Emerson Penberthy U, Penberthy L, Penberthy 2NC Installation, Operation And Maintenance Instructions

PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation, these instructions must be read carefully and understood.
PRODUCT WARRANTY
Emerson warrants its Penberthy products as designed and manufactured to be free of defects in the material and workmanship for a period of one year after the date of installation or eighteen months after the date of manufacture, whichever is earliest. Emerson will, at its option, replace or repair any products which fail during the warranty period due to defective material or workmanship.
TABLE OF CONTENTS
Product warranty ................................................ 1
1 About the manual..................................... 2
2 Introduction ............................................. 2
2.1 Features and specifications ........................ 2
2.2 Design ratings at max. and min.
operatingtemperatures .............................. 2
2.3 Application data ........................................... 2
3 Inspection and performance
confirmation ............................................ 2
3.1 Receiving inspection .................................... 2
3.2 User's rating inspection .............................. 2
4 Installation ............................................... 3
4.1 Effect of related piping strain ...................... 3
5 Operation ................................................. 4
5.1 Pre-operational check ................................. 4
5.2 Hydrostatic or vacuum test ......................... 4
5.3 Operating ...................................................... 4
6 Maintenance ............................................ 5
6.1 Preventative maintenance ........................... 5
6.2 System shut down ........................................ 5
6.2 Troubleshooting ........................................... 5
7 Removal - disassembly - reassembly ..... 6
8 Disposal at end of useful life ................... 6
9 Telephone assistance .............................. 6
10 Exploded parts diagram .......................... 7
Tables and figures
Table 1 -
Table 2 - Recommended minimum motive
Table 3 - Troubleshooting ................................ 5
Figure 1 - Assembly ........................................... 3
Figure 2 - Assembly .......................................... 3
Figure 3 - Discharge .......................................... 4
Figure 4 - Exploded parts diagram ................... 7
Design ratings
operatingtemperatures ................... 2
steam line sizes ................................ 3
at max. and min.
Prior to submitting any claim for warranty service, the owner must submit proof of purchase to Emerson and obtain written authorization to return the product. Thereafter, the product shall be returned to Emerson with freight prepaid.
This warranty shall not apply if the product has been disassembled, tampered with, repaired or otherwise altered outside of the Emerson factory, or if it has been subject to misuse, neglect or accident.
The responsibility of Emerson hereunder is limited to repairing or replacing the product at its expense. Emerson shall not be liable for loss, damage or expenses directly or indirectly to the installation or use of its products, or from any other cause or for consequential damages. It is expressly understood that Emerson is not responsible for damage or injury caused to other products, buildings, personnel or property, by reason of the installation or use of its products.
This is Emerson's sole warranty and in lieu of all other warranties, expressed or implied which are hereby excluded, including in particular all warranties of merchantability or fitness for a particular purpose.
This document and the warranty contained herein may not be modified and no other warranty, expressed or implied, shall be made by or on behalf of Emerson unless made in writing and signed by the company's general manager or director of engineering.
related
Emerson.com/FinalControl
© 2018 Emerson. All Rights Reserved. VCIOM-04064-EN 19/04
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
1 ABOUT THE MANUAL
This manual has been prepared as an aid and guide for personnel involved in installation or maintenance. All instructions must be read and understood thoroughly before attempting any installation, operation or maintenance.
IMPORTANT
Emerson does not have any control over the manner in which its jet pump is handled, installed or used. Emerson cannot and will not guarantee that a jet pump is suitable for or compatible with the user's specific application.
WARNING
Failure to follow any instruction could possibly result in a malfunction of the jet pump resulting in leakage of the contained fluid, severe physical injury or property damage.
2 INTRODUCTION
2.1 Features and specifications
Penberthy models U and L steam operated jet pumps are single stage ejectors designed for exhausting and evacuating applications using steam as the operating medium in the range of 80 to 200 psig (550 to 1380 kPaG). The model U operates most efficiently in a vacuum range of 6 to 12 inches (152to305mm) hg.
absolute
. The model L operates most efficiently in a range of 3 to 6 inches (76to 152mm) hg.
Model 2NC steam operated jet pump is a two stage non-condensing ejector designed for exhausting and evacuating applications using steam as the operating medium in the range of 100 to 200 psig (690 to 1380 kPaG).
The model 2NC operates most efficiently in a vacuum range of 0.5 to 3 inches hg. absolute.
2.2 Design ratings at maximum and minimum operating temperatures (see Table 1)
To determine the maximum allowable working pressure for a specific temperature within the design limits stated in Table 1, the user should refer to relevant technical data sheets or, when provided, the specifically stated design limits on a product proposal.
absolute
.
