Emerson Rosemount 3051HT Quick Start Manual

Page 1
Quick Start Guide
00825-0100-4091, Rev CB
February 2019
Rosemount™ 3051HT Hygienic Pressure Transmitter
with 4–20 mA HART® Revision 5 and 7 Protocol
Page 2
Quick Start Guide February 2019
NOTICE
This guide provides basic guidelines for the Rosemount 3051HT Transmitter. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Ensure device is installed in accordance with intrinsically safe or non-incendive field practices.
Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify that the operating environment of the gauge is consistent with the appropriate hazardous locations certifications.
Electrical shock can result in death or serious injury.
Care must be taken during transportation of power module to prevent electrostatic charge build-up.
Device must be installed to ensure a minimum antenna separation distance of 8 in. (20 cm) from all persons.
Process leaks may cause harm or result in death.
Handle the device carefully.
Failure to follow safe installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
Apply wrench only to the flats, not on housing.
The battery is not replaceable in a hazardous location.
Contents
System readiness........................................... 3
Transmitter installation..................................4
2 Emerson.com/Rosemount
Product certifications...................................18
Page 3
February 2019 Quick Start Guide

1 System readiness

1.1 Confirm HART Revision capability

If using HART based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART Revision of your transmitter,
see Switch HART Revision mode.

1.2 Confirm correct device driver

Verify the latest device driver (DD/DTM™) is loaded on your systems to
ensure proper communications.
Download the latest device driver at Emerson.com or hartcomm.org.
Rosemount 3051 device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 3051 Device Revisions and Files
Identify
Software Release Date
Dec-11 01 7 10 See
(1) Device driver file names use device and DD revision, e.g. 10_01. HART Protocol is
designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new device driver must be downloaded. It is recommended to download new device driver files to ensure full functionality.
(2) HART Revision 5 and 7 Selectable, Power Diagnostics, Safety Certified, Local
Operator Interface, Process Alerts, Scaled Variable, Configurable Alarms, Expanded Engineering Units.
Quick Start Guide 3
Device
HART Software Revision
Find Device Driver Review
HART Universal Revision
5 9
Device Revision
(1)
Functionality
Changes to Software
(2)
changes.
(2)
for list of
Page 4
Quick Start Guide February 2019

2 Transmitter installation

2.1 Mount the transmitter

Place the transmitter to the desired orientation before mounting. Transmitter must not be securely mounted or clamped in place when changing transmitter orientation.
Conduit entry orientation
When installing a Rosemount 3051HT, it is recommended installing so a conduit entry faces downward or parallel to the ground to maximize drainability when cleaning.
Environmental seal for housing
Thread sealing (PTFE) tape or paste on male threads of conduit is required to provide a water/dust tight conduit seal and meets requirements of NEMA Type 4X, IP66, IP68, and IP69K. Consult factory if other Ingress Protection ratings are required.
Note
IP69K rating only available on units with a SST housing and option code V9 in the model string.
For M20 threads, install conduit plugs to full thread engagement or until mechanical resistance is met.
®
In-line gage transmitter orientation
The low side pressure port (atmospheric reference) on the in-line gage transmitter is located on the neck of the transmitter via a protected gage vent (See Figure 2-1).
Keep the vent path free from obstructions including but not limited to paint, dust, and viscous fluids by mounting the transmitter so the process can drain away.
4 Emerson.com/Rosemount
Page 5
February 2019 Quick Start Guide
Figure 2-1: In-line Protected Gage Vent Low Side Pressure Port
Aluminum Polished 316 SST
A. Low side pressure port (atmospheric reference)
Clamping
When installing clamp, follow recommended torque values provided by gasket manufacturer.
Note
To maintain performance, torquing a 1.5. Tri Clamp beyond 50 in-lb is not recommended on pressure ranges below 20 psi.
2.2
Quick Start Guide 5

Set the switches

Prerequisites
Set alarm and security switch configuration before installation as shown in
Figure 2-2.
The alarm switch sets the analog output alarm to high or low.
Default alarm is high.
The security switch allows (unlocked symbol) or prevents (locked symbol)
any configuration of the transmitter.
Default security is off (unlocked symbol).
Use the following procedure to change the switch configuration:
Page 6
Quick Start Guide February 2019
Procedure
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small screwdriver.
4. Reattach the transmitter cover.
The covers must only be capable of being released or removed
with the aid of a tool to comply with applicable ordinary locations requirements.
The cover must be fully engaged to comply with explosion-proof
requirements.
Example
Figure 2-2: Transmitter Electronics Board
Aluminum
Without LCD display With LOI or LCD display
6 Emerson.com/Rosemount
Page 7
DP
A
B
D
E
C
February 2019 Quick Start Guide
Polished 316 SST
Without LCD display With LOI or LCD display
A. Alarm B. Security

