Emerson NetSure ITM 48 VDC UPS 70 kW to 280 kW Brochure

NetSure™ ITM with eSure™ Technology
Row-based, Scalable 48V DC UPS
DC Power For Business-Critical Continuity
Efficiency Without Compromise™
provides a path to optimize data center infrastructure
around design, operating and management efficiencies –
while maintaining or improving availability. This is
achieved through the proper selection and utilization of
cooling, power and monitoring technologies, supported
by key services and local expertise.
Features & Benefits
High system efficiency: Reduced power
conversion stages combined with 96% efficient eSure (PCUs) and an advanced energy optimization mode enable significant energy savings even at low loads.
Scalability and ease of deployment:
Minimize your initial investment and avoid stranded power by adding expansion DC UPS modules without interruption in the field as power needs increase.
DC architecture simplicity: Fewer
components, conversion stages and distribution breakers throughout the power chain ensure high availability; elimination of complex synchronization circuits and the need to de-rate capacity for phase balancing or harmonics makes it easy to engineer.
High reliability and exceptional resiliency:
Uninterrupted operation in the unlikely event of multiple component failures.
Ease of maintenance: Field replaceable,
hot swappable PCUs allow rapid replace­ment without critical bus disruption; low voltage allows maintenance without bypass or shutdown.
Compact footprint: Row-based, integrated
design saves considerable facility space by eliminating the need for a dedicated power room and separate PDU distribution.
power conversion units
A Complete Power Protection Solution
The NetSure™ ITM lowers the cost of data center design, operation and management. This 48V direct current solution is a row-based DC UPS that delivers simple, scalable and highly efficient power protection.
Rising power density, rapid and unpredictable growth, escalating energy consumption and cost, plus a myriad of other power-related challenges are making it increasingly complicated and expensive to protect critical network and computing equipment. The NetSure DC UPS components into a compact, highly reliable power protection system, offering the answer to your current and future 48V power needs. This three-phase 480V AC input, 48V DC output UPS provides highly available power to a wide variety of IT applications and delivers advanced operating features combined with reduced total cost of ownership.
The NetSure
ITM is designed for deployment directly on the server room floor, and provides protected 48V power to nearby equipment racks. This preserves the efficiency and reliability benefits of DC power, while minimizing the amount of copper required and enabling modular growth.
ITM integrates
NetSure™ ITM DC UPS Module Top-Cabled Configuration
Flexible deployment options: Top or
bottom cable entry allows for raised or non-raised floor installations.
Advanced control and monitoring: Real
time input and output monitoring, including power quality and consumption data, enables facility planning for the system and each branch circuit; state-of­the-art battery monitoring with Albér technology to assure optimal backup performance.
One-year warranty: Provides full system
coverage for one year.
2
Figure 1: NetSure™ ITM System Efficiency
98%
96%
System Efficiency
94%
Improvement
92%
90%
88%
System Efficiency*
86%
84%
10%
*System efficiency includes AC to DC power conversion and internal distribution losses.
Without
Energy Optimization
20% 30% 40% 50% 60% 70% 80% 90% 100%
With
Energy Optimization
Load
NetSure™ ITM delivers Efficiency Without Compromise
INFRASTRUCTURE MANAGEMENT
Improving performance of the IT infrastructure and environment
ECO AVAILABILITY
Balancing high levels of availability and efficiency
FLEX CAPACITY
Adapting to IT changes for continuous optimization and design flexibility
Unmatched Availability
Central to a data center’s strength is its overall uptime. To maintain business continuity, power systems must exhibit high availability and easily scale for increasing capacity.
NetSure UPS. Each DC UPS module includes twelve independent 5.8kW PCUs. These PCUs are globally renowned with over 2 million units deployed, offering unmatched reliability with less than
0.5% return rate (200 years MTBF). The NetSure a highly redundant package that minimizes single points of failure.
