Emerson PN MMI-20019808 User Manual

Page 1
P/N MMI-20019808, Rev. AC

Micro Motion® EtherNet/IP Module

User Manual
July 201
2
Page 2
Micro Motion Customer Service
U.S.A. 800-522-MASS (800-522-6277) (toll free)
Canada and Latin America +1 303-527-5200 (U.S.A.)
Asia Japan 3 5769-6803
All other locations +65 6777-8211 (Singapore)
Europe U.K. 0870 240 1978 (toll-free)
All other locations +31 (0) 318 495 555 (The Netherlands)
Email: flow.support@emerson.com
Page 3

Contents

Chapter 1 Before You Begin
1.1 About the Micro Motion EtherNet/IP Module............................................................1
1.1.1 Functional overview ....................................................................................1
1.1.2 Communications.........................................................................................2
1.1.3 External view of device ................................................................................3
1.1.4 Default web pages.......................................................................................3
1.1.5 Setting up for the petroleum measurement or concentration
measurement application ...........................................................................3
Chapter 2 Installation
2.1 Components ............................................................................................................5
2.2 Device installation ....................................................................................................5
2.3 Micro Motion Ethernet Config Tool installation (optional) ........................................9
2.3.1 System requirements ..................................................................................9
2.3.2 Installation steps .........................................................................................9
2.4 Final steps ..............................................................................................................10
Contents
Chapter 3 Basic Network Configuration
3.1 TCP/IP settings .......................................................................................................13
3.1.1 IP access control........................................................................................15
3.2 Modbus serial network settings..............................................................................16
Chapter 4 Micro Motion Web Server
4.1 Overview ................................................................................................................17
4.2 General access information ....................................................................................17
4.2.1 Ports..........................................................................................................17
4.2.2 Users .........................................................................................................17
4.3 Micro Motion web pages ........................................................................................17
4.3.1 Home page for standard configuration......................................................18
4.3.2 Home page for concentration measurement configuration.......................19
4.3.3 Home page for petroleum measurement configuration ............................21
User Manual I
Page 4
Contents
Chapter 5 Troubleshooting
5.1 LED indicators.........................................................................................................23
5.2 Common problems ................................................................................................24
Appendix A Connector Pin Assignments
A.1 Ethernet connector ................................................................................................25
A.2 Power connector....................................................................................................25
A.3 Micro Motion Ethernet Config Tool connection ......................................................26
A.3.1 Configuration cable...................................................................................26
A.3.2 RJ-11 (EtherNet/IP Module) .......................................................................26
A.3.3 DBF9 (PC)..................................................................................................27
A.4 Modbus serial network interface.............................................................................27
A.4.1 Bias resistors .............................................................................................27
A.4.2 Termination ..............................................................................................27
A.4.3 Pin assignments (EtherNet/IP Module) ......................................................28
A.5 Typical connection .................................................................................................28
Appendix B Device Profile
B.1 Object classes.........................................................................................................29
B.2 Object details .........................................................................................................29
B.2.1 Identity Object, Class 01h..........................................................................29
B.2.2 Message Router, Class 02h ........................................................................31
B.2.3 Assembly Object, Class 04h.......................................................................31
B.2.4 Port Object, Class F4h................................................................................33
B.2.5 TCP/IP Interface Object, Class F5h .............................................................34
B.2.6 Ethernet Link Object, Class F6h..................................................................36
B.2.7 Diagnostic Object, Class AAh.....................................................................36
B.2.8 Parameter Data Input Mapping Object, Class B0h......................................37
B.2.9 Parameter Data Output Mapping Object, Class B1h ..................................38
B.3 I/O data ..................................................................................................................39
B.3.1 Input assembly for standard configuration ................................................39
B.3.2 Output assembly for standard configuration .............................................40
B.3.3 Input parameters (explicit data) for standard configuration.......................40
B.3.4 Output parameters (explicit data) for standard configuration ...................42
B.3.5 Input assembly for concentration measurement configuration .................43
B.3.6 Output assembly for concentration measurement configuration..............44
B.3.7 Input parameters (explicit data) for concentration measurement
configuration ............................................................................................44
B.3.8 Output parameters (explicit data) for concentration measurement
configuration ............................................................................................46
B.3.9 Input assembly for petroleum measurement configuration.......................47
B.3.10 Output assembly for petroleum measurement configuration....................48
II Micro Motion EtherNet/IP Module
Page 5
Contents
B.3.11 Input parameters (explicit data) for petroleum measurement
configuration ............................................................................................48
B.3.12 Output parameters (explicit data) for petroleum measurement
configuration ............................................................................................50
B.4 Get and Set services................................................................................................51
B.4.1 Get Attribute Single service.......................................................................51
B.4.2 Set Attribute Single service........................................................................51
B.5 Data types ..............................................................................................................52
B.6 Codes and integer values........................................................................................52
B.7 Status words...........................................................................................................61
B.7.1 Status Word 1 ...........................................................................................61
B.7.2 Status Word 2 ...........................................................................................61
B.7.3 Status Word 3 ...........................................................................................62
B.7.4 Status Word 4 ...........................................................................................62
B.7.5 Status Word 5 ...........................................................................................63
B.7.6 Status Word 6 ...........................................................................................64
B.7.7 Status Word 7 ...........................................................................................65
Appendix C Specifications
C.1 Physical ..................................................................................................................67
C.1.1 Housing.....................................................................................................67
C.1.2 Dimensions ...............................................................................................67
C.2 Electrical.................................................................................................................67
C.2.1 Power supply.............................................................................................67
C.2.2 Power consumption ..................................................................................67
C.3 Environmental........................................................................................................67
C.3.1 Relative humidity ......................................................................................67
C.3.2 Temperature.............................................................................................67
C.4 Regulatory compliance...........................................................................................68
C.4.1 EMC compliance (CE) ................................................................................68
C.4.2 UL/c-UL compliance ..................................................................................68
C.4.3 Galvanic isolation on Modbus serial interface ............................................68
Appendix D Return Policy
D.1 Requirements.........................................................................................................69
D.1.1 New and unused equipment......................................................................69
D.1.2 Used equipment........................................................................................69
User Manual III
Page 6
Contents
IV Micro Motion EtherNet/IP Module
Page 7
Before You Begin

1 Before You Begin

1.1 About the Micro Motion EtherNet/IP Module

The Micro Motion EtherNet/IP Module is a customization of the Anybus Communicator from HMS Industrial Networks. The EtherNet/IP Module enables integration of industrial devices into the Ethernet network with no loss of functionality, control, or reliability. The EtherNet/IP Module can be used for new or retrofit installations.
This manual contains only the information required to install, configure, and use the EtherNet/ IP Module. Other OEM features are still enabled on the device, but are not documented here. For information on other features of the device, see the manual entitled Anybus Communicator User Manual, available on the HMS web site.

1.1.1 Functional overview

The EtherNet/IP Module acts as a gateway between the serial output of a Micro Motion device and an EtherNet/IP network.
The EtherNet/IP Module is a Modbus master and an Ethernet slave. On the Modbus side, it polls the transmitter for a standard set of process variables and stores the data locally. See Section B.3 for a list of available data. On the Ethernet side, it receives requests for data and responds with the current values.
The following figures illustrate the EtherNet/IP Module in operation.
In Figure 1-1, the EtherNet/IP Module is installed with a Model 1500 or Model 2500
transmitter. See the Product Data Sheet for a list of all supported transmitters. All sensor connections are supported (integral, 4-wire, 9-wire).
In Figure 1-2, the EtherNet/IP Module is part of an MVD Direct Connect installation.
The web browser is used for transmitter configuration and administration, via a
connection to the Micro Motion web pages on the EtherNet/IP Module.
The configuration loop is used only by the Micro Motion Ethernet Config Tool. In typical
installations, this tool is not needed.
User Manual 1
Page 8
Before You Begin
PLC
EtherNet/IP Module
Transmitter
Other devices (SCADA, PC, Inverter)
To sensor
PC with Micro Motion Ethernet Config Tool
Configuration loop (with configuration cable)
Modbus/RS-485
Ethernet
Web browser
PLC
EtherNet/IP Module
Core processor
Other devices (SCADA, PC, Inverter)
To sensor
PC with Micro Motion Ethernet Config Tool
Configuration loop (with configuration cable)
Modbus/RS-485
Ethernet
Web browser
Barrier
Figure 1-1 EtherNet/IP Module with Model 1500 or Model 2500 transmitter
Figure 1-2 EtherNet/IP Module in MVD Direct Connect installation

1.1.2 Communications

The following communications methods and protocols are supported:
EtherNet/IP Module to Micro Motion transmitter: Modbus RTU on RS-485
EtherNet/IP Module to Ethernet network:
2 Micro Motion EtherNet/IP Module
EtherNet/IP group 2 and 3 servers
Web server
10/100 Mbit/sec, twisted pair
Page 9

1.1.3 External view of device

A
Ethernet connector
B
Configuration Switches
C
Status LEDs
D
PC connector (configuration)
E
Modbus serial connector (transmitter)
F
Power connector
G
DIN rail connector
Figure 1-3 External view of device
Before You Begin

1.1.4 Default web pages

The EtherNet/IP Module is preloaded with the Micro Motion standard web pages. These web pages allow the user to view process data and alerts, to configure the most commonly used parameters on the transmitter, to perform maintenance procedures, and to download support files from the device.
1.1.5 Setting up for the petroleum measurement or concentra­tion measurement application
To support the petroleum measurement or concentration measurement application, Micro Motion supplies alternate sets of web pages and configuration files. These are available for download from the Micro Motion web site.
User Manual 3
Page 10
Before You Begin
4 Micro Motion EtherNet/IP Module
Page 11
21
44 (RS-485/B)
43 (RS-485/A)
42 (VDC +)
41 (VDC –
14 (RS-485/B)
13 (RS-485/A)
12 (VDC +)
11 (VDC –
I.S. terminals
for connection to core processor
Non-I.S. terminals
for connection to remote host and power supply
Barrier

