This installation guide provides basic guidelines for Rosemount™ 3051P
Transmitters. It does not provide instructions for configuration, diagnostics,
maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or
intrinsically safe (I.S.) installations. Refer to the Rosemount 3051P Reference
Manual for more instruction. This manual is also available electronically on
Emerson.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international
standards, codes, and practices. Review the approvals section of the
Rosemount 3051P Reference Manual for any restrictions associated with
a safe installation.
Do not remove the transmitter cover in explosive atmospheres when the
circuit is live.
Process leaks could result in death or serious injury.
To avoid process leaks, only use the O-ring designed to seal with the
corresponding flange adapter.
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing
enclosure use a ½–14 NPT form. Only use plugs, adapters, glands, or
conduit with a compatible thread form when closing these entries.
Physical access
Unauthorized personnel may potentially cause significant damage to
and/or misconfiguration of end users’ equipment. This could be
intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and
fundamental to protecting your system. Restrict physical access by
unauthorized personnel to protect end users’ assets. This is true for all
systems used within the facility.
Quick Start Guide3
Quick Start GuideMay 2019
2System readiness
2.1Confirm HART revision capability
• If using HART® based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7. This
transmitter can be configured for either HART Revision 5 or 7.
• For instructions on how to change the HART revision of your transmitter,
see Switch HART revision mode.
2.2Confirm correct device driver
Procedure
1. Verify the latest Device Driver (DD/DTM™) is loaded on your systems
to ensure proper communications.
2. Reference Emerson.com or FieldCommGroup.org for the lated DD.
3. Select desired product and download the DD.
a) Reference Table 1, for the correct DD.
Table 2-1: Device Revisions and Files
Identify deviceFind device driver
Software
release
date
August
2016
(1) NAMUR revision is located on the hardware tag of the device. Differences in level 3 changes,
(2) HART software revision can be read using a HART capable configuration tool. Value shown
(3) Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is designed
4Emerson.com/Rosemount
NAMUR
hardware
revision
(1)
1.1.xx1.0.xx03710Rosemount
signified above by xx, represent minor product changes as defined per NE53. Compatibility
and functionality are preserved and product can be used interchangeably.
is minimum revision that could correspond to NAMUR revisions.
to enable legacy device driver revisions to continue to communicate with new HART devices.
To access new functionality, the new device driver must be downloaded. It is recommended
to download new device driver files to ensure full functionality.
NAMUR
software
revision
(1)
HART
software
revision
(2)
®
files
HART
universal
revision
59
Device
revision
(3)
Review
instructions
00809-0100
-4007
3051P Inline Pressure
Transmitter
with HART
Protocol
Reference
Manual
Review
functionality
Changes to
software
™
(4)
(4)
May 2019Quick Start Guide
(4) HART Revision 5 and 7 selectable, Local Operator Interface (LOI), scaled variable,
Mount directly to the impulse line without using an additional mounting
bracket or mount directly to a wall, panel, or two-inch pipe using an optional
mounting bracket.
Figure 3-1: Transmitter Direct Mounting
Do not apply torque directly to the electronics housing. To avoid damage,
apply torque only to the hex-shaped process connection.
A. Process connection
Figure 3-2: Panel and Pipe Mounting
Panel mountPipe mount
6Emerson.com/Rosemount
May 2019Quick Start Guide
3.1Mount the transmitter in liquid applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so the drain/vent valves are oriented upward.
Figure 3-3: Mounting the Transmitter in Liquid Applications
In-line
3.2Mount the transmitter in gas applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Figure 3-4: Mounting the Transmitter in Gas Applications
Inline
Quick Start Guide7
Quick Start GuideMay 2019
3.3Mount the transmitter in steam applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Figure 3-5: Mounting the Transmitter in Steam Applications
In-line
3.4Environmental seal for housing
Thread sealing (PFTE) tape or paste on male threads of conduit is required to
provide a water/dust tight conduit seals and meets requirements of NEMA
Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings
are required.
For M20 threads, install conduit plugs to full thread engagement or until
mechanical resistance is met.
3.5
8Emerson.com/Rosemount
Gage transmitter orientation
The low side pressure port (atmospheric reference) on the inline gage
transmitter is located in the neck of the transmitter, behind the housing. The
vent path is 360° around the transmitter between the housing and sensor.
