Emerson XJ200, PW-200J Installation And Operating Instructions Manual

Page 1
technical bulletin
XJ200 Installation and Operating Instructions
General Description
The XJ200 wireless communication modules are radio communication systems for con­trolling and supervising units. The XJ200 consists of the XJ200 radio module P/N 318-5050 and its power supply PW-200J P/N 318-5051.
The XJ200 can cover a variety of functions within the monitoring network:
Master: when it is connected to the X-WEB or E2 monitoring system.
Slave/Repeater: when it is connected to the subnets of devices equipped with RS485.
Repeater: when it is assigned the function as a simple bridge towards other subnets that cannot be reached directly by the master.
The XJ200 modules enable 2-way communication between Dixell devices/modules equipped with an RS485 output that are appropriately connected to each other and the X­WEB or E2 unit, thereby replacing the connection via an RS485 cable.
Up to 15 devices can be connected to the same XJ200 (communication between the module and the devices is via RS485), thereby covering several workstations with the same commu­nication module. Up to 30 XJ200 modules can be connected to one (1) master XJ200.
The maximum distance possible between the XJ200 modules in an open space (with no obstacles) is 200 meters (656 feet approx.). This distance can be remarkably reduced in the presence of interference such as radio emitters, generators of electrical or magnetic fields or solid objects that can affect the proper communication between the XJ200 modules.
The range of serial addresses allowed on the instruments connected to the XJ200 modules is from 1 to 244.
Note that in order to work with the XJ200 modules, the instruments must be equipped with an RS485 serial port and use MODBUS-RTU communication protocol.
Document Part # 026-4833 Rev 0 26-FEB-2013
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 2
technical bulletin
XJ200 Installation and Operating Instructions
General Warnings and Safety Precautions
CAUTION! Read the following precautions before using this manual:
•This bulletin forms an integral part of the product and must be kept near the device for quick and easy reference.
•The device must not be used for purposes other than those described below and particularly, it cannot be used as a safety device.
•Verify the limits of application before proceeding.
SAFETY PRECAUTIONS
•Verify that the connections comply with the instructions in this manual before connecting the device.
•Do not expose the unit to water or humidity: use the device only within the stipulated working limits, avoiding sudden changes in temperature and high atmospheric humidity in order to pre­vent condensation from forming.
•Caution: disconnect the electrical connections of the device before any maintenance.
•The module must never be opened.
•If the device is faulty or malfunctions, return it to the retailer or refer to the return address with a precise description of the fault.
Front Panel LEDs
The XJ200 module has three LEDs on the front panel:
Figure 1 - XJ200
POWER Green - Flashing with a frequency of 1 Hz: the module is ON and running RS485 Yellow - Data is being transmitted/received via RS485 by the module RADIO Green - The module is transmitting via radio
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 2 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 3
technical bulletin
XJ200 Installation and Operating Instructions
Installation and Assembly
Package Contents
Figure 2 - XJ200 Package Contents
Each XJ200 package contains the following components:
1. XJ200 radio device
2. Two self-tapping screws 3.9x6.5T to mount the XJ200 to the fixing bracket
3. Wall fixing bracket
4. Instruction manual
XJ200 Required Tools for Mounting
Mounting Directly
Parts required for assembly (not supplied)
Figure 3 - Parts Required For Assembly
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 3 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 4
technical bulletin
XJ200 Installation and Operating Instructions
1. To fix the module directly to the wall, use Figure 4 as a guide to make the two holes “B” at the distance indicated in Figure 4.
Figure 4 - Dimensions (not to scale)
2. Insert the dowels and mount the screws with a maximum distance of 8 mm from the head to the wall.
3. Fix the XJ200 to the head of the screws by rotating the con­tainer appropriately.
Fixing with the Use of Bracket
A suitable fastening bracket is included in every package to be used to:
• shelf mounting
• pipe mount fitting with appropriate retaining clamps (not supplied)
• wall mounting
As shown in the following pictures:
CAUTION!
Set the XJ200 in the desired place in a VERTICAL POSITION.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 4 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 5
technical bulletin
XJ200 Installation and Operating Instructions
Avoid horizontal or slanting positions.
