Emerson Rosemount 3051S FOUNDATION Series, Rosemount 3051SF FOUNDATION Series Quick Start Manual

Quick Start Guide
00825-0100-4805, Rev FD
March 2018
Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flow Meter
with FOUNDATION™ Fieldbus Protocol
Quick Start Guide
March 2018
NOTICE
This guide provides basic guidelines for Rosemount 3051S Series Pressure Transmitters. It also provides the basic electronics guidelines for the Rosemount 3051SFA Reference Manual
Reference Manual
troubleshooting. Refer to the Rosemount 3051S F instruction. This document is also available electronically on Emerson.com/Rosemount
Explosions can result in death or serious injury.
Do not remove the transmitter covers in explosive environments when the circuit is live.Both transmitter covers must be fully engaged to meet explosion-proof requirements.Make sure the instrument is installed in accordance with intrinsically safe or nonincendive field wiring
practices.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adaptor.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock.
. It does not provide instructions for configuration, diagnostics, maintenance, service,
OUNDATION Fieldbus Reference Manual for more
and Rosemount 3051SFC
.
Contents
Mount the transmitter . . . . . . . . . . . . . . . . . . . . 3
Tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Consider housing rotation . . . . . . . . . . . . . . . . . 8
Connect wiring and power up . . . . . . . . . . . . . . 8
2
Verify configuration . . . . . . . . . . . . . . . . . . . . . 10
To display level or flow, use AI block out. . . . . 11
Product Certifications . . . . . . . . . . . . . . . . . . . 13
March 2018
Flow
Flow
Flow
1.0 Mount the transmitter
1.1 Liquid flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
1.2 Gas flow applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Quick Start Guide
Flow
1.3 Steam flow applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
3
Quick Start Guide
Figure 1. Panel and Pipe Mounting
March 2018
Panel mount Pipe mount
Coplanar flange
Traditional flange
Plantweb
In-line
Housings
Junction box Remote mount display
4
March 2018
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4 × 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
1.4 Bolting considerations
If the transmitter installation requires assembly of the process flanges, manifolds, or flange adaptors, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 2. Common Transmitter Assemblies
Quick Start Guide
as spare parts. Figure 2
A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adaptors C. Transmitter with traditional flange and optional flange adaptors D. Transmitter with coplanar flange and optional manifold and flange adaptors
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1 on page 6. If bolt material is not shown in Table 1 on page 6, contact the local Emerson representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 1 on page 6 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1 on page 6 for final torque value.
5. Verify the flange bolts are protruding through the isolator plate before applying pressure.
5
Quick Start Guide
316
316
316
SW
316
STM
316
R
B8M
A
B
C
Rosemount 3051S/3051/2051/4088
D
Table 1. Torque Values for the Flange and Flange Adaptor Bolts
Bolt material Head markings Initial torque Final torque
March 2018
Carbon Steel (CS) 300 in-lb 650 in-lb
Stainless Steel (SST)
1.5 O-rings with flange adaptors
Failure to install proper flange adaptor O-rings may cause process leaks, which can result in death or serious injury. The two flange adaptors are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adaptor, as shown below:
B7M
150 in-lb 300 in-lb
A. Flange adaptor B. O-ring C. PTFE based (profile is square)
D. Elastomer (profile is round)
Whenever the flanges or adaptors are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the O-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE O-ring.
6
March 2018
1.6 In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located under the sensor module neck label. (See Figure 3.)
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that any contaminants can drain away.
Figure 3. In-line Gage Transmitter
A
A. Low side pressure port (under neck label)
Quick Start Guide
2.0 Tagging
2.1 Commissioning (paper) tag
To identify which device is at a particular location, use the removable tag provided with the transmitter. Ensure the physical device tag (PD Tag field) is properly entered in both places on the commissioning tag. Tear off the bottom portion of the tag and write “physical tag” on this portion. This can now be given to the person who can associate the device ID to the desired tag.
