Emerson Network Router User Manual

Instruction Manual
P/N 20001909, Rev. D July 2006
ProLink® II Software for Micro Motion® Transmitters
Installation and Use Manual
©2006, Micro Motion, Inc. All rights reserved. ELITE, ProLink, and the Micro Motion logo are registered trademarks of Micro Motion, Inc., Boulder, Colorado. MVD and MVD Direct Connect are trademarks of Micro Motion., Inc., Boulder, Colorado. Micro Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Emerson logo is a trademark of Emerson Electric Co. All other trademarks are property of their respective owners.

Contents

Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 About this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 About ProLink II software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.1 Supported transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.2 Uses of ProLink II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 ProLink II requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 PC requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.2 Installation kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Determining your transmitter type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Chapter 2 Installation and Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Installation and setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2.1 Ensure required privileges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2.2 Install the ProLink II software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2.3 Generate the temporary license. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2.4 Determine your connection type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2.5 Install the signal converter and connect the wires . . . . . . . . . . . . . . . . . . 11
2.2.6 Configure ProLink II connection parameters and connect to the
transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.2.7 Obtain and configure a site key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.3 Troubleshooting the ProLink II installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.3.1 Insufficient privileges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.3.2 Missing or corrupt registry entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.4 Troubleshooting the ProLink II connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.4.1 OPC server or OPC client issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.4.2 Other issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Installation and Use Manual i
Contents
Chapter 3 Using ProLink II Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.2 ProLink II user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3.1 Connecting to a transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.3.2 Disconnecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.4 ProLink II help system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.5 Viewing installed options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6 Viewing process data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.7 Viewing and resetting totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.8 Viewing meter status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.9 Viewing and acknowledging alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.9.1 Viewing alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.9.2 Acknowledging alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.10 Managing the ProLink II license . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.10.1 Transferring to same PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.10.2 Transferring to different PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Chapter 4 Initial Transmitter Startup Procedures. . . . . . . . . . . . . . . . . . . . . . 43
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.2 Loop tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.3 Trimming the milliamp (mA) output(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
4.4 Zeroing the meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 5 Transmitter Configuration, Characterization,
and Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.2 Using configuration files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.2.1 Saving a configuration file to a PC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5.2.2 Loading a configuration file to a transmitter. . . . . . . . . . . . . . . . . . . . . . . 52
5.3 Configuring a transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5.3.1 Using the Gas Unit Configurator tool. . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
5.4 Characterizing the meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.4.1 When to characterize. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.4.2 Characterization parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.4.3 How to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.5 Calibrating the meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.5.1 When to calibrate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.5.2 Density calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.5.3 Temperature calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.6 Compensating for pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.6.1 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.6.2 Pressure correction factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.6.3 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.7 Compensating for temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.8 Configuring polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
ii ProLink® II Software for Micro Motion® Transmitters
Contents
Chapter 6 Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.2 Running the meter verification test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.2.1 First panel: Sensor and Transmitter Configuration. . . . . . . . . . . . . . . . . . 67
6.2.2 Second panel: Test Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
6.2.3 Third panel: Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.2.4 Fourth panel: Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.2.5 Fifth panel: Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Chapter 7 Data Logger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.2 Using Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.2.1 Defining the log file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.2.2 Specifying log contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.2.3 Starting and stopping the logging function. . . . . . . . . . . . . . . . . . . . . . . . 79
7.2.4 Data Logger tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Appendix A Transmitter Terminal Reference . . . . . . . . . . . . . . . . . . . . . . . . . . 81
A.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
A.2 Transmitter terminal diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendix B Configuring the Discrete Batch Application . . . . . . . . . . . . . . . . . . 87
B.1 About this appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
B.2 About discrete batching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
B.3 Discrete batch configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
B.3.1 Flow source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
B.3.2 Control options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
B.3.3 Configure presets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
B.3.4 Batch control methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
B.4 Running a batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
B.5 Performing Batch AOC calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Installation and Use Manual iii
iv ProLink® II Software for Micro Motion® Transmitters
Chapter 1

Before You Begin

1.1 About this manual

This manual explains how to install the Micro Motion on your personal computer (PC).
This manual also provides an overview of using ProLink II with Micro Motion transmitters. Before using this instruction manual, the reader should be familiar with the Microsoft Windows operating system.
There are a number of transmitter and application features that may appear in your ProLink II installation: for example, the enhanced density application, the petroleum measurement application, the custody transfer application, event configuration, or display configuration. This manual contains information on configuring and using the discrete batch application (see Appendix B). For detailed information on configuring and using other transmitter-specific or application-specific features, see the appropriate transmitter or application manual. If you still have questions, contact the Micro Motion Customer Service Department. Telephone numbers are listed in Section 1.5.
®
ProLink®II software program, v2.5 and later,
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin

1.2 About ProLink II software

This section provides an overview of ProLink II software.