2.3 Application data
Models U and L are single stage steam operated jet pumps for exhausting or evacuating applications with the model U operating at a higher vacuum range than the model L.
The model 2NC is a two stage non-condensing ejector with a vacuum range lower than that of the model L jet pump.
Note: For specific application data within the ranges stated in Table 1, the user should consult the product proposal for the specific model and size jet pump, or should request the supply of the applicable technical data sheet.
WARNING
Under no circumstances should these design ratings or application data be exceeded. Exceeding design ratings or application data may cause severe physical injury or property damage.
3 INSPECTION AND PERFORMANCE CONFIRMATION
3.1 Receiving inspection
Upon receipt of the jet pump, check all components carefully for damage incurred in shipping. If damage is evident or suspected, do not attempt installation. Notify the carrier immediately and request a damage inspection.
3.2 User's rating inspection
The user should confirm that:
1. The jet pump size, model, part number and motive pressure rating stamped on nameplate (Figure 4 item 163) conforms to the description on the user's purchase order.
2. The operating conditions described in the purchase order agree with the actual operating conditions at the installation site.
3. The actual operating conditions at the installation site are within the application data shown on the relevant technical data sheet or product proposal referred to above.
4. The materials of construction of the jet pump are compatible with both the contained fluid and the surrounding atmosphere in the specific application.
IMPORTANT
If the size, model or performance data of the jet pump as received does not conform with any of the criteria above, do not proceed with installation. Contact an authorized Penberthy distributor for assistance.
TABLE 1 - DESIGN RATINGS AT MAXIMUM AND MINIMUM OPERATING TEMPERATURES
Material Bodies
Iron
Stainless steel
80 psig [550 kPaG] at -20°F [ -29°C] to +150°F [66°C] 50 psig [340 kPaG] at +350°F [177°C] 200 psig [1380 kPaG] at -150°F [-101°C] to +150°F [66°C] 125 psig [ 860 kPaG] at +400°F [ 204°C]
2
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
4 INSTALLATION
Installation should only be undertaken by qualified personnel who are familiar with equipment of this type. They should have read and understood all of the instructions in this manual. The user should refer to the relevant technical data sheet or the product proposal to obtain dimensional information for the specific size and model of jet pump.
Check the cut away views (Figure 4) for the location of steam inlet, suction and discharge connections to insure correct hook up.
4.1 Effect of related piping and precautions
1. Model U and L jet pumps can be installed and operated in any position.
2. Model 2NC jet pumps must be installed in correct sequence in accord with outline drawings furnished with the jet pump. Two stage jet pumps may be assembled directly with the Y stage connected to the Z stage as shown in Figure 1, or an elbow may be located between the Y stage discharge and the Z stage inlet as shown in Figure 2.
IMPORTANT
It is very important that model 2NC two stage ejectors be assembled in the required sequence as noted previously. First stage ejector suction connection is to be connected to the vacuum system and discharge into the second stage suction connection. Second stage discharges to atmospheric pressure.
3. Steam must be dry and saturated at not less than the specified motive steam pressure. Motive steam pressure is defined as that pressure at the ejector-steam-inlet connection as measured with a recently calibrated, good quality steam gauge. A small amount of super-heat, 5 to 10° is preferred. Steam separators and small super-heaters are recommended as a cure for wet steam.
4. It is recommended that all single stage ejector models smaller than L-10H or U-10H and all two stage ejectors have a strainer installed in the steam line to prevent dirt and scale from collecting in the steam line flow to the nozzle where it can build up and block the nozzle causing a malfunction of the ejector.
5. Recommended minimum motive steam line sizes to the ejector are shown in Table 2 below. These sizes are based on a pressure drop of 2% per 100 feet of pipe.
Standard ejector steam connections may not be identical with the steam line size selected, or shown in Table 2. Correct bushings to suit the selected pipe size are not supplied and must be furnished by the user. All motive steam piping should be insulated and liquid removed through traps in accordance with good practice.