2 Installation

2.1 Components

Ensure that you have all required components:
Micro Motion EtherNet/IP Module
Power connector
Micro Motion EtherNet/IP Resource CD
- Micro Motion EtherNet/IP Module User Manual
- EDS file
- Micro Motion Ethernet Config Tool
Configuration cable
Modbus serial cable and connector (included)
Ethernet cable and connector (not included)
Installation

2.2 Device installation

1. If you are using the EtherNet/IP Module with a transmitter, mount the transmitter and
wire it to the sensor and to power.
2. If you are using a Micro Motion MVD Direct Connect flowmeter, mount and wire the
core processor and barrier. See the following illustration to identify the barrier terminals.
User Manual 5
Page 12
Installation
1
2
1
2
Snap on Snap off
Power
1) 24 VDC
2) Ground
1
9
5
6
1
2
4
1
3. If you are using a transmitter:
a. Power up the transmitter. b. Set the Modbus address on the transmitter to 1. c. If your transmitter does not support Modbus auto-detect, configure its RS-485
terminals as follows:
- Modbus RTU
- 38400 baud
- 2 stop bits
- No parity
4. If you are using MVD Direct Connect:
a. Power up the core processor and barrier. b. Set the Modbus address on the core processor to 1.
5. Ensure that the following slot registers are available for use by the EtherNet/IP Module:
- 655–750
- 751–846
If you are currently using these slot registers, you must reprogram your Modbus interface.
6. Mount the EtherNet/IP Module on the DIN rail.
7. Wire the EtherNet/IP Module to power (24 VDC).
6 Micro Motion EtherNet/IP Module
Page 13
Installation
1
9
5
6
1
2
4
1
Modbus serial connector
1) Not used
2) Not used
3) Not used
4) Not used
5) Not used
6) Not used
7) Not used
8) RS-485/A
9) RS-485/B
Transmitter
Modbus terminals
RS-485/A RS-485/B
Model 1500 33 34
Model 1700 with analog outputs 5 6
Model 2500 33 34
Model 2700 with analog outputs 5 6
Model 3500 with screw-type or solder-tail terminals
32a 32b
Model 3500 with I/O cables 25 24
Model 3700 12 11
EtherNet/IP Module
8. Install the Modbus serial cable between the EtherNet/IP Module and the RS-485
terminals on the transmitter (or the I.S. barrier, if present).
9. Set the configuration dip switches on the EtherNet/IP module as follows:
- Switches 1–7: Off
- Switch 8: On
User Manual 7
This sets the IP addess to 192.168.0.1.
10. If you are using a Model 1500, Model 2500, or Series 3000 transmitter, ensure that the
RS-485 terminals are in RS-485 mode. You may need to cycle power to the transmitter and wait 15 seconds before applying power to the EtherNet/IP Module.
11. Power up the EtherNet/IP Module. At this point, the module will attempt to make a
Modbus connection to the transmitter. If the Subnet Status LED (LED 5) is green, continue. If it is not green, see Section 5.1.
12. Set the network settings for the EtherNet/IP Module.
a. Change Ethernet address setting for your PC so that it is on the same subnet as
the device. When prompted, enter the following:
- IP address: 192.168.0.x, where x is something other than 1
- Subnet mask: 255.255.255.0
b. Disable the popup blocker on your web browser. c. Use a crossover cable (or a standard cable with a switch) and your web browser
to connect to the device, using the IP address assigned in Step 6: 192.168.0.1.
d. At the login screen, log in as user admin. The default password is admin. Ignore
the auto-configuration popup window.
e. On the Network Settings page, change the settings as required, and close the
web browser. f. At the EtherNet/IP Module, set all dip switches to Off. g. Cycle power to the EtherNet/IP Module.
Page 14
Installation
1
3
5
2
4
6
EtherNet connector
1) TD+
2) TD–
3) RD+
4) Termination
5) Termination
13. Connect the EtherNet/IP Module to the Ethernet network.
14. Wait for the auto-configuration process to complete.
IMPORTANT
For initial startup, you must use the auto-configuration process to ensure that device memory is completely set up.
15. Add the EtherNet/IP Module to the Ethernet network control system. The EDS file is available on the Resource CD, the EtherNet/IP Module (download from Administration page), and the MicroMotion web site.
For more information on transmitter installation and wiring, see your transmitter installation manual. For information on configuring the RS-485 terminals and making an RS-485 connection, see your transmitter configuration manual.
8 Micro Motion EtherNet/IP Module
Page 15
Installation

2.3 Micro Motion Ethernet Config Tool installation (optional)

If you do not plan to use the Micro Motion Ethernet Config Tool, you do not need to install it. The Micro Motion Ethernet Config Tool is used for the following tasks:
Configuration of some network settings. Depending on your network, you may be able
to use switches for all required settings.
(Petroleum measurement or concentration measurement application only)
Downloading the alternate web pages and configuration files into the EtherNet/IP Module.
IMPORTANT
The configuration files and web pages are tightly coupled. Download files provided by Micro Motion only if you plan to use the Micro Motion web pages, Do not change any settings or transactions in the configuration file.

2.3.1 System requirements

Pentium 133 MHz or higher
10 MB of free space
8 MB RAM
Windows NT v4.0 or higher, Windows 2000, or Windows XP
Internet Explorer v4.01 SP1 or higher

2.3.2 Installation steps

1. Install the software program. Locate and run the EtherNet/IP Module setup program on
the EtherNet/IP Module Resource CD and follow the on-screen instructions.
User Manual 9
Page 16
Installation
1
9
5
6
1
2
4
1
PC connector
1) Ground
2) Ground
3) RS-232 Rx
4) RS-232 Tx
2. Connect the configuration cable from your PC to the EtherNet/IP Module.
Note
For information on the Micro Motion Ethernet Config Tool user interface, see the Anybus Communicator manual.

2.4 Final steps

1. From your browser, login to the EtherNet/IP Module as user admin.
2. Use the Device Configuration page to configure the EtherNet/IP Module.
3. Set up I/O at your Ethernet host.
- If you are not using RSLogix, use your standard method. For information on the
I/O assemblies, see Section B.3.
- If you are using RSLogix, select ETHERNET-MODULE - Generic Ethernet Module
and enter the required information. See the following figures.
Note
If Comm Format is anything other than INT, the data sizes will be different from the sizes shown.
10 Micro Motion EtherNet/IP Module
Page 17
Installation
Figure 2-1 I/O setup for the EtherNet/IP Module with standard configuration
Figure 2-2 I/O setup for the EtherNet/IP Module with concentration measurement
User Manual 11
Page 18
Installation
Figure 2-3 I/O setup for the EtherNet/IP Module with petroleum measurement
12 Micro Motion EtherNet/IP Module
Page 19
Basic Network Configuration

3 Basic Network Configuration

3.1 TCP/IP settings

To participate on the Ethernet network, the EtherNet/IP Module needs a valid TCP/IP configuration.
The EtherNet/IP Module can retrieve the TCP/IP settings from a DHCP or BootP server. If no such server is found, the EtherNet/IP Module uses the settings from the system file \ethcfg.cfg. If this file is not found, or the settings are invalid, the EtherNet/IP Module will halt and report an error on the status LED. However, the network configuration may still be accessed via the Ethenet Config Tool.
You can define the TCP/IP settings for the EtherNet/IP Module in four ways:
Micro Motion Network Configuration web page (recommended)
Configuration switches on the device
Ethernet Config Tool
System file \ethcfg.cfg on the device

Micro Motion web page

The Network Configuration page, in the Micro Motion web pages, allows you to set the IP address, gateway address, and subnet address. If you connect to the EtherNet/IP Module using a crossover cable and the default IP address, you can set all three parameters. The changes will take effect at the next connection.

Configuration switches

If the configuration switches on the EtherNet/IP module are set to any non-zero value, the device is locked to the following network settings:
User Manual 13
Page 20
Basic Network Configuration
Table 3-1 Network settings, locked
Parameter Value
IP address 192.168.0.x
Gateway 192.168.0.255
Subnet 255.255.255.0
DHCP OFF
To set the IP address, see the following table.
Table 3-2 Network settings using switches
Switch
1 2 3 4 5 6 7 8
where x is determined by the switches
IP address
OFF OFF OFF OFF OFF OFF OFF ON 192.168.0.1
OFF OFF OFF OFF OFF OFF ON OFF 192.168.0.2
OFF OFF OFF OFF OFF OFF ON ON 192.168.0.3
... ... ... ... ... ... ... ... ...
ON ON ON ON ON ON ON OFF 192.168.0.254
ON ON ON ON ON ON ON ON Invalid

Ethernet Config Tool

See the Anybus Communicator manual for instructions.
IMPORTANT
If you change the network settings using the Ethernet Config Tool, you will not be able to use the Micro Motion web pages to change network settings in the future. All future changes to network settings must beperformed using the Ethernet Config Tool.

ethcfg.cfg file

To set the network settings using the \ethcfg.cfg file:
1. Set all configuration switches on the device to OFF.
2. Make a connection to the device from the Ethernet Config Tool and disable TCP/IP Settings (Fieldbus parameter section). Alternatively, you can access the TCP/IP parameters using the TCP/IP Interface Object.
14 Micro Motion EtherNet/IP Module
Page 21
3. From the FTP server, access and edit \ethcfg.cfg as desired.
In this scenario, if no \ethcfg.cfg file is found, the EtherNet/IP Module will attempt to retrieve the settings via DHCP for 30 seconds. If the attempt fails, the EtherNet/IP Module will halt and indicate an error via the LEDs.
See the Anybus Communicator manual for more information.

