584622100 (19” MAIN SHELF), 584622200 (19” EXPANSION SHELF) 584622300 (23” MAIN SHELF), 584622400 (23” EXPANSION SHELF)
DCS48375
NetSure™ +24VDC to -48VDC Converter System
Installation and User Instructions
UM584622100 (Issue AC, July 3, 2012)
Business-Critical Continuity™, Emerson Network Power, and the Emerson Network
Power logo are trademarks and service marks of Emerson Electric Co.
NetSure™, NetSpan™, NetReach™, NetXtend™, and NetPerform™
are trademarks of Emerson Network Power, Energy Systems, North America, Inc.
All other trademarks are the property of their respective owners.
The products covered by this instruction manual are manufactured and/or
sold by Emerson Network Power, Energy Systems, North America, Inc.
The information contained in this document is subject to change without notice and may not be
suitable for all applications. While every precaution has been taken to ensure the accuracy and
completeness of this document, Emerson Network Power, Energy Systems, North America, Inc.
assumes no responsibility and disclaims all liability for damages resulting from use of this information
or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct
methods, tools, and materials to be used in performing procedures not specifically described in this document.
This document is the property of Emerson Network Power, Energy Systems, North America, Inc.
and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use or disclosure of it without the written permission
of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
TABLE OF CONTENTS
CONTENTS PAGE
STATIC WARNING ................................................................................................................... iii
ADMONISHMENTS .................................................................................................................. iv
General Safety .................................................................................................................................................... iv
Voltages .............................................................................................................................................................. iv
Circuit Card Handling .......................................................................................................................................... iv
CHAPTER 1. DESCRIPTION AND INSTALLATION ACCEPTANCE CHECKLIST .................. 1
System Description .............................................................................................................................................. 1
CHAPTER 2. INSTALLING THE SYSTEM ................................................................................ 3
General Requirements ......................................................................................................................................... 3
Mounting the Shelf(s) ........................................................................................................................................... 5
Securing the Main Shelf to a Relay Rack ...................................................................................................... 5
Securing the Expansion Shelf(s) to a Relay Rack and Installing the Expansion Wiring Cover on
the Main Shelf ................................................................................................................................................ 6
To Distribution Bus Row .............................................................................................................................. 18
To Optional Bullet Nose 6-Position GMT Fuse Block .................................................................................. 20
FA/CBA and CAN Bus Interconnections ..................................................................................................... 22
DC Input Connections ........................................................................................................................................ 23
CHAPTER 5. INSTALLING THE CONVERTER MODULES AND INITIALLY STARTING THE
SYSTEM ................................................................................................................................... 25
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Initially Starting and Checking System Operation .............................................................................................. 26
Initially Starting the System ......................................................................................................................... 26
Checking System Status ............................................................................................................................. 26
Using the Converter System with an ACU+ Controller ...................................................................................... 27
Local Indicators and Test Points ........................................................................................................................ 27
Local Indicators............................................................................................................................................ 27
Test Points ................................................................................................................................................... 28
System Maintenance Procedures ...................................................................................................................... 29
CHAPTER 8. TROUBLESHOOTING AND REPAIR ................................................................ 30
Contact Information ............................................................................................................................................ 30
System Troubleshooting Information ................................................................................................................. 30
Replacement Information ................................................................................................................................... 30
Replacing a Converter Module .................................................................................................................... 31
Replacing a Distribution Device ................................................................................................................... 31
Replacing the System Interface Circuit Card .............................................................................................. 34
REVISION RECORD ................................................................................................................ 36
Page ii Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
STATIC WARNING
The printed circuit cards used in this equipment contain static sensitive components. The warnings listed below
must be observed to prevent damage to these components. Disregarding any of these warnings may result in
personal injury or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any static sensitive component or printed circuit card containing such a component,
discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm
resistor. Some wrist straps, such as Emerson Network Power Part Number 631810600, have a built-in
one megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s
instructions outlining use of a specific wrist strap.
3. Do not touch the traces or components on a printed circuit card containing static sensitive components.
Handle the printed circuit card only by the edges that do not have connector pads.
4. After removing a printed circuit card containing a static sensitive component, place the printed circuit card
only on conductive or anti-static material such as conductive foam, conductive plastic, or aluminum foil.
Do not use ordinary Styrofoam or ordinary plastic.
5. Store and ship static sensitive devices or printed circuit cards containing such components only in static
shielding containers.
6. If necessary to repair a printed circuit card containing a static sensitive component, wear an appropriately
grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded
test equipment.
Static Warning Page iii
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
ADMONISHMENTS
GENERAL SAFETY
Danger: YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These
procedures should be performed by qualified technicians familiar with the
hazards associated with this type of equipment. These hazards may
include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other jewelry.
c) Prior to contacting any uninsulated surface or termination, use a
voltmeter to verify that no voltage or the expected voltage is present.
d) Wear eye protection and use recommended tools.
e) Use double insulated tools appropriately rated for the work to be
performed.
VOLTAGES
Danger: This system operates from DC input power. All DC power sources must
be completely disconnected from the branch circuit wiring used to
provide power to this system before DC input connections are made.
Danger: This system produces DC power.