Figure 5 - Correct Mounting Positions
Parts required for assembly (not supplied)
1. Mount the XJ200 to the fixing bracket using the two screws in the package.
2. The two screws are to be entered in holes “A” as shown in Figure 4.
3. The bracket can be bent and fixed so that the XJ200 is installed in a vertical position.
Recommendations for Proper Installations
• If possible, place the module high up in order to guarantee enhanced data transmission or reception.
• If possible, avoid intermediate obstacles such as barriers, walls, floors and counters between the modules.
• If necessary, pass through the obstacle using the cable and install the module on the opposite side in order to have it in direct view with the master module connected to the X-WEB or E2.
• The maximum distance possible between the XJ200 modules in an open space (with no obstacles) is 200 meters (656 feet approx.).
• If the installation spans over a number of floors, try to position all the modules on the same floor and connect the devices via cable in order to prevent communication prob­lems due to obstacles caused by the floor or ceiling.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 5 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 6
technical bulletin
• The allowed temperature range for correct functioning is between 0°C and 60°C (32°F to 140°F). Avoid places subject to heavy vibrations, corrosive gas, excessive filth, or humidity.
Connections
XJ200 Installation and Operating Instructions
Each module is supplied complete with a 1.5 meter (4.9 feet approx.) cable to connect the serial com­munication line and the power line.
Figure 6 - XJ200 with Cable
The XJ200 is powered by 5V supplied by the PW­200J power supply. The PW-200J requires 24VAC supply voltage input.
Figure 7 - PW-200J Power Supply
X-WEB - XJ200 Master Connection
Set the XJ200 to Master
The XJ200 connected to the X-WEB must be configured as master.
1. Remove the cover of the XJ200.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 6 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 7
technical bulletin
XJ200 Installation and Operating Instructions
2. Close the jumper found inside the XJ200 by inserting the micro switch as shown in the picture below.
Figure 8 - Micro Switch
3. Close the cover of the XJ200 once again.
4. Connect the XJ200, PW200J and the X-WEB as shown in the connection diagram below.
Figure 9 - XJ200 and X-WEB Connection
NOTE: When using the XJ200 with an XR, XM, or XEV controller,
the XJ200 external power supply
must be used.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 7 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 8
technical bulletin
XJ200 Installation and Operating Instructions
XJ200 and X-WEB Connection
Remove the Phoenix-style connector (supplied with the PW-200J) and use as a junction for the RS485 line. The connection between the XJ200 and X-WEB is then implemented as fol­lows:
1. Connect the GREEN wire of the XJ200 to the RS485 “+” terminal of the X-WEB.
2. Connect the PINK wire of the XJ200 to the RS485 “-” terminal of the X-WEB.
3. Power the X-WEB and the PW200J once again.
XJ200 Connection and Devices Equipped with a Serial Output
XJ200 and PW-200J Connection
1. Connect the white 5-pin connector to the “+5V supply” 5-pin connector of the PW-200J.
2. Connect the other devices to the RS485 serial line in compliance with the polarity.
3. Remove the Phoenix-style connector (supplied with the PW-200J) and use as a junction for the RS485 line with the XJ200 as follows:
• Connect the GREEN wire of the XJ200 to the RS485 “+” terminal.
• Connect the PINK wire of the XJ200 to the RS485 “-” terminal.
Figure 10 - XJ200 and PW-200J Connection
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 8 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 9
technical bulletin
XJ200 Installation and Operating Instructions
Device Equipped with a TTL Serial Output
Device with TTL Output but Not Capable of Powering the XJ200. Example Ranges: Prime
CX, Wing Basic New, XC400C and XC600C
XJ200 and PW-200J Connection
1. Connect the GREEN wire to the RS485 “+” terminal of the PW-200J.
2. Connect the PINK wire to the RS485 “-” terminal of the PW-200J.
3. Connect the white connector to the “+5V supply” connector of the PW-200J.
Controller Connection with TTL and PW-200J
1. Connect the other devices to the RS485 serial line in compliance with the polarity.
2. Connect the two TTL outputs of the PW-200J and the device.
3. Then connect the RS485 line to the PW-200J, in compliance with the polarity.
Figure 11 - XJ200 with TTL and PW-200J Connection
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 9 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 10
technical bulletin
XJ200 Installation and Operating Instructions
E2 and XJ200 Networking
XJ200 Wireless New Installation Procedure
E2-XJ200 Master Connection
In the new installation, you need to find a location in the store that has a direct line of sight with at least one or two wireless modules (slave modules) on the sales floor. If the system performs up to four hops, those in the indirect view can find their way to the master wireless module location to them.
