9. Programming the Receiver Operating Frequency . . . . . .23
READ AND SAVE THESE INSTRUCTIONS
Safety Instructions
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK,
OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
a. Use this unit only in a manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
b. Before servicing or cleaning unit, switch power off
at service panel and lo c k service panel
disconnecting means to prevent power from being
switched on accidentally. When the service
disconnecting means cannot be locked, securely
fasten a warning device, such as a tag, to the
service panel.
4. The downrod furnished with the fan provides the
minimum recommended floor to fan blade clearance
for an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least
7 feet from the floor to prevent accidental contact with
the fan blades.
6. Follow the recommended instructions for the proper
method of wiring your ceiling fan. If you do not know
enough about electrical wiring, have your fan installed
by a licensed electrician.
NOTE: This fan is suitable for use with solid-state speed
controls.
NOTE: All set screws must be checked and re-tightened
where necessary before installation.
1. Read your owner’s manual carefully and keep it for
future reference.
2. Be careful of the fan and blades when cleaning,
painting, or working near the fan. Always turn off the
power to the ceiling fan before servicing.
3. Do not put anything into the fan blades while they are
turning.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned
off at the fuse box before wiring, and do not operate
fan without blades.
2. All wiring must be in accordance with the National
Electrical Code “ANSI/NFPA 70-2014” and Local
Electrical Codes. Use the National Electrical Code if
Local Codes do not exist. The ceiling fan must be
grounded as a precaution against possible electrical
shock. Electrical installation should be made or
approved by a licensed electrician.
3. The outlet box and joist must be securely mounted and
capable of reliably supporting at least 50 pounds. Use
only U.L. outlet boxes listed as “Acceptable for Fan
Support of 22.7kg. (50 lbs.) or less”, and use the
mounting screws provided with the outlet box. Most
outlet boxes commonly used for support of light fixtures
are not acceptable for fan support and may need to be
replaced. Consult a qualified electrician if in doubt.
WARNING
To reduce the risk of electrical shock, this fan must be
installed with an isolating wall control/switch.
To reduce the risk of fire or electrical shock, this fan
should only be used with fan speed control, Model No.
FR-7861, manufactured by Rhine Electric Co., Ltd.
This product is designed to use only those parts
supplied with this product and/or any accessories
designated specifically for use this product by Emerson
Electric Co. Substitution of parts or accessories not
designated for use with this product by Emerson could
result in personal injury or property damage.
To reduce the risk of personal injury, do not bend the
blade f lange w h e n in s t a l l i ng t h e blade flanges,
balancing the blades or cleaning the fan. Do not insert
foreign objects in between rotating fan blades.
!
ETL Model No.: CF630
2
1. Unpacking Instructions
6
3
5
4
1
2
11
10
9
7
8
WARNING
Do not install or use fan if any part is damaged or
missing. Call Toll-Free for replacement parts:
!
1-800-654-3545
WARNING
This product is designed to use only those parts
supplied with this product and/or any accessories
designated specifically for use with this product by
Emerson Electric Co. Subs t i t u t i o n of parts or
accessories not designated for use with this product
by Emerson Electric Co. could result in personal injury
or property damage.
!
1.1
Check to see that you have received the following parts:
NOTE: If you are uncertain of part description, refer
to exploded view illustration.
HARDWARE BAG CONTENTS
Part Description Quantity
1 Threaded Studs, #8-32 x 1-1/4” 2
2 Lockwashers, External Tooth #8 2
3 Knurled Knobs, #8-32 2
4 Wire Connectors 5
5 Clevis Pin 1
6 Hairpin Clip 1
7 #6-32 x 1/2” Truss Head Screws w/Lockwashers 6
8 #8-32 x 1/4” Washer Head Screws 16
9 1/4-20 x 9/16” Pan Head Screws
with Lockwashers 11
10 #6-32 x 3/8” Truss Head Screw w/Lockwasher 2
11 Blade Balance Kit 1
NOTE: Place the parts from the hardware bags in a
small container to keep them from being lost.
If any parts are missing, call 1-800-654-3545
for replacement parts before proceeding.
PACKAGE CONTENTS
Part Description Quantity
A Fan Motor Assembly 1
B Ceiling Cover 1
C Motor Coupler Cover 1
D Lower Housing 1
E Light Kit Housing Assembly 1
F Decorative Grill 1
G Glass Shade 1
H Fan Blade Flanges 5
I Ceiling Fan Blades
J Hanger Bracket 1
K Hanger Ball / 4.5” Downrod Assembly 1
L 13-Watt CFL / E26 Medium Base Bulbs 3
M RCFP Receiver 1
N SW406 Wall Control with Hardware 1
E
A
F
B
C
D
5
J
K
L
G
M
N
H
....
