Emerson PENBERTHY FHS Installation, Operation And Maintenance Instructions

Page 1
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation, these instructions must be read carefully and understood.
PRODUCT WARRANTY
Emerson warrants its Penberthy products as designed and manufactured to be free of defects in the material and workmanship for a period of one year after the date of installation or eighteen months after the date of manufacture, whichever is earliest. Emerson will, at its option, replace or repair any products which fail during the warranty period due to defective material or workmanship.
Prior to submitting any claim for warranty service, the owner must submit proof of
TABLE OF CONTENTS
Product warranty ................................................ 1
1 About the manual..................................... 2
2 Introduction ............................................. 2
2.1 Features and specifications ........................ 2
2.2 Design ratings at max. and min.
operatingtemperatures .............................. 2
2.3 Application data ........................................... 2
3 Inspection and performance
confirmation ............................................ 2
3.1 Receiving inspection .................................... 2
3.2 User's rating inspection .............................. 2
4 Installation ............................................... 3
4.1 Mounting ....................................................... 3
4.2 Effect of related piping and precautions .... 3
5 Operation ................................................. 3
5.1 Pre-operational check ................................. 3
5.2 Operating ...................................................... 4
5.3 Shutdown ...................................................... 4
6 Maintenance ............................................ 4
6.1 Preventative maintenance ........................... 4
6.2 Maintenance procedures ............................ 4
6.3 Troubleshooting ........................................... 4
7 Disassembly - reassembly ...................... 5
8 Disposal at end of useful life ................... 6
9 Telephone assistance .............................. 6
10 Exploded parts drawing ........................... 7
purchase to Emerson and obtain written authorization to return the product. Thereafter, the product shall be returned to Emerson with freight prepaid.
This warranty shall not apply if the product has been disassembled, tampered with, repaired or otherwise altered outside of the Emerson factory, or if it has been subject to misuse, neglect or accident.
The responsibility of Emerson hereunder is limited to repairing or replacing the product at its expense. Emerson shall not be liable for loss, damage or expenses directly or indirectly to the installation or use of its products, or from any other cause or for consequential damages. It is expressly understood that Emerson is not responsible for damage or injury caused to other products, buildings, personnel or property, by reason of the installation or use of its products.
This is Emerson's sole warranty and in lieu of all other warranties, expressed or implied which are hereby excluded, including in particular all warranties of merchantability or fitness for a particular purpose.
related
Tables and figures
Table 1 -
Figure 1 - Installation ......................................... 3
Figure 2 - Reassembly ...................................... 5
Figure 3 - Valve body .......................................... 6
Figure 4 - Exploded parts drawing .................... 7
Figure 5 - Exploded parts drawing (valve) ........ 8
Emerson.com/FinalControl
Design ratings
operatingtemperatures ................... 2
at max. and min.
This document and the warranty contained herein may not be modified and no other warranty, expressed or implied, shall be made by or on behalf of Emerson unless made in writing and signed by the company's general manager or director of engineering.
© 2018 Emerson. All Rights Reserved. VCIOM-04059-EN 19/04
Page 2
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
1 ABOUT THE MANUAL
This manual has been prepared as an aid and guide for personnel involved in installation or maintenance. All instructions must be read and understood thoroughly before attempting any installation, operation or maintenance.
IMPORTANT
Emerson does not have any control over the manner in which its FHS is handled, installed or used. Emerson cannot and will not guarantee that an FHS is suitable for or compatible with the user's specific application.
WARNING
Always wear safety glasses when installing, servicing or operating an FHS automatic liquid heating system. Failure to follow any instruction could possibly result in a malfunction of the FHS automatic liquid heating system resulting in severe physical injury or property damage.
2 INTRODUCTION
2.1 Features and specifications
Penberthy model FHS automatic liquid heating system is a complete, pre-engineered package including: a steam ring heater, steam inline check valve, temperature controller, steam flow control valve, dial thermometer, steam strainer and associated piping. The model FHS is designed to maintain a preset outlet temperature by controlling the amount of steam condensed into the inlet liquid as it passes through the steam ring heater.