Figure 4. Commissioning Tag
Foundation Fieldbus revision ITK5 (default option)
COMMISSIONING TAG Device ID:
0011513051010001440-121698091725
PD Tag:
PT- 101
Revision: 23
Support files available at Emerson.com/Rosemount
Tear H ere
Revision: 23
Support files available at Emerson.com/Rosemount
Device Serial Number:
XXXXXXXXXX
Device ID:
0011513051010001440-121698091725
PD Tag:
PT-101
Foundation Fieldbus revision ITK6 (option code IT6)
COMMISSIONING TAG Device ID:
001151AA00010001440-121698091725
PD Tag:
PT- 101
Revision: 24
Support files available at Emerson.com/Rosemount
Revision: 24
Support files available at Emerson.com/Rosemount
Device Serial Number:
XXXXXXXXXX
Device ID:
001151AA00010001440-121698091725
PD Tag:
PT-101
Tear H ere
7
Quick Start Guide
A
Note
The device description loaded in the host system must be at the same revision as this device. The device description can be downloaded from Emerson.com/Rosemount
Fieldbus.org.
3.0 Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. First, rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit).
3. Retighten the housing rotation set screw.
Figure 5. Transmitter Housing Set Screw
PlantWeb
March 2018
or
A. Housing rotation set screw (3/32-in.)
4.0 Connect wiring and power up
4.1 Cable connection
The segment cable can enter the transmitter through either conduit connection on the housing. Cable entering the housing vertically should be avoided. Drip loops are recommended for installations where moisture can accumulate and enter the terminal compartment.
4.2 Power supply
The transmitter requires between 9 and 32 Vdc (9 and 17.5 Vdc for FISCO) at the terminals to operate and provide complete functionality.
4.3 Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.
8
March 2018
FIELDBUS WIRING
DP
B
D
A
C
Minimize distance
4.4 Signal termination
Every Fieldbus segment requires terminators at each end of the segment. Failure to properly terminate segments may cause communication errors with devices on the segment.
4.5 Transient protection
Transient protection devices require the transmitter be grounded for proper operation. Refer to Grounding for further information.
4.6 Grounding
Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protect terminal blocks are installed or to fulfill local regulations.
1. Remove the FIELD TERMINALS housing cover.
2. Connect the wiring pair and ground as indicated in Figure 6. a. The terminals are not polarity sensitive.
b. The cable shield should be:
Trimmed close and insulated from touching the transmitter housing Continuously connected to the termination point Connected to a good earth ground at the power supply end
Quick Start Guide
Figure 6. Wiring
A. Connect shield back to power supply ground C. Ground for transient protection B. Trim shield and insulate D. Insulate shield
3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
NOTICE
The enclosed pipe plug must be installed in unused conduit open ing wit h a minimum of five thr ead engagement to comply with explosion-proof requirements. Refer to the Rosemount 3051S
OUNDATION Fieldbus Reference Manual for more information. This manual is also available
F electronically on Emerson.com/Rosemount
.
9
Quick Start Guide
5.0 Verify configuration
Use the following block examples to do basic configuration to the transmitter. For more advanced configurations see the Rosemount 3051S FOUNDATION Fieldbus Reference Manual
Note
DeltaV™ users should use DeltaV Explorer for the resource and transducer blocks and Control Studio for the function blocks.
5.1 To configure the AI block
AI block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
Parameters Enter data
Channel 1 = Pressure or 2 = Sensor temp
.
