gb; DIP A20 T
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: For information on the
dimensions of the flameproof joints the manufacturer shall be contacted.
2. The relationship between T code and ambient temperature range are as follows:
105 °C; IP66
A
T code Ambient temperature range
T6 -50 °C ~ +65 °C
T5 -50 °C ~ +80 °C
3. The earth connection facility in the enclosure should be connected reliably.
4. During installation, use and maintenance of the product in explosive atmosphere,
observe the warning “Do not open cover when circuit is alive”. During installation, use, and maintenance in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”.
5. During installation there should be no mixture harmful to the housing.
6. During installation, use and maintenance in explosive dust atmosphere, product
enclosure should be cleaned to avoid dust accumulation, but compressed air should not be used.
20
Page 21
August 2016
Quick Start Guide
7. During installation in a hazardous location, cable glands and blanking plugs certified by
state appointed inspection bodies with Ex d IIC Gb or Ex d IIC Gb DIP A20 [Flowmeters] IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.
8. End users are not permitted to change any components, but to contact the
manufacturer to avoid damage to the product.
9. Maintenance should be done when no explosive gas and dust atmosphere is present.
10. During installation, use and maintenance of this product, observe following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)” GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
I3 China Intrinsic Safety
Certificate: 3051SMV: GYJ14.1040X [Mfg USA, China, Singapore]
3051SFx: GYJ11.1707X [Mfg USA, China, Singapore]
Standards: 3051SMV: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
3051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2000
Markings: 3051SMV: Ex ia IIC T4 Ga
3051SFx: Ex ia IIC T4 Ga, DIP A20 T
105 °C; IP66
A
Special Conditions for Safe Use (X):
1. The enclosure may contain light metal, attention should be taken to avoid ignition
hazard due to impact or friction.
2. The apparatus is not capable of withstanding the 500 V electrical strength test defined
in Clause 6.3.12 of GB3836.4-2010.
3. Ambient temperature range: -60 °C
+70 °C
~
4. Intrinsically safe electric parameters:
Maximum input
voltage: U
SuperModule 7.14 300 887 110 0
i
30 300 1.0 14.8 0
RTD 30 2.31 17.32 0 0
Maximum input
(V)
Max output
voltage: U
current: I
(V)
i
(mA)
i
current: I
Maximum input
power: P
Max output
(mA)
i
(W)
i
Maximum internal parameters
Ci(nF) Li(μH)
Max output
power: P
(W)
i
external parameters
Ci(nF) Li(μH)
Maximum
5. The cables between this product and associated apparatus should be shielded cables.
The shield should be grounded reliably in non-hazardous area.
6. The product should be used with Ex certified associated apparatus to establish
explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
7. End users are not permitted to change any components, contact the manufacturer to
avoid damage to the product.
21
Page 22
Quick Start Guide
8. During installation in hazardous location, cable glands, conduit, and blanking plugs
certified by state-appointed inspection bodies with DIP A20 IP66 type of protection should be used. Redundant cable entries should be blocked with blanking plugs.
9. During installation, use, and maintenance in explosive dust atmosphere, observe the
warning “Do not open when an explosive dust atmosphere is present”.
10. Maintenance should be done when no explosive dust atmosphere is present.
11. During installation, use and maintenance of this product, observe following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres” GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)” GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
8.10 EAC – Belarus, Kazakhstan, Russia
EM Technical Regulation Customs Union (EAC) Flameproof
Certificate: RU C-US.AA87.B.00094 Markings: Ga/Gb Ex d IIC T6…T4 X
August 2016
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: RU C-US.AA87.B.00094 Markings: 0Ex ia IIC T4 Ga X
8.11 Japan
E4 Japan Flameproof
Certificate: TC19070, TC19071, TC19072, TC19073 Markings: Ex d IIC T6
8.12 Republic of Korea
EP Republic of Korea Flameproof [HART Only]
Certificate: 12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore] Markings: Ex d IIC T5 or T6
IP Republic of Korea Intrinsic Safety [HART Only]
Certificate: 10-KB4BO-0021X [Mfg USA, SMMC] Markings: Ex ia IIC T4
8.13 Combinations
K1 Combination of E1, I1, N1, and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7, I7, and N7 KA Combination of E1, I1, E6, and I6 KB Combination of E5, I5, E6, and I6 KC Combination of E1, I1, E5, and I5 KD Combination of E1, I1, E5, I5, E6, and I6 KM Combination of EM and IM KP Combination of EP and IP
22
Page 23
August 2016
8.14 Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 00-HS145383 Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications
on ABS classed vessels, marine, and offshore installations. [HART Only]
SBV Bureau Veritas (BV) Type Approval
Certificate: 31910 BV Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class Notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS.
[HART only]
SDN Det Norske Veritas (DNV) Type Approval
Certificate: A-14186 Intended Use: Det Norske Veritas' Rules for Classification of Ships, High Speed & Light
Craft, and Det Norske Veritas' Offshore Standards. [HART Only]
Application:
Location classes
Ty pe 3051S
Tem p er at ur e D
Quick Start Guide
Humidity B
Vibration A
EMC A
Enclosure D/IP66/IP68
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5. [HART Only]
23
Page 24
Quick Start Guide
Figure 12. Rosemount 3051SMV Declaration of Conformity
August 2016
24
Page 25
August 2016
Quick Start Guide
25
Page 26
Quick Start Guide
August 2016
26
Page 27
August 2016
Quick Start Guide
27
Page 28
Quick Start Guide
August 2016
28
Page 29
August 2016
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 3051SMV
List of Rosemount 3051SMV Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㚄㤟䟊
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
XO O O O O
༣փ㓴Ԧ
Housing
Assembly
XO O X O O
Րᝏಘ㓴Ԧ
Sensor
Assembly
XO O X O O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Quick Start Guide
29
Page 30
Global Headquarters
Emerson Process Management
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
*00825-0100-4853*
Quick Start Guide
00825-0100-4853, Rev AD
August 2016
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947
Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Process-Management
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/ user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found at
www.Emerson.com/en-us/pages/Terms-of-Use.aspx
The Emerson logo is a trademark and service mark of Emerson Electric Co. MultiVariable, SuperModule, Rosemount, and Rosemount logotype are trademarks of Emerson Process Management. HART is a registered trademark of FieldComm Group. FOUNDATION Fieldbus is a trademark of the FieldComm Group. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. National Electrical Code is a registered trademark of National Fire Protection Association, Inc. All other marks are the property of their respective owners. © 2016 Emerson Process Management. All rights reserved.
Loading...