This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K.0870 240 1978Australia800 158 727
1.4 Best practices................................................................................................................................... 7
1.5 Temperature limits...........................................................................................................................7
Chapter 5Purge the sensor case ..................................................................................................15
Installation Manual 3
Page 4
ContentsInstallation Manual
April 2019MMI-20040393
4Micro Motion TA Series
Page 5
Installation Manual
MMI-20040393April 2019
Planning
1Planning
1.1About this document
This manual provides information on planning, mounting, and grounding the meter. For
information on full configuration, maintenance, troubleshooting, or service of the
transmitter, see the configuration and use manual.
The information in this document assumes that users understand:
• Basic transmitter and sensor installation, configuration, and maintenance concepts
and procedures
• All corporate, local government, and national government safety standards and
requirements that guard against injuries and death
1.2Related documentation
You can find all product documentation on the product documentation DVD shipped with
the product or at www.emerson.com.
For more information, see any of the following documents:
Product Data Sheets
• Micro Motion TA-Series Flow and Density Meters Product Data Sheet
• Micro Motion Model 5700 Product Data Sheet
Other installation manuals
• Micro Motion Model 5700 Transmitters with Configurable Outputs: Installation Manual
• Micro Motion Model 5700 with Ethernet Transmitters: Installation Manual
• Micro Motion Model 5700 Transmitters for FOUNDATION™ Fieldbus: Installation Manual
• Micro Motion Model 5700 Transmitters with Intrinsically Safe Outputs: Installation Manual
Configuration and use manuals
• Micro Motion Model 5700 Transmitters with Configurable Outputs: Configuration and Use
Manual
• Micro Motion Model 5700 with Ethernet Transmitters: Configuration and Use Manual
• Micro Motion Model 5700 Transmitters for FOUNDATION™ Fieldbus: Configuration and Use
Manual
• Micro Motion Model 5700 Transmitters with Intrinsically Safe Outputs: Configuration and
Use Manual
Other documents
• Modbus Interface Tool
• For hazardous area installations, see the approval documentation shipped with the
transmitter, or download the appropriate documentation at www.emerson.com.
Installation Manual 5
Page 6
PlanningInstallation Manual
April 2019MMI-20040393
1.3Installation checklist
□ Safety messages are provided throughout this content to protect personnel and
equipment. Read each safety message carefully before proceeding to the next step.
□ If possible, install the meter in a location that will prevent direct exposure to sunlight.
The environmental limits for the meter may be further restricted by hazardous area
approvals.
□ If you plan to mount the meter in a hazardous area:
— Verify that the meter has the appropriate hazardous area approval. Each meter has
a hazardous area approval tag attached to the meter housing.
— For ATEX/IECEx installations, strictly adhere to the safety instructions documented
in the ATEX/IECEx approvals documentation available on the Product
Documentation DVD shipped with the product or at www.emerson.com. Be sure to
reference this documentation in addition to the information shown in this guide.
□ Verify that the local ambient and process temperatures are within the limits of the
meter.
1.3.1
□ Follow the wiring instructions in the Model 5700 installation manual for signal and
power wiring.
□ Mount the meter in a location and orientation that allows sufficient clearance to open
the housing cover. Allow 8 in (203 mm) to 10 in (254 mm) clearance at the wiring
access points.
□ Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. Flow direction is also software-selectable.
Orientation options
You can mount the meter in any orientation as long as the conduit openings or display do
not point upward. Keep the sensor tubes full of process fluid to achieve best performance.
CAUTION
Installing the meter with the conduit openings or display facing upward risks moisture
entering the housing, which could damage the meter.
Use the extended mount junction box (electronic interface code H) for process
temperatures above 176 °F (80.0 °C).
Installation Manual 7
Page 8
PlanningInstallation Manual
April 2019MMI-20040393
8Micro Motion TA Series
Page 9
Installation Manual Mounting
MMI-20040393April 2019
2Mounting
2.1Mount the meter
Use your common practices to minimize torque and bending load on process connections.
Prerequisites
Read the installation checklist and best practices if you have not yet done so already. See
Installation checklist and Best practices.
Procedure
Mount the meter using the following illustration.
Installation Manual 9
Page 10
MountingInstallation Manual
April 2019MMI-20040393
10Micro Motion TA Series
Page 11
Installation Manual Wiring
MMI-20040393April 2019
3Wiring
3.1Tantalum wiring
• A 9-wire cable is limited to 1,000 ft (304.80 m) between the sensor and the
transmitter.
• If you are using the Smart Meter Verification (SMV) application, the 9-wire cable is
limited to 60 ft (18.29 m) maximum.
• Use Teflon™ jacketed cable for SMV applications.
DANGER
Make sure the hazardous area specified on the sensor approval tag is suitable for the
environment in which the sensor will be installed. Failure to comply with the
requirements for intrinsic safety in a hazardous area could result in an explosion.
CAUTION
Fully close and tighten all housing covers and conduit openings. Improperly sealed
housings can expose electronics to moisture, which can cause measurement error or
flowmeter failure. Inspect and grease all gaskets and O-rings.
3.1.1
Connect the 9-wire cable
Procedure
1. Prepare and install the cable according to the instructions in the Micro Motion 9-Wire
Flowmeter Cable Preparation and Installation Guide.
2. Insert the stripped ends of the individual wires into the terminal blocks of the
junction box. Ensure that no bare wires remain exposed.
Terminal block number
1Blue
Wire color
Installation Manual 11
Page 12
WiringInstallation Manual
April 2019MMI-20040393
Terminal block numberWire color
2Gray
3Green
4White
5Orange
6Yellow
7Purple
8Red
9Brown
shield
3. Match the wires color for color. For wiring at the transmitter or remote core
processor, refer to the transmitter documentation.