1.2.1 Supported transmitters

The ProLink II program provides communication between a personal computer and the following Micro Motion transmitters and devices:
Model 1700/2700
Model 1500/2500
Model 2400S
Core processor and Enhanced core processor
•MVD
Series 3000 with 4-wire sensor interface (MVD™)
RFT9739
RFT9712
IFT9701/9703
Note: MVD Direct Connect is a direct host meter that does not include a transmitter. However, ProLink II can be used to communicate with the core processor component in MVD Direct Connect installations.
Direct Connect
Installation and Use Manual 1
Before You Begin

1.2.2 Uses of ProLink II

Using ProLink II, you can:
Perform initial transmitter startup procedures
Read process variables
Manage totalizers and inventories
Configure the transmitter
Perform verification and calibration procedures
Read meter status information and alarm conditions
Troubleshoot the meter

1.3 ProLink II requirements

Before starting the ProLink II installation, review the requirements in this section.

1.3.1 PC requirements

To install and run ProLink II, your PC must meet or exceed the following requirements:
200 MHz Pentium processor
One of the following:
- Windows 98 (initial release or second edition) with 32 megabytes (MB) RAM
- Windows ME with 64 MB RAM
- Windows NT 4.0 with Service Pack 6a and 64 MB RAM
- Windows 2000 with Service Pack 3 and 128 MB RAM
- Windows XP with Service Pack 1 and 128 MB RAM
24 MB of available hard disk space
Video with support for 256 or more colors
An available serial port or USB port
Note: Windows NT does not support the USB port.

1.3.2 Installation kits

Micro Motion provides ProLink II installation kits for RS-485 connections (serial port or USB) and for Bell 202 connections (serial port or USB). Kit contents are listed in Table 1-1. If you need a ProLink II installation kit, contact Micro Motion.
2 ProLink® II Software for Micro Motion® Transmitters
Before You Begin
Tabl e 1-1 ProLink II installation kits
Physical layer Connection Kit contents
RS-485 Serial port • Black Box Async RS-232 <-> 2-wire RS-485 Interface Converter
(Code IC521A-F)
• DB9-DB25 adapter
• DB9-DB9 tester
•Cable
USB • Black Box Async RS-232 <-> 2-wire RS-485 Interface Converter
(Code IC521A-F)
• Black Box USB-to-serial (RS-232) converter (Code IC138A)
• DB9-DB25 adapter
• DB9-DB9 tester
•Cable
Bell 202 Serial port • MACTek VIATOR RS232 HART Interface with integral HART cable
terminating in two clips (Model 010001)
• DB9-DB9 tester
USB • MACTek VIATOR USB HART Interface with integral USB cable and
integral HART cable terminating in two clips (Model 010031)
Note: If you use a different RS-232 to RS-485 signal converter or HART interface, it is your responsibility to ensure that your equipment provides equivalent functionality. See the ReadMe.txt file in the ProLink II installation directory, or contact Micro Motion customer support for assistance or additional information.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Note: A Windows driver is required for correct operation of the VIATOR USB HART Interface. This driver is provided with the VIATOR USB HART Interface. Ensure that the driver is installed before attempting to connect through the USB port. If this driver is not installed, Windows will not recognize the USB converter when it is plugged into the USB port.

1.4 Determining your transmitter type

To configure, use, and troubleshoot the transmitter, you must know your transmitter type, installation/mounting type, and outputs option board type (Series 1000/2000 transmitters only). The transmitter’s model number, which is provided on a tag attached to the transmitter, provides this information. See Figure 1-1 for assistance in interpreting the model number.
If you are using MVD Direct Connect, refer to the model number on the sensor.