CIRCUIT CARD HANDLING
Warning: Installation or removal of the circuit cards requires careful handling.
Before handling any circuit card, read and follow the instructions
contained on the Static Warning Page.
Page iv Admonishments
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
CHAPTER 1.
DESCRIPTION AND INSTALLATION
ACCEPTANCE CHECKLIST
SYSTEM DESCRIPTION
+24VDC to -48VDC @ up to 375A Converter System.
The NetSure™ DCS48375 Converter System is comprised of a main shelf and up to two
(2) expansion shelves. Each shelf provides mounting positions for up to four (4)
converter modules. Each shelf also provides a 15-position distribution row (19” version)
or 20-position distribution row (23” version) which accepts bullet nose circuit breakers
and TPS/TLS fuseholders. A GMT fuse block option is also available.
Note: Refer to SAG584622100 (System Application Guide) for additional system
information.
Note: Refer to UM1C24481500 (Converter Module User Instructions) for converter
module information.
INSTALLATION ACCEPTANCE CHECKLIST
Provided below is an Installation Acceptance Checklist. This checklist helps ensure
proper installation and initial operation of the system. As the procedures presented in
Chapters 2 through 5 of this document are completed, check the appropriate box on this
list. If the procedure is not required to be performed for your installation site, also check
the box in this list to indicate that the procedure was read. When installation is done,
ensure that each block in this list has been checked. Some of these procedures may
have been factory performed for you.
Chapter 1. Description and Installation Checklist Page 1
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Note: The system is not powered up until the end of this checklist.
Note: Some of these procedures may have been factory performed.
Chapter 2. Installing the System
Optional Wiring Access Panel Installed on Top of Shelf(s), if desired
Main Shelf Secured to Relay Rack
Expansion Shelf(s) Secured to Relay Rack (if furnished)
and Expansion Wiring Cover installed on Main Shelf
Optional Lug Adapter Busbar Kits Installed
Bullet Nose Circuit Breakers Installed
Bullet Nose Fuseholders and TPS/TLS Fuses Installed
Optional Bullet Nose GMT Fuse Block Installed (if furnished)
Chapter 3. Setting Jumper and Switch Options
Jumper on System Interface Circuit Card Set
Switches on System Interface Circuit Card Set
Chapter 4. Making Electrical Connections
Shelf(s) Grounding (Frame Ground) Connection Made
External Alarm, Reference, Monitoring, and Control Connections Made
Load Connections Made
Expansion Shelf(s) Interconnections Made (if furnished)
DC Input Connections Made
Chapter 5. Installing the Converter Modules and Initially Starting the System
Converter Modules Installed
System Started and Checked
Page 2 Chapter 1. Description and Installation Checklist
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
CHAPTER 2.
INSTALLING THE SYSTEM
GENERAL REQUIREMENTS
The shelf is designed for mounting in a 19-inch or 23-inch wide relay rack with 1-3/4
inch multiple drilling.
The installer should be familiar with the installation requirements and techniques to
be used in securing the shelf(s) to a relay rack.
This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product must be located in a Controlled Environment with access to
Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO,
vault, hut, or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a
Network Telecommunication Facility (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the
front of the relay rack and 2' for the rear of the relay rack.
Converter module and mounting shelf ventilating openings must not be blocked and
temperature of air entering system must not exceed rated Operating Ambient
Temperature Range found in SAG584622100.
Chapter 2. Installing the System Page 3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
1. Open front door.
2. Remove top panel.
3. Install Wiring Access Cover
(use same hardware removed from top panel).
INSTALLING OPTIONAL WIRING ACCESS COVER
ON TOP OF SHELF(S), IF DESIRED
The optional wiring access cover is a 1U high panel that is installed on top of the shelf(s)
to allow greater access to load distribution return connection points.
Procedure
1) To install the optional wiring access cover, perform the procedure in Figure 2-1.
Figure 2-1
Installing Optional Wiring Access Cover
Page 4 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
584622100 and 584622200
Reversible MountingAngle
Torque mounting angle to
shelf connections to 20 in-lbs.
Torque mounting angle to
relay rack connections to 70 in-lbs.
The 584622100 and 584622200 shelves are equipped with reversible mounting angles
for mounting in a standard 19-inch or 23-inch wide relay rack having 1-3/4 inch multiple
drillings.
The 584622300 and 584622400 shelves mount in a standard 23-inch wide relay rack
having 1-3/4 inch multiple drillings.
Note: Refer to the “General Requirements” section at the beginning of this chapter.
Securing the Main Shelf to a Relay Rack
Procedure
1) 584622100 and 584622200: Reverse the mounting angles if required to fit your
relay rack. Refer to Figure 2-2.
2) Secure the shelf mounting angles to the relay rack at four (4) locations per side.
Use grounding washers at one (1) location per side. Refer to Figure 2-2. Ensure
the grounding washers are oriented properly to enable the teeth to dig into the
mounting angle surface for a secure ground connection.
Figure 2-2
Reversing the Mounting Angles (if required) and Securing the Shelf to a Relay Rack
Chapter 2. Installing the System Page 5
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Expansion Wiring Cover
(supplied loose with Expansion
Shelf, attach to Main Shelf)
Replace this cover with the
Expansion Wiring Cover
Remove these tabs at the bottom of the top shelf and
at the top of the bottom shelf to allow wiring between
shelves.