4. Tighten the screws to hold the wires in place.
5. Ensure integrity of gaskets, then tightly close and seal the junction box cover and all
housing covers.
6. Refer to the transmitter installation manual for signal and power wiring
instructions.
12Micro Motion TA Series
Page 13
Installation Manual Grounding
MMI-20040393April 2019
4Grounding
The meter must be grounded according to the standards that are applicable at the site.
The customer is responsible for knowing and complying with all applicable standards.
Prerequisites
Use the following guides for grounding practices:
• In Europe, IEC 60079-14 is applicable to most installations, in particular Sections
16.2.2.3 and 16.2.2.4.
• In the U.S.A. and Canada, ISA 12.06.01 Part 1 provides examples with associated
applications and requirements.
If no external standards are applicable, follow these guidelines to ground the sensor:
• Use copper wire, 14 AWG (2.08 mm²) or larger wire size.
• Keep all ground leads as short as possible, less than 1 Ω impedance.
• Connect ground leads directly to earth, or follow plant standards.
CAUTION
Ground the flowmeter to earth, or follow ground network requirements for the facility.
Improper grounding can cause measurement error.
Procedure
• Check the joints in the pipeline.
• If the joints in the pipeline are ground-bonded, the sensor is automatically
grounded and no further action is necessary (unless required by local code).
• If the joints in the pipeline are not grounded, connect a ground wire to the
grounding screw located on the sensor electronics.
Tip
The sensor electronics may be a transmitter, core processor, or junction box. The
grounding screw may be internal or external.
Installation Manual 13
Page 14
GroundingInstallation Manual
April 2019MMI-20040393
14Micro Motion TA Series
Page 15
Installation Manual Purge the sensor case
MMI-20040393April 2019
5Purge the sensor case
Prerequisites
Make sure the following are available before beginning the purge procedure:
• Teflon™ tape
• Argon or nitrogen gas sufficient to purge the sensor case
Whenever a purge plug is removed from the sensor case, you must repurge the case.
Procedure
1. Shut down the process, or set control devices for manual operation. Before
performing the case purging procedure, shut down the process or set the control
devices for manual operation. Performing the purge procedure while the flowmeter
is operating could affect measurement accuracy, resulting in inaccurate flow
signals.
2. Remove both purge plugs from the sensor case. If purge lines are being used, open
the valve in the purge lines.
DANGER
• Stay clear of the rupture disk pressure relief area. High-pressure fluid escaping
from the sensor can cause severe injury or death. The sensor must be oriented
so that personnel and equipment will not be exposed to any discharge along
the pressure relief path.
• Take all necessary precautions when removing purge plugs. Removing a purge
plug compromises the secondary containment of the sensor and could expose
the user to process fluid.
• Improper pressurization of the sensor case could result in personal injury.
CAUTION
Be sure to use thread protectors when removing the purge fitting so as not to
damage the disk membrane surrounding the rupture disk.
3. Prepare the purge plugs for reinstallation by wrapping them with 2–3 turns of
Teflon tape.
4. Connect the supply of nitrogen or argon gas to the inlet purge connection or open
inlet purge line. Leave the outlet connection open.
• Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants
into the sensor case.
• If the purge gas is heavier than air (such as argon), locate the inlet lower than the
outlet, so that the purge gas will displace air from bottom to top.
• If the purge gas is lighter than air (such as nitrogen), locate the inlet higher than
the outlet, so that the purge gas will displace air from top to bottom.
Installation Manual 15
Page 16
Purge the sensor case Installation Manual
April 2019MMI-20040393
5. Make sure that there is a tight seal between the inlet connection and sensor case, so
that air cannot be drawn by suction into the case or purge line during the purging
process.
6. Run purge gas through the sensor.
The purge time is the amount of time required for full exchange of atmosphere to
inert gas. The larger the line size, the greater amount of time is required to purge
the case. If purge lines are being used, increase the purge time to fill the additional
volume of the purge line.
Note
Keep the purge gas pressure below 7.25 psi (0.5 bar).
7. At the appropriate time, shut off the gas supply, then immediately seal the purge
outlet and inlet connections with the purge plugs.
Avoid pressurizing the sensor case. If pressure inside the case elevates above
atmospheric pressure during operation, the flowmeter density calibration will be
inaccurate.
8. Make sure that the purge fitting seals are tight so that air cannot be drawn by
suction into the sensor case.
16Micro Motion TA Series
Page 17
Installation Manual
MMI-20040393April 2019
Installation Manual 17
Page 18
*MMI-20040393*
MMI-20040393
Rev. AD
2019
Micro Motion Inc. USA
Worldwide Headquarters
7070 Winchester Circle
Boulder, Colorado USA 80301
T +1 303-527-5200
T +1 800-522-6277
F +1 303-530-8459
www.emerson.com
Micro Motion Asia
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
Republic of Singapore
T +65 6363-7766
F +65 6770-8003
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE,
ProLink, MVD and MVD Direct Connect marks are marks of one of the Emerson Automation
Solutions family of companies. All other marks are property of their respective owners.
Micro Motion Europe
Emerson Automation Solutions
Neonstraat 1
6718 WX Ede
The Netherlands
T +31 (0) 70 413 6666
F +31 (0) 318 495 556
www.micromotion.nl
Micro Motion United Kingdom
Emerson Automation Solutions
Emerson Process Management Limited
Horsfield Way
Bredbury Industrial Estate
Stockport SK6 2SU U.K.
T +44 0870 240 1978
F +44 0800 966 181
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.