Rosemount™ 3051S Series Scalable
Pressure, Flow, and Level Solution
with HART® Protocol
Reference Manual
March2024
™
Safety messages
WARNING
Read this manual before working with the product. For personal and system safety, and for optimum product
performance, ensure the contents are thoroughly understood before installing, using, or maintaining this product.
WARNING
Explosions could result in death or serious injury.
Do not remove the transmitter cover in explosive atmospheres when the circuit is live.
Fully engage both transmitter covers to meet explosion-proof requirements.
Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments in the segment
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations
certifications.
WARNING
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals.
WARNING
Process leaks could result in death or serious injury.
Install and tighten all four flange bolts before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
WARNING
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure
retaining capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’
equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental in protecting your system. Restrict
physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the
facility.
2
NOTICE
Improper assembly of manifolds to traditional flange can damage SuperModule™ Platform.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (also called bolt
hole) but must not contact sensor module housing.
SuperModule and electronics housing must have equivalent approval labeling in order to maintain hazardous
location approvals.
When upgrading, verify SuperModule and electronics housing certifications are equivalent. Differences in
temperature class ratings may exist, in which case the complete assembly takes the lowest of the individual
component temperature classes (for example, a T4/T5 rated electronics housing assembled to a T4 rated
SuperModule is a T4 rated transmitter.)
Severe changes in the electrical loop may inhibit HART® communication or the ability to reach alarm values.
Therefore, Emerson cannot absolutely warrant or guarantee that the correct failure alarm level (HIGH or LOW)
can be read by the host system at the time of annunciation.
NOTICE
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause
inaccurate readings.
For information on Rosemount nuclear-qualified products, contact Emerson.com/global.
A.2 Ordering Information, Specifications, and Drawings........................................................ 163
6Emerson.com/RosemountRosemount 3051S
Reference ManualIntroduction
00809-0100-4801March2024
1 Introduction
1.1 Models covered
The following transmitters and the Rosemount 300S Housing Kit are covered in this
manual:
The Rosemount 3051S provides a wide range of applications, and many of these different
applications have their own reference manuals. This manual covers the 3051S HART®,
Advanced Diagnostics, and Safety Instrumented Systems (SIS).
Kits are available for all models of 3051S Pressure Transmitters.
1.2
Product recycling/disposal
Consider recycling equipment and packaging.
Dispose of the product and packaging in accordance with local and national legislation.
8Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
2 Configuration
2.1 Overview
This section contains information on commissioning and tasks that should be performed
on the bench prior to installation.
Instructions for performing configuration functions are given for handheld communication
devices like the Field Communicator or asset management software like Emerson's
AMS Device Manager. For convenience, Field Communicator Fast Key sequences (where
supported) are labeled Fast Keys for each software function below the appropriate
headings.
2.1.1 Example software function
The Device Dashboard Fast Keys apply to Device Descriptor Revision 9 or newer. The HART
5 with Diagnostics Fast Keys apply to Device Descriptor Revision 1. The HART 7 Fast Keys
apply to Device Descriptor Revision 2. Contact Emerson or refer to previous reference
manuals for information on older revisions.
®
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys1, 2, 3, etc.
HART 7 Fast Keys1, 2, 3, etc.
2.2 Commissioning on the bench
Commissioning consists of testing the transmitter and verifying transmitter configuration
data. Rosemount™ 3051S Pressure Transmitters can be commissioned either before or after
installation. Commissioning the transmitter on the bench before installation using a Field
Communicator or AMS Device Manager ensures all transmitter components are in working
order.
Equipment required to commission on the bench includes a power supply, a milliamp
meter, and a Field Communicator or AMS Device Manager. Wire the equipment as
shown in Figure 2-1. Verify transmitter terminal voltage is between 10.5–42.4 Vdc. To
ensure successful communication, a resistance of at least 250 ohms must be present
between the Field Communicator loop connection and the power supply. Connect the
Field Communicator leads to the terminals labeled PWR/COMM on the terminal block.
(Connecting across the “TEST” terminals will prevent successful communication.)
