Rosemount® 3051 Pressure Transmitter
Rosemount 3051CF Series Flowmeter
Transmitter
with F
OUNDATION
™
fieldbus protocol
Note
Before installing the transmitter, confirm the correct device driver is loaded on the host
systems. See “System readiness” on page 3.
Page 2
Quick Start Guide
June 2014
NOTICE
This installation guide provides basic guidelines for Rosemount 3051 transmitters. It does not
provide instructions for configuration, diagnostics, maintenance, service, troubleshooting,
Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the 3051 reference
manual (document number 00809-0100-4774) for more instruction. This manual is also
available electronically on www.emersonprocess.com/rosemount.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review the
approvals section of the 3051 reference manual for any restrictions associated with a safe
installation.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when
power is applied to the unit.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the o-ring designed to seal with the corresponding flange
adapter.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can
cause electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
form. Only use plugs, adapters, glands, or conduit with a compatible thread form when
closing these entries.
Download the correct device driver at your host vendor download site,
www.emersonprocess.com or www.fieldbus.org.
Rosemount 3051 device revisions and drivers
Ta bl e 1 provides the information necessary to ensure you have the correct device
driver and documentation for your device.
™
) is loaded on your systems to
Table 1. Rosemount 3051 F
Device
revision
HostDevice driver (DD)
(1)
AllDD4: DD Rev 1www.fieldbus.org
AllDD5: DD Rev 1www.fieldbus.org
Emerson
8
Emerson
Emerson 375 / 475: DD Rev 2Easy Upgrade Utility
AllDD4: DD Rev 3www.fieldbus.org
AllDD5: NAN/A
Emerson
7
Emerson
1.
1. FOUNDATION fieldbus device revision can be read using a FOUNDATION fieldbus capable configuration tool.
2.Device driver file names use device and DD revision. To access functionality, the correct device driver must be installed
Emerson 375 / 475: DD Rev 6Easy Upgrade Utility
AMS V 10.5 or higher:
DD Rev 2
AMS V 8 to 10.5:
DD Rev 1
AMS V 10.5 or higher:
DD Rev 6
AMS V 8 to 10.5:
DD Rev 4
OUNDATION fieldbus Device Revisions and Files
(2)
Obtain at
www.emersonprocess.com
www.emersonprocess.com
www.emersonprocess.com
www.emersonprocess.com
Device driver (DTM)
www.emersonprocess.com
www.emersonprocess.com
Manual document
00809-0100-4774
Rev. CA or newer
00809-0100-4774
Rev. BA
number
on your control and asset management hosts, and on your configuration tools.
3
Page 4
Quick Start Guide
Figure 1. Installation Flowchart
Start
Locate device
June 2014
1. Transmitter
installation
Commissioning
2.
tag
3. Housing
rotation
4. Set switches
and software
write lock
5. Grounding,
wiring and
power up
6. Configuration
7. Zero trim the
transmitter
Done
4
Page 5
June 2014
Transmitter installation
Step 1: Mount the transmitter
Quick Start Guide
Liquid applications
1. Place taps to the side of the
line.
2. Mount beside or below the
taps.
3. Mount the transmitter so
that the drain/vent valves are
oriented upward.
Gas applications
1. Place taps in the top or side of
the line.
2. Mount beside or above the
taps.
Steam applications
1. Place taps to the side of the
line.
2. Mount beside or below the
taps.
3. Fill impulse lines with water.
CoplanarIn-Line
CoplanarIn-Line
CoplanarIn-Line
5
Page 6
Quick Start Guide
Figure 2. Panel and Pipe Mounting
Panel mount
(1)
June 2014
Pipe mount
Coplanar flange
Traditional flange
Rosemount 3051T
1.
1. 5/16 x 1 1/2 Panel Bolts are customer supplied.
Bolting considerations
If the transmitter installation requires assembly of the process flanges, manifolds,
or flange adapters, follow the assembly guidelines to ensure a tight seal for
optimal performance characteristics of the transmitters. Use only bolts supplied
with the transmitter or sold by Emerson
illustrates common transmitter assemblies with the bolt length required for
proper transmitter assembly.
6
®
as spare parts. Figure 3 on page 7
Page 7
June 2014
4 x 1.75-in. (44 mm)
4 x 2.88-in. (73 mm)
A
B
C
D
4 x 1.75-in. (44 mm)
4 x 1.50-in. (38 mm)
4 x 1.75-in. (44 mm)
4 x 2.25-in. (57 mm)
Quick Start Guide
Figure 3. Common Transmitter Assemblies
A. Transmitter with Coplanar Flange
B. Transmitter with Coplanar Flange and Optional Flange Adapters
C. Transmitter with Traditional Flange and Optional Flange Adapters
D. Transmitter with Coplanar Flange and Optional Manifold and Flange Adapters
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing
the markings on the head of the bolt and referencing Table 2 on page 8. If bolt
material is not shown in
Tab l e 2, contact a local Emerson Process Management
representative for more information.
Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant
should be applied when installing either type of bolt.
Use the following bolt installation procedure:
1. Finger tighten the bolts.
2. Torque the bolts to the initial torque value using a crossing pattern. See Ta b le 2
for initial torque value.
3. Torque the bolts to the final torque value using the same crossing pattern. See
Ta bl e 2 for final torque value.
4. Verify the flange bolts are protruding through the sensor module bolt holes
before applying pressure.