(See Figure 3-6.)
®
May 2019Quick Start Guide
CAUTION
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the transmitter so the
contaminants can drain away.
Figure 3-6: Gage Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
Quick Start Guide9
Quick Start GuideMay 2019
4Set the switches
Set alarm and security switch configuration before installation as shown in
Figure 4-1.
• The alarm switch sets the analog output alarm to high or low. Default
alarm is high.
• The security switch allows (
transmitter. Default security is off ( ).
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not
remove the instrument cover in explosive atmospheres when the
circuit is live.
3. Slide the security and alarm switches into the preferred position
using a small screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to
comply with explosion-proof requirements.
Figure 4-1: Transmitter Electronics Board
Without LCD display
) or prevents ( ) any configuration of the
With LOI/LCD display
A. Alarm
B. Security
10Emerson.com/Rosemount
May 2019Quick Start Guide
5Connect the wiring and power up
CAUTION
Do not tamper with or remove the electronics board in the Rosemount
3051P. This will cause permanent damage to the transmitter.
Shielded twisted pair cable should be used for best results. Use 24 AWG or
larger wire that does not exceed 5000 ft. (1500 m) in length. If applicable,
install wiring with a drip loop. Arrange the drip loop so the bottom is lower
than the conduit connections and the transmitter housing.
Figure 5-1: Wiring the Transmitter (4–20 mA HART)
A. Vdc supply
B. RL≥ 250 (necessary for HART® communication only)
™
CAUTION
• Installation of the transient protection terminal block does not provide
transient protection unless the transmitter case is properly grounded.
• Do not run signal wiring in conduit or open trays with power wiring, or
near heavy electrical equipment.
• Do not connect the powered signal wiring to the test terminals. Power
could damage the test diode in the terminal block.
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the leads as shown in Figure 5-1.
3. Tighten the terminal screws to ensure full contact with the terminal
block screw and washer. When using a direct wiring method, wrap
wire clockwise to ensure it is in place when tightening the terminal
block screw.
Quick Start Guide11
DP
A
B
C
D
E
Quick Start GuideMay 2019
Note
The use of a pin or ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important that the instrument cable
shield:
• Be trimmed close and insulated from touching the transmitter
housing.
• Be connected to the next shield if cable is routed through a
junction box.
• Be connected to a good earth ground at the power supply end.
6. If transient protection is needed, refer to section Grounding for
A. Trim shield and insulate
B. Insulate shield
C. Terminate cable shield drain wire to earth ground
D. Internal ground location
5.1
E. External ground location
Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing
and inside the terminal compartment. These grounds are used when the
12Emerson.com/Rosemount
May 2019Quick Start Guide
transient protection terminal blocks are installed. It is recommended that 18
AWG or larger wire is used to connect housing ground to earth ground
(internal or external).
If the transmitter is currently not wired for power up and communication,
follow procedures 1 to 7 of Connect the wiring and power up. When the
transmitter is properly wired, refer to Figure 5-2 for internal and external
transient grounding locations.
Quick Start Guide13
Quick Start GuideMay 2019
6Verify transmitter configuration
Verify the configuration using any HART® capable configuration tool or LOI option code M4. Configuration instructions for a Field Communicator and
LOI are included in this step. See Rosemount™ 3051P Reference Manual for
configuration instructions using AMS Device Manager.
6.1Verifying configuration with a Field Communicator
A Rosemount™ 3051P DD must be installed on the Field Communicator to
verify configuration. Fast Key sequences vary depending on device and DD
revisions. Use the Determine Fast Key sequence table process below to
identify the appropriate Fast Key sequences.
6.2Field Communicator user interface
6.2.1Determine Fast Key sequence table
Procedure
1. Connect Field Communicator to Rosemount™ 3051P.
2. If Home screen matches Figure 6-1, refer to Table 6-1 for Fast Key
sequences.
3. If Home screen matches Figure 6-2:
a) Perform Fast Key sequence 1,7,2 to identify Field Revision and
HART® Revision.
b) Refer to Table 6-2 and the appropriate column based on your
Field Revision and HART Revision for Fast Key sequences.
Example
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit Emerson.com or HARTComm.org.
Figure 6-1: Traditional Interface
14Emerson.com/Rosemount
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.