3.1.1 IP access control

You can limit the set of IP addresses that are allowed to connect to the EtherNet/IP Module. This information is stored in the system file \ip_accs.cfg.
Sample file:
[Web]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module web
...
[FTP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module FTP
...
[EtherNet/IP]
xxx.xxx.xxx.xxx (All nodes listed can access the EtherNet/IP Module via
...
[All]
xxx.xxx.xxx.xxx (Fallback setting; used when one or more of the above
...
Basic Network Configuration
server)
server)
EtherNet/IP)
keys is omitted)
User Manual 15
Page 22
Basic Network Configuration

3.2 Modbus serial network settings

The default parameters for the Modbus serial network are listed in the following table.
Table 3-3 Default parameters for Modbus serial network
Parameter Default setting Valid values
Baud 38400 1200 to 57600
Data bits 8 (Modbus RTU) 7 (Modbus ASCII)
8 (Modbus RTU)
Parity None None
Odd Even
Physical layer RS485 RS485 (required for EtherNet/IP Module)
Start bits 1 1
Stop bits
(1)
(1) For baud rates of 38400 and above, 2 stop bits are required.
21
2
These must match the RS-485 parameters configured in the transmitter. To change them in the EtherNet/IP Module, you must use the Ethernet Config Tool. See the Anybus Communicator manual for more information.
16 Micro Motion EtherNet/IP Module
Page 23
41

4 Micro Motion Web Server

4.1 Overview

The configuration and administration functions of the Micro Motion EtherNet/IP Module are implemented as web pages on the device. Users use their web browsers to connect to the web server. They are automatically directed to the Micro Motion web pages.

4.2 General access information

4.2.1 Ports

The web server communicates through port 80.

4.2.2 Users

Micro Motion Web Server
Two users are predefined for the Micro Motion web pages. You can change the passwords, but you cannot add or delete users.
Username
admin admin Complete access to all functions on the Micro Motion web pages
operator operator Read-only access to the Micro Motion web pages
Default password
Description

4.3 Micro Motion web pages

When the user connects to the EtherNet/IP Module, he is prompted for a user name and password, then taken to the EtherNet/IP Module home page. The home page looks different depending on the configuration file installed on the EtherNet/IP Module.
User Manual 17
Page 24
Micro Motion Web Server

4.3.1 Home page for standard configuration

Figure 4-1 EtherNet/IP Module home page
On this page, current data for the most commonly used process variables is displayed. Tabs provide access to other web pages:
Administration page; allows the admin user to change passwords and perform
downloads from the EtherNet/IP Module (the EDS file).
Network Configuration page: allows the user to view or configure EtherNet/IP Module
network settings
All other pages: various transmitter tasks, including viewing process data,
configuration, calibration, stopping and starting totalizers, and Smart Meter Verification. For more information about any of these tasks, see your transmitter’s configuration manual.
18 Micro Motion EtherNet/IP Module
Page 25
Micro Motion Web Server
Note
If the EtherNet/IP Module loses communication with the Micro Motion device, all process variables are shown as 0.0f. Also, an explicit read to 0xB0-0x01-0x1D returns a value of 0.

4.3.2 Home page for concentration measurement configuration

Figure 4-2 EtherNet/IP Module home page with concentration measurement
User Manual 19
Page 26
Micro Motion Web Server
On this page, panels are used to provide access to the most commonly used standard process variables and to concentration measurement process variables. Tabs provide access to other web pages:
Administration page: allows the admin user to change passwords and perform
Network Configuration page: allows the user to view or configure EtherNet/IP Module
All other pages: various transmitter tasks, including viewing process data,
Note
If the EtherNet/IP Module loses communication with the Micro Motion device, all process variables are shown as 0.0f. Also, an explicit read to 0xB0-0x01-0x1D returns a value of 0.
downloads from the EtherNet/IP Module (the EDS file).
network settings
configuration, calibration, stopping and starting totalizers, and Smart Meter Verification. For more information about any of these tasks, see your transmitter’s configuration manual.
20 Micro Motion EtherNet/IP Module
Page 27
Micro Motion Web Server

4.3.3 Home page for petroleum measurement configuration

Figure 4-3 EtherNet/IP Module home page with petroleum measurement
On this page, panels are used to provide access to the most commonly used standard process variables and to petroleum measurement process variables. Tabs provide access to other web pages:
Administration page: allows the admin user to change passwords and perform
downloads from the EtherNet/IP Module (the EDS file).
Network Configuration page: allows the user to view or configure EtherNet/IP Module
network settings
User Manual 21
Page 28
Micro Motion Web Server
All other pages: various transmitter tasks, including viewing process data,
Note
If the EtherNet/IP Module loses communication with the Micro Motion device, all process variables are shown as 0.0f. Also, an explicit read to 0xB0-0x01-0x1D returns a value of 0.
configuration, calibration, stopping and starting totalizers, and Smart Meter Verification. For more information about any of these tasks, see your transmitter’s configuration manual.
22 Micro Motion EtherNet/IP Module
Page 29
51

5 Troubleshooting

5.1 LED indicators

LED Number/Name Status Meaning
Troubleshooting
1Module
Status
2Network
EtherNet
Status
N/A 3 Link Off The module does not sense a link.
N/A 4 Activity Flashing green Packet is received or transmitted.
5 Subnet
Status
6Device
Modbus Serial
Status
Off No power applied to the module.
Solid green The module is operating correctly.
Flashing green Standby; the module has not been initialized.
Flashing red Minor fault. The module may or may not be able to recover.
Solid red Major fault. No recovery is possible. The module must be retuned to
Micro Motion for repair. See the manual for the return policy.
Flashing green/red Self-test.
Off The module has not power or no IP address has been assigned.
Solid green The module has at least one established EtherNet/IP connection.
Flashing green There are no EtherNet/IP connections established to the module.
Flashing red One or more of the connections to this module has timed out.
Solid red The module has detected that its IP address is already in use.
Flashing green/red Self-test.
Green The module is connected to an Ethernet network.
Off Power off.
Flashing green Running correctly, but one or more transaction errors has occurred.
Green Running.
Red Transaction error/timeout or network stopped. Check the Modbus serial
network wiring and configuration, especially the baud.
Flashing red Missed transactions.
Off Power off.
Flashing red/green Configuration missing or invalid.
Red Contact Micro Motion customer service.
Flashing red Contact Micro Motion customer service.
Green Initializing.
Flashing green Configuration OK.
User Manual 23
Page 30
Troubleshooting

5.2 Common problems

Symptom Resolution
Problem during configuration Upload / Download.
The Config Line LED turns red in the Ethernet Config Tool.
The serial port seems to be avail­able, but it is not possible to connect to the EtherNet/IP Module.
Poor performance • In the Ethernet Config Tool, right-click
No Modbus serial network func­tionality
Process variables displayed or reported as 0
Serial communication failed. Try again.
Serial communication failed. Try again.
• The serial port may be in use by another application. Exit the EtherNet/IP Module Configuration Tool and close all other applications, including the ones in the system tray. Try again.
• Select another serial port. Try again.
select
Sub-Network Status to see status / diagnostic information about the Moldbus
serial network. If the EtherNet/IP Module reports a large number of re-transmissions, check your cabling and/or try a lower baud rate setting for the Modbus serial network (if possible).
• Is the Sub-Net Monitor in the Ethernet Config Tool active? The sub-network monitor has a negative influence on the overall performance of the gateway, and should be used only when necessary.
• Is the Node Monitor in the Ethernet Config Tool active? The node monitor has a negative influence on the overall performance of the gateway, and should be used only when necessary.
• Use the Data logger functionality of the Ethernet Config Tool to record the serial data communication on the sub-network.
• If no data is being transmitted, use the Ethernet Config Tool to check the configura­tion.
• If no data is being received, check the cables and connections. Also verify that the transmitted data is correct.
• Verify the Modbus connection between the EtherNet/IP Module and the device.
Sub-Network in the Navigation window and
24 Micro Motion EtherNet/IP Module
Page 31
Connector Pin Assignments
18
Pin Signal
Housing Cable shield
1TD+
2TD
3RD+
4Termination
5Termination
6RD
7Termination
8Termination
12
Pin Description
124 VDC
2Ground

Appendix A: Connector Pin Assignments

A.1 Ethernet connector

A.2 Power connector

Use 60/75 or 75 x C copper (CU) wire only.
The terminal tightening torque must be between 5 and 7 lbs-in (0.5 to 0.8 Nm).
User Manual 25
Page 32
Connector Pin Assignments
1
2
3
4
5
6
7
8
9
1
2
3
4
DP9F (PC) RJ-11 (EIP)
Ground
Ground
Rx
Tx
RS232 Tx
RS232 Rx
Ground
1
2
3
4
Pin Description
1Ground
2Ground
3 RS-232 Rx (Input)
4 RS-232 Tx (Output)

A.3 Micro Motion Ethernet Config Tool connection

A.3.1 Configuration cable

A.3.2 RJ-11 (EtherNet/IP Module)

26 Micro Motion EtherNet/IP Module
Page 33

A.3.3 DBF9 (PC)

Pin Description
1Ground
2Ground
3 RS-232 Rx (Input)
4 RS-232 Tx (Output)
96
15 (female)

A.4 Modbus serial network interface

The Modbus serial network is based on an RS-485 physical layer.
Connector Pin Assignments

A.4.1 Bias resistors

When idle, RS-485 enters an indeterminate state, which may cause the serial receivers to pick up noise from the serial lines and interpret this as data. To prevent this, the serial lines should be forced into a known state using pull-up and pull-down resistors, commonly known as bias resistors.
The bias resistors forms a voltage divider, forcing the voltage between the differential pair to be higher then the threshold for the serial receivers, typically >200 mV. Note that bias resistors shall only be installed on one node. Installing bias resistors on several nodes may compromise the signal quality on the network and cause transmission problems.