2.2 Design ratings at maximum and minimum
operating temperatures
1. Steam valve: 150 psig (1.03 MPa) at -20°F
(-29°C) to +370°F (188°C)
2. Heater and wetted parts as stated in Table 1
below.
To determine maximum allowable working pressure for a specific temperature within the design limits stated above, the user must refer to relevant data sheets or, when provided, the specifically stated design limits on a product proposal.
2.3 Application data
The Penberthy FHS is designed to operate at liquid line pressures from 10 to 100 psig (70to690 kPaG), steam pressures from 30to 150 psig (205 to 1035 kPaG) and at an air supply pressure of 18 psig ± 1 psig (125±5kPaG).
Note: For specific application data within the above ranges, the user should consult the product proposal for the specific model and size FHS, or should request the supply of the applicable technical data sheet.
WARNING
Under no circumstances should these design ratings or application data be exceeded. Exceeding design ratings or application data limits may cause severe physical injury or property damage.
3 INSPECTION AND PERFORMANCE CONFIRMATION
3.1 Receiving inspection
Upon receipt of the FHS, check all components carefully for damage incurred in shipping. If damage is evident or suspected, do not attempt installation. Notify the carrier immediately and request a damage inspection.
3.2 User's rating inspection
The user should confirm that:
1. The FHS size and model, stamped on the nameplate (163), conforms to the description on the user's purchase order.
2. The operating conditions described in the purchase order agree with the actual operating conditions at the installation site.
3. The actual operating conditions at the installation site are within the application data shown on the relevant technical data sheet or product proposal referred to above.
4. The materials of construction of the FHS are compatible with both the contained fluid and the surrounding atmosphere in the specific application.
IMPORTANT
If the size, model or performance data of the FHS as received does not conform with any of the criteria above, do not proceed with installation. Contact an authorized Penberthy distributor for assistance.
TABLE 1 - DESIGN RATINGS AT MAX. AND MIN. OPERATING TEMPERATURES
Material Rating
Bronze
316 SS
200 psig [1.38 MPa] at -20°F [-29°C] to +150°F [66°C] 125 psig [0.86 MPa] at +400°F [204°C] 200 psig [1.38 MPa] at -150°F [-101°C] to +150°F [66°C] 125 psig [0.86 MPa] at +400°F [204°C]
2
Page 3
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4 INSTALLATION
Installation should only be undertaken by qualified, experienced personnel who are familiar with this equipment and have read and understand thoroughly all the instructions in this manual. The user should refer to the relevant technical data sheet or product proposal to obtain dimensional information for the specific size and model of FHS. Check Figure 1 for the location of the liquid inlet and outlet, steam inlet and air inlet connections to insure correct hook up.
4.1 Mounting
Although the FHS can be oriented in any position, it is recommended to position the steam valve actuator horizontally. In this manner, the thermometer dial will be upright, the steam piping and steam ring heater will be in a position to favor removal of condensate at start up, the steam line strainer will point downward, and the temperature controller will be located as recommended by the controller manufacturer.
4.2 Effect of related piping and precautions
1. The FHS should be installed with piping and fittings which provide minimum resistance to flow. Pipe line friction losses must always be a consideration when estimating FHS performance.
2. It is recommended that provisions be made for pressure gauge connections near the liquid inlet and outlet, and the steam inlet connections of the FHS. If performance problems occur during operation, it may be necessary to install pressure gauges to identify the problem.
3. Steam must not have over 20°F (-7°C) of superheat, or performance will differ from that published in the relevant technical data sheet or product proposal referred to above.
4. The steam line must be clean, insulated and as short as possible to prevent condensation and line friction losses.
5. Do not impose system piping loads on an FHS. The unit is designed to be supported by the liquid inlet and outlet and steam inlet piping.
6. Provide the steam line with a hand-operated valve for maintenance and emergency shut­off. The steam line should be provided with a steam trap.
7. Provide an air line with an air pressure regulator capable of maintaining 18 psig (125 kPaG) air pressure. Also, it is recommended that an air pressure gauge be installed in this line.
FIGURE 1
Air connection
5 OPERATION
5.1 Pre-operational check
1. Ensure that all installation procedures have been completed.
2. Ensure that any restrictions in the discharge line have been removed.
3. Ensure that discharge line valves are fully open.
4. Ensure that the manually operated steam line valve is fully closed.
5. Ensure that the temperature controller knob is set to the lowest possible reading by turning it counterclockwise as far as it willgo.
