Emerson NetSure 9500 Installation Manual

Page 1
NetSure™ 9500 120kW 400V DC Power System
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Specification Number: 584001200 Model Number: 9500
Page 2
NetSure™ 9500 120kW 400V DC Power System
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
This page is intentionally blank.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 3
NetSure™ 9500 120kW 400V DC Power System
[i]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Table of Contents
Admonishments Used in this Document ............................................................................................................... iii
Important Safety Instructions .............................................................................................................................. iv
General Safety ............................................................................................................................................................ iv
Voltages ..................................................................................................................................................................... iv
AC Input Voltages ............................................................................................................................................... iv
DC Output and Battery Voltages ......................................................................................................................... iv
Battery (if equipped) .................................................................................................................................................. iv
Personal Protective Equipment (PPE) .......................................................................................................................... v
Maintenance and Servicing Procedures ....................................................................................................................... v
General ................................................................................................................................................................ v
Dual Hazardous Input Power Sources .................................................................................................................. vi
Hazardous Voltage ..................................................................................................................................................... vi
Handling Equipment Containing Static Sensitive Components .................................................................................. vi
Static Warning .................................................................................................................................................... vii
General Information and Installation Checklist ...................................................................................................... 1
Customer Documentation Package ........................................................................................................................... 1
NetSure™ 9500 120kW 400V DC Power System Installation Manual ................................................................... 1
NetSure™ 9500 120kW 400V DC Power System Operation Manual ..................................................................... 1
NetSure™ 9500 400V DC Battery Cabinet Installation and Operation Manual ...................................................... 1
NetSure™ ACU+ Controller User Manual .............................................................................................................. 1
USB Drive with All Customer Documentation ..................................................................................................... 1
Recommended Tools and Test Equipment ................................................................................................................. 1
Installation Acceptance Checklist ............................................................................................................................... 1
Installing the System .......................................................................................................................................... 2
Making Electrical Connections ............................................................................................................................ 2
Installing the Rectifiers ....................................................................................................................................... 2
System Startup ................................................................................................................................................... 2
Installing the System ............................................................................................................................................. 2
General Requirements ............................................................................................................................................... 2
Inspecting the Equipment and Storing for Delayed Installations ................................................................................. 2
Inspecting the Equipment ................................................................................................................................... 2
Storing for Delayed Installation ........................................................................................................................... 2
Positioning and Securing the Power Module/Bay (584001200 List 01) and Distribution Module/Bay
(584001200 List 07) to the Floor ................................................................................................................................ 3
Positioning and Securing the Battery Cabinet (584001200 List 90, 91, 92, 93) to the Floor ........................................ 4
Making Electrical Connections .............................................................................................................................. 4
Important Safety Instructions .................................................................................................................................... 4
Wiring Considerations ................................................................................................................................................ 4
General Grounding/Earthing Guidelines ..................................................................................................................... 4
Output Ground Configuration .................................................................................................................................... 4
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 4
NetSure™ 9500 120kW 400V DC Power System
[ii]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Cable Routing ............................................................................................................................................................. 4
Torque ........................................................................................................................................................................ 4
Electrical Connections to Power Module/Bay (584001200 List 01) .............................................................................. 4
Power Module/Bay Rack Frame Grounding/Earthing Connection ........................................................................ 4
Power Module/Bay HRMG Connection ................................................................................................................ 4
Power Module/Bay AC Input Power and AC Input Equipment Grounding/Earthing Connections.......................... 5
Power Module/Bay DC Load Distribution Connections (if DC distribution panel installed) ................................... 5
Power Module/Bay IB2 (ACU+ Controller Interface Board P/N MA4C5U31) Connections ..................................... 6
Power Module/Bay Temperature Probe Connections .......................................................................................... 6
ACU+ Controller Ethernet Connection ............................................................................................................... 11
Power Module/Bay External EPO (Emergency Power Off) Connections .............................................................. 11
Power Module/Bay Battery Breaker Alarm/Shunt Trip Connections ................................................................... 12
Power Module/Bay Battery Shunt Connections ................................................................................................. 12
Power Module/Bay Battery Connections ........................................................................................................... 12
Electrical Connections to Distribution Module/Bay (584001200 List 07) ................................................................... 15
Distribution Module/Bay Rack Frame Grounding/Earthing Connection ............................................................. 15
Distribution Module/Bay Distribution Panel List 21HA Connections .................................................................. 15
Electrical Connections to Battery Cabinet (584001200 List 90, 91, 92, 93) ............................................................... 17
Installing the Rectifier Module ............................................................................................................................. 17
System Startup .................................................................................................................................................... 18
Important Safety Instructions ................................................................................................................................... 18
Initial Preparation ..................................................................................................................................................... 18
Initially Starting the System ...................................................................................................................................... 18
ACU+ Controller Initialization ................................................................................................................................... 20
Verifying the Configuration File ................................................................................................................................ 21
Changing Battery Capacity Rating in the ACU+ ......................................................................................................... 21
Checking Basic System Settings ................................................................................................................................ 21
Configuring the ACU+ Identification of Rectifiers ...................................................................................................... 22
Checking the EPO (Emergency Power Off) Circuit (if connected) .............................................................................. 23
EPO (Emergency Power Off) Function ................................................................................................................ 23
Checking System Status ........................................................................................................................................... 23
Final Steps ................................................................................................................................................................ 23
NetPerform™ Optimization Services (North America) ......................................................................................... 24
NetPerform™ Optimization Services (EMEA) ....................................................................................................... 25
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 5
NetSure™ 9500 120kW 400V DC Power System
[iii]
DANGER!
if not avoided. (ANSI, OSHA)
WARNING!
serious injury if not avoided. This admonition is not used for situations that pose a risk only to equipment, software, data, or service. (ANSI)
CAUTION!
moderate injury if not avoided. (ANSI, OSHA) This admonition is not used for situations that pose a risk only to equipment, data, or service, even if such use appears to be permitted in some of the applicable standards. (OSHA)
ALERT!
data, or service. (ISO)
ALERT!
software corruption, data loss, or service inter
FIRE SAFETY!
locations of fire
SAFETY!
to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Admonishments Used in this Document

Warns of a hazard the reader will be exposed to that will likely result in death or serious injury
D
an
g
er
Warns of a potential hazard the reader may be exposed to that could result in death or
W
ar
Caution
Alert
Alert
Fi
re Safet
n
in
g
Warns of a potential hazard the reader may be exposed to that could result in minor or
Alerts the reader to an action that must be avoided in order to protect equipment, software,
Alerts the reader to an action that must be performed in order to prevent equipment damage,
ruption. (ISO)
Informs the reader of fire safety information, reminders, precautions, or policies, or of the
-fighting and fire-safety equipment. (ISO)
y
Informs the reader of general safety information, reminders, precautions, or policies not related
S
afety
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 6
NetSure™ 9500 120kW 400V DC Power System
[iv]
Danger
D
an
g
er
Warning
Wa
rning
Dange
r
Danger
Dang
er
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Important Safety Instructions

General Safety

DANGER!
YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should be performed by qualified technicians familiar with the hazards associated with this type of equipment. These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order
indicated.
b) Remove watches, rings, and other metal objects.
c) Prior to contacting any uninsulated surface or
termination, use a voltmeter to verify that no voltage or the expected voltage is present. Check for voltage with both AC and DC voltmeters prior to making contact.
d) Wear eye protection.
e) Use certified and well maintained insulated tools.
Use double insulated tools appropriately rated for the work to be performed.
DC Output and Battery Voltages
DANGER! This system produces DC Power and may have
a battery source connected to it. The DC voltage IS hazardously high and the rectifiers and/or battery can deliver large amounts of current. Exercise extreme caution not to inadvertently contact or have any tool inadvertently contact an output terminal or battery terminal or exposed wire connected to an output terminal or battery terminal. NEVER allow a metal object, such as a tool, to contact more than one termination or battery terminal at a time, or to simultaneously contact a termination or battery terminal and a grounded object. Even a momentary short circuit can cause sparking, explosion, and injury.
Follow local lockout/tagout procedures to ensure DC branch circuit breakers remain de-energized during installation at loads, as required.
Extreme caution is required when performing maintenance. Be constantly aware that this system contains high DC as well as AC voltages.
The maximum output voltage is 400V DC and is potentially lethal.
f) Do not work on an energized system without full arc
flash and PPE protection.
DANGER! All power and control wiring should be
installed by a qualified electrician. All power and control wiring must comply with the National Electrical Code (NEC) and applicable local codes. For operation in countries where the NEC is not recognized, follow applicable codes.

