Emerson Rosemount 3051SF Series, Rosemount 3051SFA, Rosemount 3051S Series, Rosemount 3051SFP, Rosemount 3051SFC Quick Start Manual

Quick Start Guide
00825-0100-4801, Rev NB
December 2018
Rosemount™ 3051S Series Pressure Transmitter and Rosemount 3051SF Series Flowmeter
with HART® Protocol
Safety messages
NOTICE
This guide provides basic guidelines for Rosemount™ 3051S Series Pressure Transmitters. It also provides the basic electronic guidelines for the Rosemount 3051SFA Reference Manual, Rosemount 3051SFC Reference Manual, and Rosemount 3051SFP Reference Manual. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Rosemount 3051S HART Reference Manual for more instruction. This document is also available electronically on
Emerson.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
Review the Rosemount 3051S/3051SFx/3051S-ERS Product Certifications section of this guide for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power
is applied to the unit.
Use appropriately rated Ex adaptors, blanking elements, or glands during installation.
Keep process insulation at least 1 inch (25 mm) from transmitter connection.
Process leaks could result in death or serious injury.
Install and tighten process connectors before applying pressure.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT thread form.
Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands,
or adapters in cable/conduit entries.
Contents
Mount the transmitter................................... 5
Consider housing rotation............................11
Set switches and jumpers.............................12
Connect wiring and power up...................... 14
Verify configuration..................................... 22
Trim the transmitter.................................... 26
Safety instrumented systems installation.....28
Rosemount 3051S/3051SFx/3051S-ERS
Product Certifications.................................. 29
Quick Start Guide December 2018
2 Rosemount 3051S
Rosemount 3051S Declaration of Conformity
.................................................................... 45
China RoHS.................................................. 49
December 2018 Quick Start Guide
Quick Start Guide 3
Quick Start Guide December 2018
4 Rosemount 3051S
1 Mount the transmitter
1.1 Liquid flow applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
A
A. Direction of flow
1.2 Gas flow applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
A
A. Direction of flow
December 2018 Quick Start Guide
Quick Start Guide 5
1.3 Steam flow applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
A
A. Direction of flow
1.4 Using a mounting bracket
If the transmitter requires the use of a mounting bracket, use the images below for instructions on how to properly mount the transmitter using the Emerson™ provided mounting brackets. Use only bolts provided with the transmitter or sold as Emerson spare parts.
1.5
Bolting considerations
About this task
If the transmitter installation requires assembly of a process flange, manifold, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter. Only use bolts supplied with the transmitter or sold by Emerson™ as spare parts. Figure 1-1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Quick Start Guide December 2018
6 Rosemount 3051S
Figure 1-1: Common Transmitter Assemblies
A
4 × 1.75-in.
(44 mm)
D
4 × 1.75-in.
(44 mm)
4 × 2.25-in.
(57 mm)
C
4 × 1.75-in.
(44 mm)
4
× 1.50-in.
(38 mm)
B
4 × 2.88-in.
(73 mm)
A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adapters C. Transmitter with traditional flange and optional flange adapters
D. Transmitter with coplanar flange and optional Rosemount Conventional
Manifold and flange adapters
Note
For all other manifolds, contact Customer Central technical support.
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1-1 . If bolt material is not shown in Table 1-1, contact the local Emerson representative for more information.
Use the following bolt installation procedure:
Procedure
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See Table 1-1 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1-1 for final torque value.
December 2018 Quick Start Guide
Quick Start Guide 7
5. Verify the flange bolts are protruding through the sensor module before applying pressure (see Figure 1-2).
Example
Table 1-1: Torque Values for the Flange and Flange Adapter Bolts
Bolt material Head markings Initial torque Final torque
Carbon Steel (CS)
B7M
300 in-lb 650 in-lb
Stainless Steel (SST)
316
316
316
SW
316
STM
316
R
B8M
150 in-lb 300 in-lb
Figure 1-2: Proper Bolt Installation
A
B
A. Bolt B. Sensor module
Quick Start Guide December 2018
8 Rosemount 3051S
1.6 O-rings with flange adapters
WARNING
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. Only use the O-ring that is designed for its specific flange adapter.
A
B
C D
A. Flange adapter B. O-ring C. PTFE-based profile (square)
D. Elastomer profile (round)
Whenever the flange or adapters are removed, visually inspect the O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the O­rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the O-rings.