1.5 Micro Motion customer service

For customer service, phone the support center nearest you:
In the U.S.A., phone 1-800-522-MASS (1-800-522-6277)
In Canada and Latin America, phone (303) 527-5200
In Asia, phone (65) 6770-8155
In the U.K., phone 0870 240 1978 (toll-free)
Outside the U.K., phone +31 (0) 318 495 670
Installation and Use Manual 3
Before You Begin
Figure 1-1 Transmitter model numbers and codes
RFT9739
R F T 9 7 3 9 x x x x x x x
Mounting:
• R = rack-mount or panel-mount
• D, E = field-mount
Transmitter model
Series 3000
3 x x 0 x x x x x x x x x x x x
Sensor interface:
• 0 = none (MVD)
• 5, 6 = 4-wire (MVD) Mounting:
• R = rack-mount
• P = panel-mount
• A = field-mount Transmitter model
Model 1500/2500
x 5 0 0 x x x x x x x x x x x x
RFT9712
R F T 9 7 1 2 x x x x x x x
Transmitter model
IFT9701/9703
I F T 9 7 0 x x x x x x x x
Mounting:
•I, M = integral
• R, L, J, S, A = remote Transmitter model
Model 1700/2700
x 7 0 0 x x x x x x x x x x
Software option 1:
• B = Filling and Dosing application
(1)
Outputs option board:
• A = analog outputs option board
• B, C = configurable input/outputs option board Mounting/installation type:
• D = 4-wire to sensor with integral core processor
• B = remote core processor with remote transmitter Transmitter model
(1) Model 1500 transmitter with filling and dosing application only.
Requires Outputs option board C.
Outputs option board:
• A = analog outputs option board
• B, C = configurable input/outputs option board
• D = intrinsically safe outputs option board
•E = F
OUNDATION fieldbus outputs option board
• G = PROFIBUS PA outputs option board Mounting/installation type:
• R = remote (4-wire remote installation)
• I = integral (transmitter mounted on sensor)
• C = transmitter/core processor assembly (9-wire remote installation)
• B = remote core processor with remote transmitter Transmitter model
4 ProLink® II Software for Micro Motion® Transmitters
Before You Begin
Figure 1-1 Transmitter model numbers and codes continued
Model 2400S
2 4 0 0 S x x x x x x x x x
User interface option:
• 1 = display/LCD with glass lens
• 2 = no display/LCD
• 3 = display/LCD with non-glass lens Outputs option board:
• A = analog outputs option board
• C = DeviceNet I/O option board
• D = PROFIBUS DP I/O option board Transmitter model
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Installation and Use Manual 5
6 ProLink® II Software for Micro Motion® Transmitters
Chapter 2

Installation and Setup

2.1 Overview

This chapter provides information on installing ProLink II software, connecting to the transmitter, and troubleshooting the installation or connection.
To install and set up ProLink II, the following steps are required:
1. Ensure required privileges (see Section 2.2.1)
2. Install the ProLink II software onto your PC (see Section 2.2.2)
3. Generate the temporary license (see Section 2.2.3)
4. Determine your connection type (see Section 2.2.4)
5. Install the signal converter and connect the wires between the PC and the transmitter (see Section 2.2.5)
6. Configure the connection and connect to the transmitter (see Section 2.2.6)
7. Obtain and configure a site key (see Section 2.2.7)
For troubleshooting information, see Section 2.3 and Section 2.4.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin

2.2 Installation and setup

To install and set up ProLink II, follow the steps below.

2.2.1 Ensure required privileges

Installing and running ProLink II requires specific privileges. Install ProLink II using the required user account, and ensure that all persons who will run ProLink II have the required privileges. See Tabl e 2 -1 .
Tabl e 2-1 Required privileges
Operating system To install ProLink II To run ProLink II
Windows NT 4.0 Must be the built-in Admin account • Read/write local hard drive
Windows 2000 Must be member of the Administrators
Windows XP Must be member of the Administrators
Windows 98 Not applicable Not applicable
Windows ME Not applicable Not applicable
group
group
• Read/write Windows registry
• Read/write local hard drive
• Read/write Windows registry
• Read/write local hard drive
• Read/write Windows registry
Installation and Use Manual 7
Installation and Setup
During installation on a Windows NT, Windows 2000, or Windows XP system, if the installer is not in the Administrator group, the installation wizard may display a message warning that the installation may not be successful. If this occurs, the installation wizard will run to completion but the Windows registry may not be updated correctly. If you are subsequently unable to connect to a transmitter, reinstall the software using the required user account.

2.2.2 Install the ProLink II software

To install ProLink II software:
1. Insert the ProLink II CD-ROM into the PC’s CD-ROM drive.
2. If the setup program does not start automatically, locate and run the SETUP.EXE file. The file is located in the root directory on the CD-ROM (e.g., D:\setup.exe, where “D” is your CD-ROM drive letter).
3. Follow the on-screen instructions to complete the installation. If you have a previous version of ProLink II installed on your PC, you may be prompted to remove it before installing the new version.
Note: The ProLink II site key is associated with a disk drive and specific folder on your PC. If you decide to move ProLink II after installation, you will have to transfer the license and reinstall ProLink II. To avoid this step, be sure to install ProLink II into a location that you can use permanently.
Note: If you have a Model 2700 transmitter with transmitter software earlier than v3.4, and you have the enhanced density application installed, you cannot access the enhanced density functions with ProLink II v2.1 or later. To configure and manage the enhanced density application from ProLink II, you must either upgrade your transmitter software to v3.4 or later, or continue to use ProLink II v1.x with enhanced density support. You can install both ProLink II v1.x and ProLink II v2.0 or later on the same PC, and you can use ProLink II v2.0 or later with your pre–v3.4 transmitter for all functions except enhanced density. You can also use ProLink v1.2 with transmitter software v3.4 and later; however, not all transmitter functions will be accessible using the older program.