Voltages

AC Input Voltages
DANGER! This system operates from AC input voltage
capable of producing fatal electrical shock. AC input power must be completely disconnected from the branch circuits wiring used to provide power to the system before any AC electrical connections are made. Follow local lockout/tagout procedures to ensure upstream branch circuit breakers remain de-energized during installation. DO NOT apply AC input power to the system until all electrical connections have been completed and checked.
Check for voltage with both AC and DC voltmeters prior to making contact.

Battery (if equipped)

DANGER! When connected together, the battery
terminal voltage is 400V DC and is potentially lethal. Battery strings should be isolated from the power system before servicing.
WARNING! Correct polarity must be observed when
connecting battery leads.
WARNING! Special safety precautions are required for
procedures involving handling, installing, and servicing batteries. Observe all battery safety precautions in this manual and in the battery instruction manual. These precautions should be followed implicitly at all times.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 7
NetSure™ 9500 120kW 400V DC Power System
[v]
W
a
rn
in
g
Dang
er
Alert
Danger
Wa
rning
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
WARNING! A battery can present a risk of electrical
shock and high short circuit current. Servicing of batteries should be performed or supervised only by properly trained and qualified personnel knowledgeable about batteries and the required precautions.
The following precautions should be observed when working on batteries:
Remove watches, rings, and other metal objects.
Eye protection should be worn to prevent injury
from accidental electrical arcs.
Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the work to be performed. Ensure that wrenches with more than one working end have only one end exposed.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or
disconnecting battery terminals.
Risk of explosion if battery is replaced with an incorrect type or if polarity is reversed. When replacing batteries, replace with the same manufacturer and type, or equivalent.
FOR THESE REASONS, IT IS OF CRITICAL IMPORTANCE THAT YOU READ THESE INSTRUCTIONS AND FOLLOW THEM EXACTLY.
WHEN WORKING WITH LEAD-ACID BATTERIES:
Wear complete protection for eyes, face, hands, and clothing. Examples are safety goggles or face shield, a rubber apron and gloves.
If battery acid enters your eye, immediately flush your eye with running cold water for at least 15 minutes. Get medical attention immediately.
If battery acid contacts skin or clothing, wash immediately with soap and water.
ALERT! Performing maintenance and/or
troubleshooting procedures may interrupt power to the loads, if battery reserve is not sufficient.

Personal Protective Equipment (PPE)

DANGER! ARC FLASH AND SHOCK HAZARD.
Appropriate PPE and tools required this equipment. An appropriate flash protection boundary analysis should be done determine the “hazard/risk” category, and to select proper PPE. Notice that PPE is applicable for both AC and DC voltages.
when working on
Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a fire. They may explode.
ALWAYS FOLLOW THE BATTERY MANUFACTURER’S RECOMMENDATIONS AND SAFETY INSTRUCTIONS.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and is toxic. If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
DANGER! This equipment may be used in conjunction
with lead-acid batteries. Working near lead-acid batteries is dangerous!
Batteries contain sulfuric acid.
Batteries generate explosive gases during normal
operation. Systems containing batteries should never be installed in an airtight room or space. Only install in a ventilated environment.
Batteries are an energy source that can produce high amounts of electrical current.
This product is intended only for installation in a restricted access location.
Only authorized and properly trained personnel should be allowed to install, inspect, operate, or maintain the rack/equipment.
Do not work on LIVE parts. If required to work or operate live parts, obtain appropriate Energized Work Permits as required by the local authority, per NFPA 70E “Standard for Electrical Safety in the Workplace” or applicable local codes.

Maintenance and Servicing Procedures

General
WARNING! All equipment maintenance and servicing
procedures involve internal access and should be carried out only by trained personnel on a de-energized system. Extreme caution is required when performing maintenance and servicing procedures. Be constantly aware that this system contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters prior to making contact.
Special safety precautions are required for procedures involving maintenance of this system and the batteries.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 8
NetSure™ 9500 120kW 400V DC Power System
[vi]
Da
ng
e
r
Alert
W
a
rn
in
g
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Observe all safety precautions in this manual and in the battery instruction manual before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near the batteries. Service personnel and test equipment should be standing on rubber mats. Service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground).
This equipment contains several circuits that are energized with dangerous voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned OFF, dangerously high electric charges may exist within the system.
Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.
Dual Hazardous Input Power Sources
WARNING! The system may be powered from dual
hazardous input power sources simultaneously: Commercial AC and Battery DC. Disconnect both sources of power before servicing.

Hazardous Voltage

DANGER! Hazard of electrical shock. More than one
disconnect may be required to de-energize the system before servicing.

Handling Equipment Containing Static Sensitive Components

ALERT! Installation or removal of equipment containing
static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 9
NetSure™ 9500 120kW 400V DC Power System
[vii]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Static Warning

This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to these components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any equipment containing static sensitive components, discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm resistor. Some wrist straps, such as Emerson Network Power Part Number 631810600, have a built-in one megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s instructions outlining use of a specific wrist strap.
3. Do not touch traces or components on equipment containing static sensitive components. Handle equipment containing static sensitive components only by the edges that do not have connector pads.
4. After removing equipment containing static sensitive components, place the equipment only on conductive or anti-static material such as conductive foam, conductive plastic, or aluminum foil. Do not use ordinary Styrofoam
5. Store and ship equipment containing static sensitive components only in static shielding containers.
6. If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment.
or ordinary plastic.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 10
NetSure™ 9500 120kW 400V DC Power System
[viii]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
This page is intentionally blank.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 11
NetSure™ 9500 120kW 400V DC Power System
[1 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

General Information and Installation Checklist

Customer Documentation Package

This document (IM584001200) provides Installation Instructions for NetSure™ 9500 120kW 400V DC Power System Model 9500, Spec. No. 584001200.
The complete Customer Documentation Package consists of…
NetSure Manual
NetSure™ 9500 120kW 400V DC Power System Operation Manual
NetSure Operation Manual
NetSure
USB Drive with All Customer Documentation
9500 120kW 400V DC Power System Installation
Power System Installation Instructions: IM584001200
Power System Operation Instructions: UM584001200
Rectifier Instructions: UM1R40015000e
Power System “System Application Guide”:
SAG584001200
9500 400V DC Battery Cabinet Installation and
Battery Cabinet Installation and Operation Instructions: IM58400120090
ACU+ Controller User Manual
ACU+ Controller User Instructions: UM1M820NNB-2
Power System Installation Instructions: IM584001200
Power System Operation Instructions: UM584001200
Battery Cabinet Installation and Operation Instructions:
IM58400120090
Rectifier Instructions: UM1R40015000e
Power System “System Application Guide”:
SAG584001200
ACU+ Controller User Instructions: UM1M820NNB-2
Engineering Drawings
Also provided on the USB drive is an ACU+ configuration
drawing and the ACU+ configuration files loaded into the ACU+ as shipped.

Recommended Tools and Test Equipment

The following tools and test equipment are recommended to install the DC Power System.
Contact Emerson for a full turn key installation quote.
Non-Contact Voltage Detector
Digital Multimeter (DMM), Capable of Measuring System
AC Input and DC Output Voltages, 600V AC/DC Rated
NO-OX-ID-A or Approved Equivalent
Lineman's Scissors
Lineman's Strippers
Lineman's Cutters
Electrician's Insulated Screwdrivers, Phillips, No. 1 and 2
Electrician's Insulated Screwdrivers, Flat-Blade, Small and
Large
Insulated Nut Driver Set
Hexagonal Bit Set
Ratchet, 1/2" (13mm) Drive
10mm Socket, 13mm Socket, 14mm Socket or 14mm
Wrench
Adjustable Torque Wrench, 1/2" (13mm) Drive, 0 in-lb. (0 Nm) to 125 in-lb. (14 Nm)
Lug Compression Crimp Tool, for Field Provided Battery Power Cable Terminations (as required)
Pallet Jack or Forklift, Required to Move the Power Module/Bay (367 Kg / 810 lbs.), Distribution Module/Bay (204 Kg / 450 lbs.), and Battery Cabinet (1500 Kg / 3300 lbs.) in Place
Tools Required for Rack/Cabinet Floor Fastening Hardware

Installation Acceptance Checklist

Provided in this section is an Installation Acceptance Checklist. This checklist helps ensure proper installation and initial operation of the system. As the procedures presented in this document are completed, check the appropriate box in this list. If the procedure is not required to be performed for your installation site, also check the box in this list to indicate that the procedure was read. When installation is done, ensure that each block in this list has been checked. Some of these procedures may have been factory performed for you.
Note:
The system is not powered up until the end of the Installation
Acceptance Checklist.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 12
NetSure™ 9500 120kW 400V DC Power System
[2 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Note:
Some of these procedures may have been performed at the
factory for you.