6. Ensure that the air pressure regulator valve is shut off.
Note: When the control valve is completely installed and connected and ready to be put into operation, it is necessary for the user to check for correct travel, freedom of friction, and correct action (air-to-open) to match the temperature controller. If adjustments are necessary, follow all instructions printed in the installation instruction manual prepared for the specific actuator by its manufacturer.
Liquid outlet
Liquid inlet
Steam
inlet
3
Page 4
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
5.2 Operating
1. Turn operating liquid valve fully on and establish full flow. Keep it on throughout the entire operation process.
WARNING
Failure to maintain the liquid flow while operating the FHS with steam can cause live steam to be driven into the liquid piping, resulting in severe personal injury or property damage.
2. Turn on the air pressure regulator and adjust the air pressure knob to 18 psig (125kPaG).
3. Set the knob of the temperature controller at 120°F (49°C) and check for proper operation of the steam valve, which should be fully open in about 20 seconds time. Ifthe steam valve does not open in about 20seconds, adjustment of the temperature controller is necessary. Follow all steps and precautions printed in the installation instruction manual prepared for the specific controller by its manufacturer.
4. Bleed out trapped air inside the pipe cross where the thermometer is installed by slightly loosening the thermometer connection until liquid begins to drip out, then retighten the thermometer in place.
5. Slowly and partially open the manually operated steam line valve to first check for leaks. If leaks are evident, close the valve, allow the line to cool off, tighten connections and repeat the procedure until all leaks are stopped.
6. Turn the temperature controller knob to 100°F (38°C) to allow steam to flow while checking for leaks. If leaks are evident, shut off the steam supply, allow the line to cool off, tighten connections and repeat the procedure until all leaks are stopped.
7. Fully open the operated steam valve manually.
8. Turn the temperature controller knob gradually to the desired outlet liquid temperature and allow the FHS to stabilize. Compare the knob setting with the thermometer reading and adjust if necessary.
There are two distinct operating noise levels typical of the FHS, within specific operating conditions. For detailed information on these operating conditions, request Emerson to supply the relevant technical data sheet.
5.3 Shutdown
1. Turn the manually operated steam line valve off in order to first lower the steam line pressure as much as possible before shut down.
2. Set the temperature controller knob to the lowest possible reading by turning it counterclockwise as far as it will go. This will cause the steam flow control valve to close fully.
3. Turn the air pressure regulator valve off fully.
4. Gradually turn the operating liquid flow off fully.
WARNING
Failure to maintain the liquid flow throughout the shutdown procedure may cause live steam to drive into the liquid piping, resulting in severe personal injury or property damage.
6 MAINTENANCE
WARNING
Maintenance should only be undertaken by qualified, experienced personnel who are familiar with this equipment and have read and understood thoroughly all the instructions in this manual. DO NOT proceed with any maintenance unless the FHS has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to follow these instructions may cause severe personal injury or property damage.
6.1 Preventative maintenance
The user must create maintenance schedules, safety manuals and inspection details for each specific installation of an automatic liquid heating system. On all installations, the following items should be evaluated regularly by the user for purposes of maintenance:
1. FHS components for corrosion and to remove debris build up.
2. Piping and fittings for corrosion and to remove debris build up.
3. All connections to maintain tightness and eliminate leaks.
4. Air pressure regulator to maintain 18 psig (125 kPaG).
5. Outlet liquid temperature to maintain desired setting.
6. Steam line strainer to remove debris buildup.
7. Temperature controller response and sensitivity.
The user must determine an appropriate maintenance schedule necessary for his or her own specific application upon evaluation of their operating experience. Realistic maintenance schedules can only be determined with full knowledge of the services and application situation involved.
6.2 Maintenance procedures
1. For servicing the actuator, the user must follow all steps and precautions printed in the installation instruction manual prepared for the specific actuator by its manufacturer.
2. For servicing the steam flow control valve, the user must follow all steps and precautions in Section 7.
3. For servicing the steam ring heater, the user must follow all steps and precautions printed in the installation manual prepared for the specific steam ring heater.