A.4.2 Termination

To avoid reflections on the serial lines, it is important to properly terminate the sub-network by placing termination resistors between the serial receivers near the end nodes.
Additionally, if the distance from the EtherNet/IP Module to the transmitter is greater than 100 feet, Micro Motion recommends adding the termination resistors.
The resistor value should ideally match the characteristic impedance of the cable, typically 100 to 120 Ω.
User Manual 27
Page 34
Connector Pin Assignments
Pin Description
1 5 V output (100 mA max)
2 Unused
3 Unused
4 Unused
5Ground
6 Unused
7 Unused
8 RS-485/A (Tx+)
9 RS-485/B (Tx–)
(housing) Cable shield
96
15 (female)
5 V
RS-485/A
Signal ground
Cable shield
RS-485/B
470 Ω
120 Ω
470 Ω
120 Ω
EtherNet/IP Module
Signal ground RS-485/B RS-485/A
Node

A.4.3 Pin assignments (EtherNet/IP Module)

A.5 Typical connection

28 Micro Motion EtherNet/IP Module
Page 35

Appendix B: Device Profile

B.1 Object classes

Table B-1 lists and describes all object classes supported by the EtherNet/IP Module.
Table B-1 Object classes and descriptions
Device Profile
Object Class ID
Identity 0x01 Required Contains information that uniquely describes the device
Message Router 0x02 Required Tracks the accessibility of the object classes and instances
Assembly 0x04 Required Contains a list of attributes that data can be written to (sink) or read from
Port 0xF4 Required
TCP/IP Interface 0xF5 Required Groups settings related to TCP/IP.
Ethernet Link 0xF6 Required Groups diagnostic information for the Ethernet interface
Diagnostic 0xAA Optional Groups diagnostic information for the fieldbus interface
Parameter Data Input Mapping
Parameter Data Output Mapping
0xBO Optional Used for acyclic access to input data
0xB1 Optional Used for acyclic acces to output data
Optional/ required
Description
(source)

B.2 Object details

B.2.1 Identity Object, Class 01h

This object provides identification of and general information about the device. It contains informational attributes that uniquely describe the device.
Example: The use of attributes Vendor ID, Device Type, Product Code, and Serial Number together uniquely identify this device.
User Manual 29
Page 36
Device Profile
Supported services
Class services:
Get Attribute All
Get Attribute Single
Instance services:
Get Attribute All
Get Attribute Single
Reset
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
Instance attributes
# Access Name Type Value Description
1 Get Vendor ID UINT Default: 0392h Micro Motion Inc
2 Get Device Type UINT Default: 000Ch Communication Adapter
3 Get Product Code UINT Default: 0002h 2 = Micro Motion
EtherNet/IP Module
4 Get Revision Struct of: -
USINT Major fieldbus version
USINT Minor fieldbus version
5 Get Status WORD - Device status; see
following table
6 Get Serial Number UDINT Serial number (set at production)
7 Get Product Name SHORT_STRING “Micro Motion EtherNet/IP Module” Name of product
Device status
Bit(s) Name
0Module Owned
1 (reserved)
2Configured
3 (reserved)
30 Micro Motion EtherNet/IP Module
Page 37
4... 7 Extended Device Status:
Value Meaning
0000b Unknown
0010b Faulted I/O Connection
0011b No I/O connection established
0100b Non-volatile configuration bad
0110b Connection in Run mode
0111b Connection in Idle mode
(other) (reserved)
8 Set for minor recoverable faults
9Set for minor unrecoverable faults
10 Set for major recoverable faults
11 Set for major unrecoverable faults
12... 15 (reserved)
Device Profile
Reset service
When the Identity Object receives a Reset request, it:
Determines if it can provide the type of reset requested
Responds to the request
Attempts to perform the type of reset requested

B.2.2 Message Router, Class 02h

The Message Router Object provides a messaging connection point through which a Client may address a service to any object class or instance residing in the physical device.

B.2.3 Assembly Object, Class 04h

The Assembly Object binds attributes of multiple objects, which allows data to or from each object to be sent or received over a single connection. Assembly objects can be used to bind input data or output data. The terms “input” and “output” are defined from the network's point of view. An input produces data on the network and an output consumes data from the network.
This object provides access to the I/O Data in the Input and Output Data areas in the Micro Motion EtherNet/IP Module.
User Manual 31
Page 38
Device Profile
Supported services
Class services:
Get Attribute Single
Instance services:
Get Attribute Single
Set Attribute Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0002h Revision 2
2 Get Max Instance UINT - The highest initiated instance
number
Instance attributes - Instance/Connection Point 64h
This instance corresponds to I/O Data (Input) in the Micro Motion EtherNet/IP Module. The EtherNet/IP Module supports two different configurations. Specific input assembly attributes depend on the configuration in use.
Configuration
Basic See Section B.3.1
Concentration measurement See Section B.3.5
Note
The default input data size is non-zero. The actual size depends on the configuration in use. If the I/O input data size is set to 0, this instance will NOT be initialized.
# Access Name Type Value Description
3 Get Data Array of BYTE - Data produced by the Micro Motion
Input assembly attributes
EtherNet/IP Module
32 Micro Motion EtherNet/IP Module
Page 39
Device Profile
Instance attributes - Instance/Connection Point 96h
This instance corresponds to I/O Data (Output) in the Micro Motion EtherNet/IP Module. The EtherNet/IP Module supports two different configurations. Specific input assembly attributes depend on the configuration in use.
Configuration
Basic See Section B.3.2
Concentration measurement See Section B.3.6
Note
The default output data size is non-zero. The actual size depends on the configuration in use. If the I/O output data size is set to 0, this instance will NOT be initialized.
# Access Name Type Value Description
3 Set Data Array of BYTE - Data consumed by the Micro Motion
Note
Rockwell Automation PLCs have the first four bytes consumed by a device defined as status information. This behavior is specific to devices from Rockwell Automation and is not defined in the EtherNet/IP specification. However, since all known PLCs are implemented this way, the Micro Motion EtherNet/IP Module adopts this behavior and strips off the corresponding four bytes from the consumed data.
Output assembly attributes
EtherNet/IP Module

B.2.4 Port Object, Class F4h

Supported services
Class services:
Get Attribute Single
Get Attribute All
User Manual 33
Page 40
Device Profile
Instance services:
Get Attribute Single
Get Attribute All
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0002h 2 is the highest instance number
3 Get No. of instances UINT 0001h 1 instance is implemented
8 Get Entry Port UINT 0002h Returns the instance of the Port object that
describes the port.
9 Get All Ports Array of
STRUCT
{UINT; UINT;} 0000h
0000h 0000h
0000h
0004h 0002h
Array of structure containing attributes 1 and 2 from each instance. Instance 1 is at byte offset 4. Instance 2 is at byte offset 8, etc. The 4 bytes at offset 0 shall be 0. (Default)
Instance attributes, Instance 02h
# Access Name Type Value Comments
1 Get Port Type UINT 0000h TCP/IP
2 Get Port Number UINT 0002h Port 2
3 Get Port Object Struct of:
Path Size UINT 0002h -
Path Padded EPATH 20 F5 24 01h TCP class, Instance 1
4 Get Port Name SHORT_STRING “TCP/IP” Name of port
8 Get Node Address Padded EPATH - -

B.2.5 TCP/IP Interface Object, Class F5h

This object groups TCP/IP-related settings.
Supported services
Class services:
Get Attribute All
Get Attribute Single
34 Micro Motion EtherNet/IP Module
Page 41
Device Profile
Instance services:
Get Attribute All
Get Attribute Single
Set Attribute Single
Class attributes
# Access Name Type Value Comments
1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0001h 1 is the highest
instance number
3 Get No. of instances UINT 0001h 1 instance is imple-
mented
Instance attributes
# Access Name Type Value Comments
1 Get Status DWORD 00000001h Attribute #5 contains valid infor-
mation.
2 Get Configuration Capability DWORD 00000016h Attribute #5 is settable. Capable
of obtaining network configura­tion via DHCP.
3 Get/Set Configuration Control DWORD - 0: Configuration from non-
volatile memory 2: Configuration from DHCP
4 Get Port Object Struct of:
Path Size UINT 0002h 2 words
Path Padded EPATH 20 F6 24 01h Path to Ethernet Class, Instance 1
5 Get/Set Interface Configuration Struct of:
IP Address UDINT - IP address
Subnet Mask UDINT - Subnet mask
Gateway Address UDINT - Gateway Address
Name Server 1 UDINT - Primary DNS
Name Server 2 UDINT - Secondary DNS
Domain Name STRING - Default domain name
6 Get/Set Host Name STRING - Host name
User Manual 35
Page 42
Device Profile

B.2.6 Ethernet Link Object, Class F6h

This object groups diagnostic information for the Ethernet interface.
Supported services
Class services:
Get Attribute All
Get Attribute Single
Instance services:
Get Attribute All
Get Attribute Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
2 Get Max Instance UINT 0001h 1 is the highest instance number
3 Get No. of instances UINT 0001h 1 instance is implemented
Instance attributes
# Access Name Type Value Comments
1 Get Interface Speed UDINT 10 or 100 Actual Ethernet interface
speed
2 Get Interface Flags DWORD - -
3 Get Physical Address Array of 6 USINTS (MAC ID) Physical network address

B.2.7 Diagnostic Object, Class AAh

This object groups diagnostic information for the fieldbus interface.
Supported services
Class services:
Get Attribute All
Instance services:
Get Attribute Single
36 Micro Motion EtherNet/IP Module
Page 43
Device Profile
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
Instance attributes
# Access Name Type Description
01h Get Module serial number UDINT Serial number
02h Get Vendor ID UINT Manufacturer Vendor ID
03h Get Fieldbus Type UINT Fieldbus Type
04h Get Module Software version UINT Module software version
0Ah Get Module Type UINT Module Type
0Fh Get IN cyclic I/O length UINT Size of I/O Input area (in bytes)
11h Get IN total length UINT Total number of IN bytes supported
12h Get OUT cyclic I/O length UINT Size of I/O Output area (in bytes)
14h Get OUT total length UINT Total number of OUT bytes supported