Installing the System

Equipment Inspection Completed
Rack(s) / Cabinet(s) Secured to Floor
Making Electrical Connections
POWER MODULE/BAY (584001200 LIST 01)
Rack Frame Grounding/Earthing Connection Made
HRMG Connection Made
AC Input Power and AC Input Equipment
Grounding/Earthing Connections Made
DC Load Distribution Connections Made (if DC
distribution panel installed)
System Startup
System Started, Configured, and Checked
Installing the System

General Requirements

This product is intended only for installation in a
The installer should be familiar with the installation
Temperature of air entering the system must not exceed
restricted access location on or above a non-combustible surface.
requirements and techniques to be used in securing the rack(s) cabinet(s) to the floor.
rated operating ambient temperature range found in SAG584001200.
IB2 (ACU+ Controller Interface Board) Connections Made
(if required)
Temperature Probe Connections Made (if required)
ACU+ Controller Ethernet Connection Made
External EPO (Emergency Power Off) Connections Made
(if required)
Battery Breaker Alarm/Shunt Trip Connections Made (if
required)
Battery Connections Made (if required)
DISTRIBUTION MODULE/BAY (584001200 LIST 07)
Rack Frame Grounding/Earthing Connection Made
DC Load Distribution Connections Made
DC Distribution Panels Interconnected (if required)
DC Input Connections Made
BATTERY CABINET (584001200 LIST 90, 91, 92, 93)
Battery Cabinet Frame Grounding/Earthing Connection
Made
48V Battery Breaker Shunt Trip Connection Made
Battery Breaker Alarm Connections Made
Battery Connections to the Power Module/Bay Made
(positive and negative leads)
Installing the Rectifiers
Rectifiers Installed
Front and rear access is required for installation.

Inspecting the Equipment and Storing for Delayed Installations

Inspecting the Equipment
Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Emerson representative immediately.
While the system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling.
As the equipment is moved off the truck and unpacked, visually examine the system for transit damage.
Do not attempt to install the system if damage is apparent.
If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Emerson Network Power (see “NetPerform™ Optimization Services (North America)” on page24 or “NetPerform™ Optimization Services (EMEA)” on page25 for contact information) to inform them of the damage claim and the condition of the equipment.
Storing for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 95%, non­condensing. The storage area must protect the system from excessive moisture.
Note:
For optimal battery life, store Battery Cabinet at a temperature
between -4°F to +77°F (-20°C to +25°C).
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 13
NetSure™ 9500 120kW 400V DC Power System
[3 of 25]
Rack will rest on casters wh
en
re
moving the shipping/bolt-down bracket.
Shippi
ng/
Anch
or
Br
ac
ke
t
Remove lag bo
lts
from
brackets on front and rear of
the
rack to free the shipping bracket
from
the p
allet.
Leave brackets bolted to the rack if theywill be use
d
to secure
the rack
to the
floor.
Notes:
1. Dimensions are in mm (inches).
Bottom View
441
(17.37)
84
(3.314)
84
(3.314)
898
(35.37)
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Positioning and Securing the Power Module/Bay (584001200 List 01) and Distribution Module/Bay (584001200 List 07) to the Floor

Position and secure the Power Module/Bay and/or Distribution Module/Bay to the floor per site requirements. Refer also to “General Requirements on page 2.
The Power Module/Bay and Distribution Module/Bay consists of rack P/N 557861 (standard) or P/N 557858 (Seismic). Refer to the following procedures.
STANDARD RACK (P/N 557861) INSTALLATION PROCEDURE
1. Use at least two people when moving the rack.
2. Using a pallet jack or forklift, move the rack on its pallet to the installation location.
3. Cut the shrink wrap and remove all packaging.
4. Use a 14mm socket or a 14mm wrench to remove the lag bolts securing each shipping bracket to the shipping pallet. There are two brackets, one in the front and one at the rear of the rack. Each bracket is secured by four bolts (see Figure 1).
Note:
Shipping brackets can also be used as an anchor
bracket once unit is at final resting place. Leave the shipping brackets attached if they will be used to secure the rack to the floor.
6. Use a pallet jack or forklift to raise the rack off the shipping pallet.
7. Slide the shipping pallet out from under the rack.
8. Position the rack for installation with the pallet jack or forklift.
9. Bolt the rack to the floor per site requirements.
Figure 1. Removing Rack P/N 557861 from Shipping Pallet
5. Use a pallet jack or forklift to raise the rack off the shipping pallet.
6. Slide the shipping pallet out from under the rack.
7. The rack may be positioned for installation either with the pallet jack or forklift or by rolling the rack on its casters. If the casters are to be used to move the rack, the leveling feet must be raised. Position the rack and either lower the leveling feet or bolt the rack to the floor with the shipping/anchoring brackets.
SEISMIC RACK (P/N 557858) INSTALLATION PROCEDURE
1. Use at least two people when moving the rack.
2. Refer to Figure 2 and prepare the floor for the anchors being used to secure the rack.
3. Using a pallet jack or forklift, move the rack on its pallet to the installation location.
4. Cut the shrink wrap and remove all packaging.
5. Remove the bolts securing the rack to the shipping pallet.
Figure 2. Rack P/N 557858 Floor Hole Drilling Pattern
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 14
NetSure™ 9500 120kW 400V DC Power System
[4 of 25]
Rear Rear
Ground Bar
(M6 studs on 16mm [5/8”] centers)
(Recommended Torque: 84 in-lbs [9.5 Nm])
Ground Bar
(M6 studs on
16mm [5/8”]
centers)
(Recommended
Torque:
84 in-lbs [9.5 Nm])
120kW Power Module/Bay
584001200 List 01
Da
n
ge
r
CautionDang
er
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Positioning and Securing the Battery Cabinet (584001200 List 90, 91, 92, 93) to the Floor

Position and secure the Battery Cabinet to the floor per site requirements. Refer also to “General Requirementson page 2.
The Battery Cabinet is furnished with separate installation and operation instructions. Refer to these instructions (IM58400120090) to position and secure the Battery Cabinet to the floor.
A pallet jack or forklift is required to install the Battery Cabinet (3500 lb capacity; batteries shipped installed in the cabinet).

Making Electrical Connections

Important Safety Instructions

Danger! Adhere to the “Important Safety Instructions”
presented at the front of this document.

Wiring Considerations

All AC input and 400V DC output wiring, branch circuit protection, and grounding/earthing should follow the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and applicable local codes. For operation in countries where the NEC is not recognized, follow applicable codes.

Cable Routing

The Power Module/Bay and Distribution Module/Bay are provided with top plates that have cable routing holes that either accept conduit fittings or corded connections.

Torque

Torque all connections as specified in the illustrations presented in this section.

Electrical Connections to Power Module/Bay (584001200 List 01)

Power Module/Bay Rack Frame Grounding/Earthing Connection
Refer also to “General Grounding/Earthing Guidelines” on page 4.
Supply a grounding/earthing lead from site ground/earth to the rack ground bar. Refer to Figure 3 for connection point.
Figure 3. Power Module/Bay Rack Frame Grounding/Earthing
For wire size, branch circuit protection, crimp lug, and general wiring recommendations; refer to System Application Guide SAG584001200 and the Battery Cabinet manual (IM58400120090).

General Grounding/Earthing Guidelines

Danger! Failure to follow proper grounding/earthing
For grounding/earthing requirements, refer to the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your specific site requirements. For operation in countries where the NEC is not recognized, follow applicable codes.
Refer also to the grounding/earthing procedures in this document.