2.3 Connect the wiring and power up

Figure 2-3: Transmitter Wiring Diagrams (4–20 mA) - Aluminum
A. 24 Vdc supply B. RL ≥ 250 C. Current meter (optional)
Quick Start Guide 7
Page 8
DP
A
B
D
E
C
Quick Start Guide February 2019
Figure 2-4: Transmitter Wiring Diagrams (4–20 mA) - Polished 316 SST
A. 24 Vdc supply B. RL ≥ 250 C. Current meter (optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 ft. (1,500 m) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
CAUTION
Installation of the transient protection terminal block does not provide
transient protection unless the Rosemount 3051HT case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or
near heavy electrical equipment.
Do not connect the powered signal wiring to the test terminals. Power
could damage the test diode in the terminal block.
Use the following steps to wire the transmitter:
Procedure
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the “–” terminal.
8 Emerson.com/Rosemount
Page 9
February 2019 Quick Start Guide
3. Ensure full contact with Terminal Block screw and washer. When using a direct wiring method, wrap wire clockwise to ensure it is in place when tightening the terminal block screw.
Note
The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important the instrument cable shield be:
Trimmed close and insulated from touching the transmitter
housing
Connected to the next shield if cable is routed through a junction
box
Connected to a good earth ground at the power supply end
6. If transient protection is needed, refer to section Grounding for
transient terminal block for grounding instructions.
7. Plug and seal unused conduit connections.
8. Reattach the transmitter covers.
The covers must only be capable of being released or removed
with the aid of a tool to comply with applicable ordinary locations requirements.
The cover must be fully engaged to comply with explosion-proof
requirements.
Quick Start Guide 9
Page 10
DP
A
B
D
E
C
DP
A
B
D
E
C
Quick Start Guide February 2019
Example
Figure 2-5: Wiring
Aluminum Polished 316 SST
A. Minimize distance B. Trim shield and insulate C. Protective grounding terminal (do not ground cable shield at the
transmitter)
D. Insulate shield
E. Connect shield back to the power supply ground

2.3.1 Grounding for transient terminal block

Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow Connect the wiring and power up. When the transmitter is properly wired, refer to Figure 2-5 for internal and external transient grounding locations.
Note
The Rosemount 3051HT polished 316 SST housing only provides ground termination inside the terminal compartment.
10 Emerson.com/Rosemount
Page 11
February 2019 Quick Start Guide

2.4 Verify configuration

Verify the configuration using any HART capable configuration tool or Local Operator Interface (LOI) - option code M4. Configuration instructions for a Field Communicator and LOI are included in this step.

2.4.1 Verifying configuration with a Field Communicator

A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 2-1. For Fast Key sequences using legacy DD's, contact your local Emerson representative.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com/Field-Communicator for information on updating the DD Library.
Procedure
Verify device configuration using the Fast Key sequences in Table 2-1.
A check () indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of configuration and startup.
Table 2-1: Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
Function Fast Key Sequence
HART 7 HART 5
Alarm and Saturation Levels 2, 2, 2, 5, 7 2, 2, 2, 5, 7
Damping 2, 2, 1, 1, 5 2, 2, 1, 1, 5
Range Values 2, 2, 2 2, 2, 2
Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1
Transfer Function 2, 2, 1, 1, 6 2, 2, 1, 1, 6
Units 2, 2, 1, 1, 4 2, 2, 1, 1, 4
Burst Mode 2, 2, 5, 3 2, 2, 5, 3
Custom Display Configuration 2, 2, 4 2, 2, 4
Date 2, 2, 7, 1, 4 2, 2, 7, 1, 3
Descriptor 2, 2, 7, 1, 5 2, 2, 7, 1, 4
Digital to Analog Trim (4–20 mA Output) 3, 4, 2 3, 4, 2
Disable Configuration Buttons 2, 2, 6, 3 2, 2, 6, 3
Rerange with Keypad 2, 2, 2, 1 2, 2, 2, 1
Quick Start Guide 11
Page 12
Quick Start Guide February 2019
Table 2-1: Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence (continued)
Function Fast Key Sequence
HART 7 HART 5
Loop Test 3, 5, 1 3, 5, 1
Lower Sensor Trim 3, 4, 1, 2 3, 4, 1, 2
Message 2, 2, 7, 1, 6 2, 2, 7, 1, 5
Scaled D/A Trim (4–20 mA Output) 3, 4, 2 3, 4, 2
Sensor Temperature/Trend (3051S) 3, 3, 3 3, 3, 3
Upper Sensor Trim 3, 4, 1, 1 3, 4, 1, 1
Digital Zero Trim 3, 4, 1, 3 3, 4, 1, 3
Password 2, 2, 6, 5 2, 2, 6, 4
Scaled Variable 3, 2, 2 3, 2, 2
HART Revision 5 to HART Revision 7 switch 2, 2, 5, 2, 3 2, 2, 5, 2, 3
Long Tag
Find Device
Simulate Digital Signal
(1)
(1)
(1)
2, 2, 7, 1, 2 N/A
3, 4, 5 N/A
3, 4, 5 N/A
(1) Only available in HART Revision 7 mode.