1.7
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located under the sensor module neck label. (See Figure 1-3)
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that any contaminants can drain away.
December 2018 Quick Start Guide
Quick Start Guide 9
Figure 1-3: In-line Gage Transmitter
A
A. Low side pressure port (under neck label)
Quick Start Guide December 2018
10 Rosemount 3051S
2 Consider housing rotation
About this task
To improve field access to wiring or to better view the optional LCD display:
Procedure
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw.
Figure 2-1: Transmitter Housing Set Screw
A. LCD display B. Housing rotation set screw (3/32-in.)
CAUTION
Do not rotate the housing more than 180° without first performing a disassembly procedure. Over-rotation may sever the electrical connection between the sensor module and the electronics.
December 2018 Quick Start Guide
Quick Start Guide 11
3 Set switches and jumpers
About this task
If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm “high” and the security “off”.
Procedure
1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the transmitters is live, set the loop to manual and remove power.
2. Remove the electronics compartment cover. On the Plantweb housing the cover is opposite the field terminals side, or on the junction box housing remove the terminal block cover. Do not remove the housing cover in explosive environments.
3. On the Plantweb housing, slide the security and alarm switches into the preferred position by using a small screwdriver (An LCD display or an adjustment module must be in place to activate the switches). On the junction box housing pull the pins out and rotate 90° into desired position to set the security and alarm.
4. Reinstall the housing cover so metal contacts metal to meet explosion­proof requirements.
Figure 3-1: Transmitter Switch and Jumper Configuration (Plantweb)
A
B
C
A. Meter/adjustment module
B. Security
C. Alarm
Quick Start Guide December 2018
12 Rosemount 3051S
Figure 3-2: Transmitter Switch and Jumper Configuration (Junction Box)
B
C
A. Meter/adjustment module B. Security C. Alarm
December 2018 Quick Start Guide
Quick Start Guide 13
4 Connect wiring and power up
Procedure
1. Remove and discard orange conduit plugs.
2. Remove the housing cover labeled “Field Terminals.”
Note
Do not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted pairs yield best results. Use 24–14 AWG wire and do not exceed 5,000 ft. (1,500 m). For single compartment housing (Junction Box housing), shielded signal wiring should be used in high EMI/RFI environments.
3. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal.
4. CAUTION
When the enclosed threaded plug is utilized in the conduit opening, it must be installed with a minimum thread engagement in order to comply with explosion-proof requirements. For straight threads, a minimum of seven threads must be engaged. For tapered threads, a minimum of five threads must be engaged.
Plug and seal the unused conduit connection with the provided conduit plug.
5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
6. Reinstall the housing cover and tighten so the cover is fully seated with metal to metal contact between the housing and cover in order to meet explosion proof requirements.
The figures below show the wiring connections necessary to power a transmitter and enable communications with a hand-held Field Communicator.
Quick Start Guide December 2018
14 Rosemount 3051S
Figure 4-1: Transmitter Wiring (Plantweb Housing)
A
B
A. RL ≥ 250 Ω B. Power supply
Figure 4-2: Transmitter Wiring (Junction Box Housing)
A
B
A. RL ≥ 250 Ω B. Power supply
Note
Installation of the transient protection terminal block does not provide transient protection unless the Rosemount 3051S case is properly grounded.
4.1
Ground signal wiring
About this task
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the terminal compartment. These grounds are used when transient protection terminal blocks are installed or to fulfill local regulations.
Procedure
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 4-3. The cable shield should:
December 2018 Quick Start Guide
Quick Start Guide 15
Be trimmed close and insulated from touching the transmitter
housing
Continuously connect to the termination point
Be connected to a good earth ground at the power supply end
Figure 4-3: Wiring
DP
C
A
B
B
D
E
A. Insulate shield
B. Minimize distance
C. Connect shield back to the power supply ground
D. Trim shield and insulate
E. Safety ground
3. Replace the housing cover. It is recommended the cover be tightened until there is no gap between the cover and the housing.
4. Plug and seal the unused conduit connection with the provided conduit plug.
4.2
Remote display wiring and power up (if applicable)
The remote mount display and Interface system consists of a local transmitter and a remote mount LCD display assembly. The local Rosemount 3051S assembly includes a Junction Box housing with a three-position terminal block integrally mounted to a sensor module. The remote mount LCD display assembly consists of a dual compartment Plantweb housing with a seven position terminal block. See Figure 4-4 for complete wiring instructions. The following is a list of necessary information specific to the remote mount display system:
Each terminal block is unique for the remote display system.