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation. Refer to Wire the device.
When using a Field Communicator, any configuration changes made must be sent to
the transmitter by using the Send key. AMS Device Manager configuration changes are
implemented when the Apply button is selected.
1, 2, 3, etc.
2.2.1
Setting the loop to Manual
Whenever sending or requesting data that would disrupt the loop or change the output
of the transmitter, set the process application loop to Manual. The Field Communicator
or AMS Device Manager will prompt you to set the loop to manual when necessary.
9
A
B
ConfigurationReference Manual
March202400809-0100-4801
Acknowledging this prompt does not set the loop to Manual. The prompt is only a
reminder; set the loop to manual as a separate operation.
2.2.2 Wiring diagrams
Benchhook-up
Connect the bench equipment as shown in Figure 2-1, and turn on the Field Communicator
or log into AMS Device Manager. The Field Communicator or AMS Device Manager will
search for a HART®-compatible device and indicate when the connection is made. If the
Field Communicator or AMS Device Manager fail to connect, it indicates that no device was
found. If this occurs, refer to Troubleshooting.
Fieldhook-up
Figure 2-1 illustrates wiring loops for a field hook-up with a Field Communicator or AMS
Device Manager. The Field Communicator or AMS Device Manager may be connected
at “PWR/COMM” on the transmitter terminal block, across the load resistor, or at any
termination point in the signal loop. Signal point may be grounded at any point or left
ungrounded.
Figure 2-1: Typical wiring (4–20mA)
A. Power supply
B. RL ≥ 250Ω
2.3
Field Communicator
For convenience, Field Communicator Fast Key sequences are labeled Fast Keys for each
software function below the appropriate headings. The Device Dashboard Fast Keys apply
to Device Descriptor Revision 9 or newer. The HART® 5 with Diagnostics Fast Keys apply to
Device Descriptor Revision 1. The HART 7 Fast Keys apply to Device Descriptor Revision 2.
10Emerson.com/RosemountRosemount 3051S
SAVE
3051S DIAG: HDT 93207
Online
1 Overview
2 Configure
3 Service Tools
Reference ManualConfiguration
00809-0100-4801March2024
2.3.1 Field Communicator user interface
Figure 2-2: HART 5 with Diagnostics Dashboard
Note
The corresponding menu tree is shown in Figure 2-3. The Fast Key sequence can be viewed
on Device Dashboard Fast Key sequence.
11
Home
Overview
1 Device Status
2 Comm Status
3 Pressure
4 PV Loop Current
5 Pressure URV
6 Pressure LRV
7 Device Information
Device Information
1 Identification
2 Revisions
3 Material of Construction
4 RS Material of Construction
5 Analog Alarm
6 Security
Identification
1 Tag
2 Model
3 Transmitter S/N
4 Date
5 Description
6 Message
7 Model Number 1
8 Model Number 2
9 Model Number 3
1 Module Configuration
2 Sensor Range
3 Upper Sensor Limit
4 Lower Sensor Limit
5 Isolator Materials
6 Fill Fluid
7 Process Connection
8 Process Connection Material
9 O-Ring Material
10 Drain Vent Material
RS Material of Construction
1 # of Remote Seals
2 RS Seal Type
3 RS Fill Fluid
4 RS Isolator Material
Analog Alarm
1 Alarm Direction
2 High Alarm
3 High Saturation
4 Low Saturation
5 Low Alarm
Security
1 Write Protect Status
2 Local Zero/Span
1 Overview
2 Configure
3 Service Tools
ConfigurationReference Manual
March202400809-0100-4801
2.4 Field Communicator menu trees
Device Dashboard menu tree
Figure 2-3: Overview
12Emerson.com/RosemountRosemount 3051S