7
Page 8
Quick Start Guide
316
316
316
SW
316
STM
316
R
B8M
A
A
B
B
C
D
D
C
Rosemount 3051S / 3051 / 2051 / 3001 / 3095
Rosemount 1151
June 2014
Table 2. Torque Values for the Flange and Flange Adapter Bolts
Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious
injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is
designed for its specific flange adapter, as shown below.
Figure 4. O-ring Location
8
A. Flange Adapter
B. O-ring
C. PTFE Based
D. Elastomer
Page 9
June 2014
Whenever the flanges or adapters are removed, visually inspect the o-rings.
Replace them if there are any signs of damage, such as nicks or cuts. If you replace
the o-rings, re-torque the flange bolts and alignment screws after installation to
compensate for seating of the PTFE o-ring.
Quick Start Guide
Inline gage transmitter orientation
The low side pressure port (atmospheric reference) on the inline gage transmitter
is located in the neck of the transmitter, behind the housing. The vent path is 360°
around the transmitter between the housing and sensor. (See
Keep the vent path free of any obstruction, including but not limited to paint,
dust, and lubrication by mounting the transmitter so that fluids can drain away.
Figure 5. Inline Gage Low Side Pressure Port
A. Pressure Port Location
Figure 5.)
A
Step 2: Tagging
Commissioning (paper) tag
To identify which device is at a particular location use the removable tag provided
with the transmitter. Ensure the physical device tag (PD Tag field) is properly
entered in both places on the removable commissioning tag and tear off the
bottom portion for each transmitter.
Note
The device description loaded in the host system must be at the same revision as this device,
see “System readiness” on page 3.
9
Page 10
Quick Start Guide
Commissioning Tag
DEVICE ID:
0011513051010001440-121698091725
DEVICE REVISION: 7.2
PHYSICAL DEVICE TAG
DEVICE ID:
0011513051010001440-121698091725
DEVICE REVISION: 7.2
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A
Commissioning Tag
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION: 8.1
PHYSICAL DEVICE TAG
DEVICE ID:
001151AC00010001440-121698091725
DEVICE REVISION: 8.1
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A
Figure 6. Commissioning Tag
A. Device revision
Note
The device description loaded in the host system must be at the same revision as this
device. The device description can be downloaded from the host system website or
www.rosemount.com by selecting Download Device Drivers under Product Quick Links.
You can also visit www.fieldbus.org and select End User Resources.
June 2014
Step 3: Housing rotation
To improve field access to wiring or to better view the optional LCD display:
Figure 7. Housing Rotation
A. Housing Rotation Set Screw (5/64-inch)
1. Loosen the housing rotation set screw using a 5/64 -in. hex wrench.
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread limit, rotate the
4. Retighten the housing rotation set screw to no more than 7 in-lbs when
10
housing counterclockwise to the desired location (up to 360° from thread
limit).
desired location is reached.
Page 11
June 2014
Quick Start Guide
Step 4: Set the switches
Set Simulate and Security switch configuration before installation as shown in
Figure 8.
The simulate switch enables or disables simulated alerts and simulated AI
Block status and values. The default simulate switch position is enabled.
The Security switch allows (unlocked symbol) or prevents (locked symbol)
any configuration of the transmitter.
- Default security is off (unlocked symbol).
- The security switch can be enabled or disabled in software.
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the
instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and simulate switches into the preferred position.
4. Replace the housing cover.
Note
It is recommended the cover be tightened until there is no gap between the cover and the housing.
Figure 8. Simulate and Security Switches
C
B
A
A. Simulate Disabled Position
B. Simulate Switch
C. Simulate Enabled Position (default)
D. Security Locked Position
E. Security Switch
F. Security Unlocked Position (default)
D
E
F
11
Page 12
Quick Start Guide
DP
A
E
D
F
B
Step 5: Wire, ground, and power up
Use of copper wire of sufficient size to ensure that the voltage across the
transmitter power terminals does not drop below 9 vdc. Power supply voltage
can be variable, especially under abnormal conditions such as when operating on
battery backup. A minimum of 12 vdc under normal operating conditions is
recommended. Shielded twisted pair Type A cable is recommended.
1. To power the transmitter, connect the power leads to the terminals indicated
on the terminal block label.
June 2014
Figure 9. Wiring Terminals
C
A. Minimize distance
B. Trim shield and insulate
C. Protective Grounding Terminal (do not ground cable shield at the transmitter)
D. Insulate Shield
E. Minimize distance
F. Connect Shield Back to the Power Supply Ground
Note
The 3051 power terminals are polarity insensitive, which means the electrical polarity of the power
leads does not matter when connecting to the power terminals. If polarity sensitive devices are
connected to the segment, terminal polarity should be followed. When wiring to the screw
terminals, the use of crimped legs is recommended.
2. Tighten the terminal screws to ensure adequate contact. No additional power
is needed.
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy
electrical equipment. Grounding terminations are provided on the outside of the
electronics housing and inside the Terminal Compartment. These grounds are
used when transient protect terminal blocks are installed or to fulfill local
regulations.
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 9.
12
Page 13
June 2014
a. Trim the cable shield as short as practical and insulate from touching the
transmitter housing.
Note
Do NOT ground the cable shield at the transmitter; if the cable shield touches the
transmitter housing, it can create ground loops and interfere with communications.
b. Continuously connect the cable shields to the power supply ground.
c. Connect the cable shields for the entire segment to a single good earth
ground at the power supply.