A 316 SST housing adaptor is permanently secured to the remote mount
LCD display Plantweb housing, providing an external ground and a means for field mounting with the provided mounting bracket.
A cable is required for wiring between the transmitter and remote mount
LCD display. The cable length is limited to 100 ft.
50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring
between the transmitter and remote mount LCD display. Option M7 does not include cable; see recommended specifications below.
Quick Start Guide December 2018
16 Rosemount 3051S
Cable type
Recommend Madison AWM Style 2549 cable. Other comparable cable may be used as long as it has independent dual twisted shielded pair wires with an outer shield. The power wires must be 22 AWG minimum and the CAN communication wires must be 24 AWG minimum.
Cable length
The cable length is up to 100 ft .depending upon cable capacitance.
Cable capacitance
The capacitance from the CAN communications line to the CAN return line as wired must be less than 5,000 picofarads total. This allows up to 50 picofarads per foot for a 100 foot cable.
Intrinsic safety consideration
The transmitter assembly with remote display has been approved with Madison AWM Style 2549 cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the installation control drawing or certificate. Refer to appropriate approval certificate or control drawing in Appendix B of the Rosemount 3051S
Reference Manual for remote cable IS requirements.
CAUTION
Do not apply power to the remote communications terminal. Follow wiring instructions carefully to prevent damage to system components.
December 2018 Quick Start Guide
Quick Start Guide 17
Figure 4-4: Remote Mount Display Wiring Diagram
A
B
C
(white) 24 AWG
(blue) 24 AWG (black) 22 AWG
(red) 22 AWG
A. Remote mount display B. Junction box housing C. 4–20 mA
Note
Wire colors provided are per Madison AWM Style 2549 cable. Wire color may vary depending on cable selected.
Madison AWM Style 2549 cable includes a ground shield. This shield must be connected to earth ground at either the sensor module or the remote display, but not both.
4.3
Quick connect wiring (if applicable)
About this task
As standard, the Rosemount 3051S Quick Connect arrives properly assembled to the sensor module and is ready for installation. Cordsets and field wireable connectors (in shaded area) are sold separately.
Quick Start Guide December 2018
18 Rosemount 3051S
Figure 4-5: Rosemount 3051S Quick Connect Exploded View
A
B
D
E
F
C
A. Straight field wireable connector (part number 03151-9063-0001),
supplied by customer
B. Right angle field wireable connector (part number 03151-9063-0002),
supplied by customer
C. Quick Connect housing
D. Cordset, supplied by vendor
E. Coupling nut F. Quick Connect coupling nut
Important
If Quick Connect is ordered as a Rosemount 300S spare housing or is removed from the sensor module, follow the instructions below for proper assembly prior to field wiring.
Procedure
1. Place the Quick Connect onto the sensor module. To ensure proper pin alignment, remove coupling nut prior to installing quick connect onto the sensor module.
2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb (34 N-m).
3. Tighten the set screw up to 30 in-lb using a 3/32-in. hex wrench.
4. Install cordset/field wireable connectors onto the Quick Connect. Do not over tighten.
December 2018 Quick Start Guide
Quick Start Guide 19
Figure 4-6: Quick Connect Housing Pin-Out
A
B
+
“-”
A. Ground
B. No connection
Note
For other wiring details, refer to pin-out drawing and the cordset manufacturer’s installation instructions.
4.4 Conduit electrical connector wiring (option GE or GM)
For Rosemount 3051S with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, non-incendive or FM FISCO Intrinsically Safe hazardous locations, install in accordance with Rosemount drawing 03151-1009. See Appendix B of the Rosemount 3051S Reference Manual.
4.5
Power supply
The DC power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces.
Note
The resistance of intrinsic safety barriers, if used, must be included.
Quick Start Guide December 2018
20 Rosemount 3051S
Figure 4-7: Load Limitation
1387
1000
500
0
10.5 20 30
42.4
Voltage (Vdc)
Load (Ohms)
Operating
Region
Maximum loop resistance = 43.5 x (power supply voltage – 10.5)
The Field Communicator requires a minimum loop resistance of 250Ω for communication.
December 2018 Quick Start Guide
Quick Start Guide 21
5 Verify configuration
Use any HART-compliant master to communicate with and verify configuration of the Rosemount 3051S.