Apply the provided material along the exposed edges
of the cutouts to provide protection to the wires as they
are passed between shelves.
Securing the Expansion Shelf(s) to a Relay Rack and
Installing the Expansion Wiring Cover on the Main Shelf
SECURING AN EXPANSION SHELF TO A RELAY RACK
Secure an expansion shelf to a relay rack, directly below the shelf above it, per the
previous procedure. The optional 1U wiring access panel is recommended for expansion
shelves to facilitate load cable connections.
INSTALLING THE EXPANSION WIRING COVER ON THE MAIN SHELF
PERFORM THIS PROCEDURE AFTER PARALLELING THE OUTPUTS OF BOTH
SHELVES AS DESCRIBED IN THE “MAKING ELECTRICAL CONNECTIONS”
CHAPTER.
Procedure
1) Remove the cover shown in Figure 2-3 from the main shelf.
2) Remove the expansion wiring cover from the expansion shelf as shown in Figure
2-3.
3) On the expansion wiring cover for both the expansion shelf and the main shelf
(provided loose with the expansion shelf), remove the tabs shown in Figure 2-3
so wiring can pass between the shelves. Apply the provided material along the
exposed edges of the cutouts to provide protection to the wires as they are
passed between shelves.
4) Make the paralleling connections as described in the “Making Electrical Connections” chapter.
5) Refer to Figure 2-3, and install the expansion wiring covers to both the main shelf
and the expansion shelf.
Installing the Expansion Wiring Cover on the Main Shelf
Page 6 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-3
Installation and User Instructions UM584622100
P/N 545405
P/N 545404
P/N 545571
1. Open the shelf’s front door.
2. Install the lug adapter busbar kits as shown.
Apply anti-oxidizing compound to busbar
mating surfaces before installing.
3. Torque connections to 58 in-lbs using the
supplied 1/4” hardware.
4. Close the front door after wiring is complete.
Top Cover Removed in
Illustration for Clarity Only
1) Refer to Figure 2-4 to install the optional lug adapter busbar kits.
Figure 2-4
Installing Optional Lug Adapter Busbar Kits
Chapter 2. Installing the System Page 7
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
INSTALLING BULLET NOSE CIRCUIT BREAKERS
AND/OR FUSEHOLDERS (WITH TPS/TPL FUSES)
Caution: For ambient temperatures at or below +40°C (+104°F), overcurrent
devices rated 100A or greater MUST HAVE an empty mounting position
between it and any other overcurrent protective device. Maximum size
circuit breakers that can be used are 100A single pole, 200A double pole,
and 250A triple pole. Maximum size fuse is 100A. The distribution row is
rated for a maximum of 250A.
For ambient temperatures between +40°C (+104°F) and +65°C (+149°F),
overcurrent devices rated 60A or greater MUST HAVE an empty
mounting position between it and any other overcurrent protective
device. Maximum size circuit breakers that can be used are 70A single
pole. No double pole or triple pole circuit breakers can be used.
Maximum size fuse 70A. The distribution row is rated for a maximum of
250A.
Note: Circuit breakers and/or fuses may have been factory installed for you. If so, verify
their positions and sizes.
Procedure
1) Open the shelf’s front door.
2) Circuit Breakers and Fuses: Ensure that a circuit breaker is in the OFF
position. Orient the distribution device as shown in Figure 2-5. Insert the
terminals on the rear of the distribution device into their corresponding sockets
on the distribution row. Ensure the alarm contact on the back of the distribution
device makes contact with the alarm terminal on the mounting circuit card. Push
distribution device in firmly until fully seated in the distribution row.
3) Fuses: When all fuseholders are installed, install an appropriately sized
TPS/TLS fuse in each. To do this, remove the fuse carrier from the mounted
fuseholder body by pulling it straight out. Slide the fuse in place between the
contacts of the fuse carrier. When done, push the fuse carrier back into the
fuseholder body. Note that a polarizing key on the bottom of the carrier prevents
the carrier from being inserted upside down. Verify that an 18/100 ampere alarm
fuse is present in each fuseholder and that a plastic safety cover is installed on
this fuse.
4) Record all circuit breaker and/or fuse sizes on the label provided.
5) Close the shelf's front door.
Page 8 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Fuseholder AssemblyCircuit Breaker
Insert these terminals
into corresponding sockets
on distribution row.
Insert these terminals
into corresponding sockets
on distribution row.
Longer Side
to the Bottom
Shorter Side
to the Top
Longer Side
to the Bottom
Shorter Side
to the Top
Fuse Carrier
Fuseholder Body
TPS/TLS Fuse
Alarm Fuse
(Replacement
P/N 248610301)
Safety Cover
(Replacement
P/N 248898700)
Polarizing Keyway
Matches Key on
Bottom of Fuse Carrier
Fuseholder Assembly
Exploded View
FuseholderAssembly (P/N 117201) includes
body & carrier,alarm fuse, and alarm fuse safety cover.