Home
1 Overview
2 Configure
3 Service Tools
1 Pressure Alert
2 Temperature Alert
Alert Setup
Configure
1 Guided Setup
2 Manual Setup
3 Alert Setup
Pressure Alert
1 Alert Mode
2 High Alert Value
3 Low Alert Value
Temperature Alert
1 Alert Mode
2 High Alert Value
3 Low Alert Value
Guided Setup
1 Basic Setup
2 Zero
3 Configure Display
4 Variable Mapping
5 Configure Alarm and Sat levels
6 Process Alerts
7 Scaled Variable
Manual Setup
1 Basic Setup
2 Scaled Variable
3 Display
4 HART
5 Device Information
6 Materials of Construction
7 Security
Basic Setup
1 Tag
2 Unit
3 Range Values
4 Transfer Function
5 Pressure Damping
6 Module Temperature Units
7 Configure Alarm and Sat Levels
8 Range by Applying Pressure
Scaled Variable
1 SV Data Points
2 SV Units
3 SV Transfer Function
4 SV Linear Offset
5 SV Config
Display
1 Pressure
2 Scaled Variable
3 Module Temperature
4 Percent of Range
1 Most Recent Status Event
2 View Other Status Events
3 Total Operating Time
4 Clear Log
Pressure Variable Logging
1 Pressure Variable Log
2 Time Outside Sensor Limits
3 Pressure
4 Total Operating Time
5 Reset All Pressure Events
Temperature Variable Logging
1 Temperature Variable Log
2 Time Outside Sensor Limits
3 Module Temperature
4 Total Operating Time
5 Reset All Temperature Events
Sensor Calibration
1 Upper Sensor Trim
2 Lower Sensor Trim
3 Zero
Range Values
1 Upper Range value (20 mA)
2 Lower Range Value (4 mA)
Current Measurement
1 Pressure
2 Damping
3 Transfer Function
Last Calibration Points
1 Upper
2 Lower
Sensor Limits
1 Upper
2 Lower
3 Minimum Span
SPM Status (cont.)
1 SPM Insufficient Variability
2 SPM Low Pressure Status
Most Recent Status Event
1 Event 1 - Time since
View Other Status Events
1 Event 2 - Time since
2 Event 3 - Time since
3 Event 4 - Time since
4 Event 5 - Time since
5 Event 6 - Time since
6 Event 7 - Time since
7 Event 8 - Time since
8 Event 9 - Time since
9 Event 10 - Time since
Pressure Variable Log
1 Minimum Pressure
2 Time Since Minimum Event
3 Reset Minimum
4 Maximum Pressure
5 Time Since Maximum Event
6 Reset Maximum
Time Outside Sensor Limits
1 Above Upper Sensor Limit
2 Below Lower Sensor Limit
3 Reset Time Since 1st Events
Temperature Variable Log
1 Minimum Temperature
2 Time Since Minimum Event
3 Reset Minimum
4 Maximum Temperature
5 Time Since Maximum Event
6 Reset Maximum
Time Outside Sensor Limits
1 Above Upper Sensor Limit
2 Below Lower Sensor Limit
3 Reset Time Since 1st Events
General
1 Tag
2 Model
3 Date
4 Descriptor
5 Message
6 Serial Number
Model Numbers
1 Model Number 1
2 Model Number 2
3 Model Number 3
1 Process Variables
2 Analog Output
3 Scaled Variable
4 Display Options
5 HART
6 Security
7 Device Information
Initial Setup
1 Basic Setup
2 Zero Trim
Diagnostics Setup
1 Statistical Process Monitoring
2 Power Advisory
3 Process Alerts
4 Service Alert
Optional Configuration
1 Configure Display
2 Configure Burst Mode
Basic Setup
1 Device Tagging
2 Units of Measure
3 Pressure Damping
4 Variable Mapping
5 Analog Output
6
Config Alarm & Saturation Levels
Display Options
1 Pressure: On or Off
2 Scaled Variable: On or Off
3 Module Temperature: On or Off
4 Percent of Range: On or Off
5 Standard Deviation: On or Off
6 Mean: On or Off
7 Coefficient of Variation: On or Off
Process Variables
1 Pressure Setup
2 Module Temperature Setup
Analog Output
1 Set Range Points
2 Set Range Points Manually
3 Sensor Limits
4 Readings
5 Alarm and Saturation Levels
Pressure Setup
1 Pressure
2 Units