Connection to
vacuumsystem
Motive steam
FIGURE 1
Motive steam
Z stage
Y stage
Discharge to atmosphere
Connection to
vacuumsystem
Elbow
FIGURE 2
Motive steam
Y stage
Motive steam
Discharge to
atmosphere
Z stage
TABLE 2 - RECOMMENDED MINIMUM MOTIVE STEAM LINE SIZES
Model number Line size (in) Model number Line size (in)
L-1H, U-1H ½ 2NC1H, 2NC2H ¾ L-2H, L-3H, U-2H, U-3H ¾ 2NC3H, 2NC4H 1 L-4H, L-5H, U-4H, U-5H 1 2NC5H, 2NC6H, 2NC7H 1¼ L-6H, L-7H, L-8H, U-6H, U-7H, U-8H 2NC8H, 2NC9H 1½ L-9H, L-10H, L-11H, U-9H, U-10H, U-11H 2NC10H, 2NC11H, 2NC12H, 2NC13H 2 L-12H, L-13H, L-14H, U-12H, U-13H, U-14H 2 2NC14H, 2NC15H 2½ L-15H, L-16H, U-15H, U-16H 2NC16H 3
3
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
6. Steam valves should be installed at each ejector stage with pressure-tap openings for attachment of pressure gauges when required. Pressure readings must be between the valve and the steam inlet.
7. Discharge piping must permit free flow of exhaust vapors to prevent back pressure from exceeding 32 in. (813 mm) hg. absolute and the ejector discharge connection and design flow conditions.
WARNING
Ejector exhaust must be piped to atmosphere in a safe place due to the nature of the gases being pumped. If exhaust is not piped to a safe place properly, it could cause severe physical injury or property damage.
Discharge silencers can be applied by the user when desired and when sized properly for pressure drop. If ejectors are discharged vertically upward to atmosphere, a discharge trap as shown in Figure 3 should be provided.
Intermediate ejector-stage-discharge piping must be as short as possible and limited to not more than one 90°bend. Other arrangements are possible, but are not recommended without factory approval of the proposed arrangement to evaluate pressure loss.
8. Care must be taken to insure leak-tight ejector suction piping connections. Ejector can be connected directly to the system from which gases and vapors are being pumped, however, it is recommended that an isolating valve be provided between the ejector suction connection and the system. Operating problems on new processes will be easier to diagnose and ejector performance will be checked more easily if an isolating valve is installed. Leak-tight gate or butterfly valves are most suitable for this application.
9. Eliminate or drain possible points of condensate collection adequately to prevent freezing.
10. Insulate all steam lines.
11. Do not impose system piping stresses upon the ejector.
12. Allow clearance for removal of ejector.
FIGURE 3
Piping size equal to
ejector discharge size
or larger
Ejector
discharge
Suction
Motive
steam
5 OPERATION
5.1 Pre-operational check
1. Ensure that all installation procedures have been completed.
2. Check to determine that all connections are pressure tight.
5.2 Hydrostatic or vacuum test
1. Take all the precautions necessary to handle the possibility of leakage during the test.
2. Hydrostatic pressure test to 100 psig (690kPaG) or vacuum test and correct any leakage before proceeding.
5.3 Operating
Note: Steam-jet ejectors are devices using the
energy of the high velocity steam jet as it is reduced in pressure from steam-inlet pressure and expanded to suction pressure to entrain and compress suction gases and vapors from their inlet-pressure condition to a discharge pressure that may be 10 or more times greater than suction-inlet pressure for each individual stage. Ejector stages are connected in series to increase total system-compression range and permit pumping gases and vapors from as low as 0.25 in. (6.4 mm) hg. absolute pressure to atmospheric discharge pressure.
Discharge to atmosphere
Drain leg
¼ drain valve
Drain line
1. Single stage ejectors
a. The first step in placing a single stage
model U or L ejector into operation is to apply steam at the design pressure to the nozzle.
b. The second step is waiting a period of time
to heat up and clear the steam lines and ejector of all condensate. At this time, the ejector should meet its guaranteed performance.
2. Two stage ejectors
a. The first step in the start up of the two stage
model 2NC ejector system, particularly for evacuation service, that is, reducing the pressure within a closed space to some predetermined value, is to place the Z stage in operation by admitting design pressure steam to the Z stage steam inlet.
b. The second step is to admit design steam
pressure to the Y stage steam inlet after the vacuum system pressure has been reduced to 10 to 8 inches (254 to 203 mm) of mercury absolute.
c. After a period of operation sufficiently
long to heat up and clear the steam lines and ejectors of all condensate, the ejector system should meet its guaranteed performance.
4
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
6 MAINTENANCE
WARNING
Maintenance should only be undertaken by qualified, experienced personnel who are familiar with this equipment and have read and understood all the instructions in this manual. DO NOT proceed with any maintenance unless the jet pump has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to follow these instructions may cause a sudden release of pressure resulting in personal injury or property damage.
6.1 Preventative maintenance
The user must create maintenance schedules, safety manuals and inspection details for each specific installation of a jet pump.
On all installations the following items should be evaluated regularly by the user for purposes of maintenance:
1. Jet pump for corrosion or debris buildup.
2. Piping and fittings for corrosion or debris build up.
3. All connections for tightness.
4. Units for wear.
5. Strainers for debris build up.
6.2 System shut down
WARNING
Safety procedures must be taken if hazardous gases are being discharged from the Z stage ejector. Failure to follow safety procedures may cause severe personal injury or property damage.