Installing Bullet Nose Circuit Breakers and/or Fuseholders (with TPS/TLS Fuse)
Chapter 2. Installing the System Page 9
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
INSTALLING AN OPTIONAL BULLET NOSE GMT FUSE BLOCK
Caution: At 40°C ambient, GMT fuses greater than 10A MUST HAVE an empty
mounting position between it and any other fuse. Maximum total current
is 35A. Maximum GMT fuse size is 15A.
At 65°C ambient, GMT fuses greater than 5A MUST HAVE an empty
mounting position between it and any other fuse. Maximum total current
is 21A. Maximum GMT fuse size is 10A.
Refer to Figure 2-6 while performing this procedure.
Procedure
1) Open the shelf’s front door.
2) Follow the steps in Figure 2-6.
3) Install an appropriately sized GMT fuse in each fuse mounting position on the
GMT distribution fuse block as required. If dummy fuses are installed, first
remove the dummy fuse.
a) Verify that dummy fuses are installed in all unused fuse positions on the
GMT distribution fuse block.
b) Verify that a plastic safety cover is installed on all GMT fuses on the GMT
distribution fuse block.
4) Record all fuse sizes (installed on the GMT distribution fuse block) on the label
provided.
5) Close the shelf's front door.
Page 10 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Remove two lug terminal busbars
for positions to be occupied
by GMT Fuse Block.
2.
Press in tabs to release
lug terminal busbars for
positions to be occupied
by GMT Fuse Block.
1.
Plug in GMT Fuse Block and secure
at one location on the RTN bar with
hardware provided. Torque to 58 in-lbs.
RTN Bar
3.
Top Cover Removed in
Illustration for Clarity Only
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
JUMPER AND SWITCH SETTINGS ON THE
SYSTEM INTERFACE CIRCUIT CARD
Perform the following procedures to verify the factory settings and/or make the required
settings per your site requirements. These procedures can also be used to make
adjustments on a replacement circuit card.
Refer to Figure 3-1 for switch and jumper locations.
Switch S1
Switch Positions 1 and 2 of S1
Selects the converter system’s output voltage as shown in Table 3-1.
Table 3-1
Converter System Output Voltage Selection
Switch Position 3 of S1
Selects the current scale for the output current test points as shown in Table 3-2.
Table 3-2
Output Current Test Points “Current Scale” Selection
Switch Position 4 of S1
Selects whether converter system output voltage is controlled by the system interface
circuit card (stand alone mode) or by an ACU+ as shown in Table 3-3.
Table 3-3
Output Voltage Control Selection
Page 12 Chapter 3. Setting Jumper and Switch Options
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
a) When in stand alone mode, the jumper P2 must be in place to ensure reliable
communications.
b) When an ACU+ is on the CAN bus, jumper P2 should be removed.
Figure 3-1
System Interface Circuit Card Jumper and Switch Locations
Chapter 3. Setting Jumper and Switch Options Page 13
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100 Installation and User Instructions
Crimp Lug Part No.
Crimp Tool Required1, T&B Model
TBM12 or TBM15 Hydraulic Heads
Observe the admonishments located at the beginning of this document.
WIRING CONSIDERATIONS
All wiring should follow the current edition of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC), and applicable local codes. For operation in countries where the NEC is not
recognized, follow applicable codes.
For recommended wire sizes, crimp lugs, alarm relay contact ratings, and general wiring
information and restrictions; refer to System Application Guide SAG584622100.
Refer to drawing 031110100 for lug crimping information. Refer to drawings 031110200
and 031110300 for additional lug information.
Refer to Table 4-1 for supplemental lug crimping information when using the special
application crimp lug / strap combination.
1
The lugs should be crimped to the specifications given in the
manufacturer’s instructions furnished with the crimp tool or lug.
Table 4-1
Supplemental Lug Crimping Information when using the
Special Application Crimp Lug / Strap Combination
Page 14 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
For shelf grounding requirements, refer to the current edition of the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA)
National Electrical Code (NEC), applicable local codes, and your specific site
requirements.
Note: The DC return connection to this system can remain isolated from system frame
and chassis (DC-I).
Note: This system is suitable for installation as part of the Common Bonding Network
(CBN).
1/4-20 x 0.5” studs on 5/8” center are provided for installation of a customer provided
frame ground lead terminated in a 2-hole lug.
Procedure
1) For shelf(s) grounding (frame ground) connection, refer to Figure 4-1.
Chapter 4. Making Electrical Connections Page 15
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-1
Shelf(s) Grounding (Frame Ground) Connection
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
EXTERNAL ALARM, REFERENCE, MONITORING,
AND CONTROL CONNECTIONS
External alarm, reference, monitoring, and control connections are made to terminals of
TB1 and TB2 located on the system interface circuit card mounted on the inside of the
main shelf’s front door. Refer to Figure 4-2 for location.
External FA/CBA Alarm Input: An external FA/CBA alarm signal can be connected to the
system as described in the Expansion Shelf(s) Interconnections section.
External Alarm Relays
External alarm relays are extended to terminal block TB1 located on the system interface
circuit card. Relays are energized for normal operating conditions and de-energized for
an alarm condition.