Field Communicator user interface
Fast Key sequences vary with the device driver revision. Reference Table 5-1 for DD Rev. 8 or older. Reference Table 5-2 for DD Rev. 9 or newer.
Figure 5-1: Traditional Interface - Device Revision 6 or 7 and DD Revision 7
SAVE
3051:PT 93207 Online
1 Device setup
2 PV 0.00 mbar 3 Analog Output 4.000 mA 4 PV LRV 0.00 mbar 5 PV URV 370.00 mbar
Figure 5-2: Device Dashboard - Device Revision 7 and DD Revision 9
SAVE
3051:PT 93207 Online
1 Overview
2 Configure 3 Service Tools
A check () indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 5-1: Fast Key Sequences-Traditional Interface (Device Revision 6 or 7 and DD Revision 7)
Function Fast Key sequence
Alarm Level Configuration 1, 4, 2, 7, 7
Alarm and Saturation
Levels
1, 4, 2, 7
Quick Start Guide December 2018
22 Rosemount 3051S
Table 5-1: Fast Key Sequences-Traditional Interface (Device Revision 6 or 7 and DD Revision 7) (continued)
Function Fast Key sequence
Analog Output Alarm
Direction
1, 4, 2, 7, 6
Analog Output Trim 1, 2, 3, 2
Burst Mode On/Off 1, 4, 3, 3, 3
Burst Options 1, 4, 3, 3, 4
Damping 1, 3, 6
Date 1, 3, 4, 1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4–
20 mA Output)
1, 2, 3, 2, 1
Field Device Information 1, 4, 4, 1
LCD Display Configuration 1, 3, 7
Loop Test 1, 2, 2
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Number of Requested
Preambles
1, 4, 3, 3, 2
Pressure Alert
Configuration
1, 4, 3, 5, 3
Poll Address 1, 4, 3, 3, 1
Poll a Multidropped
Transmitter
Left Arrow, 3, 1, 1
Remapping 1, 4, 3, 6
Rerange- Keypad Input 1, 2, 3, 1, 1
Saturation Level
Configuration
1, 4, 2, 7, 8
Scaled D/A Trim (4–20 mA
Output)
1, 2, 3, 2, 2
Scaled Variable
Configuration
1, 4, 3, 4, 7
Self Test (Transmitter) 1, 2, 1, 1
Sensor Information 1, 4, 4, 2
December 2018 Quick Start Guide
Quick Start Guide 23
Table 5-1: Fast Key Sequences-Traditional Interface (Device Revision 6 or 7 and DD Revision 7) (continued)
Function Fast Key sequence
Sensor Temperature 1, 1, 4
Sensor Trim 1, 2, 3, 3
Sensor Trim Points 1, 2, 3, 3, 5
Status 1, 2, 1, 2
Tag 1, 3, 1
Temperature Alert
Configuration
1, 4, 3, 5, 4
Transfer Function (Setting
Output Type)
1, 3, 5
Transmitter Security (Write
Protect)
1, 3, 4, 5
Units (Process Variable) 1, 3, 2
Upper Sensor Trim 1, 2, 3, 3, 3
Zero Trim 1, 2, 3, 3, 1
Table 5-2: Fast Key Sequences-Device Dashboard (Device Revision 7 and DD Revision 9)
Function Fast Key sequence
Alarm and Saturation
Levels
2, 2, 1, 7
Burst Mode Control 2, 2, 4, 2
Burst Option 2, 2, 4, 3
Custom Display
Configuration
2, 1, 3
Damping 2, 2, 1, 5
Date 2, 2, 5, 4
Descriptor 2, 2, 5, 5
Digital to Analog Trim (4–
20 mA Output)
3, 4, 2
Disable Zero & Span
Adjustment
2, 2, 7, 2
Rerange with Keypad 2, 2, 1, 3, 1
Quick Start Guide December 2018
24 Rosemount 3051S
Table 5-2: Fast Key Sequences-Device Dashboard (Device Revision 7 and DD Revision 9) (continued)
Function Fast Key sequence
Loop Test 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2
Message 2, 2, 5, 6
Range Values 2, 2, 1, 3
Scaled D/A Trim (4–20 mA
Output)
3, 4, 2
Sensor Temperature/Trend
(3051S)
3, 3, 3
Tag 2, 2, 5, 1
Transfer Function 2, 2, 1, 4
Transmitter Security (Write
Protect)
2, 2, 7, 1
Units 2, 2, 1, 2
Upper Sensor Trim 3, 4, 1, 1
Zero Trim 3, 4, 1, 3
December 2018 Quick Start Guide
Quick Start Guide 25
6 Trim the transmitter
Transmitters are shipped fully calibrated per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit).