B.2.8 Parameter Data Input Mapping Object, Class B0h

This object can be used to access Input Data acyclically, and is set up dynamically based on the Parameter Data Mailbox initialization (see Section B.3.3).
Supported services
Class services:
Get Attribute All
Instance services:
Get Attribute Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
User Manual 37
Page 44
Device Profile
Instance attributes, Instance 01h
Each attribute corresponds to a block of Input Data.
# Access Name Type Description
01h Get Data Array of USINT Mapped block of Input Data
02h Get Data Array of USINT Mapped block of Input Data
...
32h Get Data Array of USINT Mapped block of Input Data
The specific parameters in the block depend on the configuration in use.
Configuration
Basic See Section B.3.3
Concentration measurement See Section B.3.7
Input parameters (explicit data)

B.2.9 Parameter Data Output Mapping Object, Class B1h

This object can be used to access Output Data acyclically, and is set up dynamically (see Section B.3.4).
Supported services
Class services:
Get Attribute All
Instance services:
Get Attribute Single
Set Attribute Single
Class attributes
# Access Name Type Value Description
1 Get Revision UINT 0001h Revision 1
Instance attributes, Instance 01h
# Access Name Type Description
01h Get/Set Data Array of USINT Mapped block of Output Data
02h Get/Set Data Array of USINT Mapped block of Output Data
38 Micro Motion EtherNet/IP Module
Page 45
...
32h Get/Set Data Array of USINT Mapped block of Output Data
The specific parameters in the block depend on the configuration in use.
Device Profile
Configuration
Basic See Section B.3.4
Concentration measurement See Section B.3.8
Output parameters (explicit data)

B.3 I/O data

B.3.1 Input assembly for standard configuration

Byte Access Name Type Notes
0–3 Get Mass flow rate Float
4–7 Get Density Float
8–11 Get Temperature Float
12–15 Get Volume flow rate (liquid
volume)
16–19 Get Mass total Float
20–23 Get Volume total (liquid volume) Float
24–27 Get Drive gain Float
28–29 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
30–31 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
32–35 Get Gas standard volume flow
rate
Float Valid only when Gas Standard Volume is
not enabled.
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 1 (see Section B.7.1)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 2 (see Section B.7.2)
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 2 (see Section B.7.2)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 1 (see Section B.7.1)
Float Valid only when Gas Standard Volume is
enabled.
User Manual 39
Page 46
Device Profile
36–39 Get
Gas standard volume total
Float Valid only when Gas Standard Volume is
enabled.

B.3.2 Output assembly for standard configuration

Byte Access Name Type Notes
0–3 Get/Set External Temperature Float
4–7 Get/Set External Pressure Float
8 Get/Set Start/Stop Totals Byte 0: Stop
1: Start
9 Get/Set Reset All Process Totals Byte 0: No action
1: Reset
10 Get/Set Reset All Inventory Totals Byte 0: No action
1: Reset
11 Get/Set Start Zero Byte 0: Abort or no action
1: Start
12–13 Get/Set Start Smart Meter Verifica-
tion
Word
See
Table B-20

B.3.3 Input parameters (explicit data) for standard configuration

To update any of these attribute values, the associated trigger byte must be toggled before reading the attribute value (executing the Get service). See Section B.3.4 for more information on trigger bytes.
Trigger
Class Instance Attribute Access Name Type
Byte Write Attribute
B0h 01h 01h Get Mass flow rate unit U16 0Ch
02h Get Density unit U16 0Ch
03h Get Temperature unit U16 0Ch
04h Get Volume flow rate unit U16 0Ch
05h Get Pressure unit U16 0Ch
06h Get Mass total/inventory unit U16 0Ch
07h Get Volume total/inventory unit U16 0Ch
08h Get Zero time U16 0Dh Seconds
09h Get Standard deviation of auto zero Float 0Eh
0Ah Get Present flow signal offset at
zero flow
0Bh Get Failed Zero Calibration Value Float 0Eh
Float 0Eh
Description
See
Table B-7
See
Table B-13
See
Table B-14
See
Table B-9
See
Table B-15
See
Table B-8
See
Table B-10
40 Micro Motion EtherNet/IP Module
Page 47
Device Profile
0Ch Get Device Status Word 2 U16 0Fh See Section B.7.2
0Dh Get Device Status Word 3 U16 0Fh See Section B.7.3
0Eh Get Device Status Word 4 U16 0Fh See Section B.7.4
0Fh Get Device Status Word 5 U16 0Fh See Section B.7.5
10h Get Device Status Word 6 U16 0Fh See Section B.7.6
11h Get Device Status Word 7 U16 0Fh See Section B.7.7
12h Get External temperature input Float No trigger
byte
13h Get External pressure input Float No trigger
byte
14h Get Gas standard volume flow unit U16 10h
15h Get Gas standard volume total/
inventory unit
16h Get Smart Meter Verification:
Status
17h Get Smart Meter Verification: Run
Count
18h Get Smart Meter Verification
Algorithm State
19h Get Smart Meter Verification Abort
Code
1Ah Get Smart Meter Verification State
at Abort
1Bh Get Smart Meter Verification
Progress
1Ch Get Enable/Disable Gas Standard
Volume Calculations
1Dh Get Subnet communication status
(RS-485 connection to trans­mitter)
U16 10h
U16 13h
U16 13h
U16 11h
U16 11h
U16 11h
U16 12h % complete
U8 14h
U16 No trigger
byte
See
Table B-11
See
Table B-12
See
Table B-22
See
Table B-21
See
Table B-23
See
Table B-24
0: Communications failure Any other value: Com­munications good
User Manual 41
Page 48
Device Profile
B.3.4 Output parameters (explicit data) for standard configura-
tion
Trigger
Class Instance Attribute Access Name Type
byte write attribute
Description
B1h 01h 01h Get/Set Standard or special mass flow
rate unit
02h Get/Set Density unit U16
03h Get/Set Temperature unit U16
04h Get/Set Standard or special volume flow
rate unit
05h Get/Set Pressure unit U16
06h Get/Set Zero time U16 Seconds
07h Get/Set Zero value Float
08h Get/Set Gas Standard Volume Flow unit U16
09h Get/Set Output state during Smart
Meter Verification
0Ah Get/Set Enable/Disable Gas Standard
Volume Calculations
0Bh Get/Set Smart Meter Verification Index U16 16h Smart Meter Verifica-
0Ch Get/Set Trigger Byte-2 U8
U16
U16
U16 0 = Last measured
U8
See
Table B-7
Table B-13
See
See
Table B-14
See
Table B-10
See
Table B-15
See
Table B-11
value 1 = Fault
tion test record. 0 = most recent ... 19 = oldest
0Dh Get/Set Trigger Byte-3 U8
0Eh Get/Set Trigger Byte-6 U8
0Fh Get/Set Trigger Byte-9 U8
10h Get/Set Trigger Byte-15 U8
11h Get/Set Trigger Byte-17 U8
12h Get/Set Trigger Byte-18 U8
13h Get/Set Trigger Byte-16 U8
14h Get/Set Trigger Byte-20 U8
15h Get/Set Trigger Byte-23 U8
16h Get/Set Trigger Byte-26 U8
42 Micro Motion EtherNet/IP Module
Page 49
Device Profile
B.3.5 Input assembly for concentration measurement configura-
tion
Byte Access Name Type Notes
0–3 Get Mass flow rate Float
4–7 Get Density Float
8–11 Get Temperature Float
12–15 Get Volume flow rate (liquid
volume)
16–19 Get Mass total Float
20–23 Get Standard volume flow Float
24–27 Get Standard volume total Float
28–31 Get Standard volume inventory Float
32–35 Get Net mass flow Float
36–39 Get Net mass total Float
40–43 Get Netmass inventory Float
44–47 Get Net volume flow Float
48–51 Get Net volume total Float
52–55 Get Net volume inventory Float
56–59 Get Reference density Float
60–63 Get Specific gravity Float
64–67 Get Concentration Float
68–71 Get Density (fixed Baume units) Float
72–75 Get Volume total (liquid) Float
76–79 Get Drive gain Float
80–81 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
82–83 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
Float
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 1 (see Section B.7.1)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 2 (see Section B.7.2)
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 2 (see Section B.7.2)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 1 (see Section B.7.1)
User Manual 43
Page 50
Device Profile
B.3.6 Output assembly for concentration measurement configu-
ration
Byte Access Name Type Notes
0–3 Get/Set External Temperature Float
4–7 Get/Set External Pressure Float
8 Get/Set Start/Stop Totals Byte 0: Stop
1: Start
9 Get/Set Reset All Process Totals Byte 0: No action
1: Reset
10 Get/Set Reset All Inventory Totals Byte 0: No action
1: Reset
11 Get/Set Start Zero Byte 0: Abort or no action
1: Start
12–13 Get/Set Start Smart Meter Verifica-
tion
Word
See
Table B-20
B.3.7 Input parameters (explicit data) for concentration measure-
ment configuration
To update any of these attribute values, the associated trigger byte must be toggled before reading the attribute value (executing the Get service). See Section B.3.4 for more information on trigger bytes.
Trigger
Class Instance Attribute Access Name Type
Byte Write Attribute
B0h 01h 01h Get Mass flow rate unit U16 0Ah
02h Get Density unit U16 0Ah
03h Get Temperature unit U16 0Ah
04h Get Volume flow rate unit U16 0Ah
05h Get Pressure unit U16 0Ah
06h Get Mass total/inventory unit U16 0Ah
07h Get Volume total/inventory unit U16 0Ah
08h Get Zero time U16 0Bh Seconds
09h Get Standard deviation of auto zero Float 0Ch
0Ah Get Present flow signal offset at
zero flow
0Bh Get Failed Zero Calibration Value Float 0Ch
0Ch Get Device Status Word 2 U16 0Dh See Section B.7.2
Float 0Ch
Description
See
Table B-7
See
Table B-13
See
Table B-14
See
Table B-9
See
Table B-15
See
Table B-8
See
Table B-10
44 Micro Motion EtherNet/IP Module
Page 51
Device Profile
0Dh Get Device Status Word 3 U16 0Dh See Section B.7.3
0Eh Get Device Status Word 4 U16 0Dh See Section B.7.4
0Fh Get Device Status Word 5 U16 0Dh See Section B.7.5
10h Get Device Status Word 6 U16 0Dh See Section B.7.6
11h Get Device Status Word 7 U16 0Dh See Section B.7.7
12h Get External temperature input Float No trigger
byte
13h Get External pressure input Float No trigger
byte
14h Get Smart Meter Verification: Run
Count
15h Get Smart Meter Verification:
Status
16h Get Smart Meter Verification
Algorithm State
17h Get Smart Meter Verification Abort
Code
18h Get Smart Meter Verification State
at Abort
19h Get Smart Meter Verification
Progress
1Ah Get Concentration units code U8 13h
1Bh Get Derived variable U16 12h
1Ch Get Active matrix U16 12h
1Dh Get Subnet communication status
(RS-485 connection to trans­mitter)
U16 0Eh
U16 0Eh
U16 0Fh
U16 0Fh
U16 0Fh
U16 10h % complete
U16 No trigger
byte
See
Table B-22
See
Table B-21
See
Table B-23
See
Table B-24
See
Table B-17
0: Communications failure Any other value: Com­munications good
User Manual 45
Page 52
Device Profile
B.3.8 Output parameters (explicit data) for concentration mea-
surement configuration
Trigger
Class Instance Attribute Access Name Type
byte write attribute
Description
B1h 01h 01h Get/Set Standard or special mass flow
rate unit
02h Get/Set Density unit U16
03h Get/Set Temperature unit U16
04h Get/Set Standard or special volume flow
rate unit
05h Get/Set Pressure unit U16
06h Get/Set Zero time U16 Seconds
07h Get/Set Zero value Float
08h Get/Set Output state during Smart
Meter Verification
09h Get/Set Smart Meter Verification Index U16 11h Smart Meter Verifica-
0Ah Get/Set Trigger Byte-2 U8
0Bh Get/Set Trigger Byte-3 U8
0Ch Get/Set Trigger Byte-6 U8
U16
U16
U16 0 = Last measured
See
Table B-7
Table B-13
See
See
Table B-14
See
Table B-10
See
Table B-15
value 1 = Fault
tion test record. 0 = most recent ... 19 = oldest
0Dh Get/Set Trigger Byte-9 U8
0Eh Get/Set Trigger Byte-14 U8
0Fh Get/Set Trigger Byte-15 U8
10h Get/Set Trigger Byte-16 U8
11h Get/Set Trigger Byte-24 U8
12h Get/Set Trigger Byte-25 U8
13h Get/Set Trigger Byte-17 U8
46 Micro Motion EtherNet/IP Module
Page 53
Device Profile