Low Input Voltage Alarm: Alarms if a converter module reports a low input voltage
condition. A close loop circuit is provided between terminals 1 and 2 of TB1 and an
open loop circuit is provided between terminals 2 and 3 of TB1 during an alarm
condition.
Fuse / Circuit Breaker Alarm: Alarms if any distribution fuse or circuit breaker
opens. A close loop circuit is provided between terminals 4 and 5 of TB1 and an
open loop circuit is provided between terminals 5 and 6 of TB1 during an alarm
condition.
Converter Fail Major Alarm: Alarms if more than one converter module fails (or if
only one converter module is installed in the system and it fails). A close loop circuit
is provided between terminals 7 and 8 of TB1 and an open loop circuit is provided
between terminals 8 and 9 of TB1 during an alarm condition. Refer to the Operating
Procedures chapter for alarm conditions.
Converter Fail Minor Alarm: Alarms if one converter module fails. A close loop
circuit is provided between terminals 10 and 11 of TB1 and an open loop circuit is
provided between terminals 11 and 12 of TB1 during an alarm condition. Refer to the
Operating Procedures chapter for alarm conditions.
CAN Bus
An ACU+ can be connected to terminals 1 (CANL) and 2 (CANH) of TB2.
Output Current Signal Reference
The output current signal (also provided at the output current test points on the front door
of the main shelf) can be selected to be referenced to plus battery (input), referenced to
minus battery (input), or not referenced as detailed below. The output current signal can
be set at 1A/mV or 400A/50mV per CHAPTER 3. SETTING JUMPER AND SWITCH
OPTIONS.
Referenced to Plus Battery (input): Provide a jumper between terminals 4 (+BT)
and 5 (-IO) of TB2.
Page 16 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Inside View of Main Shelf’s Front Door
TB1
19112
TB2P2
TB1
19
112
TB2
Conv
Minor
Conv
MajorFuse / CB
Low Input
Voltage
NC C NONC C NONC C NONC C NO
E
S
T
O
P+VO-VO+IO-IO+BT-BT
CANH
CANL
CAN
TERM
P2
Recommended Torqueis 5.0 in-lbs.Recommended Torque is 5.0 in-lbs.
Relays are energized for normal operating conditions
and de-energized for an alarm condition.
Referenced to Minus Battery (input): Provide a jumper between terminals 3 (-BT)
and 6 (+IO) of TB2.
Not Referenced: Do not provide a jumper.
Output Voltage Monitoring
An output voltage monitoring device can be connected to terminals 7 (-VO) and 8
(+VO) of TB2. These terminals are internally paralleled with the test points provided
on the front door of the main shelf.
Emergency Shutdown (Estop)
The converter modules can be inhibited by applying an external ground signal (24V
Return) to terminal 9 of TB2. Converter modules automatically restart upon removal
of the ground signal.
Chapter 4. Making Electrical Connections Page 17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-2
External Alarm, Reference, Monitoring, and Control Connections
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
LOAD CONNECTIONS
To Distribution Bus Row
1/4-20 x 0.625” studs on 5/8” centers are provided for installation of customer provided
load distribution leads terminated in 2-hole lugs. Refer to Figure 4-3.
Warning: Observe correct polarity when making connections. Otherwise
equipment damage may occur.
Procedure
1) For load connections to the distribution bus row, refer to Figure 4-3.
Page 18 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Load Distribution Connections
* 1/4-20 x 0.625” studs on 5/8” centers
for installation of leads with 2-hole lugs.
* Maximum lug width 0.625”.
* Torque to 58 in-lbs.
-48VDC
Return
Front
Front
Components removed in
illustration for clarity only.
Load
Distribution
Leads Enter
Here (break
tabs off shield
as required)
P/N 545405
P/N 545404
P/N 545571
Top Cover Removed in
Illustration for Clarity Only
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Warning: Observe correct polarity when making connections. Otherwise
equipment damage may occur.
Procedure
1) For load connections to an optional GMT fuse block, refer to Figure 4-4.
Figure 4-4
Load Connections to GMT Fuse Block
Page 20 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Cable, lugs (P/N 144511), and labels are
provided loose with the Expansion Shelf
to assemble a Return and a -48V
paralleling cable.
1. Cut the cables to the proper length.
2. Lug the cables
(use standard brown die for 2 ga. cable).
3. Connect cables between terminals
as indicated below. Torque to 58 in-lbs.
4. Re-Install Expansion Wiring Covers.
(refer to procedure in the
“Installing the System” chapter.)
1) Perform the procedure in Figure 4-5 for each expansion shelf.
Figure 4-5
DC Output Paralleling Interconnections
Chapter 4. Making Electrical Connections Page 21
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Connect these connectors
to mating connectors in
shelf above.
Connect these connectors
to mating connectors in
shelf above.
If there are expansion shelves,
move the termination plug
from connector in main shelf
to same connector in bottom
most expansion shelf.
If there are expansion shelves,
unplug the external FA/CBA
lead from this connector.
Move the termination plug
from connector in main shelf
to same connector in bottom
most expansion shelf.
Plug the external FA/CBA
lead from main shelf into
same connector in bottom
most expansion shelf.
Connect an external FA/CBA lead to
the butt splice located at the end of the
external FA/CBAplug assembly.