3 Damping
4 Transfer Function
Module Temperature Setup
1 Module Temperature
2 Units
Set Range Points
1 PV Upper Range Value
2 PV Lower Range Value
3 Primary Variable
Set Range Points Manually
1 Range By Applying Pressure
Sensor Limits
1 Upper
2 Lower
3 Minimum Span
Readings
1 Analog Output
2 Percent of Range
Alarm and Saturation Levels
1 Alarm Direction
2 High Alarm
3 High Saturation
4 Low Saturation
5 Low Alarm
6 Config Alarm & Saturation Levels
Scaled Variable Setup
1 Scaled Variable
2 Units
3 Transfer Function
4 Linear Options*
5 Configure Scaled Variable
*If Square Root is selected for Transfer Function,
"Square Root Options"
Linear Options
1 Offset
Square Root Options
1 Cutoff Mode
2 Low Flow Cutoff
Display
1 Display Options
Display Options
1 Pressure: On or Off
2 Scaled Variable: On or Off
3 Module Temperature: On or Off
4 Percent of Range: On or Off
5 Standard Deviation: On or Off
6 Mean: On or Off
7 Coefficient of Variation: On or Off
HART
1 Variable Mapping
2 Burst Mode Configuration
3 Communication Settings
1 Upper Sensor Trim
2 Lower Sensor Trim
3 Zero
4 Last Calibration Points
5 Sensor Limits
Last Calibration Points
1 Upper Calibration Point
2 Lower Calibration Point
Sensor Limits
1 Upper
2 Lower
3 Minimum Span
ConfigurationReference Manual
March202400809-0100-4801
Figure 2-9: Service Tools
18Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
HART 7 menu trees
Figure 2-10: Overview
19
ConfigurationReference Manual
March202400809-0100-4801
Figure 2-11: Configure (Guided Setup and Manual Setup)
20Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
Figure 2-12: Configure (Alert Setup)
21
ConfigurationReference Manual
March202400809-0100-4801
Figure 2-13: Service Tools
Device Dashboard Fast Key sequence
The following menu indicates Fast Key sequences for common functions. A check (✓)
indicates the basic configuration parameters. At minimum, these parameters should be
verified as part of the configuration and startup procedure.
FunctionFast Key sequence
Alarm and Saturation Levels1, 4, 5
Alarm Level Configuration1, 7, 5
Analog Output Alarm Direction1, 7, 5, 1
Burst Mode Control2, 2, 4, 3
Burst Option2, 2, 4, 4
Custom Display Configuration2, 1, 3
✓Damping2, 2, 1, 5
Date2, 2, 5, 4
22Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
FunctionFast Key sequence
Descriptor2, 2, 5, 5
Digital to Analog Trim (4 - 20 mA Output)3, 4, 2
Disable Zero & Span Adjustment2, 2, 7, 2
Field Device Information1, 7
LCD Display Configuration2, 2, 3
Loop Test3, 5, 1
Lower Sensor Trim3, 4, 1, 2
Message2, 2, 5, 6
Module Temperature/Trend3, 3, 3
Poll Address1, 2, 2
Pressure Alert Configuration2, 3, 1
Range Values2, 2, 1, 3
Re-mapping2, 2, 4, 1
Rerange - Keypad Input1, 5
Rerange with Keypad2, 2, 1, 3
Saturation Level Configuration2, 2, 1, 7
Scaled D/A Trim (4–20 mA Output)3, 4, 2
Scaled Variable Configuration2, 2, 2
Sensor Information (Materials of Construction)1, 7, 3
Sensor Trim3, 4, 1
Sensor Trim Points3, 4, 1, 4
✓Tag2, 2, 5, 1
Temperature Alert Configuration2, 3, 2
✓Transfer Function (Setting Output Type)2, 2, 1, 4
Transmitter Security (Write Protect)2, 2, 7, 1
✓Units (Process Variable)2, 2, 1, 2
Upper Sensor Trim3, 4, 1, 1
Zero Trim3, 4, 1, 3
HART 5 with Diagnostics Fast Key sequence
The following menu indicates Fast Key sequences for common functions. A check (✓)
indicates the basic configuration parameters. At minimum, these parameters should be
verified as part of the configuration and startup procedure.