6.1 Zero trim
Prerequisites
Choose your trim procedure
1. Analog zero trim - sets the analog output to 4 mA. a. Also referred to as a "rerange", it sets the lower value range
(LRV) equal to the measured pressure.
b. The display and digital HART output remains unchanged.
2. Digital zero trim - recalibrates the sensor zero. a. The LRV is unaffected. The pressure value will be zero (on
display and HART output). 4 mA point may not be at zero.
b. The transmitter must be within 3 percent of URL from factory
calibrated zero pressure in order to calibrate the zero function.
6.1.1 Use the Field Communicator
Procedure
1. Equalize or vent the transmitter and connect Field Communicator.
2. At the menu, input the Fast Key sequence (refer to Field
Communicator user interface).
3. Follow the commands to perform a zero trim.
6.1.2 Use the transmitter zero adjustment button
Procedure
To perform an analog zero trim using the tansmitter buttons push and hold the zero adjustment button for at least two seconds but no longer than 10 seconds.
Quick Start Guide December 2018
26 Rosemount 3051S
Figure 6-1: Transmitter Adjustment Buttons (Plantweb Housing)
A
B
A. Zero B. Span
Figure 6-2: Transmitter Adjustment Buttons (Junction Box Housing)
A B
A. Zero B. Span
December 2018 Quick Start Guide
Quick Start Guide 27
7 Safety instrumented systems installation
For safety certified installations, refer to the Rosemount 3051S Reference
Manual for installation procedure and system requirements.
Quick Start Guide December 2018
28 Rosemount 3051S
8 Rosemount 3051S/3051SFx/3051S-ERS Product
Certifications
Rev 2.2
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Installing Equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
8.1 USA
8.1.1 E5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
FM16US0090
Standards
FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3616 ­2011, FM Class 3810 - 2005, ANSI/NEMA 250 - 2003
Markings
XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(– 50 °C ≤ Ta ≤ +85 °C); Factory Sealed; Type 4X
8.1.2 I5 US Intrinsic Safety (IS) and Nonincendive (NI)
Certificate
FM16US0089X
Standards
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 ­2004, FM Class 3810 - 2005, NEMA® 250 - 2003
Markings
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +70 °C) [HART]; T4(–50 °C ≤ Ta ≤ +60 °C) [Fieldbus]; when connected per Rosemount drawing 03151-1006; Type 4X
December 2018 Quick Start Guide
Quick Start Guide 29
Special Condition for Safe Use:
1. The Model 3051S/3051S-ERS Pressure Transmitter contains aluminum
and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03151-1006.
8.1.3 IE US FISCO Intrinsically Safe
Certificate
FM16US0089X
Standards
FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 ­2004, FM Class 3810 - 2005, NEMA 250 - 2003
Markings
IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); when connected per Rosemount drawing 03151-1006; Type 4X
Special Condition for Safe Use:
1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains
aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
8.2
Canada
8.2.1 E6 Canada Explosionproof, Dust-Ignitionproof, and Division 2
Certificate
1143113
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 213-M1987, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings
Explosionproof Class I, Division 1, Groups B, C, D; Dust­Ignitionproof Class II, Division 1, Groups E, F, G; Class III; suitable for Class I, Zone 1, Group IIB+H2, T5; suitable for Class I, Division 2, Groups A, B, C, D; suitable for Class I, Zone 2, Group IIC, T5; when connected per Rosemount drawing 03151-1013; Type 4X
8.2.2 I6 Canada Intrinsically Safe
Certificate
1143113
Quick Start Guide December 2018
30 Rosemount 3051S
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA
12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings
Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X
8.2.3 IF Canada FISCO
Certificate
1143113
Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 157-92, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No. 60529:05
Markings
FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D; suitable for Class 1, Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1016 [3051S] 03151-1313 [ERS]; Type 4X
8.3 Europe
8.3.1 E1 ATEX Flameproof
Certificate
KEMA 00ATEX2143X
Standards
EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-26:2015
Markings
II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/
T4(–60 °C ≤ Ta ≤ +80 °C)
Table 8-1: Process Temperature
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between Category 1 (process connection) and Category 2 (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the
December 2018 Quick Start Guide
Quick Start Guide 31
environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
8.3.2 I1 ATEX Intrinsic Safety
Certificate
BAS01ATEX1303X
Standards
EN 60079-0: 2012+A11:2013, EN 60079-11: 2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Table 8-2: Input Parameters
U
i
I
i
P
i
C
i
L
i
SuperModule 30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 µH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 µH
3051SAL…M7, M8, or M9 3051SAM…M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 µH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500V test as defined in Clause 6.3.13 f EN 60079-11:2012. This must be taken into account during installation.