Note
Improper grounding is the most frequent cause of poor segment communications.
3. Replace the housing cover. It is recommended that the cover be tightened
until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
Quick Start Guide
Power supply
The transmitter requires between 9 and 32 V dc (9 and 30 V dc for intrinsic safety,
and 9 and 17.5 V dc for FISCO intrinsic safety) to operate and provide complete
functionality.
Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply,
filter, and decouple the segment from other segments attached to the same
power supply.
Grounding
Signal wiring of the fieldbus segment can not be grounded. Grounding out one of
the signal wires will shut down the entire fieldbus segment.
Shield wire ground
To protect the fieldbus segment from noise, grounding techniques for shield wire
require a single grounding point for shield wire to avoid creating a ground loop.
Connect the cable shields for the entire segment to a single good earth ground at
the power supply.
Signal termination
For every fieldbus segment a terminator should be installed at the beginning and
at the end of each segment.
Locating devices
Devices are frequently installed, configured, and commissioned over time by
different personnel. A “Locate Device” capability uses the LCD display (when
installed) to assist personnel in finding the desired device.
From the device “Overview” screen, click the “Locate Device” button. This will
launch a method allowing the user to display a “Find me” message or enter a
custom message to display on the device LCD display.
13
Page 14
Quick Start Guide
Start
Device Configuration
Here
1. Verify Device Tag:
PD_TAG
7. Set Damping:
PRIMARY_VALUE_
DAMPING
8. Set up LCD Display
6. Set Low Cutoff:
LOW_CUT
9. Review Transmitter
Configuration
3. Se t Sig nal
Conditioning:
L_TYPE
5. Set Scaling
OUT_SCALE
2. Check Switches and
Software Write Lock
Done
10. Set Switches and
Software Write Lock
4. Set Scaling
XD_SCALE
When the user exits the “Locate Device” method, the device LCD display
automatically returns to normal operation.
Note
Some hosts do not support “Locate Device” in the DD.
Step 6: Configure
Each FOUNDATION fieldbus host or configuration tool has a different way of
displaying and performing configurations. Some use Device Descriptions (DD) or
DD methods for configuration and to display data consistently across platforms.
There is no requirement that a host or configuration tool support these features.
Use the following block examples to do basic configuration to the transmitter. For
more advanced configurations see the 3051 reference manual (document
number 00809-0100-4774, Rev. CA or newer).
Note
DeltaV users should use DeltaV Explorer for the Resource and Transducer blocks and Control
Studio for the Function Blocks.
Configure the AI block
If your configuration tool supports Dashboard DD's or DTM's you may use either
guided setup or manual setup. If your configuration tools don't support
Dashboard DD's or DTM's, use manual setup. Navigation instructions for each
step are provided below. In addition the screens used for each step are shown in
Figure 11, Basic Configuration Menu Tree.
June 2014
Figure 10. Configuration Flowchart
14
Page 15
June 2014
(Overview)
Pressure
Calibration
Device Information
Locate Device
Scale Gauges
(Calibration)
Primary Value
Sensor Trim
Sensor Limits
Restore Factory Calibration
Last Calibration Points
Calibration Details
(Device Information)
Identification (1)
Revisions
Materials of Construction
License
Security & Simulation
(Materials of Construction )
Sensor
Sensor Range
Flange
Remote Seal
(Configure)
Guided Setup
Manual Setup
Alert Setup
(Manual Setup )
Process Variable
Materials of Construction
Analog Input Blocks Configuration
Display
Zero Trim
Change Damping (7, 9)
Local Display Setup (8, 9)
Configure Analog Input Blocks (3, 4, 5, 6)
Standard Text – Navigation selections available
(Text) – Name of selection used on parent menu screen to access this screen
Bold Text – Automated methods
Underlined Text -- Configuration task numbers from configuration flow chart
Classic View
Figure 11. Basic Configuration Menu Tree
Quick Start Guide
Before you begin
See Figure 10 to graphically view the step by step process for basic device
configuration. Before beginning configuration you may need to verify the Device
Tag or deactivate hardware and software write protection on the transmitter. To
do this follow Step 1 through Step 3 below. Otherwise continue at “AI block
configuration” below.
1. To verify the device tag:
2. To check the switches (see
3. To disable the Software Write Lock:
a. Navigation: from the overview screen, select “Device Information” to verify
the device tag.
a. The write lock switch must be in the unlocked position if the switch has
been enabled in software.
Figure 8):
15
Page 16
Quick Start Guide
a. Navigation: from the overview screen, select “Device Information” and then
select the “Security and Simulation” tab.
b. Perform “Write Lock Setup” to disable Software Write Lock.
Note
Place the control loop in “Manual” mode before beginning Analog Input Block
configuration.
AI block configuration
1. To use guided setup:
a. Navigate to Configure, then Guided Setup.
b. Select “AI Block Unit Setup”.
Note
Guided setup will automatically go through each step in the proper order.
2. To use manual setup:
a. Navigate to Configure, Manual Setup, then Process Variable.
b. Select “AI Block Unit Setup”.
c. Place the AI Block in “Out of Service” mode.
Note
When using manual setup perform the steps in the order described in the "Configure
the AI block".