2.2.3 Generate the temporary license

The first time ProLink II is run, you will be prompted to generate a temporary license. This license will allow you to run ProLink II with full functionality for seven days, starting from the current date and time. Follow the on-screen instructions to generate the temporary license.
Note: If you are running Windows 98 or Windows ME, you must temporarily disable any anti-virus software running on your PC before you can generate the temporary license. You can re-enable the anti-virus software immediately after the temporary license has been successfully generated.
Continue with Section 2.2.4 to use ProLink II for seven days. During this time period, follow the instructions in Section 2.2.7 to obtain and configure a site key.
Note: If you attempt to use ProLink II after the temporary license has expired, ProLink II will no longer allow you to connect to a transmitter.
8 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup

2.2.4 Determine your connection type

Different transmitters and networks support different connection types.
Table 2-2 lists the supported protocols and wiring methods for IFT97xx and RFT97xx transmitters.
Table 2-3 lists the supported protocols and wiring methods for Model 1500/2500, Model 1700/2700, and Series 3000 transmitters.
Table 2-4 lists the supported protocols and wiring methods for the Model 2400S transmitter.
Table 2-5 lists the supported protocols and wiring methods for all MVD Direct Connect systems.
In these tables, and throughout the chapter:
Temporary – refers to a connection that is not permanent and is typically used only for configuration and troubleshooting. Because the transmitter housing must be open for the duration of the connection, these connections should be removed and the housing closed as soon as possible. The operator should be aware of the safety hazards that result from opening the transmitter housing.
Hard-wired – refers to a connection that is made to the permanent wiring, usually a transmitter output wire or the network that the transmitter is already using. Because hard-wired connections do not require the transmitter housing to be open, they can be left in place as desired.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
AN – refers to transmitters with the analog outputs option board
IS – refers to transmitters with the intrinsically safe outputs option board
CIO – refers to transmitters with the configurable input/outputs option board
FF – refers to transmitters with the F
OUNDATION fieldbus input/output option board
PA – refers to transmitters with the PROFIBUS-PA input/output option board
DP – refers to transmitters with the PROFIBUS-DP input/output option board
DN – refers to transmitters with the DeviceNet input/output option board
MVD Direct Connect – refers to meter installations that include the core processor but do not include a transmitter. ProLink II is connected directly to the RS-485 terminals on the core processor or the MVD Direct Connect I.S. barrier.
Once you have determined your connection type, use the Wiring Method # value in the table to direct you to the correct wiring procedure in Section 2.2.5.
Installation and Use Manual 9
Installation and Setup
Tabl e 2-2 Communication protocols and wiring methods for IFT97xx and RFT97xx transmitters
Transmitter type
Wiring method
IFT9701 IFT9703 RFT9712 RFT9739
Wiring method #
HART protocol
Bell 202 physical layer
• Temporary or hard-wired connection to transmitter or multidrop network
• Temporary connection to field-mount transmitters ✓✓ 2
• Temporary connection to rack-mount transmitters 3
RS-485 physical layer
• Temporary or hard-wired connection to transmitter or multidrop network
✓✓✓ 1
✓✓ 5
Modbus protocol (RS-485 physical layer)
• Temporary or hard-wired connection to transmitter or multidrop network
6
Tabl e 2-3 Communication protocols and wiring methods for Model 1500/2500, Model 1700/2700, and
Series 3000 transmitters
Transmitter type
Wiring method
Model 1500/2500
Model 1700/2700
Series 3000
Wiring method #
HART protocol
RS-485 physical layer
• Temporary or hard-wired connection to RS-485 terminals
Bell 202 physical layer
• Temporary or hard-wired connection to primary mA output or multidrop network
• Temporary or hard-wired connection to primary mA output or multidrop network
(1)
AN 5
AN CIO
IS 4
1
Modbus protocol (RS-485 physical layer)
• Temporary or hard-wired connection to RS-485 terminals
• Temporary connection to service port ✓✓✓ 7
(1) Except Model 1500 transmitter with the Filling and Dosing application. The Model 1500 transmitter with the Filling and Dosing
application does not support HART communication.
AN 6
10 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Tabl e 2-4 Communication protocols and wiring methods for Model 2400S transmitters
Wiring method Transmitter type Wiring method #
HART protocol
• Temporary connection to HART clips AN 8
• Temporary or hard-wired connection to primary mA output or multidrop network
(Bell 202 physical layer)
AN 1
Modbus protocol (RS-485 physical layer)
• Temporary connection to service port clips AN
DN DP
7
Tabl e 2-5 Communication protocols and wiring methods for MVD Direct Connect
Wiring method Wiring method #
Modbus protocol
• Temporary or hard-wired connection to RS-485 terminals on core processor or I.S. barrier
(RS-485 physical layer)
9