Output Ground Configuration

This system is configured for High Resistance Midpoint Ground (HRMG). Ensure the HRMG lead is properly connected to ground/earth per the instructions that follow.
procedures can result in electric shock hazard to personnel and the risk of fire, should a ground fault occur.
Power Module/Bay HRMG Connection
Refer also to “General Grounding/Earthing Guidelines” on page 4.
A ground lead exits the rear of the power and control section in the Power Module/Bay. This lead MUST be connected to ground/earth for proper operation of the HRMG circuit and the ground fault detection circuit. Refer to Figure 4 for location. THIS LEAD IS FACTORY CONNECTED TO THE RACK’S GROUND BAR.
Caution! Failure to terminate this conductor to
ground/earth will render the system ground fault detection circuit and the ±200V DC voltage reference inoperable. It is essential to properly bond this lead to ground/earth.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 15
NetSure™ 9500 120kW 400V DC Power System
[5 of 25]
Rear
Rear
Power and Control Section
HRMG Ground Connection
(M
UST BE PROPERLY CONNECTED TO GROUND)
120kW Power Module/Bay
584001200 List 01
AC Input Ground Lead Studs
(M8 studs on 25mm [1”] centers)
(Recommended Torque:
108 in-lbs [12 Nm])
Rear
Rear
AC Input Leads Opening for 51mm (2”) Conduit
AC Input Terminals (M8 studs on 25mm [1”] centers) (Recommended Torque: 108 in-lbs [12 Nm])
Power and
Control Section
L1
L2 L3
AC Input
Nominal 380V/400V/480V AC,
Three-Phase, 50/60 Hz.
Rear
120kW Power Module/Bay
584001200 List 01
Da
ng
e
r
Danger
War
ning
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 4. Power Module/Bay HRMG Connection
Power Module/Bay AC Input Power and AC Input Equipment Grounding/Earthing Connections
Figure 5. Power Module/Bay AC Input Power Connections
Danger! Adhere to the “Important Safety Instructions”
AC input connections are made to AC input terminals located behind an access panel located on the rear of the power and control section. Studs are also provided for the AC input ground/earth lead. Refer to Figure 5 for location and connection details.
Power Module/Bay DC Load Distribution Connections (if DC distribution panel installed)
Danger! Adhere to the “Important Safety Instructions”
Warning! Check for correct polarity before making
Load distribution leads are connected to the load distribution panel(s) as shown in Figure 6 and Figure 7.
presented at the front of this document. DO NOT attempt to work on an energized system.
presented at the front of this document. DO NOT attempt to work on an energized system.
connections.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 16
NetSure™ 9500 120kW 400V DC Power System
[6 of 25]
Rear
Positive (+ )
Negative (-)
Positive (+ ) Bus
Negative (-)
Bus
Recomended Torque:
84 in-lbs (9.5 Nm)
±200V DC
120kW Power Module/Bay
584001200 List 01
Distribution
Panel
Front door removed in illustration for clarity only.
Customer
Load Connections
to DC Dist ribution
Circuit Breakers
(M6 studs on
16mm [5/8”] centers)
(left and right sides)
Rear
Negative (-)
Positive (+ )
120kW Power Module/Bay
584001200 List 01
Distribution
Panel
Distribution
Panel
Distribution
Panel
Positive (+ ) Bus
Negative (-)
Bus
Recomended
Torque:
108 in-lbs (12 Nm)
±200V DC
Front door removed in illustration for clarity only.
Customer
Load Connection
(M8 studs on
25mm [1”] centers)
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 6. Power Module/Bay DC Load Distribution Connections to
Distribution Panel List 21HA
Figure 7. Power Module/Bay DC Load Distribution Connections to
Distribution Panel List 23HA
these connections is 2.2 in-lbs (0.25 Nm). Refer to Figure 8 for terminal locations. Refer to Table 1 and Table 2 for pin-out information.
Digital Inputs
Connect up to eight (8) digital inputs to the IB2. Note that you must supply both paths for the digital input (either a positive or negative signal and the opposite polarity return path). Observe proper polarity. Refer to
Figure 8 for terminal locations and Table 1 for pin-out
information.
Note:
+48V is available on terminal J5-5 and Return (RTN)
is available on terminal J5-6 for customer connection to digital inputs.
The digital inputs can be programmed to provide an alarm when the signal is applied (HIGH) or removed (LOW). Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for programming information.
Digital Input Ratings: Refer to the following.
a. Maximum Voltage Rating: 60V DC.
b. Active High: > 19V DC.
c. Active Low: < 1V DC.
Programmable Relay Outputs
The IB2 provides eight (8) programmable alarm relays with dry Form-C contacts. Connect up to eight (8) relay outputs to the IB2. Refer to Figure 8 for terminal locations and Table 2 for pin-out information.
Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for programming information.
Power Module/Bay IB2 (ACU+ Controller Interface Board P/N
Relay Ratings: Refer to the following.
a. 1A Steady State @ 30V DC.
MA4C5U31) Connections
b. 3A Peak @ 30V DC.
The IB2 (ACU+ Controller Interface Board) provides connection points for digital inputs and programmable relay outputs. The IB2 interface board is accessed from the rear of the power and control section of the Power Module/Bay. Loosen the two captive fasteners and slide the tray the IB2 assembly is mounted to out far enough to make the electrical connections. Refer to Figure 8.
When connecting input and output wires to the IB2 board, route the leads through the opening provided in the tray the IB2 assembly is mounted to (see Figure 8).
DIGITAL INPUTS AND PROGRAMMABLE RELAY OUTPUTS
Digital input and relay output leads are connected to screw-type terminal blocks located on the IB2. Recommended torque for
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Power Module/Bay Temperature Probe Connections
Note:
Each temperature probe consists of two pieces that plug
together to make a complete probe. See SAG584001200 for part numbers and descriptions.
Temperature probes are connected to connectors located on the rear of the power and control section of the Power Module/Bay. See Figure 9.
Up to six (6) temperature probes can be connected to the power and control section of the Power Module/Bay. Any combination of the six (6) temperature probes can be programmed to monitor
Page 17
NetSure™ 9500 120kW 400V DC Power System
[7 of 25]
Power and
Control Section
IB2 (ACU+ Controller
Interface Board) Assembly
(located behing panel)
IB2 I/O Wiring Opening
Rear
Rear door removed in illustration for clarity only.
Rear
120kW Power Module/Bay
584001200 List 01
IB2 (ACU+ Controller Interface Board P/N MA4C5U31)
J1
SW1
J11
J12
Relay O
utput
Term. Blocks Digital Input Term.
Blocks
J9 J8 J7 J6 J5 J4 J3
J2
Switch sections must be set to this position to interface with the ACU+ controller.
Relay
No.
18 7 6 5 4 3 2
18 7 6
5 4 3 2
Input No
. (
)
Input No. (+)
NO C NC
NO NOC NC
NO C NC
C NC
NO C
NC
NO C NC
NO C NC
NO C NC
5 3 1
46 2
5 3 1
46 2
5 3 1
46 2
5
3
1
46 2
531
46 2
5 3 1
46 2
5
3
1
4
6 2
8 6
4
2
7 5 3 1
Relay
No.
J3-J9: Wire Size Capacity: 16-26 AWG (1.5-0.5mm2). Recommended Torque: 2.2 in-lbs (0.25 Nm).
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
ambient air temperature and/or battery temperature. A temperature probe set to monitor battery temperature can also be used for the rectifier battery charge temperature compensation feature. The battery charge temperature compensation feature allows the controller to automatically increase or decrease the output voltage of the system to maintain battery float current as battery temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery with respect to temperature is maintained. A temperature probe set to monitor battery temperature can also be used for the BTRM (Battery Thermal Runaway Management) feature. The BTRM feature lowers output voltage when a high temperature condition exist to control against battery thermal runaway.
A temperature probe programmed to monitor battery temperature, battery charge temperature compensation, and/or BTRM (Battery Thermal Runaway Management) should be mounted to the center of the battery cell closest to the center of the cabinet to sense battery temperature. A temperature probe programmed to monitor ambient temperature should be mounted in a convenient location, away from direct sources of heat or cold. To mount a temperature probe, peel the backing from the self-adhesive surface and affix the probe to a clean and dry surface.
Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for programming information.
Figure 8. Power Module/Bay IB2 (ACU+ Controller Interface Board) Connections
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 18
NetSure™ 9500 120kW 400V DC Power System
[8 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Table 1. Programmable Digital Inputs – IB2
Programmable
Digital Input
1
2
3
4
5
6
7
8
-- J5-5 +48V * --
-- J5-6 RTN * --
IB2
Pin No.
J3-2 +
J3-1
J3-4 +
J3-3
J3-6 +
J3-5
J4-2 +
J4-1
J4-4 +
J4-3
J4-6 +
J4-5
J5-2 +
J5-1
J5-4 +
J5-3
Default Digital Input Function
none
none
none
none
none
none
none
none
Customer Defined
Digital Input Function
* +48V is available on terminal J5-5 and Return (RTN) is available on terminal J5-6 for customer
connection to digital inputs.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 19
NetSure™ 9500 120kW 400V DC Power System
[9 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Table 2. Programmable Relay Outputs – IB2
Programmable
Relay Output
NO J6-5
1
2
3
4
5
6
7
8
COM J6-3
NC J6-1
NO J6-6
NC J6-2
NO J7-5
NC J7-1
NO J7-6
NC J7-2
NO J8-5
NC J8-1
NO J8-6
NC J8-2
NO J9-5
NC J9-1
NO J9-6
NC J9-2
IB2
Pin No.
Alarms Assigned to this Relay
(Default)
Factory Connected
(factory use only)
none COM J6-4
none COM J7-3
none COM J7-4
none COM J8-3
none COM J8-4
none COM J9-3
none COM J9-4
Alarms Assigned to this Relay
(Custom)
Not Available
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 20
NetSure™ 9500 120kW 400V DC Power System
[10 of 25]
Rear
Rear
Power and Control Section
BATT1
CTRL
BATT2
CTRL
BATT3 CTRL
BATT4
CTRL
AC INPUT
CTRL
CAN
BATT SHUNT 4
BATT SHUNT 3
BATT SHUNT 2
400VDC
CTRL INPUT
BATT SHUNT 1
TEMP1EPO
HRMG WIRE:
THIS WIRE MUST BE
CONNECTED TO GROUND
TEMP2 TEMP3 TEMP4 TEMP5 TEM P6
120kW Power Module/Bay
584001200 List 01
Temperature Probe
Connectors
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 9. Power Module/Bay Temperature Probe Connections
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 21
NetSure™ 9500 120kW 400V DC Power System
[11 of 25]
ACU+ Controller
ESC ENT
10/100M Ethernet
Port (RJ-45)
120kW Power Module/Bay
584001200 List 01
Power and Control Section
ACU+ Controller
Front door removed in illustration for clarity only.
Rear
Rear
Power and Control Section
BATT1
CTRL
BATT2
CTRL
BATT3
CTRL
BATT4 CTRL
AC INPUT
CTRL
CAN
BATT SHUNT 4
BATT SHUNT 3
BATT SHUNT 2
400VDC
CTRL INPUT
BATT SHUNT 1
TEMP1EPO
HRMG WIRE:
THIS WIRE MUST BE
CONNECTED TO GROUND
TEMP2 TEMP3 TEMP4 TEMP5 TEMP6
120kW Power Module/Bay
584001200 List 01
EPO Connector
(Emergency Pow
er Off)
Warning
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
ACU+ Controller Ethernet Connection
The ACU+ controller provides a Web interface via an Ethernet connection. This interface can be accessed locally on a computer or remotely through a network. An RJ-45 10BaseT jack is provided on the front of the ACU+ controller for connection to a computer or into a customer's network. This jack has a standard Ethernet pin configuration scheme, twisted pair. Refer to Figure 10 for location. Use shielded Ethernet cable (grounded at both ends). Note that the ACU+ RJ-45 jack is connected to chassis ground. Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for operational details.
Warning! The intra-building port(s) of the equipment or
subassembly is suitable for connection to intra-building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly MUST NOT be metallically connected to the interfaces that connect to the OSP or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
The intra-building port (RJ-45) of the equipment or subassembly must use shielded intra-building cabling/wiring that is grounded at both ends.
Power Module/Bay External EPO (Emergency Power Off) Connections
The Power Module/Bay has an Emergency Power Off (EPO) function operated by a remote contact provided by the User.
Note:
The external EPO switch wiring must be double-insulated. The
wire must be 600V, 18-16 AWG stranded for maximum runs between 82 and 197 feet (25-60m).
When the EPO switch is momentarily closed, the main AC input circuit breaker located on the power and control section of the Power Module/Bay and the battery disconnect circuit breakers (if connected to the BATT1 CTRL, BATT2 CTRL, BATT3 CTRL, and/or BATT4 CTRL connectors located on the rear of the power and control section of the Power Module/Bay) are tripped open to isolate the system from all electrical sources. Manual intervention is required to restart the system. Restart the system by first turning ON the main AC input circuit breaker then the battery circuit breaker(s).
PROCEDURE
1. Connect a customer provided external normally open switch between the EPO terminals provided on the rear of the power and control section of the Power Module/Bay. Refer to Figure 11 for location.
Figure 11. Power Module/Bay EPO (Emergency Power Off) Terminals
Figure 10. ACU+ Ethernet Port
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 22
NetSure™ 9500 120kW 400V DC Power System
[12 of 25]
Wa
rn
i
ng
D
a
n
g
e
r
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Power Module/Bay Battery Breaker Alarm/Shunt Trip Connections
For Emerson provided Battery Cabinet, a battery breaker alarm/shunt trip cable (P/N 557867) is provided with the system. This cable connects between the power and control section of the Power Module/Bay (see Figure 12) and the Battery Cabinet (see Battery Cabinet instructions IM58400120090).
Customer battery solutions must utilize a compatible battery breaker. Also one (1) Battery Breaker Alarm/Shunt Trip cable (P/N
557867) must be ordered for each battery string. Battery breaker requirements are as follows.
Battery breaker must contain a 48V shunt trip with the following specifications.
a. Rated Voltage: 48 to 60 VDC.
b. Maximum Release Duration: 15ms.
c. Minimum Resistance: >15 ohm.
Battery breaker must contain auxiliary contacts that are normally closed if the breaker is closed. Minimum contact rating is 48V DC at 2A.
It is recommended that the battery breaker have a lock­out/tag-out feature to allow for maintenance safety.
Power Module/Bay Battery Connections
Danger! Adhere to the “Important Safety Instructions”
presented at the front of this document. DO NOT attempt to work on an energized system.
Warning! Observe proper polarity when making battery
connections.
Note:
The maximum short circuit capacity of the circuit breakers in
the system is 25kAIC. Therefore, the maximum number of Emerson provided Battery Cabinets is limited to a maximum of three (3). The use of a fourth Battery Cabinet will exceed the short circuit rating of the circuit breakers in the system.
Note:
The short circuit current generated by a customer provided
battery option cannot exceed 25kAIC.
Up to four battery strings can be connected to the battery terminals located in the Power Module/Bay. Connect the battery strings to the positive and negative battery connection points per
Figure 13. Refer to SAG584001200 for wire size and crimp lug
information. See separate Battery Cabinet instructions (IM58400120090) for connection points in the Battery Cabinet.
Power Module/Bay Battery Shunt Connections
The battery shunt connectors on the power and control section of the Power Module/Bay are factory connected to the battery shunts also located in the Power Module/Bay. See Figure 12.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 23
NetSure™ 9500 120kW 400V DC Power System
[13 of 25]
3
12
4
Battery Alarm
+48V Battery Alarm
+48V Shunt Trip
Shunt Trip RTN
(Use cable P/N 557867)
Factory Connected
BATT1
CTRL
BATT2
CTRL
BATT3
CTRL
BATT4 CTRL
AC INPUT
CTRL
CAN
BATT SHUNT 4
BATT SHUNT 3
BATT SHUNT 2
400VDC
CTRL INPUT
BATT SHUNT 1
TEMP1EPO
HRMG WIRE:
THIS WIRE MUST BE
CONNECTED TO GROUND
TEMP2 TEMP3 TEMP4 TEMP5 TEM P6
Battery Breaker (1-4) Alarm/Shunt Trip Connector Pinouts
Battery Shunt (1-4) Connector
+Battery
Shunt
-Battery Shunt
Battery Breaker (1-4)
Alarm/Shunt Trip
Connector
Rear
Rear
Power and Control Section
120kW Power Module/Bay
584001200 List 01
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 12. Power Module/Bay Battery Breaker Alarm/Shunt Trip and Battery Shunt Connections
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 24
NetSure™ 9500 120kW 400V DC Power System
[14 of 25]
Rear
Positive (+) Battery Busbar
+
Negative (-) Battery Busbars
-+-
+-+
-
Positive (+) Bus this Side
Negative (-)
Bus this Side
Main
DC Bus
CUSTOMER CONNECTION
TO BATTERY STRINGS
Battery Terminals for 400V DC Battery Strings
Recommended Torque:
108 in-lbs [12 Nm]
Rear
120kW Power Module/Bay
584001200 List 01
Power and
Control Section
Battery Terminations
(M8 studs on 25mm [1”] centers)
Batt.
String
1
Batt.
String
2
Batt.
String
3
Batt.
String
4
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 13. Power Module/Bay Battery Connections
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 25
NetSure™ 9500 120kW 400V DC Power System
[15 of 25]
Rear
Rear
Ground Bar
(M6 studs on 16mm [5/8”] centers)
(Recommended T
orqu
e:
84 in-lbs [9.5 Nm])
Ground Bar
(M6 studs on
16mm [5/8”]
centers)
(Recommended
Tor
qu
e:
84 in-lbs [9.5 Nm])
Distribution Module/Bay
584001200 List 07
D
a
n
g
e
r
Wa
r
ni
ng
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Electrical Connections to Distribution Module/Bay (584001200 List 07)