Supply a voltage signal within 1V of the
converter system output voltage to this
lead to activate the system’s fuse alarm
circuit.
1) Perform the procedure in Figure 4-6 for each expansion shelf and to connect an
external FA/CBA alarm lead to this system.
Figure 4-6
FA/CBA and CAN Bus Interconnections
Page 22 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
DC INPUT CONNECTIONS
3/8-16 x 0.875” studs on 1” centers are provided for installation of customer provided DC
input leads terminated in 2-hole lugs. Terminations are provided for each converter
module (individual feed). Adapter busbars are provided loose with each shelf which
allows two (2) converter modules to be fed by a single input. Refer to Figure 4-7.
Warning: Observe correct polarity when making connections. Otherwise
equipment damage will occur.
Note: The DC return connection to this system can remain isolated from system frame
and chassis (DC-I).
Note: This system is suitable for installation as part of the Common Bonding Network
(CBN).
Note: Recommended DC input protective device rating is 100A for individual converter
module feeds and 200A for dual converter module feeds. See SAG584622100 for
additional restrictions.
Procedure
1) For DC input connections, refer to Figure 4-7.
2) If using the dual converter module feed adapter busbars, install the busbars as
shown in Figure 4-7.
Chapter 4. Making Electrical Connections Page 23
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
DC Input Connections
* 3/8-16 x 0.875” studs on 1” centers
for installation of leads with 2-hole lugs.
* Provide separate inputs for each converter.
* Maximum lug width 0.812”.
* Torque to 240 in-lbs.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Screw
Note: Handle must be
open when installing
or removing module.
CHAPTER 5.
INSTALLING THE CONVERTER MODULES
AND INITIALLY STARTING THE SYSTEM
INSTALLING CONVERTER MODULES
The converter module is hot swappable. It can be installed with the system operating.
Warning: To prevent damage to the latching mechanism, ensure the handle is in
the open position when installing or removing a converter module.
NEVER hold the handle in the closed position when installing a
converter module into a shelf.
Procedure
1) Place the module into an unoccupied mounting slot without sliding it in
completely.
2) Loosen the captive screw on the module handle. Pull the handle to pivot it out of
the module front panel (this will also retract the latch mechanism located at the
right side of the module). Refer to Figure 5-1 for latch mechanism illustration.
3) Push the converter module completely into the shelf.
4) Push the handle into the front panel of the module. This will lock the module
securely to the shelf. Tighten the captive screw on the handle.
5) Repeat the above steps for each converter module being installed in the system.
6) After the converter modules are physically installed in the mounting shelf(s), they
are ready for operation immediately after power is supplied to them.
Figure 5-1
Converter Module Handle/Latch Mechanism
Chapter 5. Installing the Converter Modules and Initially Starting the System Page 25
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Ensure that all blocks for Chapters 2 through 4 in the Installation Acceptance
Checklist, located in Chapter 1, have been checked.
Ensure no objects block the ventilation openings on the system shelf(s).
Initially Starting the System
Procedure
1) Close the external disconnects or protective devices that supply input power to
the system. Converter modules automatically start.
2) Open each shelf’s front door.
3) Place each distribution circuit breaker (if furnished) to the ON position.
4) Close each shelf’s front door.
Checking System Status
Procedure
1) Observe the status of the indicators located on the main shelf’s front door and
the converter modules. If the system is operating normally, the status of these is
as shown in Table 5-1. Verify there are no external alarms.
Page 26 Chapter 5. Installing the Converter Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Table 5-1
Status and Alarm Indicators
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
CHAPTER 6.
OPERATING PROCEDURES
CONVERTER MODULES
Refer to UM1C24481500 (Converter Module User Instructions) for converter module
operation instructions.
USING THE CONVERTER SYSTEM
WITH AN ACU+ CONTROLLER
The following outlines the steps to set-up the converter system to be used with an ACU+
controller. Refer to the ACU+ Controller User Instructions (UM1M820BNA) for ACU+
operation.
Set switch position 4 of S1 to the “ON” position. See Figure 3-1.
Remove (and store) Jumper P2. See Figure 3-1.
Connect terminal 1 (CANL) and 2 (CANH) of TB2 to the CAN bus the ACU+ resides
on. See Figure 4-2.
Note: The converter system must be the last device on the CAN bus to function
properly.
Note: If the converter system is used with control/monitoring via an ACU+ controller and
the converter input is powered through a distribution device in the host system,
the ACU+ controller should not be set up to calculate battery current. If battery
current measurement via the ACU+ is desired, the host system must measure
battery current with a battery shunt.
LOCAL INDICATORS AND TEST POINTS
Refer to the Converter Module User Instructions (UM1C24481500) for descriptions of the
local indicators located on the converter modules.
Refer to this section for descriptions of the local indicators and test points located on the
main shelf’s front door.
Local Indicators
The following local indicators are provided on the front door of the main shelf. Refer to
Figure 6-1.
a) Circuit Breaker or Fuse Open (Red LED): Illuminates red if any distribution
fuse or circuit breaker in the system opens.
b) Input Voltage OK (Green LED): Illuminates green when all converter modules
report input voltage is OK. This indicator is off if any converter module reports a
low input voltage condition.
