Operation and Maintenance Manual–250-1100kVA, 60Hz, Three Phase Single-Module & Multi-Module
™
Page 2
BATTERY CABINET PRECAUTIONS
!
The following warning applies to all battery cabinets supplied with UPS systems. Additional warnings and cautions applicable to battery cabinets may be found in Important Safety Instructions on
page -1 and 4.4 - Battery Maintenance.
WARNING
Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet
(after initial installation).
• Do not tilt.
Failure to heed this warning could result in smoke, fire or electric hazard.
Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
For systems using DC sources other than batteries, refer to the manufacturers's
recommendations for handling and care.
Contacting Emerson Network Power® for Support
Contact Emerson Network Power Liebert® Services for information or repair service in the United
States at 1-800-LIEBERT (1-800-543-2378).
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services,
if available in your area. For areas not covered by Liebert Services, the authorized distributor is
responsible for providing qualified, factory-authorized service.
Have the following information available before calling Liebert Services:
Part Numbers: ________________________________________________________________
Serial Numbers: _______________________________________________________________
kVA Rating: __________________________________________________________________
Date Purchased: _______________________________________________________________
Date Installed: ________________________________________________________________
This manual contains important instructions that should be followed during installation and
maintenance of your Liebert NXL UPS and DC source.
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel. Refer to separate installation manual for equipment handling information and
installation procedures.
Follow all DC source safety precautions in 4.0 - Maintenance when installing, charging or
servicing DC sources. In addition to the hazard of electric shock, gas produced by batteries
can be explosive and sulfuric acid can cause severe burns.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in electrical fire fighting.
Extreme caution is required when performing maintenance. Service and maintenance work
must be performed only by properly trained and qualified personnel and in accordance with
applicable regulations as well as with manufacturers’ specifications.
Be constantly aware that the UPS system contains high DC as well as AC voltages. With
input power off and the DC source disconnected, high voltage at filter capacitors and power
circuits should be discharged within 5 minutes. However, if a power circuit failure has
occurred, assume that high voltage still exists after shutdown. Check with a voltmeter before
making contact.
AC voltage will remain on the system bypass, the UPS output terminals and the static bypass
switch, unless associated external circuit breakers are opened.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the UPS system is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the UPS chassis frame by using rubber
mats.
Some components within the cabinets are not connected to the chassis ground. Any contact
between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the
test instrument exterior does not make contact, either physically or electrically, with earth
ground.
Important Safety Instructions
This equipment contains circuitry that is energized with high voltage. Only test equipment
designated for troubleshooting should be used. This is particularly true for oscilloscopes. Always
check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when
the power is turned Off, dangerously high voltage may exist at the capacitor banks.
Observe all DC source precautions when near the DC source for any reason.
ONLY properly trained and qualified service personnel should perform maintenance on
the UPS system. When performing maintenance on any part of the equipment under power, service
personnel and test equipment should be standing on rubber mats. The service personnel should wear
insulating shoes for isolation from direct contact with the floor (earth ground).
One person should never work alone. A second person should be standing by to assist and summon
help in case an accident should occur. This is particularly true when work is performed on the DC
source.
1Liebert
®
NXL
™
Page 10
1.0INTRODUCTION
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
1.1General Description
The Liebert NXL UPS provides continuous, high-quality AC power to your business-critical
equipment, such as telecommunications and data processing equipment. The Liebert NXL UPS
supplies power that is free of the disturbances and variations in voltage and frequency common to
utility power, which is subject to brownouts, blackouts, surges and sags.
The Liebert NXL utilizes the latest in high-frequency, double-conversion pulse-width modulation
technology and fully digital controls to enhance its reliability and increase the ease of use.
As shown in Figure 1, the AC utility source is input at CB1 and the rectifier converts the AC utility
into DC power. The inverter converts that DC power from the utility—or DC power from the DC
source— into AC power for the load. The DC source will power the load through the inverter in the
event of a power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to the optional maintenance bypass.
Figure 1Typical single module UPS system one-line diagram
Introduction
Liebert® NXL
™
2
Page 11
1.2Modes of Operation
1.2.1Normal Mode
Operating in normal mode, the Liebert NXL’s rectifier derives power from a utility AC source and
supplies regulated DC power to the inverter, which regenerates precise AC power to supply the
connected equipment. The rectifier also uses the utility source power to charge the DC sources.
1.2.2Bypass Mode
When the Liebert NXL is in bypass mode, the load is directly supported by utility power and is
without DC source backup protection.
The Liebert NXL’s inverter and bypass static switch will shift the load from the inverter to bypass
mode without an interruption in AC power if the inverter is synchronous with the bypass and any of
the following occurs:
• Inverter fails
• Inverter overload capacity is exceeded
• Inverter is manually turned off by the user
NOTE
If the inverter is asynchronous with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. This interruption
will be less than 10ms. This interruption time may be altered by modifying the Output transfer
interrupt time setting.
Introduction
1.2.3Battery Mode
When utility AC power fails, the Liebert NXL protects the critical load by instantaneously channeling
DC source power to the inverter, which continues supporting the critical load without interruption.
When utility power returns and is within acceptable limits, the Liebert NXL automatically shifts back
to Normal mode, with the rectifier powering the critical load.
1.2.4Maintenance Bypass
The installation of a Maintenance Bypass Cabinet or Assembly is recommended to allow you to totally
isolate the UPS from all power sources. Use of the Maintenance Bypass is described in 2.0 - Operation.
1.2.5ECO Mode
The ECO Mode feature improves the overall efficiency by powering the critical bus from the bypass
static switch instead of the inverter.
The user has the ability to start/stop ECO Mode manually via HMI or automatically based on time
and day of week schedule entries.
When the critical bus goes out of tolerance (voltage, frequency or slew rate), the BPSS is turned off
and the inverter powers the critical bus.
The inverter is always ready to take the load in the event that the bypass source fails.
1.2.6Intelligent Paralleling
Intelligent Paralleling is intended to increase system efficiency and to reduce the operating hours on
the modules. Intelligent Paralleling will put one or more paralleled modules into standby operation
when the number of redundant modules is above the user-specified threshold, plus some hysteresis.
®
3Liebert
NXL
™
Page 12
1.3Options
A number of options are available from Liebert for your UPS system. (Some options are not available
for all ratings.) Described below are the most frequently provided options. Other options are
available. Contact your Liebert sales representative for more information.
• Battery and Racks—The batteries provide power in the event of a power outage. The Liebert
NXL UPS can use a variety of battery types, provided the battery plant is designed for the
UPS DC voltage range and the load requirements of your application.
• Battery Cabinets—Valve-regulated, lead-acid (VRLA) sealed batteries are available in
matching cabinets for convenient installation and maintenance in otherwise unprotected space.
Depending on the UPS module rating, two or more cabinets may be connected in parallel to
provide the additional run time. This option is required to complete the UPS system.
• Module Battery Disconnect—The UPS system utilizes a separate Module Battery Disconnect
for remotely located batteries. A sensing circuit in the UPS module, set at the battery low voltage
limit, trips the Module Battery Disconnect to safeguard the battery from excessive discharge. The
Module Battery Disconnect has an undervoltage release mechanism designed to ensure that
during any shutdown or failure mode all battery potential is removed from the UPS system.
• Two Breaker Maintenance Bypass—This switchboard provides make-before-break
maintenance bypass. It includes: Maintenance Bypass Breaker (MBB) and Maintenance Isolation
Breaker (MIB).
• Load Bus Synchronization—The Load Bus Sync (LBS) option keeps two or more independent
UPS systems (and therefore their critical load buses) in sync, even when the modules are
operating on DC source or asynchronous AC sources. This means that critical loads connected to
both load buses can switch seamlessly between the two.
• Customer Alarm Interface—This optional interface board allows the input and display of eight
alarms from customer-supplied contacts, each with a customer-selected name.
• Temperature-Compensated Charging—When the battery temperature exceeds a preset limit
(typically 77°F [25°C]), this optional circuit proportionally reduces float charging voltage to
prevent overcharging the battery.