2.2.5 Install the signal converter and connect the wires

All ProLink II connection methods require a signal converter. Micro Motion offers four different installation kits to cover all required signal converter types. See Section 1.3.2 for a list of the available installation kits and signal converters.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Note: A Windows driver is required for correct operation of the VIATOR USB HART Interface. This driver is provided with the VIATOR USB HART Interface. Ensure that the driver is installed before attempting to connect through the USB port. If this driver is not installed, Windows will not recognize the USB converter when it is plugged into the USB port.
To install the signal converter and connect the wires, follow the instructions for your connection type. Refer to the Wiring Method # value in Table 2-2, 2-3, 2-4 or 2-5.
WARNING
On Model 1700/2700 transmitters, opening the power supply compartment in explosive atmospheres while the power is on can cause an explosion.
Before using the service port to communicate with the transmitter in a hazardous area, make sure the atmosphere is free of explosive gases.
WARNING
On Model 1700/2700 transmitters, opening the power supply compartment can expose the operator to electric shock.
To avoid the risk of electric shock, do not touch the power supply wires or terminals while using the service port.
Installation and Use Manual 11
Installation and Setup
On Model 3350/3700 transmitters, opening the wiring compartment in explosive atmospheres can cause an explosion.
Do not remove the compartment covers in an explosive atmosphere within three minutes after power is disconnected.
On Model 2400S transmitters, removing the transmitter housing cover in a hazardous area can cause an explosion.
Because the housing cover must be removed to connect to this transmitter using the service port clips or HART clips, these connections should be used only for temporary connections, for example, for configuration or troubleshooting purposes.
When the transmitter is in an explosive atmosphere, use a different method to connect to your transmitter.
WARNING
WARNING
WARNING
Removing the core processor lid can expose the operator to electric shock.
To avoid the risk of electric shock, do not touch the power supply wires or terminals while removing or replacing the core processor lid, or while using the RS-485 terminals.
CAUTION
Connecting a HART device to the transmitter’s primary mA output could cause transmitter output error.
If the primary mA output is being used for flow control, connecting the VIATOR HART Interface to the output loop, via either the mA terminals or the HART clips, could cause the transmitter’s 4–20 mA output to change, which would affect flow control devices.
Set control devices for manual operation before connecting the VIATOR HART Interface to the transmitter’s primary mA output loop.
12 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Method 1: HART/Bell 202 temporary or hard-wired connection to transmitter or multidrop network
Note: This method is supported by RFT9739, RFT9712, and IFT9701/9703 transmitters, by Model 1700/2700 transmitters with the analog outputs option board or configurable input/outputs options board, by Model 1500/2500 transmitters, by Model 2400S transmitters with the analog outputs option board, and by Series 3000 transmitters.
Using a VIATOR HART Interface, the PC can be connected directly to a transmitter’s primary mA output terminals, to the output wires from these terminals, or to any point in a multidrop network that is wired to these terminals. Figure 2-1 shows the wiring for this connection type.
Figure 2-1 HART/Bell 202 temporary or permanent connection to transmitter or multidrop network
USB plug
R1 See Step 3
DCS or
PLC
R2 See Step 3
or R3 See Step 3
Primary mA output terminals
VIATOR
VIATOR
Tr an s m it t er
1. At the PC, connect the VIATOR HART Interface to the PC’s serial or USB port.
2. Attach the VIATOR HART Interface leads:
To any point on the network (hard-wired connection)
Directly to the primary mA output terminals on your transmitter (temporary connection). See Table 2-6
To the output wires from the primary mA output terminals on your transmitter (hard-wired connection). See Table 2-6
The connection is polarity-insensitive; you can attach either lead to either terminal. For assistance in identifying the primary mA output terminals, see Appendix A.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Installation and Use Manual 13
Installation and Setup
Tabl e 2-6 Primary mA output terminals – Method 1
Termi na ls
Transmitter
RFT9712 17 16
RFT9739 rack-mount Z30 D30
RFT9739 field-mount 17 18
IFT9701/9703 4–20 mA 4–20 mA
Model 1500/2500 21 22
Model 1700/2700 AN Model 1700/2700 CIO Model 2400S AN
Series 3000 panel-mount with screw-type connectors c2 a2
Series 3000 panel-mount with I/O cables 14 15
Series 3000 rack-mount c2 a2
Series 3000 field-mount 2 1
PV + PV –
12
3. If necessary, add a resistor to the connection as required by your transmitter (see Table 2-7).