June 2014
Note
For convenience, AI Block 1 is pre-linked to the transmitter primary variable and should
be used for this purpose. AI Block 2 is pre-linked to the transmitter sensor temperature.
The channel must be selected for AI Blocks 3 and 4.
Channel 1 is the primary variable.
Channel 2 is the sensor temperature.
If the FOUNDATION fieldbus Diagnostics Suite Option Code D01 is enabled, these
additional channels are available.
Channel 12 is the SPM mean.
Channel 13 is the SPM standard deviation.
To configure SPM refer to the 3051 FOUNDATION fieldbus users' manual
Document number 00809-0100-4774.
Note
Step 4
through Step 7 are all performed in a single step by step method under guided
setup, or on a single screen using manual setup.
16
Page 17
June 2014
Quick Start Guide
Note
If the L_TYPE selected in Step 3 is “Direct”, Step 4, Step 5 and Step 6 are not needed. If
the L_TYPE selected is “Indirect”,
unneeded steps will automatically be skipped.
Step 6 is not needed. If guided setup is used any
3. To select the Signal Conditioning “L_TYPE” from the drop down menu:
a. Select L_T YPE: “Direct” for pressure measurements using the device default
units.
b. Select L_TYPE: “Indirect” for other pressure or level units.
c. Select L_TYPE: “Indirect Square Root” for flow units.
4. To set “XD_SCALE” to the 0% and 100% scale points (the transmitter range):
a. Select the XD_SCALE_UNITS from the drop down menu.
b. Enter the XD_SCALE 0% point. This may be elevated or suppressed for level
applications.
c. Enter the XD_SCALE 100% point. This may be elevated or suppressed for
level applications.
d. If L_TYPE is “Direct”, the AI Block may be placed in AUTO mode to return the
device to service. Guided Setup does this automatically.
5. If L_TYPE is “Indirect” or “Indirect Square Root”, set “OUT_SCALE” to change
engineering units.
a. Select the OUT_SCALE UNITS from the drop down menu.
b. Set the OUT_SCALE low value. This may be elevated or suppressed for level
applications.
c. Set the OUT_SCALE high value. This may be elevated or suppressed for level
applications.
d. If L_TYPE is “Indirect”, the AI Block may be placed in AUTO mode to return
the device to service. Guided Setup does this automatically.
6. If L_TYPE is “Indirect Square Root”, a “LOW FLOW CUTOFF” function is
available.
a. Enable LOW FLOW CUTOFF.
b. Set the LOW_CUT VALUE in XD_SCALE UNITS.
c. The AI Block may be placed in AUTO mode to return the device to service.
Guided Setup does this automatically.
7. Change damping.
a. To use guided setup:
Navigate to Configure, Guided Setup, and select “Change Damping”.
Note
Guided Setup will automatically go through each step in the proper order.
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
b. To use manual setup:
Navigate to Configure, Manual Setup, Process Variable, and select
“Change Damping”.
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
17
Page 18
Quick Start Guide
8. Configure optional LCD display (if installed).
a. To use guided setup:
Navigate to Configure, Guided Setup, and select “Local Display Setup”.
Note
Guided setup will automatically go through each step in the proper order.
Check the box next to each parameter to be displayed to a maximum of
four parameters. The LCD display will continuously scroll through the
selected parameters.
b. To use manual setup:
Navigate to Configure, Manual Setup, and select “Local Display Setup”.
Check each parameter to be displayed. The LCD display will continuously
scroll through the selected parameters.
9. Review transmitter configuration and place in service.
a. To review the transmitter configuration navigate using the manual setup
navigation sequences for “AI Block Unit Setup”, “Change Damping”, and
“Set up LCD Display”.
b. Change any values as necessary.
c. Return to the “Overview” screen.
d. If Mode is “Not in Service”, click on the “Change” button, and then click on
“Return All to Service”.
Note
If hardware or software write protection is not needed, Step 10 can be skipped.
June 2014
10. Set switches and software write lock.
a. Check switches (see Figure 8).
Note
The write lock switch can be left in the locked or unlocked position. The simulate
enable/disable switch may be in either position for normal device operation.
Enable software write lock
1. Navigate from the overview screen.
a. Select “Device Information”.
b. Select the “Security and Simulation” tab.
2. Perform “Write Lock Setup” to enable Software Write Lock.
18
Page 19
June 2014
AI block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
ParametersEnter data
Channel1=Pressure, 2=Sensor Temp, 12=SPM mean, 13=SPM standard deviation
L-TypeDirect, Indirect, or Square Root
XD_ScaleScale and Engineering Units
Note
Select only the
units that are
supported by the
device.
Out_ScaleScale and Engineering Units
Pabartorr @ 0 °Cft H20 @ 4°Cm H20 @ 4 °C
kPambarkg/cm
mPapsfkg/m
hPaAtmin H20 @ 4°Cmm H20 @ 4 °Cin Hg @ 0 °C
Deg Cpsiin H20 @ 60 °Fmm H20 @ 68 °Cm Hg @ 0 °C
Deg Fg/cm2in H20 @ 68 °Fcm H20 @ 4 °C
2
2
ft H20 @ 60 °Fmm Hg @ 0 °C
ft H20 @ 68 °Fcm Hg @ 0 °C
Pressure example
ParametersEnter data
Channel1
L_TypeDirect
XD_ScaleSee list of supported engineering units.
Note
Select only the units that are supported by the device.
Quick Start Guide
Out_ScaleSet values outside operating range.