• Battery Load Testing—When activated, this option forces the battery string to assume the load
for a short period of time.
Introduction
Liebert® NXL
™
4
Page 13
2.0OPERATION
The Liebert NXL UPS is equipped with a microprocessor-based display touchscreen designed for
convenient and reliable operation. The display is driven by an easy-to- follow, menu-prompted
software.
2.1Features
The Liebert NXL interface display enables the operator to perform such tasks as:
• Quickly check operational status
• Monitor the power flow through the UPS system and all meter readings
• Execute operational procedures
• Check status reports and history files
• Adjustment programmable parameters (access limited by security access function)
The touchscreen is a white-background display with multicolor text. The display turns on
automatically, but after 15 minutes of inactivity the backlight will go out and the display will appear
very dim. Touching the screen will reactivate the backlight; the backlight will again be active for 15
minutes. If any screen other than the mimic screen is accessed, that screen will be displayed for 5
minutes without any interaction. If there is no activity for 5 minutes, the display will revert to the
basic mimic screen.
Figure 2Main component locations—250 to 400kVA
Operation
HMI Screen
EPO Button
Liebert
IntelliSlot
Housings
Input/Output
Connections
(Behind
Inner Door)
External
Interface
Board
Module Output
Circuit Breaker
(CB2)
5Liebert
Backfeed
Breaker (BFB)
Main Input
Circuit Breaker
(CB1)
®
NXL
™
Page 14
Figure 3Main component locations—500kVA
U40-5C-2000
Rev. 1
Option Box
(6 Slots)
Liebert Intellislot
Housings
Main Input Circuit
Breaker (CB1)
Module Output Circuit
Breaker CB2
Back Feed
Circuit Breaker (BFB)
Input Busbars
Doors and Inner Skins Removed
Front Doors Removed
Keylock or EMO
Button (optional)
Inter-Module
Communication Board
(Behind HMI Screen)
Bypass Busbars
Input Ground
Output
Ground
Output Busbars
DC (-) Input
Ext. Interface Board
HMI Screen
DC (+) Input
Operation
Liebert® NXL
™
6
Page 15
Figure 4Main components, 625kVA Liebert NXL, N+1 multi-module unit without static bypass
Liebert
IntelliSlot
Housings
HMI Screen
Inter-Module
Communication Board
(IMC) (behind door)
EMO Button
(Optional)
Main Input
Circuit Breaker
(CB1)
Module Output
Circuit Breaker
(CB2)
FRONT DOORS REMOVED
LIEBERT
INTELLISLOT
HOUSINGS
MAIN INPUT
CIRCUIT BREAKER
(CB1)
MODULE OUTPUT
CIRCUIT BREAKER
(CB2)
BACKFEED
CIRCUIT BREAKER
(BFB)
KEYLOCK OR
EMO BUTTON
(OPTIONAL)
FRONT DOORS REMOVED
HMI SCREEN
INTER-MODULE
COMMUNICATION
BOARD (LOCATED
BEHIND HMI SCREEN)
Operation
Figure 5Main components, 625kVA Liebert NXL UPS, SMS and 1+N multi-module unit with static bypass
7Liebert
®
NXL
™
Page 16
Figure 6Main component locations—750kVA with Static Bypass
HMI
Screen
Liebert
IntelliSlot
Housings
Main Input
Circuit
Breaker (CB1)
Module Output
Circuit Breaker
(CB2)
Backfeed
Circuit
Breaker (BFB)
Key Lock or
EMO Button
(Optional)
FRONT DOORS REMOVED
Inter-Module
Communication Board
(Behind HMI Screen)
FRONT DOORS REMOVED
Liebert
IntelliSlot
Housings
HMI Screen
Inter-Module
Communication Board
(Behind HMI Screen)
Key Lock or
EMO Button
(Optional)
Main Input
Circuit Breaker
(CB1)
Module Output
Circuit Breaker
(CB2)
Figure 7Main component locations—750kVA without Static Bypass
Operation
Liebert® NXL
™
8
Page 17
Figure 8Main components, 1+N multi-module or SMS with static bypass, 1100kVAw UPS
ABC
L-L000V
L-N000V
I 000A
KVA 000 %
KW000%
PF 0.0 0.0 0.0
KVA/KW0/0
Freq0.0Hz
Rexfer Timeout00:00
MODULE OUT PUT
DC BUS
Bypass
Input
UPS
Input
Power
Battery
Block
Load
Operation
Figure 11 Mimic display
Bypass Input—Displays the bypass input voltage and the bypass input frequency. The bypass
circuit breaker (BFB) is to the right of this block. The circuit breaker status is shown as open or
closed.
NOTE
This Bypass Input information does not apply to N+1 Multi-Module systems
UPS Input Power—Displays the UPS input voltage, current and frequency. The input circuit
breaker (CB1) is to the right of this block. The circuit breaker status is shown as open or closed.
Battery Block—Displays the DC source voltage and the charge or discharge current to or from the
DC source. Pressing this icon switches among the connected DC sources. The Module Battery
Disconnect (MBD) is to the right of this block. The circuit breaker status is shown as open or closed.
DC Bus—Displays the DC Bus voltage and the state of the charger.
Load—Displays the output line voltage, phase voltage, current, kVA, kW, power factor and
frequency. The critical load current per phase is also displayed in this block. During an overload, the
time remaining before transfer is displayed at the bottom of the load box. After an overload transfer,
retransfer timeout is displayed at the bottom of the load box.
11Liebert® NXL
™
Page 20
Figure 12 Monitor/mimic display example: Normal power flow
Green – Normal
Orange – Marginal
Gray – Absent
Black – Unknown
Green – Normal
Orange – Marginal
Gray – Absent
Black – Unknown
Figure 14 Monitor/mimic display example: load on bypass, UPS On
Green – Normal
Orange – Marginal
Gray – Absent
Black – Unknown
Green – Normal
Orange – Marginal
Gray – Absent
Black – Unknown
Operation
Figure 15 Monitor/mimic display example: load on bypass, UPS module Off
13Liebert® NXL
™
Page 22
2.2Touchscreen Navigation
2.2.1Main Display Screen
Several menu items can be accessed from the main display screen (see Figure 10). These menu items
are detailed in subsequent sections.
2.2.2Configurations Menu
Rating
This menu item will display a popup showing the following parameters (see Figure 16). These
parameters are entered during commissioning when the UPS is installed.
• Nominal Input Voltage• Unit Model
• Nominal Bypass Voltage• Unit Serial
• Nominal Output Voltage• Maintenance Bypass Model
• Nominal Source Frequency• Maintenance Bypass Serial
• Nominal Output Frequency• Battery Cabinet Model
• Nominal Cell Count• Battery Cabinet Serial
• Output kVA• Order Number 1
• Output KW• Order Number 2
• Configuration Type• Service Telephone Number
• Rectifier Type• Site ID Number
• Input Isolation Transformer• Tag Number
Operation
Figure 16 Rating Parameters
Liebert® NXL
™
14
Page 23
User Settings
System Settings
These display settings can be changed from the touchscreen. Press the box to the left of each
parameter to bring a popup window that will allow the parameter to be changed.
• Backlight Brightness—High or Low (default: Low)
• Time (24hr format)—Adjust Hour, Minute or Seconds
• Date (MM DD, YYYY format)—Adjust Month, Day or Year
• Password – Reset the password (4 characters, alphanumeric, case-sensitive)
These warning and alarm settings can be changed from the touchscreen. Press the box to the left of
each parameter to bring a popup window that will allow the parameter to be changed.
Max Load Alarm
The module will activate a warning when the load is above any of these settings:
• Phase A (%)—10% to 105% (default: 100%)
• Phase B (%)—10% to 105% (default: 100%)
• Phase C (%)—10% to 105% (default: 100%)
• Delay (second)—0 to 60 (default: 5 seconds)
Manual Xfer Bypass Voltage Limits
These set the upper and lower limits that the bypass voltage must be within for a manual transfer to
bypass to be performed.