Figure 12 - XJ200 Wireless
From the designated position, run a communication cable (three conductors) and wiring to handle 24VAC, and depending on the distance, the wire gauge needs to be calculated. The master module needs a power supply that takes 24 VAC and powers the wireless module with 5VDC.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 10 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 11
technical bulletin
XJ200 Installation and Operating Instructions
Figure 13 - XJ200 Wireless with PW-200J Power Supply
To turn a wireless module into a master module, take off the cover and move the jumper over both pins, otherwise the module remains a slave.
Figure 14 - Jumper Positions
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 11 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 12
technical bulletin
XJ200 Installation and Operating Instructions
Connect the module’s MODBUS wires to the E2 MODBUS network. The MODBUS wires have reversed polarities. The device can’t be used with the E2 right away. You may need to config­ure the device first and connect it to the E2.
Figure 15 - Dixell MODBUS Networking
NOTE: The wiring polarity between the XJ200 and E2 is reversed.
E2 Property Location E2 Property New Value
Menu-7-3-1-C7 MODBUSOffLnDly 00:02:00
Menu-7-3-1-C7 MOD1 Rsp Delay 800 ms
Menu-7-3-1-C7 MOD1 Msg Delay 30 ms
Table 1 - E2 MODBUS Delay Settings
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 12 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 13
technical bulletin
XJ200 Installation and Operating Instructions
Note that the XJ200 requires E2 version 3.03F01/4.03F01 and higher.
Figure 16 - E2 MODBUS Delay Settings
The slave wireless modules on each case needs to be mounted upright, with enough clear­ance as possible (see Figure 17).
Figure 17 - Slave Wireless Module Case Mounting
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 13 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 14
technical bulletin
XJ200 Installation and Operating Instructions
Commissioning a New Network
Once the master and slave modules are installed, wired and powered, you now may follow these steps:
1. Press the service button on each slave module. This operation will have the slave module send the master the list of nodes connected to it for the master to build a communication path (during this phase all three LEDs flash every second).
2. After one to two minutes, each slave module provides a status using the “RADIO” or “RS485” LED during the testing phase.
• If there is a good communication path, the “RADIO” will have a green LED.
• If there is a communication problem, the “RS485” will have a yellow LED. Try adjusting the module and repeat the process by pressing the service button.
3. When the network is ready to operate, start the acquisition procedure on the E2. The slaves and master modules will start to communicate when the E2 requires information to the MODBUS modules and starts coming online.
Removing a Node from the Wireless Network
The master module can recognize if a node is removed from the network. If a node is removed, the master module will act as follows:
1. The master module enters to “discovery phase” to find a new path to reach the offline nodes. While in this phase, lasting up to three seconds, the master disregards the mes­sages coming from the E2.
2. After the three discovery phases (up to three seconds per phase), the master stops for 20 minutes in the discovery phase, and forwards the messages through the last known path. Every 20 minutes a new discovery phase starts.
3. If the node is actually removed from the network, it must be deleted from the E2, to avoid the master module to keep on starting the discovery phase.
4. To remove a slave module, unplug the E2 MODBUS from the master module and initiate a discovery phase by pressing the service button, to create a new path.
Adding a Node to the Wireless Network
To add a node to the wireless network, refer to Commissioning a New Network.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 14 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 15
technical bulletin
Troubleshooting
Problem Possible Cause Possible Solution
XJ200 Installation and Operating Instructions
Device does not appear on supervisory controller.
Device appears on supervisory controller, the status goes off linebut returns to on lineafter a few minutes.
Device appears on supervisory controller but status is “off line”.
All devices appear on supervisory controller but status is “off line”.
A slave module is removed from the network but other modules seem to go “off line” with it.
A new slave module is added to the network but it does not appear as “on line” on the supervisory controller.
Device not commissioned in supervisory controller.
Communication may have been delayed to the supervisory controller.
Master is not reporting slave module to the supervisory controller.
Master is not communicating with Slave modules.