2.4.2 Verifying configuration with LOI

The optional LOI can be used for commissioning the device. The LOI is a two­button design with internal and external/rear buttons. On a polished stainless steel housing, buttons are located internally both on the display and terminal side of the transmitter. On an aluminum housing, buttons are located on the display and externally underneath the top metal tag. To activate the LOI, push any button. LOI button functionality is shown on the bottom corners of the display. See Table 2-2 and Figure 2-6 for button operation and menu information.
12 Emerson.com/Rosemount
Page 13
Assign PV
HART Revision
February 2019 Quick Start Guide
Table 2-2: LOI Button Operation
Button
Left No SCROLL
Right Yes ENTER
Figure 2-6: LOI Menu

2.4.3 Switch HART Revision mode

If the HART configuration tool is not capable of communicating with HART Revision 7, the Rosemount 3051 will load a generic menu with limited
Quick Start Guide 13
Page 14
Quick Start Guide February 2019
capability. The following procedures will switch the HART Revision mode from the generic menu:
Procedure
Select Manual Setup > Device Information > Identification > Message.
a) To change to HART Revision 5, Enter: HART5 in the Message field.
b) To change to HART Revision 7, Enter: HART7 in the Message field.
Note
See Table 2-1 to change HART Revision when the correct device driver is loaded.

2.5 Trim the transmitter

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage transmitter to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
Note
When performing a zero trim, ensure the equalization valve is open and all wet legs are filled to the correct level.
CAUTION
It is not recommended to zero an absolute transmitter, Rosemount 3051HTA model.
Procedure
Choose your trim procedure.
a) Analog zero trim – Sets the analog output to 4 mA.
Also referred to as a “rerange” it sets the lower range value (LRV)
equal to the measured pressure.
The display and digital HART output remains unchanged.
b) Digital zero trim – Recalibrates the sensor zero.
The LRV is unaffected. The pressure value will be zero (on display
and HART output). 4 mA point may not be at zero.
This requires the factory calibrated zero pressure is within a range
of 3% of the URL [0 ± 3% × URL].
Example
URV = 250 inH2O
14 Emerson.com/Rosemount
Page 15
February 2019 Quick Start Guide
Applied Zero Pressure = ± 0.03× 250 inH2O = ± 7.5 inH2O (compared to factory settings) values outside this range will be rejected by the transmitter

2.5.1 Trimming with a Field Communicator

Procedure
1. Connect the Field Communicator, see Connect the wiring and power
up for instructions.
2. Follow the HART menu to perform the desired zero trim.
Table 2-3: Zero Trim Fast Keys
Analog Zero (Set 4 mA) Digital Zero
Fast Key sequence 3, 4, 2 3, 4, 1, 3

2.5.2 Trimming with configuration buttons

A zero trim is to be performed using one of the three possible sets of configuration buttons located above the terminal block or under the top tag.
To access the configuration buttons on a polished stainless steel housing, remove the terminal side housing cover.
To access the configuration buttons on an aluminum housing, loosen the screw on the top tag and slide the tag on the top of the transmitter.
Figure 2-7: External or Rear/Terminal-Side Configuration Buttons
LOI
Aluminum
Quick Start Guide 15
Analog zero and span
Digital zero Aluminum
Page 16
Quick Start Guide February 2019
Polished 316 SST
LOI Analog zero
(1)
N/A
(1) LOI buttons (option M4) only offer front facing buttons on SST housing (option 1).
Options D4 and DZ can still be purchased for rear/terminal-side facing buttons.
and span
Digital zero Aluminum
A. Configuration buttons
Perform trim with LOI (option M4)
Use the following procedure to perform a zero trim:
Procedure
1. Set the transmitter pressure.
2. See Figure 2-6 for the operating menu. a) Perform an analog zero trim by selecting Rerange.
b) Perform a digital zero trim by selecting Zero Trim.
Perform trim with analog zero and span (option D4)
Use the following procedure to perform a zero trim:
Procedure
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform an analog
zero trim.
16 Emerson.com/Rosemount
Page 17
February 2019 Quick Start Guide
Perform trim with digital zero (option DZ)
Use the following procedure to perform a zero trim:
Procedure
1. Set the transmitter pressure.
2. Press and hold the Zero button for two seconds to perform a digital zero trim.
Quick Start Guide 17
Page 18
Quick Start Guide February 2019