March 2018
L_Type Direct, indirect, or square root
XD_Scale Scale and engineering units
Pa bar inH2O @ 68 °F cmH2O @ 4 °C
kPa mbar mmH2O @ 68 °F ftH2O
MPa atm ftH2O @ 68 °F inH2O
(1)
hPa
psi °C ftH2O @ 60 °F
torr °F ftH2O @ 4 °C
Out_Scale Scale and engineering units
1. Only available with option IT6.
psf
(1)
inH2O @ 60 °F
(1)
inHg @ 0 °C
(1)
(1)
(1)
(1)
(1)
g/cm
kg/m2
kg/cm
2
(1)
2
mmHg @ 0 °C
mmH2O @ 4 °C
inH2O @ 4 °C
mHg @ 0 °C
cmHg @ 0 °C
mH2O @ 4 °C
(1)
(1)
(1)
10
March 2018
Quick Start Guide
Pressure example
Parameters Enter data
Channel 1
L_Type Direct
XD_Scale See list of supported engineering units.
Out_Scale Set values outside operating range.
DP Flow example
Parameters Enter data
Channel 1 L_Type Square root XD_Scale 0–100 inH2O @ 68 °F Out_Scale 0–20 GPM
DP Level example
Parameters Enter data
Channel 1 L_Type Indirect XD_Scale 0–300 inH2O @ 68 °F Out_Scale 0–25 ft
To display pressure on the LCD meter
Parameters Enter data
Display parameter 1 Block type #1 Sensor transducer block Block tag Tra ns du cer Param index Primary variable Units type Auto
With option code IT6, select the “Pressure” check box on the display configuration screen.
Note
To display level or flow, use AI block out.
11
Quick Start Guide
6.0 Trim the transmitter
Note
Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).
6.1 Zero trim
A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled to the correct level. The transmitter will only allow three to five percent URL zero error to be trimmed. For greater zero errors, compensate for the offset by using the XD_Scaling, Out_Scaling and Indirect L_Type which are part of the AI block.
Using the host system
Perform a zero trim method if the host system supports methods associated with the Transducer 1100 block. Otherwise, if the host system does not support methods, see Rosemount 3051S FOUNDATION Fieldbus Reference
Manual.
March 2018
12
March 2018
7.0 Product Certifications
Rev 1.15
7.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount
7.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
7.3 Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
.
Quick Start Guide
7.4 USA
E5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: FM16US0090 Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011,
FM Class 3810 – 2005, ANSI/NEMA
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(–50 °C ≤ T
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: FM16US0089X Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
FM Class 3810 – 2005, NEMA 250 – 2003
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1,
Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C ≤ T
when connected per Rosemount drawing 03151-1006; Type 4X
Special Condition for Safe Use:
1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
+85 °C); Factory Sealed; Type 4X
a
+70 °C) [HART]; T4(–50 °C Ta +60 °C) [Fieldbus];
a
®
250 – 2003
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03151-1006.
13
Quick Start Guide
IE FM FISCO
Certificate: FM16US0089X Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
FM Class 3810 – 2005, NEMA 250 – 2003
Markings: IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ T
per Rosemount drawing 03151-1006; Type 4X
Special Condition for Safe Use:
1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
7.5 Canada
E6 CSA Explosionproof, Dust-Ignitionproof, and Division 2
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966,
CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 213-M1987, ANSI/ISA
12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings: Explosionproof Class I, Division 1, Groups B, C, D; Dust-Ignitionproof Class II,
Division 1, Groups E, F, G; Class III; suitable for Class I, Zone 1, Group IIB+H2, T5; suitable for Class I, Division 2, Groups A, B, C, D; suitable for Class I, Zone 2, Group IIC, T5; when connected per Rosemount drawing 03151-1013; Type 4X
+60 °C); when connected
a
March 2018
I6 CSA Intrinsically Safe
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 30-M1986,
CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings: Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for
Class 1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X
IF CSA FISCO
Certificate: 1143113 Standards: CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 30-M1986,
CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings: FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class
1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X
14
March 2018
7.6 Europe
E1 ATEX Flameproof
Certificate: KEMA 00ATEX2143X Standards: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015 Markings: II 1/2 G Ex d IIC T6…T4 Ga/Gb, T6(–60 °C ≤ T
Temperature class Process temperature
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and data sheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C
greater than maximum specified temperature for location where installed.