B.3.9 Input assembly for petroleum measurement configuration

Byte Access Name Type Notes
0–3 Get Mass flow rate Float
4–7 Get Density Float
8–11 Get Temperature Float
12–15 Get Volume flow rate (liquid
volume)
16–19 Get Mass total Float
20–23 Get Volume total Float
24–27 Get Drive gain Float
28–29 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
30-31 Get Status word U16 or Word • For Model 1700 Analog, Model 2700
32–35 Get Temperature-corrected
density
36–39 Get CTL Float
40–43 Get Temperature-corrected
volume flow
44–47 Get Temperature-corrected
volume total
48–51 Get Temperature-corrected
volume inventory
52–55 Get Average temperature-
corrected density
56–59 Get Average temperature Float
Float
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 1 (see Section B.7.1)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 2 (see Section B.7.2)
Analog, Model 1500 Analog, Model 2500, and all Series 3000 transmitters: SNS Status Word 2 (see Section B.7.2)
• For MVD Direct Connect and 9739 MVD transmitters: SNS Status Word 1 (see Section B.7.1)
Float
Float
Float
Float
Float
User Manual 47
Page 54
Device Profile
B.3.10 Output assembly for petroleum measurement configura-
tion
Byte Access Name Type Notes
0–3 Get/Set External Temperature Float
4–7 Get/Set External Pressure Float
8 Get/Set Start/Stop Totals Byte 0: Stop
1: Start
9 Get/Set Reset All Process Totals Byte 0: No action
1: Reset
10 Get/Set Reset All Inventory Totals Byte 0: No action
1: Reset
11 Get/Set Start Zero Byte 0: Abort or no action
1: Start
12–13 Get/Set Start Smart Meter Verifica-
tion
Word
See
Table B-20
B.3.11 Input parameters (explicit data) for petroleum measure-
ment configuration
To update any of these attribute values, the associated trigger byte must be toggled before reading the attribute value (executing the Get service). See Section B.3.4 for more information on trigger bytes.
Trigger
Class Instance Attribute Access Name Type
Byte Write Attribute
B0h 01h 01h Get Mass flow rate unit U16 0Dh
02h Get Density unit U16 0Dh
03h Get Temperature unit U16 0Dh
04h Get Volume flow rate unit U16 0Dh
05h Get Pressure unit U16 0Dh
06h Get Mass total/inventory unit U16 0Dh
07h Get Volume total/inventory unit U16 0Dh
08h Get Zero time U16 0Eh Seconds
09h Get Standard deviation of auto zero Float 0Fh
0Ah Get Present flow signal offset at
zero flow
0Bh Get Failed Zero Calibration Value Float 0Fh
0Ch Get Device Status Word 2 U16 10h See Section B.7.2
Float 0Fh
Description
See
Table B-7
See
Table B-13
See
Table B-14
See
Table B-9
See
Table B-15
See
Table B-8
See
Table B-10
48 Micro Motion EtherNet/IP Module
Page 55
Device Profile
0Dh Get Device Status Word 3 U16 10h See Section B.7.3
0Eh Get Device Status Word 4 U16 10h See Section B.7.4
0Fh Get Device Status Word 5 U16 10h See Section B.7.5
10h Get Device Status Word 6 U16 10h See Section B.7.6
11h Get Device Status Word 7 U16 10h See Section B.7.7
12h Get External temperature input Float No trigger
byte
13h Get External pressure input Float No trigger
byte
14h Get Smart Meter Verification: Run
Count
15h Get Smart Meter Verification:
Status
16h Get Smart Meter Verification
Algorithm State
17h Get Smart Meter Verification Abort
Code
18h Get Smart Meter Verification State
at Abort
19h Get Smart Meter Verification
Progress
1Ah Get API Table Type U16 14h
1Bh Get Reference temperature Float 15h
1Ch Get Thermal expansion coefficient
(TEC)
1Dh Get Subnet communication status
(RS-485 connection to trans­mitter)
U16 11h
U16 11h
U16 12h
U16 12h
U16 12h
U16 13h % complete
Float 15h
U16 No trigger
byte
See
Table B-22
See
Table B-21
See
Table B-23
See
Table B-24
See
Table B-18
0: Communications failure Any other value: Com­munications good
User Manual 49
Page 56
Device Profile
B.3.12 Output parameters (explicit data) for petroleum measure-
ment configuration
Trigger
Class Instance Attribute Access Name Type
byte write attribute
Description
B1h 01h 01h Get/Set Standard or special mass flow
rate unit
02h Get/Set Density unit U16
03h Get/Set Temperature unit U16
04h Get/Set Standard or special volume flow
rate unit
05h Get/Set Pressure unit U16
06h Get/Set Zero time U16 Seconds
07h Get/Set Zero value Float
08h Get/Set Output state during Smart
Meter Verification
09h Get/Set Smart Meter Verification Index U16 16h Smart Meter Verifica-
0Ah API Table Type U16
0Bh Reference temperature Float
0Ch Thermal expansion coefficient
(TEC)
0Dh Get/Set Trigger Byte-2 U8
0Eh Get/Set Trigger Byte-3 U8
0Fh Get/Set Trigger Byte-6 U8
10h Get/Set Trigger Byte-9 U8
11h Get/Set Trigger Byte-14 U8
12h Get/Set Trigger Byte-15 U8
13h Get/Set Trigger Byte-16 U8
14h Get/Set Trigger Byte-17 U8
15h Get/Set Trigger Byte-20 U8
16h Get/Set Trigger Byte-24 U8
U16
U16
U16 0 = Last measured
Float
See
Table B-7
Table B-13
See
See
Table B-14
See
Table B-10
See
Table B-15
value 1 = Fault
tion test record. 0 = most recent ... 19 = oldest
See Table B-18
50 Micro Motion EtherNet/IP Module
Page 57

B.4 Get and Set services

The Get Attribute Single and Set Attribute Single services are used with many objects and attributes. Details of these two services are provided here

B.4.1 Get Attribute Single service

Table B-2 Get service arguments
Parameter name Data type Required Parameter value Notes
Device Profile
Attribute ID USINT Y The attribute ID of the
attribute to be read
Table B-3 Get service response
Return value Data type
Attribute value The data type of the returned attribute
No default

B.4.2 Set Attribute Single service

Table B-4 Set service arguments
Parameter name Data type Required Parameter value Notes
Attribute ID USINT Y The attribute ID of the
attribute to be set
Attribute Value The data type of
the attribute being set
Y The value to which the
attribute will be set
No default
No default
Table B-5 Set service response
Return value Data type
No success response data
User Manual 51
Page 58
Device Profile