Chapter 6. Operating Procedures Page 27
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
c) Converter Major (Red LED): Illuminates red if more than one converter module
fails (or if only one converter module is installed in the system and it fails).
Failure conditions are as stated in d) below.
d) Converter Minor (Yellow LED): Illuminates yellow if one converter module fails.
Failure conditions are as follows.
A converter module reports a high voltage shutdown condition (HVSD).
A converter module reports a fan failure.
A converter module reports an EEPROM failure.
A converter module reports a converter failure.
A converter module reports a low input voltage condition.
A converter module reports a high temperature condition.
A converter module reports a thermal derating condition.
Test Points
The following test points are provided on the front door of the main shelf. Refer to Figure
6-1.
a) Output Voltage (+, -): Provided for measuring system output voltage.
b) Output Current (+, -): Provided for measuring system output current. Scale is
User selectable for 400A/50mV or 1A/1mV. Current measurement is User
selectable to be referenced to plus battery, minus battery, or no reference. See
CHAPTER 3. SETTING JUMPER AND SWITCH OPTIONS.
Figure 6-1
Local Indicators and Test Points
Page 28 Chapter 6. Operating Procedures
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
PROCEDURE
REFERENCED IN
COMPLETED (√)
Check ventilation openings for
obstructions such as dust,
papers, manuals, etc.
Observe the admonishments located at the beginning of this document.
SYSTEM MAINTENANCE PROCEDURES
It is recommended to perform and record the maintenance procedures listed in Table 7-1
every 6-months to ensure continual system operation.
The table references specific chapters in this document that help in performing these
procedures.
Note: This table may be reproduced as necessary to record and document
system performance.
Table 7-1
Maintenance Procedures to be Performed at 6-Month Intervals
Chapter 7. Maintenance Page 29
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
CHAPTER 8.
TROUBLESHOOTING AND REPAIR
CONTACT INFORMATION
Support contact information is provided on the inside of the back cover of this document.
ADMONISHMENTS
Observe the admonishments located at the beginning of this document.
CONVERTER MODULES
Refer to UM1C24481500 (Converter Module User Instructions) for converter module
troubleshooting and repair instructions.
SYSTEM TROUBLESHOOTING INFORMATION
This system is designed for ease in troubleshooting and repair. The various indicators as
described in CHAPTER 6. OPERATING PROCEDURES and in the Converter Module
User Instructions (UM1C24481500) are designed to isolate failure to a specific element.
Once the faulty element has been identified, refer to “Replacement Information” and
"Replacement Procedures" in this chapter.
Clearing a Converter Fail Alarm after Removing a Converter Module
If a converter module is removed from the system, a converter fail alarm is generated. If
the converter module will not be replaced, the alarm should be cleared as described in
the following procedure.
Procedure
1) Momentarily push the “Update Converter Inventory” button located on the inside
of the main shelf’s front door. Refer to Figure 3-1 for location.
REPLACEMENT INFORMATION
When a trouble symptom is localized to a faulty converter module, the converter module
should be replaced in its entirety. Other than a converter module fan replacement, no
attempt should be made to troubleshoot or repair individual components on any converter
module.
Refer to SAG584622100 (System Application Guide) for replacement part numbers.
Page 30 Chapter 8. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Refer to the Converter Module User Instructions (UM1C24481500) for a converter
module replacement procedure. Refer also to System Troubleshooting Information in this
chapter to clear a converter fail alarm after removing a converter module.
Replacing a Distribution Device
General
Replace distribution devices with the same type and rating, or equivalent. Refer to
SAG584622100 (System Application Guide) for part numbers.
Distribution Fuse “Alarm Fuse” Replacement
If a distribution fuse opens, the associated alarm fuse opens. Replace the distribution
fuse before replacing the alarm fuse.
Procedure
1) An alarm fuse is removed by pulling it straight out of the fuseholder. If the alarm
fuse is located in a modular fuse carrier, hold the fuse carrier in place with your
thumb while pulling on the alarm fuse to prevent the entire carrier from
inadvertently being pulled out.
2) Safety fuse covers are provided for all Bussmann GMT type fuses installed in the
system. These covers snap onto the fuses and provide protection from exposed
electrical terminations when a fuse opens. Insure that the safety fuse cover is
installed after replacing a fuse. Refer to Figure 8-1 for installation details.
Figure 8-1
Installation of Safety Fuse Covers
Chapter 8. Troubleshooting and Repair Page 31
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Replacing a TPS/TLS Fuse
Note: Refer to Figure 2-5 as this procedure is performed.
Procedure
1) Open the shelf’s front door.
2) Remove the fuse carrier from the mounted fuseholder body by pulling it straight
out.
3) Remove the open fuse from the fuse carrier and replace it with the same type
and rating, or equivalent.
4) Replace the alarm fuse located in the front of the fuse carrier with the same type
and rating, or equivalent. Ensure that a plastic safety cover is installed on the
alarm fuse.
5) Push the fuse carrier securely back into the mounted fuseholder body. Note that
a polarizing key on the bottom of the carrier prevents the carrier from being
inserted upside down.
6) Verify there are no alarms active.
7) Close the shelf’s front door.