• Manual Xfer Bypass Voltage Low Limit (%)—1% to 20% (default: 5%)
• Manual Xfer Bypass Voltage High Limit (%)—1% to 15% (default: 5%)
Inlet Air Temp Warning
• Inlet Air Temp Warning—30°C to 40°C (default: 35°C)
NOTE
Temperature will display in both Celsius and Fahrenheit.
Figure 18 Adjustable setpoints parameters
Liebert® NXL
™
16
Page 25
Battery Management
These DC source settings can be changed from the touchscreen. Press the box to the left of each
parameter to bring a popup window that will allow the parameter to be changed.
Battery Equalize
When Battery Equalize is activated (Manual Battery Equalize button under Batt Mgt), the module
will charge the batteries to the Equalize Voltage for the length of Equalized Time.
• Equalize Voltage, Vpc - 2.30 to 2.45 (default: 2.3)
• Equalize Time, hours - 0 to 200hours (default: 0)
NOTE
Battery Equalize must be enabled by service to be functional. If Battery Equalize is disabled,
the feature will not be available and the menu item will not be displayed.
Figure 19 Battery Equalize settings
Operation
Battery Test
• Auto Test—Enable/Disable (default: disabled)
• Test Cycle, weeks—1 to 26 (default: 13 weeks)
• Time of day, hh:mm—Set Hour and Minute; sets the start time of the automatic battery test
• Start Date, mm dd, yyyyy—Set Month, Day and Year
• Test Duration, minutes—0.5 minute to 30% of full load Operating Time (default: 0.5 minute)
• Minimum Battery Voltage, lead-acid only—1.75VPC to 1.95VPC (default: 1.75VPC); this is the
minimum voltage the battery test will stop.
Low Battery Warning Time
• Low Battery Warning Time, minutes—2 to 60, the upper limit is dependent on configured
batteries (default: 5 minutes)
Battery Temperature
• Battery Temp Warning—30°C to 50°C (default: 40°C)
• Battery Temp Limit—35°C to 60°C (default: 50°C)
• Disconnect—Enable/Disable (default: disabled)
NOTE
If Disconnect is set to Enable and the Battery Temp Limit is met, the Battery breaker will open.
• Battery Float Voltage, Vpc—2.15 to 2.3 (default: 2.25)
Liebert® NXL
™
18
Page 27
2.3Event Management
This menu item permits changing how the Liebert NXL handles Alarms, Faults and Status
information. Each event can be configured for the following:
• Latch (yes/no)—Event stays active in the event window, even if the fault condition has been
cleared, until user acknowledges it by pressing the “Reset” button.
• Audible (yes/no)—Will set Audible alarm when event occurs
• Event log (yes/no)—Will display event in Event log when it occurs
NOTE
You must press “Save” for changes to take effect.
See Table 10 for a list of alarms, fault and status messages.
Figure 21 Typical Event Management Parameters
Operation
2.4Status Reports Menu
This menu accesses the events records.
• Event Log—Up to 2048 time/date stamped events are captured in the log. The oldest record will
be overwritten with a new record once the buffer reaches 2048 events.
• System Status
• Total Operating Hours—Total number hours the UPS has been operational
• Service Reminders—Displays when service is recommended for Air Filter, AC Filter, DC Filter,
and Fan. Also shows when the Warranty and/or Maintenance Agreement will expire.
NOTE
The recommended service time is based on typical life expectancy of those components. These
components may need serviced earlier. Talk to your Liebert service representative for more
details.
19Liebert® NXL
™
Page 28
2.5Startup Menu
This menu is used to start the UPS and individual devices.
Manual—This will begin the UPS startup. See 2.15 - Manual Operations—All Systems for
details.
Devices
• Close Trap—This will start the Input filter, if installed
• Close MBD/BCB—If the MBD is motor-operated, the Close command will enable and energize the
motor to close. If the MBD is not motorized, the Close command will enable the breaker UVR. The
MBD/BCB must be closed manually. If no MBD is selected, this setting is not displayed.
2.6Shutdown Menu
This menu permits shutting down the UPS and individual devices. See 2.15 - Manual Operations—
All Systems for details.
Open Trap—Open the input trap filter
Open MBD/BCB—Opens the associated MBD or BCB breaker
UPS—Turns off inverter, rectifier and trips all DC source breakers. Transfers to bypass, if available.
NOTE
The following popup window is displayed when the UPS is about to be shut down. To shut
down the UPS, an operator must press OK.
Operation
Figure 22 UPS shutdown popup
System—Turns off inverter, rectifier and trips all DC source breakers. Will shut down UPS
completely.
NOTICE
Risk of equipment damage. This command will result in the load being shut down.
The following popup window is displayed when the UPS is about to be shut down. To shut down the
UPS, an operator must press OK.
Figure 23 System shutdown popup
2.7Transfer Menu
This menu permits switching between UPS and Bypass mode. A graph in the multipurpose window
shows if the UPS is in synch with the bypass. If the UPS and bypass are in synch, pressing Bypass
will switch the UPS to Bypass mode. Pressing UPS will switch back to Normal (Inverter) Mode (see
Figure 2.8). See 2.15 - Manual Operations—All Systems for details.
Liebert® NXL
NOTE
If the bypass and UPS are out of synch range, the transfer buttons will be disabled.
™
20
Page 29
2.8Battery Management Menu
This menu permits configuring DC source settings.
Time Remaining Graph—Displays the time remaining graph in the multipurpose window; plot the
DC source voltage against elapsed time during a Battery Discharge Cycle (see Figure 24). The
bottom black line is voltage when the module has reach End of Discharge. This line is programmed
during commissioning.
Figure 24 Time remaining display
Operation
21Liebert® NXL
™
Page 30
Manual Battery Test—Start/Stop
Manual Battery Equalize—Start/Stop; must be enabled by Emerson Network Power Liebert
Services to be active
Battery Cycle Monitor—Displays how many discharges have occurred for these time periods:
0-30sec, 31-90sec, 91-240sec, 4-15min, 15-30min, 30-60min, 60-240min, 4-8hr, 8hr and up. Each
discharge record will include: (see Figure 25)
•#•Max KW
•Date•AH
• Time• Start Temp °C
• Duration• End Temp °C
•Start kW•Battery CB Start
•Min kW•Battery CB End
Figure 25 Battery cycle monitor
Operation
Display summary (see Figure 26)
• Battery Commission Date/Time
• Last Battery Discharge Date/Time
• Active Battery Discharge Time
• Active Battery Amp Hours
• Active Battery KW
• Total Number of Discharges
Liebert® NXL
™
22
Page 31
Figure 26 Battery cycle monitor summary
Operation
2.9System View—1+N Systems Only
System View will display the status of each of the system breakers (MOB’s, MIB, MBB). It will
display the system output information including, voltage, current, kVA/kW, frequency and number of
redundant modules in the system.
Figure 27 Status View - 1+N systems only
23Liebert® NXL
™
Page 32
This button will show the following status of each module in the system:
•Comms
• Normal—UPS intermodule communication is working properly
• Failed—UPS intermodule communication is not working properly
•Events
• None—UPS has no active events
• Alarms—UPS has an Alarm
• Fault—UPS has Fault
•Inverter Ready
• NO—UPS Inverter is off
• Yes—UPS Inverter is ready to take load
• Output Volts
• Normal (UPS Output voltage is OK)
• Marginal (UPS Output Voltage is not OK)
• Fail (UPS Output voltage is outside of range)
• Output State
• Normal (UPS is in Normal Mode)
• Off (UPS Inverter is off)
Figure 28 1+N status view
Operation
2.10Metering
This button will place the metering tables in the multipurpose window.
2.11Help
This button will display the help menu.
2.12Reset
This button will reset any non-active latched events.
Liebert® NXL
™
24
Page 33
2.13Silence
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
This button will silence the audible alarm.
2.14Modes of Operation
This section illustrates the flow of power through circuit breakers, switches and UPS components
during various modes of operation. The same modes of operation apply to all configurations of the
Liebert NXL. Highlighted (thick) lines in the diagrams indicate power flow and power availability.
These illustrations do not show an alternate power source (generator) and automatic transfer switch
(external to the UPS) that might be present at your installation.