Quick Start Guide December 2018
32 Rosemount 3051S
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN
60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
8.3.3 IA ATEX FISCO
Certificate
BAS01ATEX1303X
Standards
EN 60079-0: 2012+A11:2013, EN 60079-11: 2012
Markings
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Table 8-3: Input Parameters
Parameter FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN
60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
8.3.4 ND ATEX Dust
Certificate
BAS01ATEX1374X
Standards
EN 60079-0: 2012+A11:2013, EN 60079-31: 2009
Markings
II 1 D Ex ta IIIC T105 °C T
500
95 °C Da, (–20 °C ≤ T a ≤ +85 °C),
V
max
= 42.4 V
December 2018 Quick Start Guide
Quick Start Guide 33
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.
4. The SuperModule(s) must be securely screwed in place to maintain the ingress protection of the enclosure(s).
8.3.5 N1 ATEX Type n
Certificate
BAS01ATEX3304X
Standards
EN 60079-0: 2012+A11:2013, EN 60079-15: 2010
Markings
II 3 G Ex nA IIC T5 Gc, (–40 °C ≤ Ta ≤ +85 °C), V
max
= 45 V
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.
Note
RTD Assembly is not included with the 3051SFx Type n Approval.
8.4
International
8.4.1 E7 IECEx Flameproof and Dust
Certificate
IECEx KEM 08.0010X (Flameproof)
Standards
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014
Markings
Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C)
Table 8-4: Process Temperature
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Quick Start Guide December 2018
34 Rosemount 3051S
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic buildup on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a temperature of 5 °C greater than maximum specified temperature for location where installed.
Certificate IECEx BAS 09.0014X (Dust)
Standards IEC 60079-0:2011, IEC 60079-31:2008
Markings Ex ta IIIC T105 °C T50095 °C Da, (–20 °C ≤ Ta ≤ +85 °C),
V
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.
4. The 3051S- SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure.
8.4.2 I7 IECEx Intrinsic Safety
Certificate
IECEx BAS 04.0017X
Standards
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
December 2018 Quick Start Guide
Quick Start Guide 35
Table 8-5: Input Parameters
U
i
I
i
P
i
C
i
L
i
SuperModule 30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 µH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 µH
3051SAL…M7, M8, or M9 3051SAM…M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 µH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN
60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
8.4.3 I7 IECEx Intrinsic Safety - Group I - Mining (I7 with Special A0259)
Certificate
IECEx TSA 14.0019X
Standards
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings
Ex ia I Ma (–60 °C ≤ Ta ≤ +70 °C)
Table 8-6: Input Parameters
U
i
I
i
P
i
C
i
L
i
SuperModule 30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
Quick Start Guide December 2018
36 Rosemount 3051S
Table 8-6: Input Parameters (continued)
U
i
I
i
P
i
C
i
L
i
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 µH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 µH
3051SAL…M7, M8, or M9 3051SAM…M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 µH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.
8.4.4 IG IECEx FISCO
Certificate
IECEx BAS 04.0017X
Standards
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings
Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
Table 8-7: Input Parameters
Parameter FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
December 2018 Quick Start Guide
Quick Start Guide 37
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN
60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
8.4.5 IG IECEx Intrinsic Safety - Group I - Mining (IG with Special A0259)
Certificate
IECEx TSA 04.0019X
Standards
IEC 60079-0: 2011, IEC 60079-11: 2011
Markings
FISCO FIELD DEVICE Ex ia I Ma , (–60 °C ≤ Ta ≤ +70 °C)
Table 8-8: Input Parameters
Parameter FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by Clause 6.3.13 of IEC60079-11. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.
8.4.6 N7 IECEx Type n
Certificate
IECEx BAS 04.0018X
Standards
IEC 60079-0: 2011, IEC 60079-15: 2010
Quick Start Guide December 2018
38 Rosemount 3051S
Markings
Ex nA IIC T5 Gc,(–40 °C ≤ Ta ≤ +85 °C)
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the equipment.