Distribution Module/Bay Rack Frame Grounding/Earthing Connection
Refer also to “General Grounding/Earthing Guidelines” on page 4.
Supply a grounding/earthing lead from site ground/earth to the rack ground bar. Refer to Figure 14 for connection point.
Figure 14. Distribution Module/Bay Rack Frame Grounding/Earthing
Distribution Module/Bay Distribution Panel List 21HA Connections
Danger! Adhere to the “Important Safety Instructions”
presented at the front of this document. DO NOT attempt to work on an energized system.
Warning! Check for correct polarity before making
connections.
OUTPUT CONNECTIONS
Load distribution leads are connected to the load distribution panel(s) as shown in Figure 15.
INTERCONNECTING DC DISTRIBUTION PANELS (IF REQUIRED)
DC distribution panels can be interconnected as shown in Figure
15.
INPUT CONNECTIONS
DC distribution panel DC input leads are connected to the distribution panel(s) as shown in Figure 15.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 26
NetSure™ 9500 120kW 400V DC Power System
[16 of 25]
Rear
Front
Positive (+) Bus
Negative (-)
Bus
Distribution Panel
Distribution Panel
Front door removed in illustration for clarity only.
Distribution Module/Bay
584001200 List 07
Positive (+)
Negative (-)
Recommended Torque:
84 in-lbs (9.5 Nm)
±200V DC
Customer
Load Connections
to DC Distribution
Circuit Breakers
(M6 studs on
16mm [5/8”] centers)
(left and right sides)
Torque these Connections: 108 in-lbs (12 Nm)
Customer DC Input Connections to Load Distribution Panels (M8 studs on 25mm [1”] centers)
Recommended Torque: 108 in-lbs (12 Nm)
Interconnecting Two (2)
Load Distribution Panels
Positive (+) Bus
Negative (-) Bus
±200V DC
Distribution Panel
Distribution Panel
Distribution Module/Bay
584001200 List 07
Rear
List 21HA
Distribution Panels
Rear
Positive (+) Bus
Negative (-) Bus
±200V DC
P/N 558103 List 21HA
Interconnect Busbar
(two required)
(M8 studs on
1” [25mm] centers)
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 15. Distribution Module/Bay DC Load Connections, DC Input Connections, and Interconnecting Two (2) DC Load Distribution Panels
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 27
NetSure™ 9500 120kW 400V DC Power System
[17 of 25]
D
a
n
g
e
r
W
a
rn
in
g
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