3 Product certifications

3.1 European Directive Information

A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com.

3.2 Ordinary Location Certification

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
Altitude Pollution degree
5000 m max 4 (metallic enclosure)
2 (non-metallic enclosure)

3.3 Installing Equipment in North America

The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
3.4
3.5
18 Emerson.com/Rosemount

USA

I5 Intrinsic Safety; Nonincendive
Certificate: 1053834
Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 –
2004,
FM Class 3810 – 2005
Markings: IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-1024, CL I ZONE 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D T5;
T4(–20 °C ≤ Ta ≤ +70 °C) [HART]; T4(–20 °C ≤ Ta ≤ +60 °C) [Fieldbus]; Type 4x

Canada

I6 Intrinsic Safety
Certificate: 1053834
Page 19
February 2019 Quick Start Guide
Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No.142-M1987, CSA Std.
C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987
Markings: Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T4; Suitable for Class I, Zone 0; Type 4X; Factory Sealed; Single Seal
(See drawing 03031-1053)

3.6 Europe

I1 ATEX Intrinsic Safety
Certificate: BAS97ATEX1089X
Standards: EN 60079-0:2012 + A11:2013, EN 60079-11:2012
Markings: HART:
T4(–20 °C ≤ Ta ≤ +70 °C) Fieldbus: II 1 G Ex ia IIC Ga T4(–20 °C ≤ Ta ≤ +60 °C)
Table 3-1:
II 1 G Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ Ta ≤ +40 °C),
3.7
Parameter HART Fieldbus/
Voltage U
Current I
i
Power P
i
Capacitance Ci0.012 μF 0 μF
Inductance Li0 mH 0 mH
30 V 30 V
i
200 mA 300 mA
0.9 W 1.3 W
PROFIBUS
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.

International

I7 IECEX Intrinsic Safety
Certificate: IECEx BAS 09.0076X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Quick Start Guide 19
Page 20
Quick Start Guide February 2019
Markings: HART: Ex ia IIC T5/T4 Ga, T5(–20 °C ≤ Ta ≤ +40 °C), T4(–20 °C ≤ Ta ≤ +70 °C)
Profibus: Ex ia IIC T4 Ga (–20 °C ≤ Ta ≤ +60 °C)
Table 3-2:
Parameter PROFIBUS
Voltage U
Current I
Power P
Capacitance Ci0 μF
Inductance Li0 mH
i
i
30 V
i
300 mA
1.3 W
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of EN60079-11:2012. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.