4. For servicing the temperature controller, the user must follow all steps and precautions printed in the installation manual prepared for the specific controller by its manufacturer.
6.3 Troubleshooting (see Table 2)
TABLE 2 - TROUBLESHOOTING
Problem Cause Solution
Surges in liquid flow. Pumping action. Increase pressure discharge. Surges in outlet temperature. Temperature controller overshoot. Desensitize controller. Refer to temperature
controller installation manual.
4
Page 5
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
7 DISASSEMBLY - REASSEMBLY
WARNING
Do not proceed with removal of the FHS from connecting piping unless the FHS has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to follow these instructions may cause severe personal injury.
1. Preparation Secure a workbench sufficiently sized to lay
out parts as they are removed.
2. Removal of valve sub-assembly from the FHS may be accomplished as follows:
a. Loosen and remove the air line connection
(60) from the valve actuator.
b. Connect the air hose to the air connection of
the actuator (239) and pressurize (0-12 psig, 0-85 kPaG) to open the valve 20-80%.
c. Loosen the stem connector nut (4) and stem
packing nut (26).
d. Unscrew the valve stem (17) from the
diaphragm actuator stem connector, turning counterclockwise to remove.
e. Remove the valve position indicating disc
(43) from the stem.
f. Loosen the yoke nut (4B) and remove from
the valve bonnet (20).
g. Remove the actuator diaphragm from the
valve (75).
h. Reduce the air pressure in the actuator to
0psig and remove the air line.
i. Remove the valve from connecting piping. j. Place the valve on a work bench, inlet side
down, with the stem pointing up.
k. While holding the valve body firmly, loosen
and remove the four (4) cap screws (100), and free the bonnet from the body (11) of the valve.
l. Grasp the valve piston (217) at the lower
end and slide the stem downward out of the bonnet carefully.
IMPORTANT
When sliding the stem out of the bonnet, care must be taken to avoid damaging the packing assembly with the threads of the valve stem.
m. Using a stiff wire with a short hook on its
end, remove all gaskets (7, 7A, 7B, 7C) cage (29) and seat (16) from inside body.
Note: It may be required to lightly tap the side of the body with a hammer to loosen and remove the seat.
n. Discard all removed gaskets. Do not re-use
gaskets under any circumstances.
FIGURE 2
Threads to diaphragm
actuator rod
WARNING
Gaskets are deformed permanently by compression and, if re-used, can cause leaks resulting in release of live steam causing severe personal injury or property damage.
o. Inspect the valve seat and piston for wear or
damage and replace if necessary.
3. Packing box maintenance must be performed as follows:
IMPORTANT
The valve stem must be out of the bonnet before attempting to remove the packing so that the stem is not damaged accidentally. If the packing is not to be replaced be careful when moving the valve stem through the packing, so that the stem threads do not damage the packing.
a. Remove the packing nut (26) and packing
gland (19) from the bonnet (20).
b. Using a stiff wire with a short hook on its
end, draw the packing rings (211) out of the bonnet.
4. Reassembly procedures for replacing stem packing.
a. Slide the valve stem through the packing
box of the bonnet.
b. Carefully slide a full set of new packing
rings over the valve stem (see Figure2) making sure that the packing is not damaged by the threads of the stem.
c. Replace the packing gland and packing nut
and tighten finger tight.
IMPORTANT
The stem packing nut should only be screwed down finger tight. When necessary to compress the packing more, tighten the packing nut by hand again.
Valve
packing
Steam pressure
Stem (pistonend)
5
Page 6
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
5. Reassembly of valve sub-assembly.
a. Assemble the components as shown in
Figure 5 and per instructions below.