8.5 Brazil
8.5.1 E2 INMETRO Flameproof
Certificate
UL-BR15.0393X
Standards
ABNT NBR IEC 60079-0:2008 + Corrigendum 1:2011, ABNT NBR IEC 60079-1:2009 + Corrigendum 1:2011, ABNT NBR IEC 60079-26:2008 + Corrigendum 1: 2008
Markings
Ex db IIC T* Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T5/T4(–60 °C ≤ Ta ≤ +80 °C), IP66
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm less than 1mm thick that forms a boundary between zone 0 (process connection) and zone 1 (all other parts of the equipment).The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic buildup on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
8.5.2 I2/IB INMETRO Intrinsic Safety/FISCO
Certificate
UL-BR 15.0392X
Standards
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013
Markings
Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +70 °C), IP66
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic charge buildup, it must not be rubbed or cleaned with solvents or a dry cloth.
December 2018 Quick Start Guide
Quick Start Guide 39
2. The Model 701PBKKF Power Module may be replaced in a hazardous area. The Power Module has a surface resistivity greater than 1 GΩ and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge buildup.
3. The 3051S enclosure may be made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in areas that requires EPL Ga.
Table 8-9: Input Parameters
U
i
I
i
P
i
C
i
L
i
SuperModule 30 V 300 mA 1.0 W 30 nF 0
3051S...A; 3051SF…A; 3051SAL…C
30 V 300 mA 1.0 W 12 nF 0
3051S…F; 3051SF…F 30 V 300 mA 1.3 W 0 0
3051S…F…IB; 3051SF…F…IB
17.5 V 380mA 5.32W 0 0
3051S …A…M7, M8, or M9; 3051SF …A…M7, M8, or M9;
3051SAL…C… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 60 µH
3051SAL or 3051SAM 30 V 300 mA 1.0 W 12 nF 33 µH
3051SAL… M7, M8, or M9 3051SAM… M7, M8, or M9
30 V 300 mA 1.0 W 12 nF 93 µH
RTD Option for 3051SF 5 V 500 mA 0.63 W N/A N/A
8.6 China
8.6.1 E3 China Flameproof and Dust Ignition-proof
Certificate
3051S: GYJ16.1249X 3051SFx: GYJ16.1466X 3051S-ERS: GJY15.1406X
Standards
3051S: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013
3051SFx: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB 12476.5-2013
3051S-ERS: GB3836.1-2010, GB3836.2-2010, GB3836.20-2010
Quick Start Guide December 2018
40 Rosemount 3051S
Markings
3051S: Ex d IIC T6…T4; Ex tD A20 T105 °C T
500
95 °C; IP66
3051SFx: Ex d IIC T4~T6 Ga/Gb; Ex tD A20 IP66 T105 °CT
500
95
°C; IP66 3051S-ERS: Ex d IIC T4~T6 Ga/Gb
8.6.2 I3 China Intrinsic Safety
Certificate
3051S: GYJ16.1250X[Mfg USA, China, Singapore] 3051SFx: GYJ16.1465X [Mfg USA, China, Singapore] 3051S-ERS: GYJ16.1248X [Mfg USA, China, Singapore]
Standards
3051S: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 3051SFx: GB3836.1/4-2010, GB3836.20-2010,
GB12476.1-2013, GB12476.5-2013 3051S-ERS: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Markings
3051S: Ex ia IIC T4 Ga 3051SFx: Ex ia IIC T4 Ga, Ex tD A20 IP66 T105 °CT
500
95 °C
3051S-ERS: Ex ia IIC T4 Ga
8.6.3 N3 China Type n
Certificate
3051S, 3051SHP: GYJ17.1354X 3051SFX: GYJ17.1355X
Markings
Ex nA IIC T5 Gc
8.7 EAC - Belarus, Kazakhstan, Russia
8.7.1 EM Technical Regulation Customs Union (EAC) Flameproof and Dust Ignition-proof
Certificate
RU C-US.AA87.B.00378
Markings
Ga/Gb Ex d IIC T6…T4 X
Ex tb IIIC T105 °C T
500
95 °C Db X
Ex ta IIIC T105 °C T
500
95 °C Da X
8.7.2 IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate
RU C-US.AA87.B.00378
Markings
0Ex ia IIC T4 Ga X
December 2018 Quick Start Guide
Quick Start Guide 41
8.7.3 IN Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate:
RU C-US.AA87.B.00378
Markings:
0Ex ia IIC T4 Ga X
8.8 Japan
8.8.1 E4 Japan Flameproof
Certificate
TC15682, TC15683, TC15684, TC15685, TC15686, TC15687, TC15688, TC15689, TC15690, TC17099, TC17100, TC17101, TC17102, TC18876