FunctionFast Key sequence
Alarm and Saturation Levels2, 2, 2, 5
Alarm Level Configuration2, 1, 1, 1, 6
Analog Output Alarm Direction2, 2, 2, 5, 5, 1
Burst Mode On/Off2, 2, 5, 2, 1
23
ConfigurationReference Manual
March202400809-0100-4801
FunctionFast Key sequence
Burst Option2, 2, 5, 2, 2
Damping2, 2, 1, 1, 3
Date2, 2, 7, 1, 3
Descriptor2, 2, 7, 1, 4
Digital to Analog Trim (4–20 mA Output)3, 4, 1, 2, 3
Field Device Information1, 3, 5
LCD Display Configuration2, 2, 4
Loop Test3, 5
Lower Sensor Trim3, 4, 1, 1, 1, 2
Message2, 2, 7, 1, 5
Module Temperature2, 2, 1, 2
Poll Address2, 2, 5, 3, 1
Pressure Alert Configuration2, 3, 4, 1, 3
Range Values3, 4, 1, 1, 2
Re-mapping2, 2, 5, 1
Rerange - Keypad Input2, 2, 2, 1
Rerange with Pressure Source2, 2, 2, 2
Saturation Level Configuration2, 1, 1, 1, 6
Scaled Variable Configuration2, 2, 3, 5
Sensor Information1, 3, 5, 4, 1
Sensor Trim Points1, 3, 1, 1, 4
✓Tag2, 2, 7, 1, 1
Temperature Alert Configuration2, 3, 4, 2, 3
✓Transfer Function (Setting Output Type)2, 2, 1, 1, 4
Digital to Analog Trim (4–20 mA Output)3, 4, 1, 2, 3, 1
Disable Zero & Span Adjustment2, 2, 6, 4
Field Device Information1, 7
LCD Display Configuration2, 2, 4
Loop Test3, 5, 1
Lower Sensor Trim3, 4, 1, 2
Message2, 2, 7, 1, 6
Module Temperature/Trend3, 3, 2
Poll Address2, 2, 5, 2, 1
Pressure Alert Configuration2, 3, 4, 1
Range Values2, 2, 2, 2
Re-mapping2, 2, 5, 1
Rerange - Keypad Input2, 2, 2, 2, 1
Rerange with Keypad2, 2, 2, 3
Saturation Level Configuration2, 2, 2, 5, 6
Scaled D/A Trim (4–20 mA Output)3, 4, 1, 2, 3, 2
Scaled Variable Configuration2, 2, 3, 7
Sensor Information (Materials of Construction)1, 7, 3, 1
Sensor Trim3, 4, 1, 1, 1
Sensor Trim Points3, 4, 1, 1, 4
Tag2, 2, 7, 1, 1
Temperature Alert Configuration2, 3, 4, 2
Transfer Function (Setting Output Type)2, 2, 3, 3
Transmitter Security (Write Protect)1, 7, 4, 6, 1
Units (Process Variable)2, 2, 1, 1, 2
Upper Sensor Trim3, 4, 1, 1
Zero Trim3, 4, 1, 3
2.5 Check output
Before performing other transmitter online operations, review the digital output
parameters to ensure that the transmitter is operating properly and is configured to the
appropriate process variables.
2.5.1
Process variables
The process variables for the Rosemount 3051S provide transmitter output, and are
continuously updated. The pressure reading in both engineering units and percent of
25
ConfigurationReference Manual
March202400809-0100-4801
range will continue to track with pressures outside of the defined range from the lower to
the upper range limit of the SuperModule™.
View process variables on the Field Communicator
Table 2-1: Field Communicator Fast Key sequences
Device Dashboard Fast Keys3, 2
HART 5 with Diagnostics Fast Keys3, 2, 1
HART 7 Fast Keys3, 2, 2
Enter the Fast Key sequence process variables to view the process variables.