DP Flow example
ParametersEnter data
Channel1
L_TypeSquare Root
XD_Scale0 - 100 inH20 @ 68 °F
Note
Select only the units that are supported by the device.
Out_Scale0 - 20 GPM
Low_CutinH20 @ 68 °F
19
Page 20
Quick Start Guide
June 2014
DP Level example
ParametersEnter data
Channel1
L_TypeIndirect
XD_Scale0 - 300 inH20 @ 68 °F
Note
Select only the units that are supported by the device.
Out_Scale0-25 ft.
Display pressure on the LCD display
Select the 'pressure' check box on the display configuration screen.
Step 7: Zero trim the transmitter
Note
Transmitters are shipped fully calibrated per request or by the factory default of full scale (span =
upper range limit).
A zero trim is a single-point adjustment used for compensating mounting
position and line pressure effects. When performing a zero trim, ensure that the
equalizing valve is open and all wet legs are filled to the correct level.
The transmitter will only allow 3-5% URL Zero error to be trimmed. For greater
zero errors, compensate for the offset by using the XD_Scaling, Out_Scaling and
Indirect L_Type which are part of the AI Block.
1. To use guided setup:
a. Navigate to Configure, Guided Setup, and select "Zero Trim".
b. The method will execute the zero trim.
2. To use manual setup:
a. Navigate to Overview, Calibration, Sensor Trim, and select "Zero Trim".
b. The method will execute the zero trim.
20
Page 21
March 2014 Quick Start Guide
3051 Product Certifications
Rev 1.0
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide.
The most recent revision of the EC Declaration of Conformity can be found at
www.rosemount.com.
Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a
nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational
Safety and Health Administration (OSHA).
North America
E5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 0T2H0.AE
Standards: FM Class 3600 – 1998, FM Class 3615 – 2006, FM Class 3810 – 2005,
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III; T5(-50°C ≤ Ta ≤
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is considered a potential
2. The Model 3051 transmitter with the transient terminal block (Option code T1) will not
IE FM FISCO
Certificate: 1Q4A4.AX
Standards: FM Class 3600 – 1998, FM Class 3610 – 2010, FM Class 3611 – 2004, FM Class
Markings: IS CL I, DIV 1, GP A, B, C, D when connected per Rosemount drawing 03031-
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is considered a potential
2. The Model 3051 transmitter with the transient terminal block (Option code T1) will not
C6 CSA Explosionproof, Dust-Ignitionproof, Intrinsic Safety and Nonincendive
connected per Rosemount drawing 03031-1019; NI CL 1, DIV 2, GP A, B, C, D;
T4(-50°C ≤ Ta ≤ +70°C) [HART], T5(-50°C ≤ Ta ≤ +40°C) [HART]; T4(-50°C ≤ Ta
≤ +60°C) [Fieldbus/PROFIBUS]; Type 4x
risk of ignition by impact or friction. Care must be taken into account during installation
and use to prevent impact and friction.
pass the 500Vrms dielectric strength test and this must be taken into account during
installation
3810 – 2005
1019 (-50°C ≤ Ta ≤ +60°C); Type 4x
risk of ignition by impact or friction. Care must be taken into account during installation
and use to prevent impact and friction.
pass the 500Vrms dielectric strength test and this must be taken into account during
installation
Markings: Explosionproof Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone
Zone 1, Group IIB+H2, T5; Dust-Ignitionproof Class II, Division 1, Groups E, F, G;
Class III Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D when
connected in accordance with Rosemount drawing 03031-1024, Temperature
Code T3C; Suitable for Class I, Zone 0; Class I Division 2 Groups A, B, C and D,
T5; Suitable for Class I Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal
(See drawing 03031-1053)
No.142-M1987, CSA Std. C22.2 No. 213 - M1987
1, Group IIB+H2, T5; Dust-Ignitionproof for Class II and Class III, Division 1,
Groups E, F and G; Class I, Division 2, Groups A, B, C and D; Suitable for Class I
Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing 03031-
Markings: HART: II 1 G Ex ia IIC T5/T4 Ga, T5(-60°C ≤ Ta ≤ +40°C), T4(-60°C ≤ Ta ≤
+85°C);
II 1 D Ex ta IIIC T95°C T
Temperature Class Process Temperature
T6 -50°C to +65°C
T5 -50°C to +80°C
into account the environmental conditions to which the diaphragm will be subjected. The
manufacturer’s instructions for installation and maintenance shall be followed in detail to
assure safety during its expected lifetime.
contacted.
EN60079-0. The user shall determine suitability for the specific application.
Certificate for full equipment marking.
+70°C)
Fieldbus/PROFIBUS: II 1 G Ex ia IIC T4(-60°C ≤ Ta ≤ +60°C)
DUST: II 1 D Ex ta IIIC T95°C T
HART Fieldbus/PROFIBUS
Voltage Ui 30 V 30 V
Current Ii 200 mA 300 mA
Power Pi 0.9 W 1.3 W
Capacitance Ci 0.012 µF 0 µF
Inductance Li 0 mH 0 mH
105°C Da (-20°C ≤ Ta ≤ +85°C)
500
Process Temperature
105°C Da (-20°C ≤ Ta ≤ +85°C)
500
Input Parameters
Page 23
March 2014 Quick Start Guide
Special Conditions for Safe Use (X):
The apparatus is not capable of withstanding the 500 V insulation test required by
1.