3051ERS: TC20215, TC20216, TC20217, TC20218, TC20219, TC20220, TC20221
Markings
Ex d IIC T6 Ga/Gb
Temperature class Ambient temperature Process temperature
T6 -40 °C to +70 °C -60 °C to +70 °C
Special Conditions for Safe Use:
1. This device contains a thin wall diaphragm less than 1mm thickness that forms a boundary between EPL Ga (process connection) and EPL Gb (all other parts of the equipment). The model code and datasheet are to be consulted for details of the diaphragm material. Installation, maintenance, and use shall consider the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions fr installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic discharge. Avoid installations that could cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
8.9
Republic of Korea
8.9.1 EP Republic of Korea Flameproof
Certificate
12-KB4BO-0180X [Mfg USA], 11-KB4BO-0068X [Mfg Singapore]
Markings
Ex d IIC T6...T4
Quick Start Guide December 2018
42 Rosemount 3051S
8.9.2 IP Republic of Korea Intrinsic Safety
Certificate
12-KB4BO-0202X [HART - Mfg USA],12-KB4BO-0204X [Fieldbus
- Mfg USA], 12-KB4BO-0203X [HART - Mfg Singapore], 13­KB4BO-0296X [Fieldbus - Mfg Singapore]
Markings
Ex ia IIC T4
8.10 Combinations
K1
Combination of E1, I1, N1, and ND
K2
Combination of E2 and I2
K5
Combination of E5 and I5
K6
Combination of E6 and I6
K7
Combination of E7, I7, and N7
KA
Combination of E1, I1, E6, and I6
KB
Combination of E5, I5, E6, and I6
KC
Combination of E1, I1, E5, and I5
KD
Combination of E1, I1, E5, I5, E6, and I6
KG
Combination of IA, IE, IF, and IG
KM
Combination of EM and IM
KP
Combination of EP and IP
8.11 Additional Certifications
8.11.1 SBS American Bureau of Shipping (ABS) Type Approval
Certificate
17-RJ1679518-PDA
Intended Use
Measure gauge or absolute pressure of liquid, gas or vapor applications on ABS classed vessels, marine, and offshore installations.
8.11.2 SBV Bureau Veritas (BV) Type Approval
Certificate
31910 BV
Requirements
Bureau Veritas Rules for the Classification of Steel Ships
Application
Class Notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT­IMS.
December 2018 Quick Start Guide
Quick Start Guide 43
8.11.3 SDN Det Norske Veritas (DNV) Type Approval
Certificate
TAA00000K9
Intended Use
Det Norske Veritas' Rules for Classification of Ships, High Speed & Light Craft, and Det Norske Veritas' Offshore Standards
Application
Location classes
Type 3051S
Temperature D
Humidity B
Vibration A
EMC A
Enclosure D/IP66/IP68
8.11.4 SLL Lloyds Register (LR) Type Approval
Certificate
11/60002
Application
Environmental categories ENV1, ENV2, ENV3, and ENV5
8.11.5 D3 Custody Transfer - Measurement Canada Accuracy Approval [3051S Only]
Certificate
AG-0501, AV-2380C
Quick Start Guide December 2018
44 Rosemount 3051S
9 Rosemount 3051S Declaration of Conformity
December 2018 Quick Start Guide
Quick Start Guide 45
Quick Start Guide December 2018
46 Rosemount 3051S
December 2018 Quick Start Guide
Quick Start Guide 47
Quick Start Guide December 2018
48 Rosemount 3051S
10 China RoHS
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 3051S
List of Rosemount 3051S Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X O O O O O
༣փ㓴Ԧ
Housing
Assembly
X O O X O O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X O O X O O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
December 2018 Quick Start Guide
Quick Start Guide 49
Quick Start Guide December 2018
50 Rosemount 3051S
December 2018 Quick Start Guide
Quick Start Guide 51
*00825-0100-4801*
Quick Start Guide
00825-0100-4801, Rev. NB
December 2018
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©
2018 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
Loading...