Electrical Connections to Battery Cabinet (584001200 List 90, 91, 92, 93)

Danger! Adhere to the “Important Safety Instructions”
presented at the front of this document. DO NOT attempt to work on an energized system.
Warning! Check for correct polarity before making
battery connections.
Note:
The maximum short circuit capacity of the circuit breakers in
the system is 25kAIC. Therefore, the maximum number of Emerson provided Battery Cabinets is limited to a maximum of three (3). The use of a fourth Battery Cabinet will exceed the short circuit rating of the circuit breakers in the system.
Batteries are factory installed and connected in the Battery Cabinet.
Note:
Batteries are physically factory installed, but require one series
strap connection to complete the string wiring. The batteries as shipped are connected with one wire disconnected in the middle of the string, for shipping safety.
The Battery Cabinet is furnished with separate installation instructions (IM58400120090). Refer to these instructions to make the follow connections to the Battery Cabinet.
Battery Cabinet Frame Grounding/Earthing Connection (see also “General Grounding/Earthing Guidelines” on page 4)
48V Battery Breaker Shunt Trip Connection (see also “Power Module/Bay Battery Breaker Alarm/Shunt Trip Connections” on page 12)
Battery Breaker Alarm Connections (see also “Power Module/Bay Battery Breaker Alarm/Shunt Trip Connections” on page 12)
Battery Connections to the Power Module/Bay (see also “Power Module/Bay Battery Connections” on page 12)

Installing the Rectifier Module

The rectifier module is hot swappable. It can be installed with the system operating if these instructions are carefully followed.
Note:
There is a two-step insertion process.
PROCEDURE
1. Unpack the rectifier module.
2. If present, remove the blank cover panel from the rectifier module mounting position.
3. Open the respective rectifier module’s AC input circuit breaker on the front of the power and control section of the Power Module/Bay. Refer to Figure 17 for circuit breaker location.
4. Place the “Latch Release” located on the front of the rectifier module to the LEFT position. See Figure 16.
5. Place the rectifier module into an unoccupied mounting slot without sliding it in completely. Gently push the rectifier module into the mounting slot until it stops. Note that the rectifier module will NOT be completely seated in the mounting slot until the next step is performed.
6. Live Systems: Wait for the green power indicator to illuminate. Ensuring the green power indicator stays on, slide the “Latch Release” located on the front of the rectifier module to the RIGHT position. Gently push the rectifier module into the mounting slot until it is completely seated.
De-energized Systems: Slide the “Latch Release” located on the front of the rectifier module to the RIGHT position. Gently push the rectifier module into the mounting slot until it is completely seated.
7. Secure the rectifier module to the power and control section of the Power Module/Bay by tightening the retaining screw.
8. Repeat the above steps for each rectifier module being installed in the system.
9. After the rectifier modules are physically installed in their mounting slots, they are ready for operation immediately after power is supplied to them.
10. Close the respective rectifier module’s AC input circuit breaker on the front of the power and control section of the Power Module/Bay.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 28
NetSure™ 9500 120kW 400V DC Power System
[18 of 25]
Power Indicator (Green)
Protection Indicator (Y
ellow)
Alarm Indicator (Red)
Front V
iew
Latch Release
Retaining Screw
C
aut
ion
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 16. Installing a Rectifier Module into a Power Module/Bay

System Startup

Important Safety Instructions

Caution! Performing various steps in the following
procedures may cause a service interruption and/or result in the extension of alarms. Notify any appropriate personnel before starting these procedures. Also, notify personnel when these procedures are completed.
Note:
Contact Emerson Services for startup assistance.

Initial Preparation

Refer to Figure 17 for circuit breaker locations.
Ensure that all blocks (except the last one) in the “Installation Acceptance Checklist” starting on page 1 have been checked.
Ensure the main AC input circuit breaker located on the power and control section of the Power Module/Bay is in the OFF position.
Ensure each rectifier module AC input circuit breaker located on the power and control section of the Power Module/Bay is in the OFF position.
Ensure that a rectifier module or a blank cover panel is installed in all rectifier mounting positions.
Ensure each load distribution circuit breaker in the Power Module/Bay (if distribution panel is installed) and Distribution Module/Bay(s) is in the OFF position.
Ensure each battery string circuit breaker is in the OFF position.

Initially Starting the System

PROCEDURE
1. Close the external AC disconnect or protective device that supplies AC power to the system.
2. Place the main AC input circuit breaker located on the front of the power and control section of the Power Module/Bay to the ON position.
3. Place each rectifier module AC input circuit breaker located on the front of the power and control section of the Power Module/Bay to the ON position. Rectifiers automatically start.
4. Place each battery string circuit breaker to the ON position.
5. Place each load distribution circuit breaker in the Power Module/Bay (if distribution panel is installed) and Distribution Module/Bay(s) to the ON position.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 29
NetSure™ 9500 120kW 400V DC Power System
[19 of 25]
Load Distribution Circuit Breakers
120kW Power Module/Bay
584001200 List 01
Front
Front Front
Rectifier Module AC Input Circuit Breakers (40A, 380V/400V/480V AC)
Main AC Input Circuit Breaker (250A, 380V/400V/480V AC)
Load Distribution Circuit Breakers
Load Distribution Circuit Breakers
Load Distribution Circuit Breakers
Load Distribution Circuit Breakers
Distribution Module/Bay
584001200 List 07
120kW Power Module/Bay
584001200 List 01
Front door removed in illustrations for clarity only.
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Figure 17. Circuit Breaker Locations
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 30
NetSure™ 9500 120kW 400V DC Power System
[20 of 25]
ESC ENT
Menu Navigation Keys
USB Port
10/100M Ethernet
Port (RJ-45)
Status
Indicator
(Green)
Information Alarm
Indicator (Yellow)
Warning or Critical Alarm Indicator (Red)
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