Page 32 Chapter 8. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Replacing a Bullet Nose Circuit Breaker or Fuseholder
Note: Refer to Figure 2-5 as this procedure is performed.
Procedure
1) Open the shelf’s front door.
2) Circuit Breaker: Operate a defective circuit breaker to the OFF position.
Fuseholder: Remove the fuse carrier from the mounted fuseholder body by
pulling it straight out.
3) Gently rock the defective circuit breaker or fuseholder up and down while pulling
firmly outward until the circuit breaker or fuseholder is free from the distribution
row.
4) Circuit Breaker: Ensure that the circuit breaker is in the OFF position, and is of
the correct rating.
5) Orient the distribution device as shown in Figure 2-5. Insert the terminals on the
rear of the distribution device into their corresponding sockets on the distribution
row. Ensure the alarm contact on the back of the distribution device makes
contact with the alarm terminal on the mounting circuit card. Push distribution
device in firmly until fully seated in the distribution row.
6) Circuit Breaker: Operate the replacement circuit breaker to the ON position.
Fuseholder: Push the fuse carrier securely back into the mounted fuseholder
body. Note that a polarizing key on the bottom of the carrier prevents the carrier
from being inserted upside down.
7) Verify there are no alarms active.
8) Close the shelf’s front door.
Chapter 8. Troubleshooting and Repair Page 33
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
UM584622100Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Replacing the System Interface Circuit Card
Warning: The system interface circuit card contains static-sensitive devices.
Read the Static Warning at the front of this document before performing
the following procedure.
Caution: When performing any step in this procedure that requires removal or
installation of hardware, use caution to ensure no hardware is dropped
and left inside the cabinet; otherwise service interruption or equipment
damage may occur.
Note: When performing any step in this procedure that requires removal of existing
hardware, retain all hardware for use in subsequent steps.
Note: Refer to Figure 8-2 as this procedure is performed.
Procedure
1) Refer to the Static Warning and Admonishments at the beginning of this
document before performing this procedure.
2) Performing this procedure may activate external alarms. Do one of the following.
If possible, disable these alarms. If these alarms cannot be easily disabled,
notify the appropriate personnel to disregard any future alarms associated with
this system while the procedure is being performed.
3) Open the main shelf’s front door.
Warning: Damage to the circuit card may result if the next step is not followed.
4) Connect an approved grounding strap to your wrist. Attach the other end to a
suitable ground.
5) On the replacement circuit card, set the switches and jumper to match the
existing circuit card settings. Refer to Figure 3-1.
6) Transfer any jumpers on terminal block TB2 of the existing circuit card to the
replacement circuit card. Refer to Figure 4-2.
7) Carefully label any wires connected to terminal blocks TB1 and TB2 on the
existing circuit card. These wires must be connected to the same terminals on
the replacement circuit card. Refer to Figure 4-2.
8) Remove the external wiring from terminal blocks TB1 and TB2.
9) Unplug the connector plugged into the circuit card.
10) Remove the screws securing the cover over the System Interface Circuit Card
and remove the cover and circuit card.
11) Position the replacement circuit card over its mounting position and replace the
cover. Secure the cover and circuit card with the screws previously removed.
Page 34 Chapter 8. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
12) Reconnect the external wiring to the correct terminals on terminal blocks TB1
and TB2.
13) Plug the connector removed from the old circuit card into the same position on
the replacement circuit card.
14) Remove the grounding wrist strap.
15) Enable the external alarms, or notify appropriate personnel that this procedure is
finished.
16) Ensure that there are no local or remote alarms active on the system.
17) Close the shelf’s front door.
Chapter 8. Troubleshooting and Repair Page 35
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Technical Support
Email
DCpower.TAC@Emerson.com
OSP.TAC@Emerson.com
Answers technical product and system
questions; determines status of warranties and
contractual agreements for repair.
Phone
1.800.800.5260
Services - Design, Deployment & Optimization
Email
ES.Services@Emerson.com
Provides quotes and bid responses, order
placement and scheduling for design, and
deployment and optimization services.
Download service & maintenance reports
online.
Phone
1.800.800.1280, option 7
FreedomCare
Secure.EmersonNetworkPower.com
Spare Parts
Email
DCpower.Spares@Emerson.com
OSP.Spares@Emerson.com
Pricing and PO processing of spare parts,
including but not limited to breakers, cables,
fuses, rectifier fans, misc. breaker and fuse
panels, enclosure fans, doors & switches, etc.
Phone
1.800.800.1280, option 5
DC Power Depot Repair
Email
DCpower.Repair@Emerson.com
Creates and processes RMAs, determines
lead times and pricing, provides repair
shipping information and status.
Phone
1.800.800.1280, option 6
DC Power Product Training
Email
DCpower.Training@Emerson.com
Requests for quotes, order placement and
scheduling.
Phone
1.800.800.1280, option 8
NetPerform™ Optimization Services
At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both
your business and your bottom line. That is why we offer a wide array of services to meet all of your
network infrastructure needs.
For More Information
To learn more about service offerings from Emerson Network Power, please contact your sales
representative, call 1-800-800-1280 option 7, email ES.Services@Emerson.com or visit
www.EmersonNetworkPower.com/EnergySystems.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.