Emerson QC54 FOUNDATION Installation Manual

FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
FieldQ
FieldQ Control Module
2
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
Fig. 2.1 Check proper mounting before connecting
air supply and electrical wiring.
OK
OK
Control Module Type Label =
QC54..WP.. = Foundation Fieldbus™ Weather Proof
QC54..P4..= Foundation Fieldbus™ Non­incendive/Non Sparking/FISCO ic
QC54..P1..= Foundation Fieldbus™ intrinsically safe/FISCO
Actuator Type Label =
QS xxxx = Single acting (Spring Return)
QD xxxx = Double acting
Fig. 2.2 Identification
2
1
1 Applicable modules
QC54 - FOUNDATION Fieldbus™
- Weather Proof
- Non-incendive/Non-Sparking/FISCO ic
- Intrinsically safe/FISCO
Note:
These variations can be equipped with one or two pilot valves:
* One pilot valve is default and suitable for normal
operation of double acting or spring return actuators.
* Two pilot valves are required for Fail in Last Posi-
tion function on double acting actuators. The enclosures have a IP66 or NEMA 4X, ingress protected rating.
2 Before starting
* Actuator must be isolated both pneumatically and electrically before any (dis)assembly is begun. * Hazards related to the control of external processes under measurement, are beyond the scope of of the content described in this document. * Installation, adjustment, putting into service, use, assembly, disassembly and maintenance of the control module must be done by qualified personnel. * Do not install, operate, or maintain a Q series control module without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. * To avoid personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. * Be sure that the actuator is correctly mounted before connecting air supply and electrical wiring (see Installation & Operation Manual FieldQ Valve Actuator, DOC.IOM.Q.E) * Check the module label for the right execution (see figure 2.2) * Check the type of actuator: single or double acting (see figure 2.2). * For mechanical installation of the module see installation instruction leaflet DOC.QC4.MTI.1, as shipped with the module. * If you have any questions regarding these instructions, contact your Emerson sales office before proceeding as shipped with the module.
3
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
Control Module Type Label
Terminal com­partment
Lockable Module cover
Option: 1 or 2 speed control throttles
Fig 2.4 Control module overview
Option: Local Manual Control Option: Additional Local Manual
Control for “Fail in Last Position”
2.1 Mechanical alignment and mounting of
the control module
The control module is equipped with an alignment­edge on top of the module. This allows easy align­ment and mounting of the control module on to the actuator housing.
Procedure: (see figure 2.3)
1. First take care that both mating faces from the
actuator and control module are clean and free
of dirt.
2. Check if the module has the required function
3. Remove the transparent film from the control
module.
4. Ensure seals are placed correctly.
5. Level the screws with the surface.
6. Place the alignment-edge (1) of the control
module at the top of the pneumatic interface.
7. Flip the module down taking care that the IPT
Probe (2) on the actuator fits in the mating hole
on the control module and loosely place the
screws.
8. Tighten screws according force in sequence.
Alignment-edge
Alignment-edge
Fig. 2.3 Alignment and mounting of control
module to actuator
IPT probe
Tightening moments
The Control Module should be fastened by using an Allen key and applying the following tightening moments:
- Allen Key No 5: 6.1 to 6.6 Nm (54 - 58.4 In.lbs)
(1)
(2)
4
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
3 Pneumatic connections
Fig 3.2 Install drip loops
5µm
OK
IMPORTANT
1 The actuator/valve combination can move
after connecting the air supply.
2 Ensure that the QC54 control modules are
mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
3 Check that the maximum supply pressure
P
max
= 8bar/116Psi
4 Be sure that the minimum required supply
pressure for the application is available at the actuator.
5 Take appropriate measures to prevent conden-
sation or moisture to entering the actuator or the control module. Condensation or moisture can damage these components and can result in failures.
6 The exhaust ports Ra and Rb on the module
(see figure 3.1) are shipped from the factory with transport protection.