- If no other device is connected to the primary mA output, add the resistor in parallel with the primary mA output.
- If the primary mA output is connected to a remote device such as a DCS or a PLC with an internal resistor (R2), ensure its value is within the range described in Table 2-7. If it is lower than 250 Ω, add resistor R1 to the connection so that the overall resistance (R1 + R2) is within the range described in Table 2-7.
- If your DCS or PLC does not have an internal resistor, add resistor R3 and make sure its value is within the range described in Table 2-7
.
Tabl e 2-7 Resistance requirements for HART/Bell 202 connection
Transmitter Resistance
Model 1500/2500 250–600 Ω
Model 1700/2700 AN Model 2700 CIO Model 2400S AN
Series 3000 (all models) 250–600 Ω
IFT9701 IFT9703
RFT9712 RFT9739
250–600 Ω
250–600 Ω
250–1000 Ω
14 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Method 2: HART/Bell 202 temporary connection to RFT9739 field-mount and RFT9712 transmitters
1. At the PC, connect the VIATOR HART Interface to the PC’s serial or USB port.
2. Open the transmitter’s wiring compartment.
3. Locate the Bell 202 hookups inside the wiring compartment and attach the VIATOR HART Interface leads to the prongs (see Figure 2-2). The connection is polarity-insensitive; you can attach either lead to either prong. For assistance in locating the Bell 202 hookups, see Appendix A.
4. If necessary, add resistance in the loop by installing resistor R1 with a resistance of 250–1000 Ω
. Note that the hookups use the same circuit as the primary mA output, so the
required resistance may already be installed if the primary mA output loop is connected to a remote device.
Figure 2-2 Attaching the VIATOR HART Interface to the prongs
Prongs
Transmitter
R1
or
VIATOR
USB plug
VIATOR
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Installation and Use Manual 15
Installation and Setup
Method 3: HART/Bell 202 temporary connection to RFT9739 rack-mount transmitters
1. At the PC, connect the VIATOR HART Interface to the PC’s serial or USB port.
2. Attach the leads of a Bell 202 cable to the leads of the VIATOR HART Interface, and insert the cable prongs into the HART jack on the transmitter’s faceplate (see Figure 2-3). The connection is polarity-insensitive; you can insert the cable prongs in either direction.
3. If necessary, add resistance in the loop by installing resistor R1 with a resistance of 250–1000 Ω
. Note that the hookups use the same circuit as the primary mA output, so the
required resistance may already be installed if the primary mA output loop is connected to a remote device or a HART network.
Figure 2-3 Using the HART jack
USB plug
VIA TOR
HART jack
R1
Bell 202 cable (not included)
or
VIA TOR
16 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Method 4: HART/Bell 202 temporary or hard-wired connection to Model 1700/2700 IS transmitters
Using a VIATOR HART Interface, the PC can be connected directly to a transmitter’s primary mA output terminals, to the output wires from these terminals, or to any point in a multidrop network that is wired to these terminals. Figure 2-4 shows the wiring for this connection type.
1. At the PC, connect the VIATOR HART Interface to the PC’s serial or USB port.
2. Attach the VIATOR HART Interface leads:
To any point on the network (hard-wired connection)
Directly to the primary mA output terminals on your transmitter (temporary connection).
To the output wires from the primary mA output terminals on your transmitter (hard-wired
The connection is polarity-insensitive; you can attach either lead to either terminal. For assistance in identifying the primary mA output terminals, see Appendix A.
Tabl e 2-8 Primary mA output terminals – Method 4
See Table 2-8
connection). See Table 2-8
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Termi na ls
Transmitter
Model 1700/2700 IS 1 2
PV + PV –
3. Ensure that your wiring meets the following requirements:
For basic analog output operation, the primary mA output requires an external power supply with a minimum of 250 Ω and 17.5 volts. See Figure 2-5.
For communication, the VIATOR HART Interface must be connected across a resistance of 250–600 Ω. See Figure 2-4.
To meet the resistance requirements, you may use any combination of resistors R1, R2, and R3:
- If no other device is connected to the primary mA output, add resistor R1 in series with the primary mA output.
- If the primary mA output is connected to a remote device such as a DCS or a PLC with an internal resistor (R2), ensure its value is between 250 and 600 Ω. If it is lower than 250 Ω, add resistor R1 to the connection so that the overall resistance (R1 + R2) is between 250 and 600 Ω.
- If your DCS or PLC does not have an internal resistor, add resistor R3 and make sure its value is between 250 and 600 Ω
.
Installation and Use Manual 17
Installation and Setup
Figure 2-4 HART/Bell 202 connection to Model 1700/2700 IS transmitters
DCS or
PLC
R3 See Step 3
R2 See Step 3
External power supply
R1 See Step 3
See Step 3
+ –
Primary mA output terminals See Step 2
+
Transmitter
VIATOR
or
USB plug
VIATOR
Figure 2-5 Model 1700/2700 IS transmitters: Resistance and voltage requirements for HART/Bell 202