T5/T4(–60 °C ≤ T
T6 –60 °C to +70 °C T5 –60 °C to +80 °C T4 –60 °C to +120 °C
+80 °C)
a
+70 °C),
a
Quick Start Guide
I1 ATE X Intrinsic Safet y
Certificate: BAS01ATEX1303X Standards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012 Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ T
Model U
SuperModule 3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0 3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0 3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH 3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9 RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
i
30 V 300 mA 1.0 W 30 nF 0
30 V 300 mA 1.0 W 12 nF 60 μH
30 V 300 mA 1.0 W 12 nF 93 μH
+70 °C)
a
I
i
P
i
C
i
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree
of protection of at least IP20 in accordance with IEC/EN 60529.
L
i
15
Quick Start Guide
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
IA ATEX FISCO
Certificate: BAS01ATEX1303X Standards: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012 Markings: II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ T
+70 °C)
a
March 2018
Parameter
Voltage U Current I Power P Capacitance C Inductance L
i
i
i
i
i
FISCO
17.5 V
380 mA
5.32 W 0 0
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
ND ATEX Dust
Certificate: BAS01ATEX1374X Standards: EN 60079-0: 2012+A11:2013, EN 60079-31: 2009 Markings: II 1 D Ex ta IIIC T105 °C T
V
= 42.4 V
max
95 °C Da, (–20 °C ≤ Ta +85 °C),
500
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7 J impact test.
4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s).
N1 ATEX Type n
Certificate: BAS01ATEX3304X Standards: EN 60079-0: 2012+A11:2013, EN 60079-15: 2010 Markings: II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ T
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.
Note
RTD Assembly is not included with the Rosemount 3051SFx Type n Approval.
16
+85 °C), V
a
max
= 45 V
March 2018
7.7 International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 08.0010X (Flameproof) Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014 Markings: Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ T
Temperature class Process temperature
T6 –60 °C to +70 °C T5 –60 °C to +80 °C T4 –60 °C to +120 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and data sheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid
installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C
greater than maximum specified temperature for location where installed.
Quick Start Guide
+70 °C), T5/T4(–60 °C Ta +80 °C)
a
Certificate: IECEx BAS 09.0014X (Dust) Standards: IEC 60079-0:2011, IEC 60079-31:2008 Markings: Ex ta IIIC T 105 °C T
95 °C Da, (–20 °C ≤ Ta +85 °C), V
500
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature
range of the apparatus and capable of withstanding a 7 J impact test.
4. The Rosemount 3051S SuperModule must be securely screwed in place to maintain
the ingress protection of the enclosure.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 04.0017X Standards: IEC 60079-0: 2011, IEC 60079-11:2011 Markings: Ex ia IIC T4 Ga, T4(–60 °C ≤ T
Model U
SuperModule 30 V 300 mA 1.0 W 30 nF 0 3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0 3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0 3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9
+70 °C)
a
i
30 V 300 mA 1.0 W 12 nF 60 μH
I
i
P
i
C
i
L
i
17
Quick Start Guide
March 2018
Model U
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH 3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9 RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
i
30 V 300 mA 1.0 W 12 nF 93 μH
I
i
P
i
C
i
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
I7 IECEx Intrinsic Safety – Group I - Mining (I7 with Special A0259)
Certificate: IECEx TSA 14.0019X Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: Ex ia I Ma (–60 °C ≤ T
Model U
SuperModule 30 V 300 mA 1.0 W 30 nF 0 3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0 3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0 3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH 3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9 RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
+70 °C)
a
i
30 V 300 mA 1.0 W 12 nF 60 μH
30 V 300 mA 1.0 W 12 nF 93 μH
I
i
P
i
C
i
L
i
L
i
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11:2011. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.