B.5 Data types

Table B-6 Data types
Data type Size (bytes) Description Range
BOOL 1 True/false represented as 0 = false and 1 =
true
SINT 1 8-bit signed integer –128 to +127
USINT 1 8-bit unsigned integer 0 to 255
INT 2 16-bit signed integer –32768 to +32767
UINT 2 16-bit unsigned integer 0 to 65535
DINT 4 32-bit signed integer –2147483648 to +2147483647
UDINT 4 32-bit unsigned integer 0 to 4294967296
REAL 4 IEEE single-precision floating-point –3.8E38 to +3.8E38
DREAL 8 IEEE double-precision floating-point
ENGUNITS 1 Enumerated value representing an engi-
neering unit of measure
BYTE 1 8-bit bitfield N/A
SHORT_STRING Up to 128 bytes Character array where the first byte is the
number of characters in the array, and the subsequent bytes contain the ASCII charac­ters. This is not a NULL terminated string.
0, 1
4096 to 65535
N/A

B.6 Codes and integer values

Table B-7 Mass flow measurement unit codes
Code Description
70 Grams per second
71 Grams per minute
72 Grams per hour
73 Kilograms per second
74 Kilograms per minute
75 Kilograms per hour
76 Kilograms per day
77 Metric tons per minute
78 Metric tons per hour
79 Metric tons per day
52 Micro Motion EtherNet/IP Module
Page 59
Table B-7 Mass flow measurement unit codes (Continued)
Code Description
80 Pounds per second
81 Pounds per minute
82 Pounds per hour
83 Pounds per day
84 Short tons (2000 pounds) per minute
85 Short tons (2000 pounds) per hour
86 Short tons (2000 pounds) per day
87 Long tons (2240 pounds) per hour
88 Long tons (2240 pounds) per day
253 Special
Table B-8 Mass totalizer and mass inventory measurement unit codes
Device Profile
Code Description
60 Grams
61 Kilograms
62 Metric tons
63 Pounds
64 Short tons (2000 pounds)
65 Long tons (2240 pounds)
253 Special
Table B-9 Liquid volume flow measurement unit codes
Code Description
15 Cubic feet per minute
16 U.S. gallons per minute
17 Liters per minute
18 Imperial gallons per minute
19 Cubic meters per hour
22 U.S. gallons per second
23 Million U.S. gallons per day
24 Liters per second
User Manual 53
Page 60
Device Profile
Table B-9 Liquid volume flow measurement unit codes (Continued)
Code Description
25 Million liters per day
26 Cubic feet per second
27 Cubic feet per day
28 Cubic meters per second
29 Cubic meters per day
30 Imperial gallons per hour
31 Imperial gallons per day
130 Cubic feet per hour
131 Cubic meters per minute
132
133
134
135
Barrels per second
Barrels per minute
Barrels per hour
Barrels per day
136 U.S. gallons per hour
137 Imperial gallons per second
138 Liters per hour
170
171
172
173
Beer barrels per second
Beer barrels per minute
Beer barrels per hour
Baeer brrels per day
235 U.S. gallons per day
253 Special
(1) Unit based on oil barrels (42 U.S. gallons). (2) Unit based on beer barrels (31 U.S. gallons). Not available with the standrad core processor.
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
Table B-10 Liquid volume totalizer and liquid volume inventory measurement unit codes
Code Description
40 U.S. gallons
41 Liters
42 Imperial gallons
43 Cubic meters
46
Barrels
(1)
112 Cubic feet
54 Micro Motion EtherNet/IP Module
Page 61
Device Profile
Table B-10 Liquid volume totalizer and liquid volume inventory measurement unit codes (Continued)
Code Description
170
253 Special
(1) Unit based on oil barrels (42 U.S. gallons). (2) Unit based on beer barrels (31 U.S. gallons). Not available with the standrad core processor.
Beer barrels
(2)
Table B-11 Gas standard volume flow measurement unit codes
Code Description
121 Normal cubic meters per hour
122 Normal liters per hour
123 Standard cubic feet per minute
174 Normal liters per day
175 Normal liters per minute
176 Normal liters per second
177 Standard liters per day
178 Standard liters per hour
179 Standard liters per minute
180 Standard liters per second
181 Normal cubic meters per day
182 Normal cubic meters per minute
183 Normal cubic meters per second
184 Standard cubic feet per day
185 Standard cubic feet per hour
186 Standard cubic feet per second
187 Standard cubic meters per day
188 Standard cubic meters per hour
189 Standard cubic meters per minute
190 Standard cubic meters per second
253 Special
User Manual 55
Page 62
Device Profile
Table B-12 Gas standard volume totalizer and inventory measurement unit codes
Code Description
166 Normal cubic meters
167 Normal liters
168 Standard cubic feet
171 Standard liters
172 Standard cubic meters
253 Special
Table B-13 Density measurement unit codes
Code Description
90 Specific gravity unit (not temperature corrected)
91 Grams per cubic centimeter
92 Kilograms per cubic meter
93 Pounds per U.S. gallon
94 Pounds per cubic foot
95 Grams per millileter
96 Kilograms per liter
97 Grams per liter
98 Pounds per cubic inch
99 Short tons per cubic yard
104 Degrees API
Table B-14 Temperature measurement unit codes
Code Description
32 Degrees Celsius
33 Degrees Fahrenheit
34 Degrees Rankine
35 Kelvin
Table B-15 Pressure and differential pressure measurement unit codes
Code Description
1 Inches water @ 68 °F
2 Inches mercury @ 0 °C
56 Micro Motion EtherNet/IP Module
Page 63
Table B-15 Pressure and differential pressure measurement unit codes (Continued)
Code Description
3 Feet water @ 68 °F
4 Millimeters water @ 68 °F
5 Millimeters mercury @ 0 °C
6 Pounds per square inch
7Bar
8 Millibar
9 Grams per square centimeter
10 Kilograms per square centimeter
11 Pascals
12 Kilopascals
13 Torr @ 0 °C
14 Atmospheres
145
237
238
239
Inches water @ 60 °F
Megapascals
Inches water @ 4 °C
Millimeters water @ 4 °C
(1)
(1)
(1)
(1)
Device Profile
(1) Not available with the standard core processor.
Table B-16 Concentration measurement unit codes
Code Description
100 Degrees Twaddell
101 Degrees Brix
102 Degrees Baume (heavy)
103 Degrees Baume (light)
105 % solids per weight (% mass)
106 % solids per volume (% volume)
107 Degrees Balling
108 Proof per volume
109 Proof per mass
160 Degrees Plato
253 Special (use with all systems that include an enhanced core processor)
User Manual 57
Page 64
Device Profile
Table B-16 Concentration measurement unit codes (Continued)
Code Description
255 Special (use with all systems that include a standard core processor)
Table B-17 Concentration measurement derived variable codes
Code Description
0None
256 Density at reference
512 Specific gravity
768 Mass concentration (Density)
1024 Mass concentration (Specific gravity)
1280 Volume concentration (Density)
1536 Volume concentration (Specific gravity)
1792 Concentration (Density)
2048 Concentration (Specific gravity)
Table B-18 API Table Type codes
Code Description
17 Table 5A
18 Table 5B
19 Table 5D
36 Table 6C
49 Table 23A
50 Table 23B
51 Table 23D
68 Table 24C
81 Table 53A
82 Table 53B
83 Table 53D
100 Table 54C
Table B-19 Fixed output codes for Smart Meter Verification
Value Description
0 Last measured value
58 Micro Motion EtherNet/IP Module
Page 65
Table B-19 Fixed output codes for Smart Meter Verification (Continued)
Value Description
1 Fault value
Table B-20 Enable Smart Meter Verification
Code Description
Device Profile
1
5Abort
6 Enable with continuous measurement
Enable with fixed output (see Table B-19)
Table B-21 Smart Meter Verification algorithm state
Value Description
0Inactive
1 Performing startup checks
2 Cutting drive setpoint
4 Initializing filters
6 Setting test tones
7 Ramping test tones
8 Checking drive stability
9 Setting drive voltage measurement
10 Verifying drive voltage
11 Resetting DAQ/MUX
12 Setting current calibration
13 Calibrating current amplitude
14 Resetting DAQ/MUX
15 Calculating system parameters
16 Test completed
17 Disabling test tones
18 Restoring normal drive setpoint
User Manual 59
Page 66
Device Profile
Table B-22 Smart Meter Verification status
Bit number Status
0 State at abort
1
2
3
4Abort code
5
6
7Result:
0=Pass 1=Fail
Table B-23 Smart Meter Verification abort codes
Abort code Description Suggested action
1 User-initiated abort None required. Wait for 15 seconds before
starting another test.
3 Frequency drift Ensure that temperature, flow, and density
are stable, and rerun the test.
5 High drive gain Ensure that flow is stable, minimize
entrained gas, and rerun the test.
8 Unstable flow Enter that flow is stable and rerun the test.
13 No factory reference data for meter verification
test performed on air
14 No factory reference data for meter verification
test performed on water
15 No configuration data for meter verification Contact Micro Motion customer service
Other General abort. Repeat the test. If the test aborts again,
Contact Micro Motion customer service and provide the abort code.
Contact Micro Motion customer service and provide the abort code.
and provide the abort code.
contact Micro Motion customer service and provide the abort code.
Table B-24 Smart Meter Verification state at abort
Value Description
0Inactive
1In progress
15 Debug mode
16 Measurement completed
60 Micro Motion EtherNet/IP Module
Page 67

B.7 Status words

B.7.1 Status Word 1

Bit number Status description
0 Core EEPROM Checksum Error (Config, Powerdown, Program)
1 Core RAM Test Error
2 Real-Time Interrupt Failure
3 Sensor Failure (A003)
4 Temperature Sensor Out-of-Range (A004)
5 Calibration Failure (Zero, Density, Temperature)
6Other Failure
7 Transmitter Initializing/Warming Up (Low Power Fault)
8 Primary Variable Out-Of-Limits
9 Non-Primary Variable Out-Of-Limits
10 Simulation Mode Active (A132)
11 Undefined
12 Watchdog Error
13 Cold Start (HART bit)
14 Transmitter Configuration Changed (HART bit)
15 Fault (Failure has occurred which affects accuracy)
Device Profile