3.8 Additional Certifications

®
3-A
All Rosemount 3051HT transmitters with the following connections are 3-A approved and labeled:
T32: 1 1/2-in. Tri Clamp
T42: 2-in. Tri Clamp
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of 3-A certifications.
A 3-A certificate of compliance is available by selecting option code QA.
EHEDG
All Rosemount 3051HT transmitters with the following connections are EHEDG approved and labeled:
T32: 1 1/2-in. Tri Clamp
T42: 2-in. Tri Clamp
20 Emerson.com/Rosemount
Page 21
February 2019 Quick Start Guide
If process connection B11 is selected, please reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS (00813-0100-4016) for availability of EHEDG certifications.
An EHEDG certificate of compliance is available by selecting option code QE.
Ensure gasket selected for installation is approved to meet both application and EHEDG certification requirements.
ASME-BPE
All Rosemount 3051HT Transmitters with option F2 and the following connections are designed to ASME-BPE SF4 standards
(1)
:
T32: 1 1/2-in. Tri Clamp
T42: 2-in. Tri Clamp
A self-certified certificate of compliance to ASME-BPE is also available (option QB)
(1)
Per Clause SD-2.4.4.2 (m), suitability of painted aluminum housings to be determined by end user.
Quick Start Guide 21
Page 22
EU Declaration of Conformity
No: RMD 1106 Rev. G
Page 1 of 3
We,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
declare under our sole responsibility that the product,
Rosemount™ 3051HT Pressure Transmitters
manufactured by,
Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA
to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule.
(signature)
Vice President of Global Quality
(function)
Chris LaPoint
(name)
1-Feb-19; Shakopee, MN USA
(date of issue & place)
Quick Start Guide February 2019
Figure 3-1: Rosemount 3051HT Declaration of Conformity
22 Emerson.com/Rosemount
Page 23
EU Declaration of Conformity
No: RMD 1106 Rev. G
Page 2 of 3
EMC Directive (2014/30/EU)
Models 3051HT Pressur e Transmitters
Harmonized Standards: EN 61326-1:2013, EN 61326-2-3:2013
RoHS Directive (2011/65/EU)
Models 3051HT Pressur e Transmitters
Harmonized Standard: EN 50581:2012
ATEX Directive (2014/34/EU)
Model 3051HT Pressure T ransmitter
BAS97ATEX1089X - Intrinsic Safety
Equipment Group II Category 1 G
Ex ia IIC T5/T4 Ga
Harmonized Standards: EN60079-0:2012 + A11:2013, EN60079-11:2012
BAS00ATEX3105X - Type n and Certificate
Equipment Group II Category 3 G
Ex nA IIC T5 Gc
Harmonized Standards: EN60079-0:2012 + A11:2013, EN60079-15:2010
Baseefa11ATEX0275X - Dust Certificate
Equipment Group II Category 1 D
Ex ta IIIC T95°C T
500
105°C Da
Harmonized Standards: EN60079-0:2012 + A11:2013, EN60079-31:2014
February 2019 Quick Start Guide
Figure 3-2: Rosemount 3051HT Declaration of Conformity
Quick Start Guide 23
Page 24
EU Declaration of Conformity
No: RMD 1106 Rev. G
Page 3 of 3
ATEX Notified Body
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
ATEX Notified Body for Quality Assurance
SGS FIMCO OY [Notified Body Number: 0598]
P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland
Quick Start Guide February 2019
Figure 3-3: Rosemount 3051HT Declaration of Conformity
24 Emerson.com/Rosemount
Page 25
ᴹ
China RoHS
㇑᧗⢙䍘䎵䗷ᴰབྷ⎃ᓖ䲀٬Ⲵ䜘Ԧරࡇ㺘
Rosemount 3051HT
List of Rosemount 3051HT Parts with China RoHS Concentration above MCVs
䜘Ԧ〠
Part Name
ᴹᇣ⢙䍘
/ Hazardous Substances
䫵
Lead
(Pb)
⊎
Mercury
(Hg)
䭹
Cadmium
(Cd)
ޝԧ䬜
Hexavalent
Chromium
(Cr +6)
ཊⓤ㚄㤟
Polybrominated
biphenyls
(PBB)
ཊⓤ㚄㤟䟊
Polybrominated diphenyl ethers
(PBDE)
⭥ᆀ㓴Ԧ
Electronics
Assembly
X O O O O O
༣փ㓴Ԧ
Housing
Assembly
O O O O O O
Րᝏಘ㓴Ԧ
Sensor
Assembly
X O O O O O
ᵜ㺘Ṭ㌫׍ᦞ
SJ/T11364
Ⲵ㿴ᇊ㘼ࡦ֌
This table is proposed in accordance with the provision of SJ/T11364.
O:
᜿Ѫ䈕䜘ԦⲴᡰᴹ൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿൷վҾ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.
X:
᜿Ѫ൘䈕䜘Ԧᡰ֯⭘Ⲵᡰᴹ൷䍘ᶀᯉ䟼ˈ㠣ቁᴹа㊫൷䍘ᶀᯉѝ䈕ᴹᇣ⢙䍘Ⲵ䟿儈Ҿ
GB/T 26572
ᡰ㿴ᇊⲴ䲀䟿㾱≲
X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
February 2019 Quick Start Guide
Quick Start Guide 25
Page 26
Quick Start Guide February 2019
26 Emerson.com/Rosemount
Page 27
February 2019 Quick Start Guide
Quick Start Guide 27
Page 28
*00825-0100-4091*
00825-0100-4091, Rev. CB
Quick Start Guide
February 2019
Global Headquarters
Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com
Latin America Regional Office
Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com
Asia Pacific Regional Office
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com
North America Regional Office
Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRF@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com
Linkedin.com/company/Emerson-
Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/
RosemountMeasurement
Google.com/+RosemountMeasurement
©
2019 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is mark of one of the Emerson family of companies. All other marks are the property of their respective owners.