Emerson Rosemount 2160 Quick Start Guide

Quick Start Guide
00825-0100-4160, Rev CB
Rosemount™ 2160 Wireless Level Detector
Vibrating Fork
September 2020
Quick Start Guide September 2020
About this guide...........................................................................................................................3
Installation................................................................................................................................... 6
Configuration.............................................................................................................................14
Product certifications................................................................................................................. 22
2 Rosemount 2160 Wireless Level Detector
September 2020 Quick Start Guide

1 About this guide

This Quick Start Guide provides basic guidelines for the Rosemount 2160. Refer to the Rosemount 2160 Reference Manual for more instructions. The manual and this guide are also available electronically at Emerson.com/
Rosemount.
NOTICE
Power module considerations.
Each Power Module contains two "C" size primary lithium/thionyl chloride
batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Use caution when handling the power module. The Power Module may
be damaged if dropped from heights in excess of 20 ft. (6 m).
Power modules should be stored in a clean and dry area. For maximum
battery life, storage temperature should not exceed 86 °F (30 °C).
The power module may be replaced in a hazardous area. The power
module has surface resistivity greater than one gigaohm and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
Shipping considerations for wireless products.
The unit was shipped to you without the power module installed.
Remove the power module prior to shipping.
Each power module contains two “C” size primary lithium batteries.
Primary lithium batteries are regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping.
Quick Start Guide 3
Quick Start Guide September 2020
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the level detector is installed by qualified personnel and in
accordance with applicable code of practice.
Use the level detector only as specified in this manual. Failure to do so
may impair the protection provided by the level detector.
The weight of a level detector with a heavy flange and extended fork
length may exceed 37 lb. (18 kg). A risk assessment is required before carrying, lifting, and installing the level detector.
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the level detector is consistent
with the appropriate hazardous locations certifications.
Before connecting a handheld communicator in an explosive
atmosphere, ensure that the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In explosion-proof/flameproof and non-incendive/type n installations, do
not remove the housing covers when power is applied to the level detector.
Both housing covers must be fully engaged to meet flameproof/
explosion-proof requirements.
WARNING
Process leaks could result in death or serious injury.
Ensure the level detector is handled carefully. If the process seal is
damaged, gas might escape from the vessel (tank) or pipe.
4 Rosemount 2160 Wireless Level Detector
September 2020 Quick Start Guide
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces
The flange and process seal may be hot at high process temperatures.
Allow to cool before servicing.
Quick Start Guide 5
OK
OK
A B
A B
OK
OK
OK
C
A B
Quick Start Guide September 2020

2 Installation

2.1 Fork alignment in a pipe installation

Figure 2-1: Correct Fork Alignment for Pipe Installation
A. Tri Clamp process connections have a circular notch B. Threaded process connections have a groove

2.2 Fork alignment in a vessel (tank) installation

Figure 2-2: Correct Fork Alignment for Vessel (Tank) Installation
6 Rosemount 2160 Wireless Level Detector
A. Tri Clamp process connections have a circular notch B. Threaded process connections have a groove
Flanged process connections have a circular notch
C.
A
B
A
B
September 2020 Quick Start Guide

2.3 Mounting the threaded version

2.3.1 Seal and protect the threads

Use anti-seize paste or PTFE tape according to site procedures.
A gasket may be used as a sealant for BSPP (G) threaded connections.

2.3.2 Threaded vessel (tank) or pipework connection

Vertical installation.
Horizontal installation.
A. Tighten using the hexagon nut only
B. Gasket for BSPP (G) threaded connection
Quick Start Guide 7
A
A
Quick Start Guide September 2020

2.3.3 Threaded flange connection

Procedure
1. Place the customer-supplied flange and gasket on the vessel (tank) nozzle.
A. Gasket (customer supplied)
2.
Tighten the bolts and nuts with sufficient torque for the flange and gasket.
3. Screw the level detector into the flange thread.
A. Tighten using the hexagon nut only
B. Gasket for BSPP (G) threaded connection
8 Rosemount 2160 Wireless Level Detector
A
September 2020 Quick Start Guide

2.4 Mounting the flanged version

Procedure
1. Lower the level detector into the nozzle.
A. Gasket (customer supplied)
2. Tighten the bolts and nuts with sufficient torque for the flange and gasket.
Quick Start Guide 9
A
Quick Start Guide September 2020

2.5 Mounting the Tri Clamp version

Procedure
1. Lower the level detector into the flange face.
A. Seal (supplied with Tri Clamp)
2. Fit the Tri Clamp.
10 Rosemount 2160 Wireless Level Detector
A
B
September 2020 Quick Start Guide

2.6 Wireless battery installation

To install the battery that supplies all power to the Rosemount 2160:
Procedure
Remove the housing cover on the battery compartment side.
1.
2.
Connect the battery.
3. Replace the battery cover and tighten to safety specification (metal­to-metal).
Figure 2-3: Wireless Battery Installation
A. Battery cover
Battery
B.
Quick Start Guide 11