OFF
....
....
....
I
OFFON
OFFON
FFON
O
1.2
Remov e t h e fan asse m b ly from th e p r o tecti v e
plastic bag. Place the fan assembly into the upper
styrofoam with the top of the motor facing up.
The upper styrofoam serves as a holder for the fan
during the first stages of assembly.
emersonfans.com
Please contact 1-800-654-3545 for further assistance
3
ETL Model No.: CF630
1. Unpacking Instructions (Continued)
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
THIS FAN IS SUITABLE FOR WET LOCATIONS SUCH AS
PORCHES, PATIOS, AND DECKS.
Tools Needed for Assembly
One Phillips Head Screwdriver One Stepladder
One 1/4” Blade Screwdriver One Wire Stripper
Materials
Wiring outlet box and box connectors must be of type
required by the local code. The minimum wire would be
a 3-conductor (2-wire with ground) of following size:
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
2. Electrical Requirements
Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.
WARNING
To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable for
Fan Support of 22.7 kg. (50 lbs.) or less”, and use
screws supplied with outlet box. Most outlet boxes
commonly used for support of light fixtures are not
acceptable f o r fan support and may n e e d to b e
replaced. Consult a qualified electrician if in doubt.
WARNING
Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the ceiling fan must be prope r l y grounded as a
precaution against possible electrical shock.
!
!
WARNING
Before assembling your ceiling fan, refer to section on
proper method of wiring your fan (page 13). If you feel
you do not have enough wiring knowledge or
experience, have your fan installed by a licensed
electrician.
Your Emerson Ceiling Fan comes supplied with a
RCFP Receiver and SW406 Wall Control. This system
allows you to regulate your ceiling fan speed and light
control.
SR401 Remote Control (sold separately) may be used
with this Ceiling Fan.
The outlet box must be securely anchored and capable
of withstanding a load of at least 50 pounds.
If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time and
remove the existing light fixture.
WARNING
To avoid fire or shock, follow all wiring instructions
carefully.
Any e l e c trical w o r k no t described in these
instructions should be done or approved by a licensed
electrician.
Pleas e cal l Em e r son t echni c a l s u pport at
1- 800-654-3545 if you have any quest ions ab out
installation and operation of this ceiling fan.
!
!
ETL Model No.: CF630
4
3. Ceiling Fan Assembly
PHILLIPS HEAD SET SCREW
(LOOSENED)
HANGER BALL
4.5" DOWNROD
PIN
GREEN GROUND WIRE
4.5" DOWNROD
THREE 80" MOTOR
WIRES (UNTWISTED)
3.1
Disconnect electrical power to the branch circuit at the
Circuit Breaker or Main Fuse Box before attempting to
nstall the Ceiling Fan on the Outlet Box.
i
3.2
Remove the Hanger Ball by loosening the Phillips
Set Screw in the Hanger Ball until the Ball falls freely
down the Downrod (Figure 1).
Remove the Pin from the Downrod, then remove the
Hanger Ball.
Retain the Pin and Hanger Ball for reinstallation in
Step 3.8.
NOTE: Do not loosen the screw holding the green
ground wire.
Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the ceiling fan must be prope r l y grounded as a
recaution against possible electrical shock.
p
Figure 1
!
WARNING
3.3
Separate, untwist and unkink the three 80” Motor
Wires.
Route the 80” Black, Blue and White Motor Wires
through the Downrod (Figure 2).
5
Figure 2
emersonfans.com
Please contact 1-800-654-3545 for further assistance
ETL Model No.: CF630
MOTOR
COUPLER
4.5"
DOWNROD
LOOSEN
PHILLIPS HEAD
SET SCREWS (2)
3. Ceiling Fan Assembly (Continued)
HAIRPIN
CLIP
HAIRPIN
CLIP
CLEVIS
PIN
RETIGHTEN
PHILLIPS HEAD
SET SCREWS (2)
MOTOR
COUPLER
CLEVIS
PIN
COUPLER
COVER
FAN MOTOR
HOUSING
GROMMET
DOWNROD
3.4
oosen the two Set Screws in the Motor Coupler for
L
installation of the Downrod (Figure 3).
eat the 4.5” Downrod in the Motor Coupler (Figure 3).
S
Rotate and align the Downrod holes with all the holes in
the Motor Coupler (Figure 3).
3.5
Align the Clevis Pin holes in the Downrod with the holes
in the Motor Coupler.
Figure 3
Install the Clevis Pin and secure with the Hairpin Clip
(Figure 4).
The Clevis Pin must go through the holes in the Motor
Coupler. It is critical that the Clevis Pin in the Motor
Coupler is properly installed and securely tightened.