IG IECEx FISCO
Certificate: IECEx BAS 04.0017X Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: Ex ia IIC T4 Ga, T4(–60 °C ≤ T
18
+70 °C)
a
March 2018
Quick Start Guide
Parameter
Volta ge U Current I Power P Capacitance C Inductance L
i
i
i
i
i
FISCO
17.5 V
380 mA
5.32 W 0 0
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of
protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
IG IECEx Intrinsic Safety – Group I - Mining (IG with Special A0259)
Certificate: IECEx TSA 14.0019X Standards: IEC 60079-0:2011, IEC 60079-11:2011 Markings: FISCO FIELD DEVICE Ex ia I Ma (–60 °C ≤ T
+70 °C)
a
Parameter
Volta ge U Current I Power P Capacitance C Inductance L
i
i
i
i
i
FISCO
17.5 V
380 mA
5.32 W 0 0
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11:2011. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account
during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and
sensor module housing made out of stainless steel are used in Group I applications.
N7 IECEx Type n
Certificate: IECEx BAS 04.0018X Standards: IEC 60079-0:2011, IEC 60079-15:2010 Markings: Ex nA IIC T5 Gc, (–40 °C ≤ T
+85 °C)
a
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.
19
Quick Start Guide
7.8 Brazil
E2 INMETRO Flameproof
Certificate: UL-BR15.0393X Standards: ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011,
ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1:2008
Markings: Ex d IIC T* Ga/Gb, T6(–60 °C ≤ T
IP66
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints, the manufacturer shall be contacted.
I2/IB INMETRO Intrinsic Safety/FISCO
Certificate: UL-BR 15.0392X Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011, ABNT NBR IEC 60079-11:2009 Markings: Ex ia IIC T4 Ga (–60 °C ≤ T
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GÙ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced in a hazardous area. The Power Module has a surface resistivity greater than 1 GÙ and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
3. The 3051S enclosure may be made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in areas that requires EPL Ga.
+70 °C), T5/T4(–60 °C Ta +80 °C),
a
+70 °C), IP66
a
March 2018
Model U
SuperModule 30 V 300 mA 1.0 W 30 nF 0 3051S...A; 3051SF…A; 3051SAL…C 30 V 300 mA 1.0 W 12 nF 0 3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0 3051S…F…IB; 3051SF…F…IB 17.5V 380 mA 5.32 W 0 0 3051S …A…M7, M8, or M9;
3051SF …A…M7, M8, or M9; 3051SAL…C… M7, M8, or M9
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 μH 3051SAL…M7, M8, or M9
3051SAM…M7, M8, or M9 RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
7.9 China
E3 China Flameproof and Dust Ignition-proof
Certificate: 3051S: GYJ16.1249X
3051SFx: GYJ16.1466X 3051S-ERS: GJY15.1406X
20
i
30 V 300 mA 1.0 W 12 nF 60 μH
30 V 300 mA 1.0 W 12 nF 93 μH
I
i
P
i
C
i
L
i
March 2018
Quick Start Guide
Standards: 3051S: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,
GB12476.1-2013, GB12476.5-2013
3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,
GB12476.1-2013, GB 12476.5-2013
Markings: 3051S: Ex d IIC T6…T4; Ex tD A20 T 105 °C T
3051SFx: Ex d IIC T5/T6 Ga/Gb; DIP A20 T
95 °C; IP66
500
105 °C; IP66
A
3051S-ERS: Ex d IIC T4 ~ T6 Ga/Gb
Special Conditions for Safe Use (X):
1. Only the pressure transmitters, consisting of Rosemount 3051SC Series, 3051ST Series, 3051SL Series and 300S Series, are certified.
2. Flameproof joints are not intended for repair.
3. The ambient temperature range for the 3051S and 3051SFx in a dust environment is
(
20 °C Ta 85 °C).