2.14.1 Load on Bypass
Load on Bypass, with the UPS not available, is shown in Figure 29. The UPS system could be in this
mode of operation during either initial startup or UPS system shutdown and isolation for
maintenance.
NOTE
The bypass modes of operation do not apply to N+1 multi-module systems.
NOTICE
Risk of equipment damage. When the critical load is being supplied power from the bypass
line, it is exposed to utility failure and fluctuations.
Figure 29 Load on bypass (UPS not available)
Operation
25Liebert® NXL
™
Page 34
2.14.2 OK to Transfer
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
The OK to Transfer status message will be displayed when the bypass line and UPS output power are
both available, their voltage, frequency and phase synchronization are matched within specifications,
and the Static Switch Disconnects are closed (ON). An alarm message may be displayed to indicate
Load On Bypass (Figure 30). If no alarm is displayed, the operating status is Load On UPS
(Figure 31).
When the OK to Transfer message is displayed, the load can be manually transferred from the UPS to
bypass or the load can be manually retransferred from the bypass to the UPS.
To perform a manual transfer, Use the Load Transfer Procedures screen. Refer to 2.15.4 - Load Transfer and Retransfer—Single Module System.
The UPS control logic will initiate an automatic transfer to bypass if an overload condition exceeds
the system current versus time window or if a UPS fault is detected. The control logic may initiate an
automatic retransfer to the UPS system when the system is recovering from overloads lasting less
than five minutes. Refer to 2.16 - Automatic Operations.
Figure 30 Load on bypass, UPS available
Operation
Figure 31 Load on UPS, bypass available
Liebert® NXL
™
26
Page 35
2.14.3 Input Power Failure—Load on DC Source
!
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
Bypass
Input
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
If the utility AC power source fails or is outside the acceptable range, the DC source becomes the
power source for the UPS module inverters. The UPS continues to supply power to the critical load
and also to the UPS controls.
Use the Battery Time screen at the UPS modules to monitor the present DC source voltage compared
to the shutdown value. The time the DC source can sustain the load depends on the size of the load
and the size and condition of the DC source.
Alarm messages that indicate DC source status are Battery Discharge, Low Battery and Battery
Shutdown. The voltage limits for these alarms are displayed on the UPS module Alarm Limit
Settings screen. These limits were selected for your installation by Liebert Services during initial
startup. The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge
and the current in amperes.
Figure 32 Input power fail, load on DC source
Operation
2.14.4 Off DC Source
The DC source can be disconnected from the UPS, if required for maintenance, by opening the module
battery disconnect (MBD) circuit breaker. In this situation the UPS module will continue to supply
conditioned power to the critical load, but if input power fails the UPS system cannot supply power to
the load.
CAUTION
When the UPS system is operating with the module battery disconnect (MBD) circuit
breaker(s) open, the critical load is not protected from loss of the utility source power.
Figure 33 Load on UPS, DC source not available
27Liebert® NXL
™
Page 36
2.14.5 Emergency Module Off (Optional)
Bypass
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
Input
Bypass
DC Source
DC Bus
Module
Output
BFB
CB2CB1
MBD
Input
The Emergency Module Off (EMO) mode will transfer the critical load to the bypass line and remove
power from all UPS module components except the controls, bypass circuit breaker and the static
switch.
If installed, the Emergency Module Off control is a guarded pad next to the display touchscreen
(Figures 2, 6 and 7).
Lift the cover and press the pad. The load will be transferred to bypass, and the DC source (MBD),
input and output circuit breakers will be opened (tripped). Refer to 2.15.13 - Shutdown—Single Module UPS System.
Figure 34 Emergency modules off
Operation
2.14.6 Remote Emergency Power Off
The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS
system. It usually is installed in the same room as the critical load equipment. This mode can also be
initiated by an automatic contact closure in the same external circuit as the manually operated
switch.
When the Remote Emergency Power Off switch is operated, all UPS circuit breakers are opened,
including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,
the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS
controls. Refer to 2.15.13 - Shutdown—Single Module UPS System.
Figure 35 Remote emergency power off
Liebert® NXL
™
28
Page 37
2.14.7 ECO Mode
Bypass
Input
DC Source
BFB
CB2CB1
MBD
Module
Output
DC Bus
When ECO Mode is active, the critical load is supported by the bypass source. The rectifier is On and
providing power to the DC source for charging. The inverter is on standby, available to provide power
to the critical load if a fault occurs on the bypass line. See Figure 26.
Figure 36 ECO Mode power flow
2.15Manual Operations—All Systems
The Liebert NXL UPS is designed to function while unattended by an operator. The system control
logic automatically handles many important functions, as explained in 2.16 - Automatic Operations. Other procedures must be performed manually.
Manual procedures available to the operator include startup, load transfers and shutdowns. These
procedures are performed by using the touchscreen and some manually operated circuit breakers and
switches.
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
• Startup—including initial startup, recovering from input power failure, recovering from DC
source shutdown and recovering from shutdowns for emergencies or maintenance.
• Load Transfers—including transfers from UPS to bypass and retransfers from bypass to the
UPS system.
• Maintenance Bypass Load Transfers—including transfers from internal bypass to
maintenance bypass and transfers from maintenance bypass to internal bypass.
• Shutdowns—including module shutdowns for maintenance and emergency shutdowns.
Operation
NOTE
The following procedure assumes that the UPS installation inspection and initial startup have
been performed by Liebert Services. A Liebert-authorized representative must perform the
initial system startup to ensure proper system operation.
29Liebert® NXL
™
Page 38
2.15.1 Startup—Single Module System
!
!
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure provides power to the critical load distribution system. Verify that
the critical load distribution is ready to accept power. Make sure that personnel and
equipment are ready for the critical load distribution system to be energized.
If the installation includes a Maintenance Bypass, power may already be supplied to the critical load
equipment through the Maintenance Bypass. If there is no power to the critical load, apply power
through the UPS bypass line per the following procedure.
During startup, power is supplied to the critical load through the UPS (internal) bypass line while the
UPS system is being energized. Depending on the reason for the UPS system shutdown, power may
be present in the bypass line. To determine this, check the Monitor/Mimic Display screen after control
power is available.
NOTE
If the system was shut down in response to an “Emergency Off”, there may be alarm messages
on the touchscreen that describe system conditions before (or at the time of) the shutdown.
Some or all of the alarm conditions may have been resolved. To clear these alarm messages,
turn Off control power (see Figures 2, 6 and 7). Wait at least 10 minutes for the control power
circuitry to completely de-energize. After 10 minutes, turn control power back On.
Operation
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
If the UPS has been shut down for maintenance, verify that all of the UPS system doors are
closed and latched. All test equipment must be removed from the system. All electrical
connections must be secure.
1. Before applying power to the UPS modules, determine the position of the following circuit
breakers and switches:
• Input Circuit Breaker (CB1)—Verify that this breaker on the front of the UPS cabinet
(Figures 2, 6 and 7) is in the open position.
• Module Battery Disconnect (MBD)—Verify that this external breaker is open or tripped.
If DC source cabinets are used, verify that breakers on all the cabinets are open.
• Bypass Circuit Breaker (BFB)—This circuit breaker (Figures 2, 6 and 7) should be open.
NOTE
If power to the critical load is already supplied through this breaker, keep this breaker closed.
• Output Circuit Breaker (CB2)—This motorized circuit breaker (Figures 2, 6 and 7)
should be open.
2. Provide power to the UPS controls of all UPS modules starting up to permit the display
touchscreen and system logic to function properly.
a. Close the Bypass Input Breaker (BIB). This breaker is external to the UPS; it may be in the
Maintenance Bypass Cabinet. The display touchscreen should start.
b. Close the Rectifier Feed Breaker (RFB). This breaker is external to the UPS; it may be in the
Maintenance Bypass Cabinet.
3. Start the module:
a. Press the “Start-Up” then “Manual Start” menu buttons (see Figure 37). The message “Close
BFB” will appear in the multipurpose window.
b. Close the BFB breaker (see Figures 2, 6 and 7). The message “Press OK to issue BPSS On
Command” will appear.