When a module is removed from the network, the master reconfigures the best communication path to all remaining slave modules.
Ensure the line of sight to the master is not obstructed.
Follow commissioning procedures for supervisor controller.
Check the supervisory controller’s communication summary for percentage of lost packets. If problem remains constant with one particular module, reposition that module or add a repeater.
Slave module is not communicating with the master. Press Test button on slave module and allow ample time to establish communication. If the yellow LED remains on, reposition the slave module to improve line of sight with the master.
Ensure that you have followed the installation steps in the proper order. A good communication path needs to be established between the master and slaves before connecting the supervisory controller and commissioning devices. Install the master as high as possible to ensure optimal coverage.
Allow ample time for the master to reconfigure the communication path. If other modules do not return “on line” press the Test button on the slave module that is “off line”. If the module does not return “on line”, it is possible that communication is blocked. If this is the case, reposition the slave module or add a repeater between the master and slave.
Press the Test button and allow ample time for the master to establish a new communication path.
Table 2 - Troubleshooting Guide for XJ200 Devices
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 15 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 16
technical bulletin
Problem Possible Cause Possible Solution
XJ200 Installation and Operating Instructions
The Yellow RS485 LED remains on.
The Green RADIO LED remains on.
Unable to establish communication between Master and slave module.
A good communication path has NOT been established between the master and slave module.
A good communication path has been established between the master and slave.
Obstacle blocking the radio signal.
Ensure that the master and slave module have both been powered up. Press the Test button on the front of the XJ200 slave module. Reposition the slave module for better reception, and then press the Test button again. Install another XJ200 module between the master and slave module to act as a repeater.
No problem.
Transmitters are not in line of sight. Position the master module as high as possible. Reposition the Slave module to a new position. Install another XJ200 module between the master and slave module to act as a repeater.
Table 2 - Troubleshooting Guide for XJ200 Devices
How to Verify Connection Quality Between the XJ200 Master and the Other XJ200s in the Network
The following must be implemented in order to verify the connection quality between an XJ200 and the master connected to the X-WEB or E2:
1. Connect and power the XJ200 Master to the X-WEB or E2.
2. Set the XJ200 in place where it is to be installed.
3. Power the XJ200 and press the Test button for a couple of seconds.
4. A test cycle begins and lasts a few minutes.
5. At the end of the cycle, the following remains on:
• Good communication: the GREEN “RADIO” LED is on.
• Insufficient communication: the YELLOW “RS485” LED is on; in this case, try installing the XJ200 in a better position or connect another XJ200 between the Master and the XJ200 being tested.
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 16 of 17
©2013 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 17
technical bulletin
Technical Data
Operating Frequency Europe version: XJ200 -00000: 869.4 - 869.650 MHz
Container Self-extinguishing ABS
Format Front panel 80 x 80 mm; depth 5 mm
Power Supply XJ200 +5Vdc (from the controller or from the PW-200J module)
Power Consumption 0.30 VA max.
Operating Temperature From 0°C to 60 °C (32°F to 140°F)
Storage Temperature 25°C to 60°C (-13°F to 140°F)
Relative Humidity 20 - 85% (no condensation)
XJ200 Installation and Operating Instructions
AUS and USA version: XJ200 -10000: 922 MHz
Note: the PW200J feeder or any Dixell controllers that can power the XJ200 are SELVtype. Max Power <18VA, DC current < 8A.
Table 3 - Technical Data
The XJ200 -0000 is compliant with the following standards:
• ETSI EN 300 220-2 V2.1.2 (2007-06)
• ETSI EN 301 489-3 V1.4.1 (2002-08)
• CEI EN 60950-1 (2007-02)
It therefore meets the essential requirements of the following Directives:
• Radio and telecommunications terminal equipment 99/5/EC
• Electromagnetic compatibility 2004/108/EC
• Low Voltage equipment 2006/95/EC
The XJ200 -1000 (922MHz) is compliant with the following standards and rules: AS/NZS 4268: 2008: Classification: Schedule 1: Item 45 FCC 15.247
Document Part # 026-4833 Rev 0 26-FEB-2013 Page 17 of 17
This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or
their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice.
Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-4833 26-FEB-2013 Emerson is a trademark of Emerson Electric Co. ©2013 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.
Loading...