ACU+ Controller Initialization

Note:
Your ACU+ controller was programmed with a configuration
file that provides initial settings for all adjustable parameters. Provided on a USB drive furnished with the system is an ACU+ configuration drawing (C-drawing) and the ACU+ configuration files loaded into the ACU+ as shipped
Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for detailed instructions.
Refer to Figure 18 for locations of the ACU+ local indicators and navigation keys.
Figure 18. ACU+ Controller Local Indicators and Navigation Keys
3. As initialization continues, the Main screen is displayed, but with zero volts. Initialization is not complete.
4. When initialization is complete, the Main screen displays voltage and current normally, and no alarms are active.
5. System information is displayed in multiple screens. Repetitively press the up or down arrow key to view other system information screens one by one.
6. From the Main screen, press
ENT to go to the “Main
Menu” screen.
PROCEDURE
Note:
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
The initialization routine takes several minutes. During that
time various alarm indicators may illuminate on the ACU+ front panel and an audible alarm may sound. Disregard all alarms. An audible alarm can be silenced at any time by momentarily depressing the
ENT
key on the ACU+ Controller.
1. After the ACU+ is powered on, the display alternates between the “ screen displaying “ ***** Starting…”.
2. Next, the language screen appears. Press the up or down arrow key to select the desired language. Press the key to confirm the selection. If no key is pressed within 10 seconds, the ACU+ selects the displayed language
Emerson Network Power” screen and a
Advanced Control Unit Plus Version
ENT
automatically.
7. From the Main Menu, select a sub-menu by repetitively pressing the up or down arrow key. The selected sub­menu will be indicated by the cursor. Press
ENT to open
the sub-menu.
Note:
Repeatedly press the “ESC” key to return in reverse order
level by level from any sub-menu until the Main screen appears.
8. Verify and set the ACU+ Controller as required for your application. Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for procedures. Note that you will have to program the ACU+ for any of the following.
a. Battery capacity if different then the factory default
of 120 Ah per battery string for the Emerson provided Battery Cabinet.
b. Number of battery strings connected to the system.
This is set in the Module 1 Distribution menu. Depending on the ACU+ configuration installed in your system (1 battery shunt or 4 battery shunts), the menu item displayed is “Battery Breaker 1 Installed” or “Battery String 1 Installed”. For a 1­shunt system, this sets the number of battery breakers being used in the system. For a 4-shunt
Page 31
NetSure™ 9500 120kW 400V DC Power System
[21 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
system, this sets the number of shunts being used in the system and the number of battery breakers being used in the system.
c. Temperature probes connected to the temperature
probe inputs located on the power and control section of the Power Module/Bay.
d. External inputs/outputs connected to the IB2 (ACU+
Interface Board) located on the power and control section of the Power Module/Bay.

Verifying the Configuration File

Your ACU+ controller was programmed with a configuration file that provides initial settings for all adjustable parameters. The version number of the configuration file can be found on the configuration drawing (C-drawing) that is supplied with your power system documentation, and on a label located on the ACU+. You can verify that the correct configuration file has been loaded into your ACU+ by performing the following procedure.
PROCEDURE
Note:
When viewing any of the following screens, if a key is not
depressed within approximately 10 seconds, the ACU+ will automatically return to the Main screen.
1. With the Main screen displayed, press displays the serial number and software version.
2. Press
3. Press
4. Press
ENT. A screen displays the hardware version and
MAC address.
ENT. A screen displays the configuration version
number.
ESC, or wait approximately 10 seconds, to return to
the Main screen.
ESC. A screen

Changing Battery Capacity Rating in the ACU+

To change the battery capacity setting of the ACU+ to match the battery connected to the power system, perform the following procedure.
(default password is “1”), then press ENT twice. (
you have been assigned a unique User Name and password, follow this procedure to enter these.)
3. With the Settings menu screen displayed, navigate to and select “
4. Navigate to “Rated Capacity”. Press ENT. Use the up or down keys to adjust the value as required. Press
Note:
The default capacity value is 120 Ah per battery string for
the Emerson provided Battery Cabinet. For customer provided batteries, enter the C10 battery capacity rating in Ah.
5. Return to the Main screen by repeatedly pressing (escape).
Battery” (ENT) / “Basic” (ENT).
Note:
ENT.
ESC
If

Checking Basic System Settings

Navigate through the controller menus and sub-menus to check system settings. You can adjust any parameter as required. Note that these settings can also be checked (and changed if required) via the WEB Interface.
Note:
Repeatedly press the “ESC” key to return in reverse order level
by level from any sub-menu until the Main screen appears.
PROCEDURE
To Select a Sub-Menu: Press the up or down arrow keys to move the cursor up and down the list of sub-menus in the menu screen (selects the sub-menu), then press
To Enter a Password: If a password screen opens, a password must be entered to allow the User to make adjustments. To enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press “0” is highlighted. Press the up arrow key once to change the “0” to”1” (default password is “1”), then press
have been assigned a unique User Name and password, follow this procedure to enter these.)
ENT to enter the selected sub-menu.
ENT twice. (
Note:
ENT.
If you
PROCEDURE
1. With the Main screen displayed, press Main Menu. Navigate to and select “
2. If a password screen opens, a password must be entered to allow the User to make adjustments. If a password was previously entered and has not yet timed out, skip this step and proceed to step 3). Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press Press the up arrow key once to change the “0” to”1”
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
ENT to go to the
Settings” (ENT).
ENT. “0” is highlighted.
To Change a Parameter: Press the up or down arrow keys to move the cursor up and down the list of parameters in the menu screen (selects the parameter to change), then press parameter field highlights. Press the up or down arrow keys to change the parameter value. Press
Table 3 shows the menu navigation for some basic settings. (Refer
to the ACU+ Controller Operation Instructions (UM1M820NNB-2) for details and additional settings.)
ENT to change the selected parameter. The
ENT to confirm the change.
Page 32
NetSure™ 9500 120kW 400V DC Power System
[22 of 25]
Date
Main Menu / Settings / Controller / Date
Time
Main Menu / Settings / Controller / Time
IP Communications Parameters
gateway address)
Float Voltage
Main Menu / Settings / Battery / Charge / Output Voltage
Equalize Voltage
Main Menu / Settings / Battery / Charge / EQ Voltage
Battery Capacity
Main Menu / Settings / Battery / Basic / Ttl Rated Capac
Main Menu / Settings / Battery / Basic / BTRM Voltage
Temperature Compensation Center Temperature
Temperature Compensation Slope
Main Menu / Settings / Battery / Temp Comp / Temp Comp Coeff
Temperature Compensation Sensor
Main Menu / Settings / Battery / Temp Comp / Temp Comp Probe
HVSD Limit
Main Menu / Settings / Rectifier / All Rect Set / HVSD Limit
Rectifier Current Limit
Main Menu / Settings / Rectifier / All Rect Set / Input Current Lmt
Over Voltage Alarm 1
Main Menu / Settings / Power System / Over Voltage 1
Over Voltage Alarm 2
Main Menu / Settings / Power System / Over Voltage 2
Under Voltage Alarm 1
Main Menu / Settings / Power System / Under Voltage 1
Under Voltage Alarm 2
Main Menu / Settings / Power System / Under Voltage 2
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Table 3. ACU+ Controller Basic Settings Local Menu Navigation
Parameter Menu Navigation
(IP address, subnet mask address,
BTRM Feature
Main Menu / Settings / Communication
Main Menu / Settings / Battery / Basic / BTRM Action
Main Menu / Settings / Battery / Temp Comp / Temp Comp Ref.

Configuring the ACU+ Identification of Rectifiers

When rectifier modules are all installed prior to applying power and starting the system, the order in which the ACU+ identifies the rectifiers is by serial number (lowest serial number is Rect 1, next lowest is Rect 2, etc.). If you prefer the ACU+ to identify the rectifiers by position in the system, perform the following procedure.
PROCEDURE
1. With the Main screen displayed, press Main Menu. Navigate to and select “
2. If a password screen opens, a password must be entered to allow the User to make adjustments. If a password was previously entered and has not yet timed out, skip this step and proceed to step 3). Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press Press the up arrow key once to change the “0” to”1” (default password is “1”), then press
ENT to go to the
Settings” (ENT).
ENT. “0” is highlighted.
ENT twice. (
Note:
If
you have been assigned a unique User Name and password, follow this procedure to enter these.)
3. With the Settings menu screen displayed, navigate to and select “
4. Navigate to “ rectifier identification number). Press # menu screen is displayed, and the green LED on one rectifier starts flashing. This is the rectifier currently identified by the ACU+ as rectifier #. (If this is not the rectifier you want, press screen and select a different rectifier.)
5. Navigate to and select “ up or down keys to change the ACU+ identification number for the flashing rectifier. Press
6. Press ESC to return to rectifier menu screen.
7. Repeat steps 4) through 6) for each of the remaining rectifiers in the system.
Rectifier” (ENT).
Rect #” (# is used here to represent the
ENT. The rectifier
ESC to return to rectifier menu
Rectifier ID”. Press ENT. Use the
ENT.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 33
NetSure™ 9500 120kW 400V DC Power System
[23 of 25]
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
8. When you have finished selecting identification numbers for all rectifiers, repeatedly press Main Menu.
9. Navigate to and select “ / “
All Rect Ctrl” (ENT).
10. Navigate to “Confirm ID/PH”. Press ENT. “Yes” highlights.
11. Press
Note:
12. Return to the Main screen by repeatedly pressing
ENT to select the operation. Press ENT again to
confirm.
Check your numbering to be sure it is correct. If there
where conflicts in your numbering, rectifiers with conflicts will be assigned the next available sequential number.
(escape).
Manual” (ENT) / “Rectifier” (ENT)
ESC to return to the
ESC