B.7.2 Status Word 2

Bit number Status description
0 Primary mA Output Saturated (A100)
1 Secondary mA Output Saturated (A113)
2 Primary mA Output Fixed (A101)
3 Secondary mA Output Fixed (A114)
4 Density Outside Limits (A8)
5 Drive Over-Range (A102)
6 PIC/Daughterboard Communication Failure (A029)
7 External Input Failure (A115)
8 Core EEPROM Checksum Error (Config, Powerdown, Program) (A001)
User Manual 61
Page 68
Device Profile
9 Core RAM Error (A002)
10 Sensor Not Responding (No Tube Interrupt) (A003)
11 Temperature Sensor Out-of-Range (A004)
12 Input Over-Range (A005)
13 Frequency Output Saturated (A110)
14 Transmitter Not Characterized (Flowcal or Sensor Type) (A006)
15 Real-Time Interrupt Failure (A007)

B.7.3 Status Word 3

Bit number Status description
0 Burst Mode Enabled (A106) (AI Simulate enabled on Model 2700 transmitters with PROFIBUS-PA,
firmware v2.2)
1 Power Reset Occurred (A107)
2 Transmitter Initializing/Warming Up (Low Power Fault) (A009)
3 Sensor/Xmtr Communication Failure (A028)
4 Paper Out (A130)
5 Event #2 Triggered (A108) (basic event model)
6 Event #1 Triggered (A109) (basic event model)
7 Sensor/Xmtr Communication Failure (A026)
8 Calibration Failure (Autozero, Density, Temperature) (A010)
9 Excess Calibration Correction, Zero too Low (A011)
10 Excess Calibration Correction, Zero too High (A012)
11 Process Too Noisy to Perform Auto Zero (A013)
12 Transmitter Failed (A014)
13 Data Loss Possible (Totals+Inventories Questionable) (A103)
14 Calibration-In-Progress (Autozero, Density, Temperature) (A104)
15 Slug Flow (A105)

B.7.4 Status Word 4

Bit number Status description
0 Petroleum Measurement: Temperature Outside Standard Range (A116)
1 Petroleum Measurement: Line Density Outside Standard Range (A117)
2 Line RTD Temperature Out-Of-Range (A016)
3 Case/Meter RTD Temperature Out-Of-Range (A017)
4 Flow Direction (0=Forward/Zero, 1=Reverse)
62 Micro Motion EtherNet/IP Module
Page 69
5 Factory Configuration Data Is Invalid
6 Concentration Measurement: Unable to fit curve data (A120)
7 Last Measured Value Override Active
8 Enhanced Density Extrapolation Alarm (A121)
9 Cal Factors Unentered (Flocal Mandatory) (A020)
10 1000/2000/3000 EEPROM Checksum Error (A018)
11 1000/2000/3000 RAM Test Error (A019)
12 Unrecognized/Unentered Sensor Type (K1 Mandatory) (A021)
13 Core configuration database corrupt (A022)
14 Core powerdown totals corrupt (A023)
15 Core program corrupt (A024)

B.7.5 Status Word 5

Device Profile
Bit number Status description
0 Core Protected Boot Sector Fault (invalid/corrupt application) (A025)
1 For Series 1000/2000/3000: Software Upgrade Recommended (A112)
For Enhanced Core Processors: Data Bad (Fault exists and LMV timer has expired)
2 Frequency Output Fixed (A111)
3 Primary mA Readback Failure
4 Discrete Output 1 Status (0=OFF, 1=ON)
5 Discrete Output 2 Status (0=OFF, 1=ON)
6 Density Calibration in Progress (D3)
7 Density Calibration in Progress (D4)
8 DO3 Status (0=OFF, 1=ON)
9 DO4 Status (0=OFF, 1=ON)
10 Temperature Calibration-in-Progress (Slope)
11 Temperature Calibration-in-Progress (Offset)
12 Density Calibration in Progress (Flowing Density)
13 Density Calibration in Progress (D2)
14 Density Calibration in Progress (D1)
15 Zero Calibration in Progress
User Manual 63
Page 70
Device Profile

B.7.6 Status Word 6

Bit number Status description
0 Discrete Input 1 Status (0=OFF, 1=ON)
Weights and Measures: Database Checksum for Core Processors Only
1 Discrete Input 2 Status (0=OFF, 1=ON)
Weights and Measures: Database Checksum for Core Processors Only
2 Discrete Output 1 Fixed (A118)
Weights and Measures: Database Checksum for Core Processors Only
3 Discrete Output 2 Fixed (A119)
Weights and Measures: Database Checksum for Core Processors Only
4 Discrete Output 3 Fixed (A122)
Weights and Measures: Database Checksum for Core Processors Only
5 Discrete Output 4 Fixed (A123)
Weights and Measures: Database Checksum for Core Processors Only
6 Security Breach (A27)
Weights and Measures: Database Checksum for Core Processors Only
7 Frequency Input Saturated (A124)
Weights and Measures: Database Checksum for Core Processors Only
8 Discrete Event 1 Status
Discrete Batch: Batch Timeout (A125) for 1500 and Series 3000 Only
9 Discrete Event 2 Status
Discrete Batch: Batching for 1500 and Series 3000 Only
10 Discrete Event 3 Status
Discrete Batch: Batch End Warn for Series 3000 Only
11 Discrete Event 4 Status
Discrete Batch: Batch Overrun (A126) for Series 3000 Only
12 Discrete Event 5 Status
Discrete Batch: Batch Pump for Series 3000 Only
13 Discrete Batch: Batch Primary Valve for 1500 and Series 3000 Only
14 Discrete Batch: Batch Secondary Valve for 1500 and Series 3000 Only
15 Incorrect Board Type (A30)
Discrete Batch: Start Not Okay for 1500 and Series 3000 Only
Note
Not all alarms are applicable to all transmitters. For more information, see the transmitter configuration manual for your transmitter.
64 Micro Motion EtherNet/IP Module
Page 71

B.7.7 Status Word 7

Bit number Status description
0 K1/FCF Combination Unrecognized
1Warming Up
2 Low Power (A031)
3 Tube Not Full (A033)
4 Smart Meter Verification / Outputs in fault (A032)
5 Smart Meter Verification / Outputs at last value (A131)
6 PIC UI EEPROM Error (A133)
7 NVM Initialized (transmitter)
8 Power Outage (A136)
9 NOC Measurements Paused (A137)
10 TBR Active (A138)
11 External Water Cut Out of Range (A139)
12 TMR Active (A140)
13 One or more DDC Triggers Completed (A141)
14 Smart Meter Verification failed (A34)
15 Smart Meter Verification aborted (A35)
Device Profile
User Manual 65
Page 72
Device Profile
66 Micro Motion EtherNet/IP Module
Page 73

Appendix C: Specifications

C.1 Physical

C.1.1 Housing

Plastic housing with snap-on connection to DIN rail
Protection class: IP20

C.1.2 Dimensions

4.72˝ x 2.95˝ x1.06˝ LxWxH (120 mm x 75 mm x 27 mm)

C.2 Electrical

Specifications

C.2.1 Power supply

24 V ±10%

C.2.2 Power consumption

Maximum: 280 mA on 24 V
Typical: 100 mA

C.3 Environmental

C.3.1 Relative humidity

5 to 95% non-condensing

C.3.2 Temperature

Operating: 32 °F to 131 °F (0 °C to 55 °C)
Ambient: –13 °F to +185 °F (–25 °C to +85 °C)
User Manual 67
Page 74
Specifications

C.4 Regulatory compliance

C.4.1 EMC compliance (CE)

Complies with EMC directive 2004/108/EC.
EN 61001-6-4 (2007) Emission standard for industrial environment EN 55016-2-3 (2006) Class A
EN 61000-6-2 (2005) Immunity standard for industrial environment EN 61000-4-2 (2009)
EN 61000-4-3 (2006)
EN 61000-4-4 (2004)
EN 61000-4-5 (2005)
EN 61000-4-6 (2007)

C.4.2 UL/c-UL compliance

The certification has been documented by UL in file E214107.

C.4.3 Galvanic isolation on Modbus serial interface

EN 60950-1 (2001) Pollution Degree 2
Material Group IIIb
250 VRMS or 250 VDC
500 V Secondary circuit transient rating
Working voltage
68 Micro Motion EtherNet/IP Module
Page 75

Appendix D: Return Policy

D.1 Requirements

Micro Motion procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Micro Motion employees. Failure to follow Micro Motion procedures will result in your equipment being refused delivery.
Information on return procedures and forms is available on our web support system at www.micromotion.com, or from the Micro Motion Customer Service department.

D.1.1 New and unused equipment

Only equipment that has not been removed from the original shipping package will be considered new and unused. New and unused equipment requires a completed Return Materials Authorization form.
Return Policy

D.1.2 Used equipment

All equipment that is not classified as new and unused is considered used. This equipment must be completely decontaminated and cleaned before being returned.
Used equipment must be accompanied by a completed Return Materials Authorization form and a Decontamination Statement for all process fluids that have been in contact with the equipment. If a Decontamination Statement cannot be completed (e.g., for food-grade process fluids), you must include a statement certifying decontamination and documenting all foreign substances that have come in contact with the equipment.
User Manual 69
Page 76
Return Policy
70 Micro Motion EtherNet/IP Module
Page 77
Page 78
Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, CO 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459 www.micromotion.com
Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 www.micromotion.nl
*MMI-20019808*
MMI-20019808
Rev. AC
2012
Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6777-8211 F +65 6770-8003
Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 T +44 0800 966 181
Micro Motion Japan Emerson Process Management 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan T +81 3 5769-6803 F +81 3 5769-6844
©2012 Micro Motion, Inc. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Process Management family of companies. All other marks are property of their respective owners.
Loading...