Liebert® NXL
™
30
Page 39
Operation
!
c.Press OK to continue. This will energize the load on the UPS internal bypass. The message
“Close CB1” will appear.
d. Close CB1 (see Figures 2, 6 and 7). The “Press OK to Issue Rectifier On Command” message
will appear.
e.Press “OK.” This will start the UPS’s rectifier. Load is still on internal bypass. The message
“Press OK to Issue Inverter On Command” will appear.
f.Press “OK.” The rectifier will be On and the Inverter will be on standby. Load is still on
internal bypass. The message “Press OK to Issue MBD Enable Command” will appear.
g. Press “OK.”
h. Close all battery/DC breakers. The UPS will stay in this mode until all breakers are closed.
If the DC sources are not ready to be started up, skip this command. The DC breakers can be
closed individually from the startup command at a later time (see 2.5 - Startup Menu).
NOTE
The DC source charge current may increase quickly, but should slowly decrease. If the system
is recovering from a DC source shutdown or an input power failure, the UPS rectifier will be
recharging the DC source. Recharge current can be more than 100A. The maximum allowable
recharge current for any unit depends on the kVA rating and the DC source recharge current
limit.
The message “Press OK to Issue Transfer Command” will appear.
i.Press “OK.” The load is now energized from the UPS inverter.
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is required.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery
manufacturer’s manual, available on the manufacturer’s Web site, for specific information
about equalize charging.
Figure 37 Startup commands
31Liebert® NXL
™
Page 40
2.15.2 Startup—N+1 System
!
!
The following instructions will start an individual UPS module. Repeat these steps for all the UPS
units in the system that will be started.
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
If the UPS has been shut down for maintenance, verify that all of the UPS system doors are
closed and latched. All test equipment must be removed from the system. All electrical
connections must be secure
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure may provide power (with DC source available) to the critical load
distribution system. Verify that the critical load distribution is ready to accept power. Ensure
that personnel and equipment are ready for the critical load distribution system to be energized.
NOTICE
Risk of improper startup. May cause equipment damage.
These steps should be performed after the SCC startup has been initialized.
Operation
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is needed.
NOTE
If the system was shut down in response to an “Emergency Off,” there may be alarm messages
on the touchscreen that describe system conditions before or at the time of the shutdown. Some
or all of the alarm conditions may have been resolved.
To clear these alarm messages, turn Off control power (see Figure 6). Wait at least 10 minutes
for the control power circuitry to completely de-energize. After 10 minutes, turn control power
back On.
1. Before applying power to the UPS modules, determine the position of the following circuit
breakers and switches:
• Input Circuit Breaker (CB1)—Verify that this breaker on the front of the UPS cabinet
(Figure 6) is in the open position.
• Module Battery Disconnect (MBD)—Verify that this external breaker is open or tripped. If
DC source cabinets are used, verify that breakers on all the cabinets are open.
• Output Circuit Breaker (CB2)—This motorized circuit breaker (Figure 6) should be open.
• Module Output Breaker (MOB) Optional—This circuit breaker should be open. This breaker is
external to UPS, possibly in the paralleling gear.
2. Close the Rectifier Feed Breaker (RFB). This breaker is external to UPS, possibly in the
paralleling gear. The display touchscreen should start.
3. Close the MOB breaker, if present on the system.
4. Press the “Start-Up,” then the “Manual Start” menu button (see Figure 37). The “Close CB1”
message will appear.
5. Close CB1 (see Figure 6). The “Press OK to Issue Rectifier On Command” message will appear.
6. Press “OK.” This will start the UPS’ rectifier. The message “Press OK to Issue Inverter On
Command” will appear.
7. Press “OK.” The rectifier will be On and the Inverter will be on standby. The message “Press OK
to Issue MBD Enable Command” will appear.
8. Press “OK.”
Liebert® NXL
™
32
Page 41
9. Close all Battery/DC breakers associated with this module. The UPS will stay in this mode until
!
!
all breakers are closed.
Skip this command if the DC sources are not ready to be started. The DC breakers can be closed
later from the startup command (see 2.5 - Startup Menu).
.
NOTE
The DC source charge current may increase quickly, but should slowly decrease. If the system is
recovering from a DC source shutdown or an input power failure, the UPS rectifier will be
recharging the battery. Recharge current can be more than 100A. The maximum allowable
recharge current for a unit depends on the kVA rating and the DC source recharge current limit.
The UPS is ready to be placed online. Go to the SCC Startup screen to complete the startup.
2.15.3 Startup—1+N System
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
If the UPS has been shut down for maintenance, verify that all of the UPS system doors are
closed and latched. All test equipment must be removed from the system. All electrical
connections must be secure.
Operation
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure may provide power to the critical load distribution system. Verify
that the critical load distribution is ready to accept power. Make sure that personnel and
equipment are ready for the critical load distribution system to be energized.
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is needed.
NOTE
If the system was shut down in response to an “Emergency Off,” there may be alarm messages
on the touchscreen that describe system conditions before or at the time of the shutdown. Some
or all of the alarm conditions may have been resolved.
To clear these alarm messages, turn Off control power (see Figures 2, 6 and 7). Wait at least
10 minutes for the control power circuitry to completely de-energize. After 10 minutes, turn
control power back On.
33Liebert® NXL
™
Page 42
Operation
Start buttons
on touchscreen
for 1+N systems
Startup—1+N System with External Maintenance Bypass
1. Before applying power to the UPS modules, determine the position of the following circuit
breakers and switches:
• Input Circuit Breaker (CB1)—Verify that this breaker on the front of the UPS cabinet is in the
open position (see Figures 2and 6for the location).
• Module Battery Disconnect (MBD)—Verify that this external breaker is open or tripped. If
DC source cabinets are used, verify that breakers on all the cabinets are open.
• Output Circuit Breaker (CB2)—This motorized circuit breaker should be open (see Figures 2
and 6).
• Bypass Circuit Breaker (BFB)—This circuit breaker should be open (see Figures 2and 6for
the location).
• Module Output Breaker (MOB) optional—This circuit breaker should be open. This breaker is
located external to UPS, possibly in the paralleling gear.
• Maintenance Bypass Breaker (MBB) optional—This circuit breaker should be open. This
breaker is external to UPS, possibly in the paralleling gear.
NOTE
If power to the critical load is already supplied through this breaker, keep this breaker closed.
• Maintenance Isolation Breaker (MIB) optional—This circuit breaker should be open. This
breaker is external to UPS, possibly in the paralleling gear.
a. Close the Bypass Input Breaker (BIB). These breakers are external to the UPS units, possibly
in the Maintenance Bypass Cabinet. The display touchscreens should start.
b. Close the Rectifier Feed Breaker (RFB. These breakers are external to the UPS units,
possibly in the Maintenance Bypass Cabinet.
2. On the first module, press “Start-up” then “Manual Start,” then the “All Modules” menu buttons
(see Figure 38).
Figure 38 1+N system start menu commands
Liebert® NXL
™
34
Page 43
Operation
3. If the system has optional Bypass breakers (MBB/MIB), the message “Close MBB” will appear in
the multipurpose window.
a. Close the MBB breaker. The message “Press OK to begin startup of this module” will appear.
b. Press “OK” to continue. This will begin the startup procedure for the UPS module.
The message “Close BFB” will appear in the multipurpose window.
4. Close the BFB breaker (see Figures 2and 6). The message “Press OK to issue BPSS On
Command” will appear.
5. Press “OK” to continue. This will energize the UPS internal bypass. The message “Close CB1” will
appear.
6. Close CB1 (see Figures 2and 6). The message “Press OK to Issue Rectifier On Command” will
appear.
7. Press “OK.” This will start the UPS’ rectifier. The message “Press OK to Issue Inverter On
Command” will appear.
8. Press “OK.” The rectifier will be On and the Inverter will be on standby. The message “Press OK
to Issue MBD Enable Command” will appear.