Checking the EPO (Emergency Power Off) Circuit (if connected)

EPO (Emergency Power Off) Function
The Power Module/Bay has an Emergency Power Off (EPO) function operated by a remote contact provided by the User.
When the EPO switch is momentarily closed, the main AC input circuit breaker located on the power and control section of the Power Module/Bay and the battery disconnect circuit breakers (if connected to the BATT1 CTRL, BATT2 CTRL, BATT3 CTRL, and/or BATT4 CTRL connectors located on the rear of the power and control section of the Power Module/Bay) are tripped open to isolate the system from all electrical sources. Manual intervention is required to restart the system. Restart the system by first turning ON the main AC input circuit breaker then the battery circuit breaker(s).
PROCEDURE
1. With the system operating, momentarily depress the customer furnished Emergency Power Off switch.
2. Verify that the main AC input circuit breaker located on the power and control section of the Power Module/Bay and any connected battery circuit breakers open.
3. Restart the system by first turning ON the main AC input circuit breaker then the battery circuit breaker(s).
section of the Power Module/Bay. If the system is operating normally, the status of these is as shown in
Table 4.
Table 4. Status and Alarm Indicators
Component Indicator Normal State
ACU+
Controller
Rectifier
Modules
Power and
Control Section
of Power
Module/Bay
Status
(Green)
Information
(Yellow)
Warning or
Critical
Alarm
(Red)
Power
(Green)
Protection
(Yellow)
Alarm
(Red)
Output Voltage Present (Green)
Control Voltage
Present Indicator (Green)
Ground/Insulation Fault
Alarm (Red)
On
Off
Off
On
Off
Off
On
On
Off

Final Steps

PROCEDURE
1. If any ACU+ Controller configuration settings were changed, refer to the ACU+ User Instructions (UM1M820NNB-2) and save a copy of the configuration file. This file can be used to restore the ACU+ Controller settings, if required, at a later date.
Note that provided on a USB drive furnished with the
system is an ACU+ configuration drawing (C-drawing) and the ACU+ configuration files loaded into the ACU+ as shipped.
2. Verify there are no external alarms and the local indicators are as shown in Table 4.

Checking System Status

PROCEDURE
1. Observe the status of the indicators located on the ACU+ controller, rectifier modules, and power and control
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 34
NetSure™ 9500 120kW 400V DC Power System
[24 of 25]
Customer Service (Pre-Shipment)
Email
CustomerService.ESNA@Emerson.com
Pricing and availability
, purchase orders, expediting requests
Associate.
Customer Support Center (Post-Shipment)
Email
ESNACustomerSupportCenter@Emerson.com
Phone
1.956.661.6867
Account Management
Email
AccountManagement.ESNA@Emerson.com
Provides quotes and bid responses for custom configured
[2]
DC power
(Reps, VARs & Distributors).
Spare Parts
DCpower.Spares@Emerson.com OSP.Spares@Emerson.com
Phone
1.800.800.1280 option 5
DC Power Depot Repair
Technical Support
DCpower.TAC@Emerson.com OSP.TAC@Emerson.com
Phone
1.800.800.5260
[1]
Contact Account Management for custom-configurations. Contact Spare Parts for parts and accessories.
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

NetPerform™ Optimization Services (North America)

At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both your business and your bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs.
[1,2]
Phone 1.800.800.1280 option 2
and order tracking. Ask for your company’s dedicated Customer Service
After an order has shipped, contact our Customer Support Center with related questions, concerns or claims.
Phone 1.800.800.1280 option 3
Email
Email DCpower.Repair@Emerson.com
Phone 1.800.800.1280 option 6
Email
[2]
systems and outside plant enclosures for customers and channel partners
Pricing and purchase orders for spare parts, including but not limited to breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels, enclosure fans, doors and switches, etc.
Creates and processes RMAs for depot repair and refurbishment. Determines repair and refurbishment lead times and pricing based on warranties/contractual agreements. Provides repair shipping information and status.
Answers technical product and system questions; determines status of warranties and contractual agreements for repair.
For More Information
To learn more about service offerings from Emerson Network Power, please contact your sales representative, call 1-800-800-1280 option 7, email ES.Services@Emerson.com or visit EmersonNetworkPower.com/EnergySystems.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 35
NetSure™ 9500 120kW 400V DC Power System
[25 of 25]
Technical Support
Contact your sales representative.
Freedom Care
EMEA Customer Support Center
ESEMEACustomerSupportCenter@ Emerson.com
Dealing with customer problems related to:
Quality and product support
Order DC Power & OSP, Order Status
Email
OPC.EES@EmersonNetworkPower.com
Phone
+421 32 7700 706
Request DC Power Repair Service RMA
Email
EMEA.HWServices@Emerson.com
Phone
+421 32 7700 191
Spare Parts
DC Power Product Training
Installation Manual, IM584001200 (Issue AA, April 14, 2014)

NetPerform™ Optimization Services (EMEA)

At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both your business and your bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs.
Provides quotes and bid responses, order placement and scheduling
EmersonNetworkPower.com
for design, and deployment and optimization services. Download service & maintenance reports online.
Email
Phone +421 32 7700 888
Email EMEA.HWServices@Emerson.com
Phone +421 32 7700 881
Product field performance
Product quality defects
Product dead on arrival
Incomplete or incorrect deliveries
Creates and processes orders, determines lead times and pricing, provides order shipping information and status.
Creates and processes RMAs, determines lead times and pricing, provides repair shipping information and status.
Pricing and PO processing of spare parts, including but not limited to breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels, enclosure fans, doors & switches, etc.
Email EMEA.Training@emersonenergy.com Requests for quotes, order placement and scheduling.
For More Information
To learn more about service offerings from Emerson Network Power, please contact your sales representative, or visit
EmersonNetworkPower.eu/EnergySystems.
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Page 36
NetSure™ 9500 120kW 400V DC Power System
Emer
sonNet workPower.com/EnergySystem s (North
America)
EmersonNetwork Power.eu/Energ
ySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2014.
Business -Critical Co ntinuity™, Emer son Netw ork Powe r™, the Em erso n Networ k Power logo , Emer so n™ and Conside r it Sol
ved are serv ice marks and
trademar ks of Emer son Electric Co. Ener gyMaster™, eSur
e™, NetPer form™, NetR each™, NetS pan™, NetSur e™ and N etXten d™ are tradema rks of Emers on
Net work Powe r, Energy Syste ms, Nor th America, Inc . Any other product, brand, or company names or logos are the property of the respective owner.
While every precaution has been taken to ensure accuracy and completeness herein, E merson Electric Co. assumes no r esponsibility, and disclaims all liability, for damages resulting from use of this information o r for any errors or omi ssions. Specifications subject to change without notice.
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has be
en take
n to ensure the accuracy and completeness of this document, Emerson Network Power, Energy Systems, North America, Inc. assumes no responsibility and
disclaims all liability for damages result-
ing from use of this information or for any
errors or omissions. Refer to other local
pr
actices or building cod
es as applicable for the correct methods, tools, and materials to
be used in performing procedur es not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Emerson N
etwork Power, Ene
rgy Systems, North America, Inc. This document is the property of
Emerson Ne
twork Power, Energy Syste
ms, North America, Inc. and contains confidential and
propri
etary information owned by Emerson Ne
twork Powe
r, Energy Systems, North
America, Inc. Any copying, use or disclosure of it without the written pe
rmission of Emerson
Network Power, Energy Syste
ms, North Ame
rica, Inc. is strictly prohibited.
Nam
es of companies and products are trad
emarks or registered trad
emarks of the
respective companies. Any questions regard
ing usage of tra
demark nam
es should be
directed to the original manuf
acturer.
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Spec. No: 584001200 Code: IM584001200 Model No: 9500 Issue AA, April 14, 2014
Loading...