connections
R
1000
900
800
700
600
500
400
= (V
A minimum of 250 ohms and 17.5 volts is required
max
– 12)/0.023
supply
Operating range
300
External resistance (Ohms)
200
100
0
12 3014 16 18 20 22 24 26 28
Supply voltage VDC (Volts)
18 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Method 5: HART/RS-485 temporary or hard-wired connection to transmitter or multidrop network
Note: This method is supported by RFT9739 and RFT9712 transmitters, by Model 1700/2700 transmitters with the analog outputs option board, and Series 3000 transmitters.
Using a Black Box signal converter, the PC can be connected directly to a transmitter’s RS-485 terminals, to the output wires from these terminals, or to any point on a multidrop network. Figure 2-6 shows the wiring for this connection type.
1. Ensure that your transmitter’s RS-485 terminals are configured for HART protocol. See the transmitter manual for instructions.
2. If you are using an RFT9712 transmitter, you must set a jumper on the transmitter for RS-485 communications. See the transmitter manual for instructions.
3. At the PC, attach the Black Box signal converter to the PC’s serial or USB port, using a 25-pin to 9-pin adapter if necessary. Ensure that the positive and negative wires are connected as shown in Table 2-9 and Figure 2-6.
4. Attach the other end of the signal converter leads:
To any point on the network (hard-wired connection)
Directly to the RS-485 terminals on your transmitter (temporary connection). See
To the output wires from the RS-485 terminals on your transmitter (hard-wired
For assistance in identifying the RS-485 terminals, see Appendix A.
5. For long-distance communication, or if noise from an external source interferes with the signal, add two 120-Ω terminating resistors (R1) at each end of the RS-485 network.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Tabl e 2 -9
connection). See Table 2-9
Tabl e 2-9 Lead-to-terminal assignments – Method 5
Termi na ls
Transmitter
Model 1700/2700 AN 5 6
Series 3000 panel-mount with screw-type connectors a32 c32
Series 3000 panel-mount with I/O cables 25 24
Series 3000 rack-mount a32 c32
Series 3000 field-mount 12 11
RFT9712 21 22
RFT9739 field-mount 27 26
RFT9739 rack-mount Z22 D22
RS-485/A RS-485/B
Installation and Use Manual 19
Installation and Setup
Figure 2-6 HART/RS-485 connection to transmitter or multidrop network
R1 See Step 5
BLACK
BOX
RS-485 terminals See Step 4
Transmitter
DCS or
PLC
25-pin to 9-pin serial port adapter (if necessary) (not shown)
Method 6: Modbus/RS-485 temporary or hard-wired connection to RS-485 multidrop network
Note: This method is supported by RFT9739 transmitters, by Model 1500/2500 transmitters, by Model 1700/2700 transmitters with the analog outputs option board, and by Series 3000 transmitters.
Using a Black Box signal converter, the PC can be connected directly to a transmitter’s RS-485 terminals, to the output wires from these terminals, or to any point on an RS-485 network. Figure 2-7 shows the wiring for this connection type.
1. At the PC, attach the Black Box signal converter to the PC’s serial or USB port, using a 25-pin to 9-pin adapter if necessary.
2. Attach the other end of the signal converter leads:
To any point on the network (hard-wired connection). Ensure that the positive and negative
wires are connected as shown in Table 2-9.
Directly to the RS-485 terminals on your transmitter (temporary connection). See
Table 2-10.
To the output wires from the RS-485 terminals on your transmitter (hard-wired
connection). See Table 2-10.
For assistance in identifying the RS-485 terminals, see Appendix A.
20 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Tabl e 2-1 0 Lead-to-terminal assignments – Method 6
Termi na ls
Transmitter
Model 1500/2500 33 34
Model 1700/2700 AN 5 6
Series 3000 panel-mount with screw-type connectors a32 c32
Series 3000 panel-mount with I/O cables 25 24
Series 3000 rack-mount a32 c32
Series 3000 field-mount 12 11
RFT9712 21 22
RFT9739 field-mount 27 26
RFT9739 rack-mount Z22 D22
RS-485/A RS-485/B
3. For long-distance communication, or if noise from an external source interferes with the signal, install 120-Ω, 1/2-watt resistors (R1) across terminals of both end devices.
Note: The Modbus protocol allows only one Modbus master to be active on the network at any given time. If you are connecting through a network, ensure that no other Modbus master devices are currently active.
Figure 2-7 Modbus/RS-485 connection to RS-485 multidrop network
RS-485 terminals See Step 2
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
DCS or
PLC
R1 See Step 3
BLACK
BOX
25-pin to 9-pin serial port adapter (if necessary) (not shown)
Tr an s m it t er
Installation and Use Manual 21
Installation and Setup
Method 7: Modbus/RS-485 temporary connection to service port
Note: This method is supported by all Series 1000, Series 2000 and Series 3000 transmitters.
Using a Black Box signal converter, the PC can be connected directly to a transmitter’s service port. Figure 2-8 shows the wiring for this connection type.