EN60079-11. This must be taken into account when installing the apparatus.
2.
The enclosure may be made of aluminum alloy and given a protective polyurethane
finish; how
ever care should be taken to protect it from impact or abr
asion if located in
paint
Zone 0.
Some variants of the equipment have reduced markings on the nameplate. Refer to t
3.
he
Certificate for full equipment marking.
IA ATEX
FISCO
Certificate: BAS97ATEX1089X
Standards: EN60079-0:2012, EN60079-11:2009
Markings: II 1 G Ex ia IIC T4(-60°C ≤ Ta ≤ +60°C)
Input Parameters
Voltage Ui 17.5 V
Current Ii 380 mA
Power Pi 5.32 W
Capacitance Ci <5 nF
Inductance Li <10 µH
Special Conditions for Safe Use (X):
The apparatus is not capable of withstanding the 500 V insulation test required by
1.
EN60079-11. This must be taken into account when installing the apparatus.
The enclosure may be made of aluminum alloy and given a protective polyurethane
2.
finish; how
ever care should be taken to protect it from impact or abr
Zone 0.
N1
ATEX Type n and Dust
Certificate: BAS00ATEX3105X; Baseefa11ATEX0275X
Standards: EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings: II 3 G Ex nA IIC T5 Gc (-40°C ≤ Ta ≤ +70°C);
II 1 D Ex ta IIIC T95°C T
105°C Da (-20°C ≤ Ta ≤ +85°C)
500
Special Conditions for Safe Use (X):
This apparatus is not capable of withstanding the 500V insulation test that is required by
1.
EN60079-15. This must be taken into account when installing the apparatus.
Some variants of the equipment have reduced markings on the nameplate. Refer to t
2.
Certificate for full equipment marking.
FISCO
paint
asion if located in
he
International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 09.0034X; IECEx BAS 10.0034X
Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-26:2006, IEC60079-31:2008
Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50°C ≤ Ta ≤ +65°C), T5(-50°C ≤ Ta ≤ +80°C);
Special Conditions for Safe Use (X):
1.
Ex ta IIIC T95°C T
105°C Da (-20°C ≤ Ta ≤ +85°C)
500
Process Temperature
Temperature Class Process Temperature
T6 -50°C to +65°C
T5 -50°C to +80°C
This device contains a thin wall diaphragm. Installa
into account the environmental conditions to w
manufacture
assure safet
r’s instructions for installation and maintenance shall be followed in det
y duri
ng its expected lifetime.
hich the diaphragm wi
tion, maintenance and use shall take
ll be subjected. The
ail to
Page 24
Quick Start Guide March 2014
2.For information on the dimensions of the flameproof joints the manufacturer shall be
contacted.
3.The capacitance of the wrap around label, being 1.6 nF, exceeds th
EN60079-0. The
4.
Some variants of the equipment have reduced markings on the nameplate. Refer to t
Certificate for full equipment marking.
IECEx Intrinsic Safety
I7
Certificate: IECEx BAS 09.0076X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: HART: Ex ia IIC T5/T4 Ga, T5(-60°C ≤ Ta ≤ +40°C), T4(-60°C ≤ Ta ≤ +70°C)
Special Conditions for Safe Use (X):
1.
2.
IG IECEx
Certificate: IECEx BAS 09.0076X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (-60°C ≤ Ta ≤ +60°C)
Special Conditions for Safe Use (X):
1.
2.
N7
IECEx Type n
Certificate: IECEx BAS 09.0077X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T5 Gc (-40°C ≤ Ta ≤ +70°C)
Special Conditions for Safe Use (X):
1.
Fieldbus/PROFIBUS: Ex ia IIC T4(-60°C ≤ Ta ≤ +60°C)
If the apparatus is fitted with optional 90V transient
w
ithstanding the 500V insulation test required by IEC60079-11. This
account w
The enclosure may be made of aluminum alloy and given a protective polyurethane
finish; how
Zone 0.
FISCO
If the apparatus is fitted with optional 90V transient
w
ithstanding the 500V insulation test required by IEC60079-11. This
account w
The enclosure may be made of aluminum alloy and given a protective polyurethane
finish; how
Zone 0.
The apparatus is no capable of withstanding the 500V insulation test required by
IEC60079-15. This must be taken into account when installing the apparatus.
user shall determine suitability for the specific applic
Input Parameters
Voltage Ui 30 V 30 V
Current Ii 200 mA 300 mA
Power Pi 0.9 W 1.3 W
Capacitance Ci 0.012 µF 0 µF
Inductance Li 0 mH 0 mH
stalling the apparatus.
hen in
ever, care should be taken to protect it from impact or ab
Capacitance Ci <5 nF
Inductance Li <10 µH
stalling the apparatus.
hen in
ever, care should be taken to protect it from impact or ab
This device contains a thin wall diaphragm. Installa
into account the environmental conditions to w
manufacture
assure safet
In case of repair, contact the manufacturer for information on the di
flameproof joints.
The capacitance of the wrap around label, being 1.6nF, exceeds the
ABNT NBR IEC
If the equipment is fitted with an optional 90V trans
ithstanding the 500V insulation test required by ABNT NBR IRC 60079-11:2008. Th
w
must be taken into account when i
The enclosure may be made of aluminum alloy and given a protective polyurethane
finish; how
Zone 0.