9. Press “OK.”
10. Close all battery/DC breakers. The UPS will stay in this mode until all breakers are closed.
Skip this command if the DC sources are not ready to be started. The DC breakers can be closed
later individually from the startup command (see 2.5 - Startup Menu).
NOTE
The DC source charge current may increase quickly, but then should slowly decrease. If the
system is recovering from a DC source shutdown or an input power failure, the UPS rectifier
will be recharging the DC source. Recharge current can be more than 100A. The maximum
allowable recharge current for a unit depends on the kVA rating and the DC source recharge
current limit.
This message will appear: “Close the MOB’s of this module and enough of the other modules, then
press ‘OK’ [x of y MOB’s closed].”
11. Close the MOB’s for the UPS’s in the system being started. The [x of y MOBs closed] will update
as the MOBs are closed (“x” is number of MOBs closed and “y” is number of MOBs in the system).
This message will appear: “Start enough other modules to support the total system load, then
press ‘OK’ [x of y inverters started].”
12. At each module, Press “Start-up,” then “Manual Start,” then “This Module” menu buttons (see
Figure 38).
a. Perform Steps 6through 9 on the rest of the UPS units in the system ready to be placed on-
line.
b. The [x of y inverters started] will update as inverters are brought to standby (“x” is the
number of inverters on standby and “y” is the number of inverters in the system).
NOTE
Do not transfer the module from the transfer screen from any of these modules.
13. Go to the first UPS and press “OK.” The message “Close MIB” will appear in the multipurpose
window.
14. Close the MIB breaker. The message “Open MBB” will appear in the multipurpose window.
15. Open the MBB breaker. The message “Press OK to transfer all modules to inverters” will appear.
16. Press “OK.”
This will put the system online and the load on the UPS.
35Liebert® NXL
™
Page 44
Operation
Startup—1+N System Without External Maintenance Bypass
1. Before applying power to the UPS modules, determine the position of the following circuit
breakers and switches:
• Input Circuit Breaker (CB1)—Verify that this breaker on the front of the UPS cabinet is in the
open position (see Figures 2and 6for the location).
• Module Battery Disconnect (MBD)—Verify that this external breaker is open or tripped. If
DC source cabinets are used, verify that breakers on all the cabinets are open.
• Output Circuit Breaker (CB2)—This motorized circuit breaker should be open (see Figures 2
and 6for the location).
• Bypass Circuit Breaker (BFB)—This circuit breaker should be open (see Figures 2and 6for
the location).
• Module Output Breaker (MOB) Optional—This circuit breaker should be open. This breaker is
external to UPS, possibly in the paralleling gear.
2. Provide power to the UPS controls of all UPS modules starting up to permit the display
touchscreen and system logic to function properly.
a. Close the Bypass Input Breaker (BIB). These breakers are external to each UPS, possibly in
the Maintenance Bypass Cabinet. The display touchscreens should start.
b. Close the Rectifier Feed Breaker (RFB). These breakers are external to each UPS, possibly in
the Maintenance Bypass Cabinet.
3. On the first module, press “Start-up,” then “Manual Start,” then the “All Modules” menu buttons
(see Figure 38). The message “Caution: Starting into an unknown load with less than required
number of modules may result in an Overload” will appear.
4. Press “OK.” The message “Close this Module’s BFB & MOB Breaker” will appear.
5. Close the BFB Breaker and the MOB Breaker connected to this unit. This message will appear:
“Close enough other Modules BFBs & MOBs to support the total system load, then press OK.”
6. Close the BFB breakers and MOB breakers of all the UPS units in the system that are to be
brought online.
7. Press “OK.” This message will appear: “Press OK to turn on all available Bypass Static Switches.”
8. Press “OK.” This will turn On the Bypass Static Switch of the modules with BFB breaker and
MOB breaker closed in Step 5. The message “Press OK to start this module’s UPS” will appear.
9. Press “OK.” The message “Close CB1” will appear.
10. Close CB1 (see Figures 2and 6). The message “Press OK to Issue Rectifier On Command” will
appear.
11. Press “OK.” This will start the UPS’ rectifier. The message “Press OK to Issue Inverter On
Command” will appear.
12. Press “OK.” The rectifier will be On and the inverter will be on standby. The message “Press OK
to Issue MBD Enable Command” will appear.
13. Press “OK.”
14. Close all Battery/DC breakers associated with this module. The UPS will stay in this mode until
all breakers are closed.
Skip this command if the DC sources are not ready to be started. The DC breakers can be closed
individually from the startup command (see 2.5 - Startup Menu) at a later time.
15. At each module, press “Start-up” then “Manual Start,” then “This Module” menu buttons (see
Liebert® NXL
NOTE
The DC source charge current may increase quickly, but then should slowly decrease. If the
system is recovering from a DC source shutdown or an input power failure, the UPS rectifier
will be recharging the DC source. Recharge current can be more than 100A. The maximum
allowable recharge current for a unit depends on the kVA rating and the DC source recharge
current limit.
This message will appear: “Go to other modules and select ‘This Module’ from start-up menu and
start-up that module’s UPS.”
Figure 38).
™
36
Page 45
16. Perform Steps 10 through 14 on the rest of the UPS units in the system ready to be placed on
line. This message will appear: “This Module Startup is complete. Finish the All Module Startup
in process or proceed to the Transfer menu to transfer.”
17. Press “Exit.”
NOTE
Do not transfer the module from the transfer screen from any of these modules.
18. Go to the first UPS and press “OK.” This message will appear: “Press OK to transfer all modules
to inverters.”
19. Press “OK.” This will put the system online and the load on the UPS.
2.15.4 Load Transfer and Retransfer—Single Module System
Changing the load from the UPS system to the UPS bypass is called a transfer. Changing the load
from UPS bypass to the UPS system is called a retransfer. Note that the UPS system control logic can
initiate automatic load transfers and retransfers. Refer to 2.16 - Automatic Operations.
Transfer Procedure
1. Press the “Transfer” menu button on the touchscreen. The Transfer/Retransfer screen will appear
in the multipurpose window (see Figure 2.8).
2. If the UPS output is in synchronization with the bypass, press the “Bypass” button. This will
transfer the load from the UPS to the bypass.
Retransfer Procedure
1. Press the “Transfer” menu button on the touchscreen. The Transfer/Retransfer screen will appear
in the multipurpose window (see 2.8 - Battery Management Menu).
2. If the UPS output is in synchronization with the bypass, press the “UPS” button. This will
transfer the load from Bypass to UPS.
Operation
37Liebert® NXL
™
Page 46
2.15.5 Maintenance Bypass Load Transfers—Single Module System
DC Source
DC Bus
BFB
CB2CB1
MBD
MBB
MIB
MBFB
BIB
RIB
UPS Module
Two Breaker Maintenance Bypass Cabinet
Main Input
Switchgear
Critical
Load
Follow these instructions to manually transfer the load between the Maintenance Bypass and the
UPS bypass line. Do not transfer the load between the Maintenance Bypass and the UPS module
(inverter) output. Use the Monitor/Mimic Display screen to verify that the UPS bypass line is
available.
Figure 39 UPS with two-breaker bypass cabinet
Operation
NOTICE
Risk of equipment damage. Failing to follow the proper sequence when operating any circuit
breaker may cause damage to the connected equipment. Operating a Maintenance Bypass
circuit breaker out of sequence could cut off power to the critical load.
NOTICE
Risk of equipment damage. The UPS system must be on internal bypass before performing
the following procedures and operating the MIB or the MBB, or damage to the UPS may occur
and the critical load may be lost.
Liebert® NXL
™
38
Page 47
Operation
Maintenance Bypass Load Transfers—Single Module System: If Load is on UPS Bypass
1. Transfer the UPS system to bypass (see 2.15.4 - Load Transfer and Retransfer—Single
Module System). The “OK to transfer” lamp on the key-release unit will light.
NOTE
If the maintenance bypass cabinet or switchboard has any other type of custom interlock, follow
the specific instructions for that interlock system to remove the key.
2. If using a key interlock system, depress the key-release unit push button, turn the key and
remove from key-release unit.
NOTE
The UPS system is now locked in bypass and cannot be retransferred to the Inverter until the
key is reinserted.