Note
Regardless of the range points, the 3051S will measure and report all readings within
the digital limits of the sensor. For example, if the 4and 20mA points are set to
0and10inH2O, and the transmitter detects a pressure of 25inH2O, it digitally outputs
the 25inH2O reading and a 250 percent of span reading.
View Process Variables on the AMS Device Manager
Procedure
1. Right click on the device and select Overview from the menu.
2. Select All Variables to display the primary, secondary, tertiary, and quaternary
variables.
2.5.2 Module temperature
The Rosemount 3051S contains a temperature sensor near the pressure sensor in the
SuperModule™. When reading this temperature, keep in mind module temperature is not a
process temperature reading.
View the Module Temperature reading on the Field
Communicator
Table 2-2: Field Communicator Fast Key Sequences
Device Dashboard Fast Keys3, 2, 3
HART 5 with Diagnostics Fast Keys3, 2, 1, 2
HART 7 Fast Keys3, 2, 2, 2
Enter the Fast Key sequence Module Temperature to view the module temperature
reading.
View the Module Temperature reading on the AMS Device
Manager
Procedure
1. Right click on the device and select Overview from the menu.
2. Click All Variables.
26Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
2.6 Basic setup
2.6.1 Set Process Variable Units
The PV Unit command sets the process variable units to allow you to monitor your process
using the appropriate units of measure.
Set Process Variable Units on the AMS Device Manager
Procedure
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. Select the Process Variables tab.
4. Click the Unit drop-down menu to select units.
2.6.2 Set output (transfer function)
The Rosemount 3051S has two output settings: linear and square root. Activate the square
root output option to make analog output proportional to flow. As input approaches zero,
the pressure transmitter automatically switches to linear output in order to ensure a more
smooth, stable output near zero (see Figure 2-14 ).
From 0 to 0.6 percent of the ranged pressure input, the slope of the curve is unity (y =
x). This allows accurate calibration near zero. Greater slopes would cause large changes in
output (for small changes at input). From 0.6 to 0.8 percent, curve slope equals 42 (y = 42x)
to achieve continuous transition from linear to square root at the transition point.
Note
If low flow cutoff configuration is desired, use Scaled variable configuration to configure
square root and Remapping to map the scaled variable as the primary variable.
Note
If scaled variable is mapped as the primary variable and square root mode is selected,
ensure that transfer function is set to linear. Do not set the transfer function to square root
if square root mode is selected for the primary variable, as this would cause the square
root function to be performed twice.
Set Output on the Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys2, 2, 1, 1, 4
HART 7 Fast Keys2, 2, 1, 1, 4
Procedure
1. Enter the Fast Key sequence for Set Output (Transfer Function).
2. Select Send.
2, 2, 1, 4
Set the Output on the AMS Device Manager
Procedure
1. Right click on the device and select Configure from the menu.
27
ConfigurationReference Manual
March202400809-0100-4801
2. Select Manual Setup from the left window pane.
3. Select the Process Variables tab.
4. Select the Transfer Function drop-down menu to select output.
Figure 2-14: Square Root Output Transition Point
A. Full scale output (mA DC)
B. Full scale flow (%)
C. Square root curve
D. Transition point
E. Slope = 42
F. Slope = 1
G. Pressure input
H. Sq. root curve
I. Transition point
J. Linear section
Note
For a flow turn down of greater than 10:1, it is not recommended to perform
a square root extraction in the transmitter. Instead, perform the square root
extraction in the system. Alternatively, you can configure scaled variable for square
root output. This configuration allows you to select a low flow cutoff value, which
will work best for the application. If low flow cutoff configuration is desired, use
Scaled variable configuration to configure square root and Remapping to map
scaled variable as the primary variable.
2.6.3 Rerange
Range Values command sets each of the lower and upper range analog values (4 and
The
20 mA points) to a pressure. The lower range point represents 0 percent of range and
the upper range point represents 100 percent of range. In practice, the transmitter range
values may be changed as often as necessary to reflect changing process requirements.
For a complete listing of range and sensor limits, refer to the Specifications section of the
Rosemount 3051S Series of Instrumentation Product Data Sheet.