* If ingress protection IP66 or NEMA 4X is re-
quired, appropriate connections must be used in exhaust ports Ra & Rb.
3.1 Operating media :
* Air or inert gasses. * Air filtered at 5 micron. * Dew point 10 K below operating temperature. * For subzero applications take appropriate
measures.
3.2 Single acting (spring return) or Double acting actuator :
1 Remove the transport sticker from the air supply
(Ps).
2 Connect air supply to port (Ps).
Fig. 3.1: Pneumatic connections
Single acting
Control
Module cover
Ps
1/4” BSP or 1/4” NPT
Double acting
Ps
1/4” BSP or 1/4” NPT
Ra
Ra
Rb
5
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
4 Electric Connections
WARNING
* Do not put the Control module and the Pneu-
matic module in direct contact with magnetic material. This can cause damage or malfunc­tion of the position feedback.
* If the Control Module is used in a manner not
specified by the manufacturer, the protection provided by the equipment may be impaired.
* If required, mount earth wire (1) between top
(2) and bottom (3) ring of earth wire connec­tion (see figure 4.1).
Table 4.1 Electrical data QC54 - FF
Voltage range * 9 to 32 volts Maximum current 18 mA Reverse polarity
protection
Unit is not polarity sensitive.
Required external protection
Restrict the power supply current to <600mA.
Environmental conditions :
Temperature * -20°C to +50°C
(-4°F to +122°F)
Humidity 0 to 85% at 25°C(+77°F)
derate to 50% above 40°C (104°F) (non-condensing).
Altitude Operating full power available
up to 2000 meter (6000 feet).
Use In- and outdoor.
* In case the Control module is used in Hazardous
locations, check the chapters 10, 11 or 12 for detailed instructions.
Fig.4.1 Earth wire connections
!
6
FieldQ
April 2017
Installation guide
DOC.IG.QC54.1 Rev.: 2
1 2
+
-
3
Blue
Brown
Green/Yellow
M127/8" UNC
1
2
3
4
1
2
3
4
1
2
3
1
2 4
Fig. 4.3 Terminal connections
Quick connector pinouts:
(male chassis part)
Fig. 4.4 Quick connector pinouts
Quick connector
Terminal
Electrical entries:
Button board
4.1 Procedure
1. Remove control module cover (see figure 4.2)
2. Guide the cable(s) through the electrical
entry(ies).
- Use and mount cable glands as required by
national or local legislation.
- When IP65/NEMA4X ingress protection is
required, the electrical entries must be fitted with glands rated IP65/NEMA4X or higher.
- Apply minimum thread counts:
For NPT, at least 5 full threads For Metric, at least 8 full threads for Group A/B and 5 full threads of Group C/D
3. Connect the FOUNDATION™ Fieldbus signal
to the applicable terminals (see figure 4.3).
- For 7/8” or M12 quick connector pinout,
see figure 4.3 and 4.4.
- For hazardous area connections, see the
wiring instructions in 11.5 and 11.6
4. Mount the function module cover to the hous-
ing (see figure 4.2) or continue with chapter 5.
Take care that the cover seal is in place to comply
to dust and water tightness according to
IP66/NEMA4X.
4.2 F
oundation
Fieldbus installation and
wiring guidelines
Please check www.fieldbus.org for various applica- tion guides like installation and wiring guidelines.
Table 4.2 Wiring dimensions
Wire type Dimensions
Solid wire 2.5mm2 max. Stranded wire 0.33 - 2.5mm2 or 22 - 12 AWG
Table 4.3 Tools
Too l Dimensions
Cover lock screw Allen key 2mm Tool for terminals Screw driver 0.6 x 3.5
Fig. 4.2 Installing wiring
Field wiring Actuator wiring
FF
Power supply
Wiring Terminals
3/4”NPT
or M20
1/2”NPT
or M20
Control Module Type Label
Terminal compartment
Lockable Module cover
Loading...
+ 14 hidden pages