Shut down of model 2NC ejector systems may follow the start up procedure in reverse or both stages may be shut down simultaneously. When a system is shut down and the pressure in the vacuum is still below atmospheric pressure, air will rush back into the process vacuum system. Since this action may create a harmful result to the product or may create a hazardous or explosive condition, it is recommended that the customer assess this problem prior to unit installation to protect against the event of such occurrences. Installing a manual shut-off valve in the suction line as close to the ejector as possible will help prevent such an occurrence. Another method of preventing the back flow of air into the vacuum system is to break the system vacuum by admitting inert gas into the vacuum vessel.
6.3 Troubleshooting (see table 3)
The user must determine an appropriate maintenance schedule necessary for his or her own specific application, upon evaluation of his or her own operating experience. Realistic maintenance schedules can only be determined with full knowledge of the services and application situation involved.
TABLE 3 - TROUBLESHOOTING
Problem Cause Solution
Wet steam 1. Steam temperature not high enough 1. Drain steam inlet lines and install a steam separator in the line or add a steam
superheater to raise steam temperature to about 10°F (-12°C) above saturation temperature for particularly critical low flow units.
Jet pump not performing up to capacity 1. Low steam pressure 1. Check steam pressure with a recently calibrated steam pressure gauge.
If steam pressure cannot be increased, contact an authorized Penberthy distributor for assistance
2. Motive steam nozzle becomes plugged 2. Clean out and install a strainer in the motive steam line
3. Air leakage into vacuum system 3. Hydrostatic and vacuum test unit to locate leaks
4. Superheated steam 4. Contact an authorized Penberthy representative for assistance
5
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
7 REMOVAL - DISASSEMBLY - REASSEMBLY
IMPORTANT
Do not proceed with removal of the jet pump from connecting piping unless the jet pump has been relieved of all pressure or vacuum, has been allowed to reach ambient temperature and has been drained or purged of all fluids. Failure to follow these instructions could result in personal injury or property damage.
To disassemble the unit, first attach a short piece of pipe to the suction connection as a handle. Then, grip the nozzle flats and rotate in a counterclockwise direction. When ready to reassemble the unit, be sure the seal face of the nozzle and body are free of foreign material and raised metal due to nicks. A non-hardening pipe seal compound may be applied to the threads to further promote sealing. Thread the body back on the nozzle turning in a clockwise direction.
8 DISPOSAL AT END OF USEFUL LIFE
Penberthy jet pumps are used in a variety of fluid applications. By following the appropriate federal and industry regulations, the user must determine the extent of preparation and treatment the jet pump must incur before its disposal. A Material Safety Data Sheet (MSDS) may be required before disposal services accept certain components. Metal, glass and polymers should be recycled whenever possible. Refer to order and relevant technical data sheet for materials of construction.
9 TELEPHONE ASSISTANCE
If you are having difficulty with your jet pump, contact your local Penberthy distributor. So that we may assist you more effectively, please have as much of the following information available as possible when you call:
- Model number
- Name of the company from whom you purchased the jet pump
- Invoice number and date
- Process conditions (pressure, flow rates, tank shape, etc.)
- A brief description of the problem
- Troubleshooting procedures that failed
If attempts to solve your problem fail, you may request to return your jet pump to the factory for intensive testing. You must obtain a Return Authorization (R.A.) number from Emerson before returning anything. Failure to do so will result in the unit being returned to you without being tested, freight collect. To obtain an R.A. number, the following information (in addition to that above) is needed:
- Reason for return
- Person to contact at your company
- 'Ship-to' address
There is a minimum charge for evaluation of non-warranty units. You will be contacted before any repairs are initiated should the cost exceed the minimum charge. If you return a unit under warranty, but it is not defective, the minimum charge will apply.
6
PENBERTHY MODELS U, L AND 2NC FABRICATED METAL CONSTRUCTION JET PUMPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
10 EXPLODED PARTS DIAGRAM
FIGURE 4
Steam inlet
61
MODEL U AND L
connection
11
163
'Y' stage steam inlet connection
61
Discharge
connection
PARTS LIST
Ref. nr Item
11 Body 61 Nozzle 82 Delivery jet 133 Coupling 163 Nameplate
82
Suction
connection
11
MODEL 2NC
82
163
connection
82
133
Suction
11
'Z' stage steam inlet connection
61
Discharge
connection
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Penberthy is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson andthe Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson.com/FinalControl
7
Loading...