4. The relation between temperature class and maximum temperature of process
medium is as follows:
Table 2. Rosemount 3051S
Temperature class Ambient temperature (°C) Process temperature (°C)
T6 –60 °C Ta ≤ +70 °C –60 °C Ta ≤ +70 °C
T5 –60 °C Ta ≤ +80 °C –60 °C Ta ≤ +80 °C
T4 –60 °C Ta ≤ +80 °C –60 °C Ta ≤ +120 °C
5. The earth connection facility in the enclosure should be connected reliably.
6. During installation, use and maintenance of transmitter, observe the warning
“Don’t open the cover when the circuit is alive”.
7. During installation, there should be no mixture harm to flameproof housing.
8. Cable entry, certified by NEPSI with type of protection Ex d IIC in accordance with
GB3836.1-2000 and GB3836.2-2000, should be applied when installation in hazardous location. Five full threads should be in engagement when the cable entry is assembled onto the transmitter. When pressure transmitter is used in the presence of combustible dust, the ingress of protection of the cable entry should be IP66.
9. The diameter of cable should observe the instruction manual of cable entry. The
compressing nut should be fastened. The aging of seal ring should be changed in time.
10. Maintenance should be done in non-hazardous location.
11. End users are not permitted to change any components inside.
12. When installation, use and maintenance of transmitter, observe following
standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13:Repair and overhaul for apparatus used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
GB15577-1995 “Safe regulation for explosive dust atmospheres” GB12476.2-2006 “Electrical apparatus for use in the presence of combustible dust –
Part 1-2: Electrical apparatus protected by enclosures and surface temperature limitation – Selection, installation and maintenance”
21
Quick Start Guide
I3 China Intrinsic Safety
Certificate: 3051S: GYJ16.1250X [Mfg USA, China, Singapore]
Standards: 3051S: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Markings: 3051S, 3051SFx: Ex ia IIC T4 Ga
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use: For output code A and F: This apparatus is not capable of withstanding the 500V r.m.s.
insulation test required by Clause 6.4.12 of GB3836.4-2000.
2. The ambient temperature range is:
March 2018
3051SFx: GYJ11.1707X [Mfg USA, China, Singapore]
3051S-ERS: GYJ16.1248X [Mfg USA, China, Singapore]
3051SFx: GB3836.1/4-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013 3051S-ERS: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
3051S-ERS: Ex ia IIC T4
Output code Ambient temperature
A –50 °C Ta +70 °C
F –50 °C Ta +60 °C
3. Intrinsically safe parameters:
Maximum
Output
FISCO
Housing
code
code
A =00 / 30 300 1 38 0
A 00 / 30 300 1 11.4 2.4
A 00 M7/M8/M9 30 300 1 0 58.2
F 00 / 30 300 1.3 0 0
F
00 / 17.5 500 5.5 0 0
Display
code
input
vol tag e:
(V)
U
i
Maximum
input
current:
(mA)
I
i
Maximum
input
power:
(W)
P
i
Maximum
internal
parameter:
(nF)
C
i
Maximum
internal
parameter:
(uH)
L
i
4. The product should be used with Ex-certified associated apparatus to establish
explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and associated apparatus.
5. The cable between this product and associated apparatus should be shielded cables
(the cables must have insulated shield). The shield has to be grounded reliably in non-hazardous area.
6. The product complies to the requirements for FISCO field devices specified in
IEC60079-27:2008. For the connection of an intrinsically safe circuit in accordance FISCO model, FISCO parameters of this product are as above.
7. End users are not permitted to change any components inside, but to settle the
problem in conjunction with manufacturer to avoid damage to the product.
8. When installation, use and maintenance of this product, observe the following
standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”
22
March 2018
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for
explosion atmospheres and fire hazard electrical equipment installation engineering”
N3 China Type n
Certificate: 3051S: GYJ17.1354X
3051SFX: GYJ17.1355X
Markings: Ex nL IIC T5 Gc
Special Conditions for Safe Use (X):
1. When transient protection board is chosen (Option Code T1), this apparatus is not capable of withstanding the 500V r.m.s insulation test, this must be taken into account when installing the component.