O FISCO
If the equipment is fitted with an optional 90V trans
ithstanding the 500V insulation test required by ABNT NBR IRC 60079-11:2008. Th
w
must be taken into account when i
The enclosure may be made of aluminum alloy and given a protective polyurethane
finish; how
Zone 0.
r’s instructions for installation and maintenance shall be followed in det
ng its expected lifetime.
y duri
60079-0. The user shall determine suitability for the specific applicat
Fieldbus/PROFIBUS: Ex ia IIC T4 Ga (-60°C ≤ Ta ≤ +60°C)
Input Parameters
Voltage Ui 30 V 30 V
Current Ii 200 mA 300 mA
Power Pi 0.9 W 1.3 W
Capacitance Ci 0.012 µF 0 µF
Inductance Li 0 mH 0 mH
ever, care should be taken to protect it from impact or ab
ever, care should be taken to protect it from impact or ab
HART Fieldbus/PROFIBUS
nstalling the equipment.
Input Parameters
Voltage Ui 17.5 V
Current Ii 380 mA
Power Pi 5.32 W
Capacitance Ci <5 nF
Inductance Li <10 µH
nstalling the equipment.
tion, maintenance and use shall take
hich the diaphragm wi
ient suppressor, it is not capable of
FISCO
ient suppressor, it is not capable of
ll be subjected. The
mensions of the
limit in Table 9 of
rasion if located in
rasion if located in
ail to
ion.
is
paint
is
paint
Page 26
Quick Start Guide March 2014
China
E3 China Flameproof
Certificate: GYJ14.1041X; GYJ10.1313X [Flowmeters]
Standards: GB3836.1-2000, GB3836.2-2010, GB12476-2000
Markings: Ex d IIC T6/T5, T6(-50°C ≤ Ta ≤ +65°C), T5(-50°C ≤ Ta ≤ +80°C)
Special Conditions of Use (X):
The relation between ambient temperature arrange and temperature class is as follows:
1.
When used in a combustible dust environment, the maximum ambient temperature is
80°C.
The earth connection facility in the enclosure should be connected reliably.
2.
3.
Cable entry certified by notified body with type of protection Ex d IIC in accordance wi
GB3836.1
location. When used in combustib
IP66 or highe
4.
Obey the warning “Keep tight when the circuit is alive.”
5.
End users are not permitted to change any internal
6.
During installation, use and maintenance of this product, observe the followi
standards:
GB3836.1
and overhaul fo
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electr
installations
GB3836.16-2006 “Electrical apparatus for explosive gas atmospher
Inspection and maintenance of ele
GB50257
atmospheres an
GB12476.2-2006 “Electrical apparatus for use in the presence of co
1-2: Electrical apparatus prot
Selection, installation and maintenance”
GB15577-2007 “Safety regulations for dust explosion prevention and protection”
I3 China Intrinsic Safety
Certificate: GYJ13.1362X; GYJ101312X [Flowmeters]
Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010, GB12476.1-2000
Markings: Ex ia IIC Ga T4/T5
Special Conditions for Safe Use (X):
Symbol “X” is used to denote specific conditions of
1.
a.
b.
The relation between T code and ambient temperature ran
2.
3. Intrinsically Safe parameters:
-2000 and GB3836.2-2000, should be applied when
r level should be applied.
3-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repai
r apparatus used in explosive gas atmospheres”
in hazardous area (other than mines)”
-1996 “Code for construction and acceptance of electric dev
d fire hazard electrical equipment installation engineering”.
If the apparatus is fitted with an optional 90V trans
of
withstanding the 500V insulation test for 1 minute. This must be ta
account w
The enclosure may be made of aluminum alloy and given a protective polyuretha
paint finish; however, care should
located in Zone 0
Flowmeter with 644 Temp Housing T4 -40°C ≤ Ta ≤ +60°C
hen in
Fieldbus/PROFIBUS/FISCO T4 -60°C ≤ Ta ≤ +60°C
Voltage Ui 30 V 30V 17.5 V
Current Ii 200 mA 300 mA 380 mA
Ta Temperature Class
-50°C~+80°C T5
-50°C~+65°C T6
le dust environment, cable entry in accordance wi
components.
ctrical installation (other than mine
ected by enclosures and surface temperature limitation-
use:
stalling the apparatus.
be taken to prot
.
Model T Code Temperature Range
HART T5 -60°C ≤ Ta ≤ +40°C
HART T4 -60°C ≤ Ta ≤ +70°C
HART Fieldbus/PROFIBUS FISCO
installed in a hazardous
ng
es Part 16:
s)”
ice for explosion
mbustible dust Part
ient suppressor, it is not capable
ken into
ect it from impact or abrasion if
ge is:
th
th
r
ical
ne
Page 27
March 2014 Quick Start Guide
Power Pi 0.9 W 1.3 W 5.32 W
Capacitance Ci 0.012 µF 0 µF <5 nF
Note 1: FISCO parameters apply to both Group IIC and IIB.
Note 2: [For Flowmeters] When 644 temperature transmitter is used, the 644
temperature transmitter should be used with Ex-certified associated apparatus to
establish explosion protection system that can be used in explosive gas atmospheres.
Wiring and terminals should comply with the instruction manual of both 644 temperature
transmitter and associated apparatus. The cables between 644 temperatures transmitter
and associated apparatus should be shielded cables (the cables must have insulated
shield). The shielded cable has to be grounded reliably in a non-hazardous area.