b. With the valve body resting on a work bench,
inlet side down, insert the seat gasket and seat inside body making certain that the
seat is properly seated. c. Insert the cage over the top ring of the seat. d. Place the two (2) gaskets over the top ring of
the cage in proper order. e. Insert the bonnet/body gasket into the body. f. Make certain that the stem is properly
installed in the bonnet (refer to Section 4 -
Installation) and replace the bonnet into the
body. g. Hold the valve firmly and replace the cap
screws through the bonnet and wrench
tighten. h. Replace the valve body into the piping
system using a PTFE tape or equivalent on
all male tapered pipe threads as shown in
Figure 3. i. Connect air hose and regulator to
diaphragm actuator and pressurize to fully
open valve (100%). j. Place the actuator yoke over the threads of
the valve bonnet, making sure to place the
yoke nut and valve position indicating disc
over the stem while doing this. k. Thread the valve stem into the actuator
connector rod approximately 6 full turns. l. Tighten the yoke nut down finger tight and
check to see if the yoke is seated against the
valve bonnet. m. If the yoke is not seated against the valve
bonnet, thread the valve stem further into
the actuator connector rod until the yoke
is seated against the valve bonnet, then
tighten the yoke nut in place. n. Tighten the stem connector nut against the
valve position disc and actuator connector
rod. o. Slowly reduce the air pressure to the
actuator to close the valve. At 0psig
(0kPaG), the valve position indication disc
should indicate that the valve is closed. If
the disc goes below the 0% open mark on
the actuator scale, this indicates improper
adjustment. p. To adjust the disc position, increase the
air pressure to the actuator to raise the
valve 20-40% open. Then loosen the stem
connector nut a few turns and turn the stem
counterclockwise one turn, tighten the stem
connector nut and release the air pressure.
This procedure should be repeated until the
indicating disc is exactly indicating 0% open
for the valve. q. Remove the air hose from actuator r. Reconnect the air line connection to the
actuator. s. Refer to Section 5 - Operation, when
returning the FHS to service.
FIGURE 3
1-2 threads
8 DISPOSAL AT END OF USEFUL LIFE
Penberthy FHS' are used in a variety of fluid applications. By following the appropriate federal and industry regulations, the user must determine the extent of preparation and treatment the FHS must incur before its disposal. A Material Safety Data Sheet (MSDS) may be required before disposal services accept certain components.
Metal, glass and polymers should be recycled whenever possible. Refer to order and relevant data sheet for materials of construction.
9 TELEPHONE ASSISTANCE
If you are having difficulty with your FHS, contact your local Penberthy distributor. So that we may assist you more effectively, please have as much of the following information available as possible when you call:
- Model number
- Name of the company from whom you purchased the FHS
- Invoice number and date
- Process conditions (pressure, flow rates, tank shape, etc.)
- A brief description of the problem
- Trouble shooting procedures that failed
If attempts to solve your problem fail, you may request to return your intensive testing. You must obtain a Return Authorization (R.A.) number from Emerson before returning anything. Failure to do so will result in the unit being returned to you without being tested, freight collect. To obtain an R.A. number, the following information (in addition to that above) is needed:
- Reason for return
- Person to contact at your company
- 'Ship-to' address
There is a minimum charge for evaluation of non-warranty units. You will be contacted before any repairs are initiated should the cost exceed the minimum charge. If you return a unit under warranty, but it is not defective, the minimum charge will apply.
FHS
to the factory for
Tape
Direction of wrap
6
Page 7
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
10 EXPLODED PARTS DRAWING
FIGURE 4
171
239
65
148
4B
79
99
79
75A
79
76
PARTS LIST
Ref. nr Item
4 Nut 4A Nut 4B Nut jet 43 Disc 60 Fitting 63 Cross 65 Controller 73 Bracket 75 Valve 75A Valve 76 Strainer 79 Nipple 79A Nipple 91 Thermometer 99 Union 100 Screw 137 Bolt 148 Bushing 171 Tubing 206 Elbow 239 Actuator
79
75
4
43
60
91
206
137
63
73
79A
100
Steam ring heater
4A
7
Page 8
PENBERTHY MODEL FHS AUTOMATIC LIQUID HEATING SYSTEM
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FIGURE 5 Valve (75)
100A
7
16
29
7A
7B
217
4
17
211
19
26
7C
20
100
163
11
PARTS LIST
Ref. nr Item
4 Nut 7 Gasket 7A Gasket 7B Gasket 7C Gasket 11 Body 16 Seat 17 Stem 19 Gland 20 Bonnet 26 Nut, stem packing 29 Cage 100 Screw 100A Screw 163 Nameplate 211 Packing 217 Piston
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson andthe Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson.com/FinalControl
8
Loading...