3. If using a key interlock system, insert the key into the lock for the Maintenance Bypass Breaker
(MBB); retract the bolt.
4. Close the Maintenance Bypass Breaker (MBB).
NOTICE
Risk of improper operation sequence. May cause equipment damage.
Failure to close the Maintenance Bypass Breaker (MBB) will interrupt power to the load.
5. Open the Maintenance Isolation Breaker (MIB). The UPS system is now isolated from the critical
load, and the load is now on Maintenance Bypass.
6. If using a key interlock system, remove the key from the lock for the Maintenance Isolation
Breaker (MIB).
7. If the maintenance bypass cabinet or switchboard has an optional two-key interlock system,
replace the key into the solenoid.
8. If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB).
Maintenance Bypass Load Transfers—Single Module System: If Load is on Maintenance
Bypass
1. Close the Bypass Input Breaker (BIB) or verify that it is closed. Note that the UPS Bypass circuit
breaker (motorized) must also be closed. Refer to 2.15.1 - Startup—Single Module System.
2. If using a key interlock system, depress the key-release unit push button, turn the key and
remove it from the key-release unit.
NOTE
The UPS system is now locked in bypass and cannot be retransferred to the Inverter until the
key is returned.
3. If using a key interlock system, insert the key into the lock for the Maintenance Isolation Breaker
(MIB); retract the bolt.
4. Close the Maintenance Isolation Breaker (MIB).
NOTICE
Risk of improper operation sequence. May cause equipment damage.
Failure to close the Maintenance Isolation Breaker (MIB) will interrupt power to the load.
5. Open the Maintenance Bypass Breaker (MBB). Load is now on UPS Internal Bypass.
6. If using a key interlock system, remove the key from the lock for the Maintenance Bypass Breaker
(MBB) to lock it open.
7. If the maintenance bypass cabinet or switchboard has an optional two-key interlock system,
reinsert the key into the solenoid.
8. The UPS system may now be transferred from bypass to UPS (see 2.15.4 - Load Transfer and Retransfer—Single Module System).
39Liebert® NXL
™
Page 48
2.15.6 Load Transfer—N+1 System: Remove UPS from N+1 System (Collective)
1. Press the “Transfer” menu button on the touchscreen. The Connect/Remove Inverter screen will
appear in the multipurpose window (see Figure 40 - N+1 Transfer menu commands).
2. Press “Remove Inverter” button. This will open CB2.
NOTE
If disengaging this UPS from the system will cause the other UPS units in the system to
overload, then the “Remove Inverter” will not be activated.
Figure 40 N+1 Transfer menu commands
Operation
2.15.7 Load Transfer—N+1 System: Add UPS to N+1 System (Collective)
1. Verify that the UPS is On and the Inverter is in standby mode (see 2.15.2 - Startup—N+1
System).
2. Press the “Transfer” menu button on the touchscreen. The Connect/Remove Inverter screen will
appear in the multipurpose window (see Figure 40 - N+1 Transfer menu commands).
3. Press “Connect Inverter” button. This will close CB2.
NOTE
If the UPS is not synchronized with the other units in the system, then the “Connect Inverter”
button will be disabled.
Liebert® NXL
™
40
Page 49
2.15.8 Load Transfer—1+N System: Remove a UPS from System (Collective)
1. Under the “Transfer” menu button on the touchscreen, press the “This Module” button.
The Transfer/Retransfer screen will appear in the multipurpose window (see Figure 41).
2. If the system has enough capacity to turn Off the unit, press the “Remove Inverter” button. This
will open CB2.
NOTE
If disengaging this UPS from the system will cause the other UPS units in the system to
overload, then the “Remove Inverter” will be disabled.
3. To isolate the UPS from the critical bus, open the MOB breaker. This breaker is external to UPS,
possibly in the paralleling gear.
4. See 2.15.7 - Load Transfer—N+1 System: Add UPS to N+1 System (Collective) to reconnect
the module to the collective.
Figure 41 1+N UPS Transfer to Bypass menu commands
Operation
41Liebert® NXL
™
Page 50
2.15.9 Load Transfer—1+N System: Add a UPS to the System (Collective)
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
1. Provide power to all the UPS controls to permit the display touchscreen and system logic to
function properly.
a. Close the Bypass Input Breaker (BIB). This breaker is external to the UPS, possibly in the
Maintenance Bypass Cabinet. The display touchscreen should startup.
b. Close the Rectifier Feed Breaker (RFB). This breaker is external to the UPS, possibly in the
Maintenance Bypass Cabinet
c.Bypass Circuit Breaker (BFB)—This circuit breaker should be open (see Figures 2and 6for
the location).
d. Optional Module Output Breaker (MOB)—This circuit breaker should be open. This breaker
is external to UPS, possibly in the paralleling gear.
2. Start the UPS and put the Inverter in Standby Mode.
a. Close the MOB breaker associated with this module.
b. Press “Start-up,” then “Manual Start,” then “This Module” menu buttons (see Figure 38).
The “Close BFB” message will appear in the multipurpose window.
c.Close the BFB breaker (see Figures 2and 6). The “Close CB1” message will appear.
d. Close CB1 (see Figures 2and 6). This message will appear: “Press OK to Issue Rectifier On
Command.”
e.Press “OK.” This will start the UPS’ rectifier. The message “Press OK to Issue Inverter On
Command” will appear.
f.Press “OK.” The rectifier will be On and the Inverter will be on standby. The message “Press
OK to Issue MBD Enable Command” will appear.
g. Press “OK.”
h. Close all Battery/DC breakers associated with this module. The UPS will stay in this mode
until all breakers are closed.
Operation
NOTE
Skip this command if the DC sources are not ready to be started. The DC breakers can be closed
individually from the startup command later (see 2.5 - Startup Menu).
This message will appear: “ ‘This Module Startup’ is complete. Proceed to Transfer menu to
connect this Inverter.”
3. Press “Exit.”
4. Under the Transfer menu on the touchscreen, press the “This Module” button. The
Transfer/Retransfer screen will appear in the multipurpose window (see Figure 41.
5. Press the “Connect Inverter” button. This will close CB2.
NOTE
If the UPS is not synchronized with the other units in the system, then the “Connect Inverter”
will be disabled.
Liebert® NXL
™
42
Page 51
Figure 42 1+N UPS Transfer to Inverter menu commands
Operation
43Liebert® NXL
™
Page 52
2.15.10 Load Transfer—1+N System: Transfer System to Bypass
1. Under the “Transfer” menu button on the touchscreen, press the “All Modules” menu button. The
Transfer/Retransfer screen will appear in the multipurpose window (see Figure 43).
2. If the UPS outputs are synchronized with their bypass, press the “1+N Bypass” button. This will
turn On all available static switches and open CB2 in all the modules.
NOTE
If this UPS is not part of the collective, then the “1+N Bypass” will not be activated.
NOTE
The load will now be on Static Bypass in each UPS. It is no longer protected by the UPS.
Figure 43 1+N System Transfer menu commands
Operation
2.15.11 Load Transfer—1+N System: Transfer System to Inverter
1. Verify that all the UPS units are On and the Inverters are in standby mode (See 2.15.3 Startup—1+N System.)
2. Under the “Transfer” menu button on the touchscreen, press the “All Modules” menu button. The
Transfer/Retransfer screen will appear in the multipurpose window (see Figure 41).
3. Press “1+N UPS” button. This will close CB2 and open the Bypass Static Switch in all the
modules.
NOTE
If the UPS is not synchronized with the other units in the system, then the “1+N UPS” will not
be activated.
Liebert® NXL
™
44
Page 53
2.15.12 Load Transfer—1+N System: Transfer to Maintenance Bypass
Follow these instructions to manually transfer the load between Maintenance Bypass and the System
Static Bypass. Do not transfer the load between Maintenance Bypass and the System Inverter output.
Use the Monitor/Mimic Display screen to determine whether the UPS bypass line is available.