1. At the PC, attach the Black Box signal converter to the PC’s serial or USB port, using a 25-pin to 9-pin adapter if necessary.
2. At the transmitter, connect the signal converter leads to the service port terminals. See Table 2-11. For assistance in identifying the terminals, see Appendix A.
If you are connecting to a Model 1700/2700 or to a Model 2400S transmitter, the service
If you are connecting to a Model 1500/2500 transmitter or a Series 3000 transmitter, the
port terminals are available at any time.
RS-485 terminals on these transmitters are accessible as a service port for a 10-second interval after power-up:
- If a service port connection is made during this interval, the port will remain in service port mode indefinitely until power is cycled.
- If no service port connection is made during this interval, the terminals switch to Modbus/RS-485 mode, and must be accessed using the RS-485 communication settings configured in the transmitter (see Method 6).
Service port connections to these transmitters are discussed in detail in Section 2.2.6.
Note: The Modbus protocol allows only one Modbus master to be active on the network at any given time. If you are connecting through a network, ensure that no other Modbus master devices are currently active.
Note: All service ports are accessed using the default address of 111. If you are connecting over a multidrop network with multiple service ports, it is not possible to specify which device to connect to.
Figure 2-8 Modbus/RS-485 connection to the service port
Service port terminals See Step 2
Transmitter
25-pin to 9-pin serial port adapter (if necessary) (not shown)
BLACK
BOX
22 ProLink® II Software for Micro Motion® Transmitters
Installation and Setup
Tabl e 2-1 1 Lead-to-terminal assignments – Method 7
Terminals
Transmitter
Model 1500/2500 transmitters 33 34
All Model 1700/2700 transmitters 8 7
All Model 2400S transmitters
Series 3000 panel-mount with screw-type connectors a32 c32
Series 3000 panel-mount with I/O cables 25 24
Series 3000 rack-mount a32 c32
Series 3000 field-mount 12 11
(1) On Model 2400S transmitters, service port connections are made via the service port clips which are located on the user interface.
Alternatively, service port connections are possible via the transmitter infrared port. For more information on using the infrared port, refer to the transmitter configuration and use manual.
(1)
RS-485/A RS-485/B
AB
Method 8: HART/Bell 202 temporary connection to HART clips
Note: This method is supported by Model 2400S transmitters that support HART communication.
Using a VIATOR HART Interface, the PC can be connected directly to the HART clips on the face of the transmitter. Figure 2-9 shows the wiring for connection to the HART clips.
1. At the PC, attach the VIATOR HART Interface to the PC’s serial or USB port, using a 25-pin to 9-pin adapter if necessary.
2. At the transmitter, remove the housing cover.
3. Connect the HART interface leads to the HART clips.
ProLink II Setup Transmitter StartupUsing ProLink IIBefore You Begin
Figure 2-9 HART/Bell 202 connection to HART clips
HART clips
4. If necessary, add a resistance across the HART clips. The VIATOR HART interface must be connected across a resistance of 250–600 Ω. Note that the HART clips use the same circuit as the mA output, so the required resistance may already be installed if the mA output loop is connected to a remote device or a HART network (see Figure 2-1).
VIATOR
Installation and Use Manual 23
Installation and Setup
Method 9: Modbus/RS-485 temporary connection to MVD Direct Connect
Using a Black Box signal converter, the PC can be connected directly to the RS-485 terminals on the core processor or the MVD Direct Connect I.S. barrier.
1. At the PC, attach the Black Box signal converter to the PC’s serial or USB port, using a 25-pin to 9-pin adapter if necessary.
2. If connecting to the core processor, remove the lid.
3. Connect the signal converter leads to the RS-485 terminals. See Table 2-12, and:
For connecting to the standard core processor, see Figure 2-10.
For connecting to the enhanced core processor, see Figure 2-11.
For connecting to the I.S. barrier, see Figure 2-12.
Note: The Modbus protocol allows only one Modbus master to be active on the network at any given time. If you are connecting through a network, ensure that no other Modbus master devices are currently active.
Note: Before using ProLink II to communicate with the core processor, disconnect any wiring to a remote PLC. Be careful not to disconnect the power supply wiring. After using ProLink II to communicate with the core processor, reconnect the wiring to the remote PLC.
Tabl e 2-1 2 Lead-to-terminal assignments – Method 9
Terminals
Device
I.S. barrier
Core processor
(1) Connection is intrinsically safe. (2) Connection is not intrinsically safe.
(1)
(2)
RS-485/A RS-485/B
13 14
34
Figure 2-10 Modbus/RS-485 connection to RS-485 terminals on standard core processor
RS-485/B
Core processor
25 to 9 pin serial port adapter (if necessary)
RS-485/A
24 ProLink® II Software for Micro Motion® Transmitters
RS-485 to RS-232 signal converter
Loading...
+ 80 hidden pages