4.
Transmitters comply with the requirements for FISCO field dev
IEC60079FISCO
The product should be used with Ex-certified associated apparatus
5.
explosion protect
terminals should comply
apparatus.
6.
The cables between this product and associated apparatus should
(the cables must have insulated shield). The shielded cable has to b
in a non-hazardous area.
End users are not permitted to change any intern components but to settle the probl
7.
in conjunction w
During installation, use and maintenance of this product, observe the followi
8.
standards:
GB3836.1
and overhaul fo
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electr
installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospher
Inspection and maintenance of ele
GB50257
atmospheres an
GB12476.2-2006 “Electrical apparatus for use in the presence of co
1-2: Electrical apparatus prot
Selection, installation and maintenance”
GB15577-2007 “Safety regulations for dust explosion prevention and protection”
N3 China Type n
Certificate: GYJ101111X
Standards: GB3836.1-2000, GB3836.8-2003
Markings: Ex nA IIC T5 (-40°C ≤ Ta ≤ +70°C)
Special Conditions for Safe Use (X):
1.
Symbol “X” is used to denote specific conditions of use: The appara
ithstanding the 500V test to earth for one minute. The must be tak
w
during installation.
The ambient temperature range is -40°C ≤ Ta ≤ +70°C.
2.
3.
Maximum input voltage: 55V.
Cable glands, conduit or blanking plugs, certified by NEPSI with Ex e or Ex n prot
4.
ype and IP66 degree of protection provided by enclosure, should be used on extern
t
connections and redundant cable entries.
5.
Maintenance should be done in non-hazardo
6.
End users are not permitted to change any internal components but to settle the probl
in conjunction w
7.
During installation, use and maintenance of this product, observe the followi
standards:
GB3836.1
and overhaul fo
Inductance Li 0 mH 0mH <10 µH
27:2008. For the connection of an intrinsically safe circuit in accordance wi
Model, FISCO paramete
ion system that can be used in explosive gas atmo
ith the manufacturer to avoid damage to the product.
3-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repai
r apparatus used in explosive gas atmospheres”
-1996 “Code for construction and acceptance of electric dev
d fire hazard electrical equipment installation engineering”.
ith manufacturer to avoid damage to the prod
3-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repai
r apparatus used in explosive gas atmospheres”
rs are listed in the table above.
with the instruction manual of the product a
ctrical installation (other than mine
ected by enclosures and surface temperature limitation-
us location.
ices specified in
to establish
spheres. Wiring and
nd associated
be shielded cables
e grounded reliably
ng
es Part 16:
s)”
ice for explosion
mbustible dust Part
tus is not capable of
en into consideration
uct.
ng
th
em
r
ical
ection
al
em
r
Page 28
Quick Start Guide March 2014
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical
installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16:
Inspection and maintenance of electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for explosion
atmospheres and fire hazard electrical equipment installation engineering”
K2 combination of E2 and I2
K5 combination of E5 and I5
K6 combination of C6, E8 and I1
K7 combination of E7, I7 and N7
K8 combination of E8, I1 and N1
KB combination of E5, I5 and C6
KD combination of E8, I1, E5, I5 and C6
Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 09-HS446883A-PDA
Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications on
ABS classed vessels, marine, and offshore installations.
Certificate: 23155/A3 BV
Requirements: Bureau Veritas Rules for the Classification of Steel Ships
Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS; Pressure
transmitter type 3051 cannot be installed on diesel engines
SDN Det Norske Veritas (DNV) Type Approval
Certificate: A-12801
Intended Use: Det Norske Veritas’ Rules for Classification of Ships, High Speed & Light Craft
and Det Norske Veritas’ Offshore Standards
Application:
TemperatureD
HumidityB
VibrationA
EnclosureD
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002
Application: Environmental categories ENV1, ENV2, ENV2 and ENV5
C5 Custody Transfer - Measurement Canada Accuracy Approval
Certificate: AG-0226; AG-0454; AG-0477
Location Classes
Type3051
EMCB
Page 29
June 2014
Quick Start Guide
Page 30
Quick Start Guide
June 2014
Page 31
June 2014
Quick Start Guide
Page 32
Quick Start Guide
June 2014
Page 33
June 2014
Quick Start Guide
Page 34
00825-0100-4774, Rev. FA, 06/14
?00825-0100-4774?
Quick Start Guide
00825-0100-4774, Rev FA
June 2014
Device
revision
Host
(1)
AllDD4: DD Rev 1www.fieldbus.org
AllDD5: DD Rev 1www.fieldbus.org
Emerson
8
Emerson
1.
1. FOUNDATION fieldbus device revision can be read using a FOUNDATION fieldbus capable configuration tool.
2.Device driver file names use device and DD revision. To access functionality, the correct device driver must be
Emerson 375 / 475: DD Rev 2 Easy Upgrade Utility
Device driver
(2)
(DD)
AMS V 10.5 or
higher: DD Rev 2
AMS V 8 to 10.5:
DD Rev 1
Obtain at
www.emersonprocess.com
www.emersonprocess.com
Device driver (DTM)
www.emersonprocess.com
Manual document
number
00809-0100-4774
Rev. CA or newer
installed on your control and asse t management hosts, and on your configuration tools.
Rosemou nt Inc.
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 906-8889
Emerson Process
Management
Asia Pacific Priva te Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743