28Emerson.com/RosemountRosemount 3051S
Reference ManualConfiguration
00809-0100-4801March2024
Note
Transmitters are shipped from Emerson fully calibrated per request or by the factory
default of full scale (zero to upper range limit.)
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
•Rerange with a Field Communicator or AMS Device Manager only.
•Rerange with a pressure input source and a Field Communicator or AMS Device
Manager.
•Rerange with a pressure input source and the local zero and span buttons (option D1).
Note
If the transmitter security jumper/switch is ON, adjustments to the zero and span cannot
be made. Refer to Wiring the device for security information.
Rerange with a Field Communicator or AMS Device Manager
only
The easiest and most popular way to rerange is to use the Field Communicator only. This
method changes the range values of the analog 4 and 20 mA points independently without
a pressure input. This means that when you change either the 4 or 20 mA setting, you also
change the span.
An example for the 4–20 mA HART output:
If the transmitter is ranged so that
4 mA = 0 inH2O, and 20 mA = 100 inH2O,
and you change the 4 mA setting to 50 inH2O using the communicator only, the new
settings are:
4 mA = 50 inH2O, and 20 mA = 100.
Note that the span was also changed from 100 inH2O to 50 inH2O, while the 20 mA setpoint
remained at 100 inH2O.
To obtain reverse output, simply set the 4 mA point at a greater numerical value than the
20 mA point. Using the above example, setting the 4 mA point at 100 inH2O and the 20 mA
point at 0 inH2O will result in reverse output.
Rerange on Field Communicators
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys2, 2, 2, 1
HART 7 Fast Keys2, 2, 2, 4
From the HOME screen, enter the Fast Key sequence Rerange with a Field CommunicatorOnly.
Procedure
1. From Keypad Input, select 2 and use the keypad to enter lower range value.
2. From Keypad Input, select 1 and use the keypad to enter upper range value.
3. To complete reranging the transmitter, select Send.
1, 5
29
ConfigurationReference Manual
March202400809-0100-4801
Rerange on AMS Device Manager
Procedure
1. Right click on the device and select Configure from the menu.
2. Select Manual Setup from the left window pane.
3. In the Analog Output tab, locate the Configuration box and perform the following
procedure:
a) Enter the lower range value (LRV) and the upper range value (URV) in the
fields provided.
b) Select Send.
c) After carefully reading the warning provided, select Yes.
Rerange with a Pressure Input Source and a Field
Communicator or AMS Device Manager
Reranging using the Field Communicator and applied pressure is a way of reranging the
transmitter when specific 4 and 20mA points are not calculated.
Note
The span is maintained when the 4 mA point is set. The span changes when the 20 mA
point is set. If the lower range point is set to a value that causes the upper range point to
exceed the sensor limit, the upper range point is automatically set to the sensor limit, and
the span is adjusted accordingly.
Rerange with a Pressure Input Source and Field Communicator
Device Dashboard Fast Keys
HART 5 with Diagnostics Fast Keys2, 2, 2, 2, 1
HART 7 Fast Keys2, 2, 2, 3
From the HOME screen, enter the Fast Key sequence Rerange with a Pressure InputSource and a Field Communicator or AMS Device Manager. Follow the on-screen
instructions.
2, 2, 1, 8
Rerange with a Pressure Input Source and AMS Device Manager
Procedure
1. Right click on the device, select Calibrate, then Apply Values from the menu.
2. After the control loop is set to manual, select Next.
3. From the Apply Values menu, follow the online instructions to configure lower and
upper range values.
4. Select Exit to leave the Apply Values screen.
5. Select Next to acknowledge the loop can be returned to automatic control.
6. Select Finish to acknowledge the method is complete.
Rerange with a Pressure Input Source and the local zero and
span buttons (option D1)
Reranging using the local zero and span adjustments and a pressure source is a way
of reranging the transmitter when specific 4 and 20 mA points are not known and a
communicator is not available.
30Emerson.com/RosemountRosemount 3051S
Loading...
+ 134 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.