7.10 EAC – Belarus, Kazakhstan, Russia
EM Technical Regulation Customs Union (EAC) Flameproof
Certificate: RU C-US.AA87.B.00378 Markings: Ga/Gb Ex d IIC T6…T4 X
Ex tb IIIC T105 °C T Ex ta IIIC T105 °C T
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: RU C-US.AA87.B.00094 Markings: 0Ex ia IIC T4 Ga X
95 °C Db X
500
95 °C Da X
500
Quick Start Guide
7.11 Japan
E4 Japan Flameproof
Certificate: TC15682, TC15683, TC15684, TC15685, TC15686, TC15687, TC15688,
TC15689, TC15690, TC17099, TC17100, TC17101, TC17102, TC18876 3051ERS: TC20215, TC20216, TC20217, TC20218, TC20219, TC20220, TC20221
Markings: Ex d IIC T6
7.12 Republic of Korea
EP Republic of Korea Flameproof
Certificate: 12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore] Markings: Ex d IIC T6…T4
IP Republic of Korea Intrinsic Safety
Certificate: 12-KB4BO-0202X [HART – Mfg USA],
12-KB4BO-0204X [Fieldbus – Mfg USA], 12-KB4BO-0203X [HART – Mfg Singapore], 13-KB4BO-0296X [Fieldbus – Mfg Singapore]
Markings: Ex ia IIC T4
23
Quick Start Guide
7.13 Combinations
K1 Combination of E1, I1, N1, and ND K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7, I7, and N7 KA Combination of E1, I1, E6, and I6 KB Combination of E5, I5, E6, and I6 KC Combination of E1, I1, E5, and I5 KD Combination of E1, I1, E5, I5, E6, and I6 KG Combination of IA, IE, IF, and IG KM Combination of EM and IM KP Combination of EP and IP
7.14 Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 00-HS145383-6-PDA Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on
ABS classed vessels, marine, and offshore installations.
March 2018
SBVBureau Veritas (BV) Type Approval
Certificate: 31910 BV Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class Notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS
SDNDet Norske Veritas (DNV) Type Approval
Certificate: A-14186 Intended Use: Det Norske Veritas’ Rules for Classification of Ships, High Speed & Light
Craft, and Det Norske Veritas’ Offshore Standards
Application:
Location classes
Ty pe 3051S
Tem pe r at ur e D
Humidity B
Vibration A
EMC A
Enclosure D/IP66/IP68
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3, and ENV5
D3 Custody Transfer – Measurement Canada Accuracy Approval [3051S Only]
Certificate: AG-0501, AV-2380C
24
March 2018
EU Declaration of Conformity
No: RMD 1044 Rev. AA
Page 1 of 4
We,
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount 3051S Series Pressure Transmitters
Rosmeount 3051SFx Series Flowmeter Transmitters
Rosemount 300S Housings
manufactured by,
Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function name - printed)
Chris LaPoint
(name - printed)
13-April-2017
(date of issue)
Figure 7. Rosemount 3051S Declaration of Conformity
Quick Start Guide
25
Quick Start Guide
EU Declaration of Conformity
No: RMD 1044 Rev. AA
Page 2 of 4
EMC Directive (2014/30/EU)
Harmonized Standards:
EN 61326-1:2013, EN 61326-2-3:2013
PED Directive (2014/68/EU)
Rosemount 3051S Series Pressure Transmitters
Rosemount 3051S_CA4; 3051S_CD2, 3, 4, 5 (also with P0 & P9 option) Pressure Transmitters
QS Certificate of Assessment – EC Certificate No. 59552-2009-CE-HOU-DNV Module H Conformity Assessment Evaluation standards: ANSI / ISA 61010-1:2004
All other Rosemount 3051S Pressure Transmitters
Sound Engineering Practice
Transmitter Attachments: Diaphragm Seal, Process Flange, or Manifold