Proven power conversion topology
Redundant configuration
rectifiers or power conversion units (PCUs) are the heart of the NetSure™ ITM DC
Each PCU delivers conditioned,
isolated power to a common distribution bus
PCUs function in parallel for seamless
redundancy without switching
Units are hot swappable in the field
without system adjustment; minimum field repair time (MTTR) increases overall uptime
Redundancy can be achieved both
within a DC UPS module by PCU (N+x), and by complete system (2N)
Internal power distribution through
(22) branch circuit breakers allows redundant A+B power paths to each rack
Battery backup via three parallel
battery strings
Optional dual AC inputs allow
upstream switchgear maintenance without system outage
ITM provides many robust features to create
Resilient design
System bus charges batteries and
distributes power
without additional
rack conversions
directly to the server
switching or
65k AIC withstand rating on AC
input breaker(s)
Controller outage does not interrupt
power delivery to the critical load and is field replaceable without system outage
Battery monitoring technology from Albér
Detects failing battery cells before
they affect the critical load
Checks each cell and associated
connections via a proactive, patented resistance test to reliably predict battery performance
Provides early warning of cell
problems without frequent discharge tests or battery degradation; mini­mum technician visits with maximum run time protection
System controller stores raw data
accessible via webpage or external monitoring system
HIGH DENSITY
Delivering architectures from 10–60 kW/Rack to minimize space and cost
Lower Total Cost of Ownership
DC power is often associated with telecommunications where it has delivered extremely high reliability for decades. Since DC power is both provided by backup power sources and consumed by electronic equipment, a DC power architecture minimizes conversion stages from grid to chip, thus enabling higher overall efficiency with increased availability.
Factory integrated system for fast and
easy site installation
Service or expansion can be performed
while the DC UPS is in operation, reducing maintenance costs
Compact footprint with built-in
batteries and distribution, minimizes required floor space
Designed for scalable growth to
postpone additional capex until capacity is needed
Energy Optimization Mode Intelligent Power Matching [Figure 1]
• Achieves near-peak UPS efficiency down to 5% system load by optimizing individual PCU performance, greatly reducing energy costs over time in real world conditions
• Matches delivered power from the UPS to real-time demand, keeping a minimum of PCUs active and putting the rest on standby
• Balances the run time of each PCU by rotating the active and standby units
• Maintains the ability to respond quickly to changing load conditions
3
Whatever the physical layout of your data center,
the NetSure
ITM minimizes required floor space. With DC UPS
building block modules, you can mix and match configurations
and standard layouts to fit your available space.
Flexibility to Meet the Needs of Any Data Center
The NetSure™ ITM solution is a modular system in 70 kW increments, expandable up to 280 kW (4 DC UPS modules) with one controller.
Flexible Capacity
Each integrated DC UPS module occupies
only 24" (W) x 41" (D) of floor space, including batteries and primary distribution
Delivered fully configured for quick and
easy field installation
Typically installed in either the middle or at
the end of a row of server racks
Deploy only the capacity that is initially
needed; DC UPS modules can be added at any time to row configurations on the data center floor
Choose from top and bottom cabled
variants for installation in either concrete or raised floor environments
As Figure 2 illustrates, the NetSure solution starts with a primary DC UPS module rated for 70kW. As your power needs increase, you can add up to three expansion DC UPS modules, for a maximum capacity of 280kW that may be configured for N+1 redundancy by subtracting one 6kW PCU from the rating. Each DC UPS module also includes 48V primary power distribution with 22 circuit breakers (6 fuses optional). Various server rack densities are supported with 5-10 minutes of battery backup time across three parallel 48V battery strings.
ITM
Figure 3 depicts two top-cable installation
scenarios. Depending on your site and budget requirements, the NetSure solution can either be installed as a single deployment [Figure 3a], or incrementally by row [Figure 3b] as power requirements grow. In either scenario, DC distribution cabling to each rack is reduced by placing the NetSure ITM in-the-row.
ITM
Figure 2: System Scalability
70kW (64kW N+1)
140kW (134kW N+1)
210kW (204kW N+1)
280kW (274kW N+1)
Both AC and DC loads can be accommodated at the same site. AC loads can either be protected by an AC UPS or via a rack-mount DC to AC inverter fed from the DC UPS, both available from your local Emerson Network Power representative.
Figure 2: Primary DC UPS module with 3 expansion modules (top-cabled configuration shown) Install only the capacity required; link up to four DC UPS modules to one controller
4