Retighten the Phillips Head Set Screws to secure the
Downrod to the Motor (Figure 4).
WARNING
3.6
Make sure the Grommet is properly installed in the
Coupler Cover, then slide the Coupler Cover on the
Dow n r o d until it r e s t s on the Fan M otor Housing
(Figure 5).
!
It is critical that the clevis pin and set screws in the
motor coupler are properly installed and securely
tightened. Failure to verify that the pin and set screws
are properly installed could result in the fan falling.
Figure 4
Figure 5
ETL Model No.: CF630
6
3. Ceiling Fan Assembly (Continued)
COUPLER
COVER
4.5" DOWNROD
CEILING
C
OVER
4.5" DOWNROD
HANGER BALL
PIN
SET SCREW
HANGER BALL/
DOWNROD
ASSEMBLY
6 to 9
INCHES
3.7
Place the Ceiling Cover over the 4.5” Downrod and rest
it on the Coupler Cover (Figure 6).
Be sure both the Ceiling Cover and the Coupler Cover
are oriented correctly as in Figure 6.
3.8
NOTE: Only use the hanger ball supplied with this
ceiling fan.
Figure 6
Route the three 80” Motor Wires through the Hanger
Ball.
Reinstall the Hanger Ball (Figure 7) on the Downrod as
follows:
Position the Hanger Ball Pin through the two holes in
the Downrod and align the Ball so the Pin is captured in
the groove in the top of the Hanger Ball.
Pull the Hanger Ball up tight against the Pin a nd
securely tighten the Set Screw in the Hanger Ball.
NOTE: A loose set screw could create fan wobble.
3.9
The fan comes with Black, Blue and White Wires that
are 80-inches long.
Before installing the fan, measure up approximately
6 t o 9-inch es above top of H anger Bal l/Downro d
Assembly (Figure 8).
Cut off excess Wires and strip back insulation 1/2-inch
from end of Wires.
Figure 7
7
Figure 8
emersonfans.com
Please contact 1-800-654-3545 for further assistance
Carefully turn the partially assembled Ceiling Fan over
and place it on the styrofoam for final preparation
Figure 9).
(
Remove the five Shipping Spacers and the Spacer
ttachment Screws from the Motor before installation of
A
blade assemblies (Figure 9).
Discard the five shipping spacers and spacer screws.
3.11
Your ceiling fan is supplied with one set of five fan
blades.
Mount Blade Flange to Ceiling Fan Blade using three
#8-32 x 1 /4” W a sher Hea d Sc r e ws ( s u pplie d )
(Figure 10).
Repeat this procedure for the other four fan blades and
blade flanges.
Figure 9
Figure 10
ETL Model No.: CF630
8
3. Ceiling Fan Assembly (Continued)
#6-32 x 3/8" TRUSS
HEAD SCREW WITH
LOCKWASHER
LOWER HOUSING
1/4-20 x 9/16" PAN HEAD
SCREW w/LOCKWASHER
(2 per blade/flange assembly)
BLADE/ FLAN GE AS SEMB LY
MOTOR HUB
3.12
Loosely attach one Blade/Flange Assembly to the
Motor Hub by securing the two 1/4-20 x 9/16” Pan
ead Screws with Lockwashers (supplied) (Figure 11).
H
Make sure the screws are NOT
procedure for other four Blade/Flange Assemblies.
Once all five Blade/Flange Assemblies are secured to
the Motor Hub, proceed to tightening all 1/4-20 x 9/16”
Pan Head Screws with Lockwashers at this time.
WARNING
To reduce the risk of personal injury, do not bend the
blade f lange w h e n in s t a l l i ng t h e blade flanges,
balancing the blades or cleaning the fan. Do not insert
foreign objects in between rotating fan blades.
!
tightened. Repeat this
3.13
Remove one #6-32 x 3/8” Truss Head Screw with
Lockwasher from the Fan Motor Housing (retain for
later use).
Loosen the other two screws to assemble the Lower
Housing to the Fan Motor Housing (Figure 12).
Figure 11
Rotate the Lower Housing to engage the two loosened
screws in the two key hole slots.
Replace the #6-32 x 3/8” Truss Head Screw with
Lockwasher (removed previously) and tighten all three
screws to secure the Lower Housing to the Fan Motor
Housing.
NOTE: Make sure wires are not pinched between
the Lower Housing and the Fan Motor Housing.
A spa r e #6-3 2 x 3/ 8 ” Trus s Hea d Scr e w with
Lockwasher is provided in hardware bag, if needed.
Figure 12
emersonfans.com
Please contact 1-800-654-3545 for further assistance
9
ETL Model No.: CF630
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.