Sound Engineering Practice
Rosemount 3051SFx Series Flowmeter Pressure Transmitters
See DSI 1000 Declaration of Conformity
March 2018
26
March 2018
EU Declaration of Conformity
No: RMD 1044 Rev. AA
Page 3 of 4
ATEX Directive (2014/34/EU)
BAS01ATEX1303X – Intrinsic Safety Certificate
Equipment Group II, Category 1 G Ex ia IIC T4 Ga Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-11:2012
BAS01ATEX3304X – Type n Certificate
Equipment Group II, Category 3 G Ex nA IIC T5 Gc Harmonized Standards Used: EN 60079-0:2012+A11:2013, EN 60079-15:2010
BAS01ATEX1374X – Dust Certificate
Equipment Group II, Category 1 D Ex ta IIIC T105°C T
500
95°C Da Harmonized Standards Used: EN 60079-0:2012+A11:2013 Other Standards Used:
EN 60079-31:2009 (a review against EN 60079-31:2014, which is harmonized, shows no significant changes relevant to this equipment so EN 60079-31:2009 continues to represent “State of the Art”)
BAS04ATEX0181X – Mining Certificate
Equipment Group I, Category M1 Ex ia I Ma Harmonized Standards Used: EN 60079-0:2012, EN 60079-11:2012
BAS04ATEX0193U – Mining Certificate: Component
Equipment Group I, Category M1 Ex ia I Ma Harmonized Standards Used: EN 60079-0:2012, EN 60079-11:2012
KEMA00ATEX2143X – Flameproof Certificate
Equipment Group II, Category 1/2 G Ex db IIC T6…T4 Ga/Gb Harmonized Standards: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015
Quick Start Guide
27
Quick Start Guide
EU Declaration of Conformity
No: RMD 1044 Rev. AA
Page 4 of 4
PED Notified Body
Rsoemount 3051S Series Pressure Transmitters
DNV GL AS [Notified Body Number: 0575]
Veritasveien 1, N-1322 Hovik, Norway
ATEX Notified Bodies for EU Type Examination Certificate
DEKRA Certification B.V. [Notified Body Number: 0344]
Utrechtseweg 310 Postbus 5185 6802 ED Arnhem Netherlands
SGS Baseefa Limited [Notified Body Number: 1180] Rockhead Business Park, Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom
ATEX Notified Body for Quality Assurance
SGS Baseefa Limited [Notified Body Number: 1180]
Rockhead Business Park, Staden Lane Buxton, Derbyshire SK17 9RZ United Kingdom
March 2018
28
March 2018
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
䜘Ԧ〠
ᴹᇣ⢙䍘䍘
䫵
⊎
䭹
ޝԧ䬜䬜
ཊⓤ㚄㚄㤟
ཊⓤ㚄㚄㤟䟊
China RoHS
Rosemount 3051S
List of Rosemount 3051S Parts with China RoHS Concentration above MCVs
/ Hazardous Substances
Quick Start Guide
Part Name
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr +6)
Polybrominated
biphenyls
(PBB)
Polybrominated
diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
XO O O O O
Assembly
༣փ㓴Ԧ
Housing
XO O X O O
Assembly
Րᝏಘ㓴Ԧ
Sensor
XO O X O O
Assembly
ᵜ㺘Ṭ㌫׍ᦞ
This table is proposed in accordance with the provision of SJ/T11364.
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
O: O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
X: X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
29
Quick Start Guide
March 2018
30
March 2018
Quick Start Guide
31
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
*00825-0100-4805*
Quick Start Guide
00825-0100-4805, Rev FD
March 2018
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947
Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/ user/RosemountMeasurement
Google.com/+RosemountMeasurement
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners. © 2018 Emerson. All rights reserved.
Loading...