Load Transfer—1+N System: Transfer to Maintenance Bypass if Load is on System Static
Bypass
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
1. Transfer the UPS system to bypass (see 2.15.10 - Load Transfer—1+N System: Transfer
System to Bypass). The “OK to transfer” lamp on the key-release unit will light.
NOTE
If the maintenance bypass cabinet or switchboard has any other type of custom interlock, follow
the specific instructions for that interlock system to remove the key.
2. If using a key interlock system, depress the key-release unit push button, turn the key and
remove it from key-release unit.
NOTE
The UPS system is now locked in bypass and cannot be transferred until the key is returned.
3. If using a key interlock system, insert the key into the lock for the Maintenance Bypass Breaker
(MBB); retract the bolt.
4. Close the Maintenance Bypass Breaker (MBB).
Operation
NOTE
Failure to close the Maintenance Bypass Breaker (MBB) will interrupt power to the load.
5. Open the Maintenance Isolation Breaker (MIB). The UPS system is now isolated from the critical
load and the load is now on Maintenance Bypass.
6. If using a key interlock system, remove the key from the lock for the Maintenance Isolation
Breaker (MIB).
7. If the maintenance bypass cabinet or switchboard has an optional, two-key interlock system,
reinsert the key into the solenoid.
8. If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB).
Load Transfer—1+N System: Transfer to UPS if Load is on Maintenance Bypass
1. If the UPS modules are Off, start the system. Refer to 2.15.3 - Startup—1+N System.
2. Place all the UPS units in the system on Static Bypass. Refer to 2.15.10 - Load Transfer—1+N System: Transfer System to Bypass.
3. If using a key interlock system, depress the key-release unit push button, turn the key and
remove from key-release unit.
4. If using a key interlock system, insert the key into the lock for the Maintenance Isolation Breaker
(MIB); retract the bolt.
5. Close the Maintenance Isolation Breaker (MIB).
NOTE
Failure to close the Maintenance Isolation Breaker (MIB) will interrupt power to the load
6. Open the Maintenance Bypass Breaker (MBB). Load is now on UPS System Static Bypass.
7. If using a key interlock system, remove the key from the lock for the Maintenance Bypass Breaker
(MBB) to lock it open.
8. If the maintenance bypass cabinet or switchboard has an optional two-key interlock system,
reinsert the key into the solenoid.
The UPS system can now be transferred from bypass to UPS (see 2.15.11 - Load Transfer—1+N System: Transfer System to Inverter).
45Liebert® NXL
™
Page 54
2.15.13 Shutdown—Single Module UPS System
Perform a Module Shutdown to remove power from a UPS module.
Read all warnings in 4.0 - Maintenance before performing any maintenance on your Liebert NXL
UPS. These warnings and cautions must be observed during any work on the UPS.
NOTE
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations as well as with manufacturers’
specifications.
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
UPS Shutdown
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers.
Transfers to bypass if available
1. Press the “Shutdown” menu button on the touchscreen.
The Shutdown screen will appear in the multipurpose window (see Figure ).
2. Press the “UPS” button. This brings up a warning that pressing “OK” will shut down the UPS
and, if bypass is not available, drop the load (see Figure 22).
3. Press “OK” to shut down the UPS.
Operation
UPS System Shutdown
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers. Will
shut down UPS completely.
1. Press the “Shutdown” menu button on the touchscreen. The Shutdown screen will appear in the
multipurpose window (see Figure ).
2. Press the “System” button. This brings up a warning that pressing “OK” will shut down the UPS
and, if bypass is not available, drop the load (see Figure 22).
3. Press “OK” to shut down the system.
Liebert® NXL
™
46
Page 55
2.15.14 Shutdown—N+1 UPS System
Perform a Module Shutdown Procedure when you want to disconnect power from a UPS module. For
System shutdown, see the SCC operation and maintenance manual, SL-25514, available at the
Liebert Web site: www.liebert.com
Read all warnings in 4.0 - Maintenance before performing any maintenance on a Liebert NXL UPS.
These warnings and cautions must be observed during any work on the UPS.
NOTE
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations as well as with manufacturers’
specifications.
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers.
Transfers load to bypass, if available.
1. Press the “Shutdown” menu button on the touchscreen. The Shutdown screen will appear in the
multipurpose window (see Figure 44).
2. Press the “UPS” button. This brings up a warning that pressing “OK” will shut off the UPS and
transfer the load to bypass, if available (see Figure 22).
3. Press “OK” to shut down the UPS.
Operation
Figure 44 N+1 Shutdown menu commands
47Liebert® NXL
™
Page 56
2.15.15 Shutdown—1+N UPS: UPS Shutdown
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
Perform a Module Shutdown Procedure to remove power from a single UPS module in the system.
Read all warnings in 4.0 - Maintenancebefore performing any maintenance on your Liebert NXL
UPS. These warnings and cautions must be observed during any work on the UPS.
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers.
Transfers to bypass if available
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
1. Press “Shutdown” then “This Module” menu buttons (see Figure 38). The Shutdown screen will
appear in the multipurpose window (see Figure 45).
2. Press the “UPS” button to transfer the load to Bypass Static Switch Bypass and shut down the
UPS.
2.15.16 Shutdown—1+N UPS: System Shutdown
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
Perform a Module Shutdown Procedure when you want to remove power from a single UPS module in
the system.
Operation
Read all warnings in 4.0 - Maintenancebefore performing any maintenance on your Liebert NXL
UPS. These warnings and cautions must be observed during any work on the UPS.
NOTE
This shutdown turns Off the inverter and the rectifier and trips all DC source breakers. This
will shut down the UPS completely.
1. Press the “Shutdown” then “This Module” menu buttons (see Figure 38). The Shutdown screen
will appear in the multipurpose window (see Figure 45).
2. Press the “System” button to shut down the UPS including the Bypass Static Switch.
Liebert® NXL
™
48
Page 57
Figure 45 1+N UPS shutdown menu commands
Operation
49Liebert® NXL
™
Page 58
2.15.17 1+N System Shutdown
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
Perform a System Shutdown Procedure when you want to remove power from the entire UPS system.
Read all warnings in 4.0 - Maintenancebefore performing any maintenance on your Liebert NXL
UPS. These warnings and cautions must be observed during any work on the UPS.
NOTE
Service and maintenance must be performed only by properly trained and qualified personnel
and in accordance with applicable regulations as well as with manufacturers’ specifications.
Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
System Shutdown Procedure
1. On any module, press “Shutdown,” then press the “All Modules” menu button (see Figure 38).
This message will appear: “This system has no MBB. If shutdown is started, the load will no
longer be support by the UPS. Load drop may occur.”
2. Press “OK”. The Shutdown screen will appear in the multipurpose window (see Figure 46).
3. Press the “1+N” button. All modules in the system will transfer to Bypass.
4. If an external wrap-around bypass is not installed:
a. This message will appear: “UPS output will turn-off. Do you want to proceed?” Press “Yes” to
continue the shutdown.
b. All the UPS breakers—CB1, CB2, BFB and DC source—will open. The message “Open all
MOB’s” will appear.
c.Open all the MOB breakers to isolate the UPS units from each other
d. To isolate the system, open all the MOB breakers and utility feeds to the bypass and rectifier
inputs
5. If an external, wraparound bypass is installed:
a. If using a key interlock system, depress the key-release unit push button, turn the key and
remove it from the key-release unit.
Operation
NOTE
The UPS system is now locked in bypass and cannot be transferred until the key is returned.
b. If using a key interlock system, insert the key into the lock for the Maintenance Bypass
Breaker (MBB); retract the bolt.
c.Close the Maintenance Bypass Breaker (MBB).
NOTE
Failure to close the Maintenance Bypass Breaker (MBB) will interrupt power to the load.
d. Open the Maintenance Isolation Breaker (MIB). The UPS system is now isolated from the
critical load and the load is now on Maintenance Bypass.
NOTE
The UPS units will shut down
e.If using a key interlock system, remove the key from the lock for the Maintenance Isolation
Breaker (MIB).
f.If the maintenance bypass cabinet or switchboard has an optional two-key interlock system,
reinsert the key into the solenoid.
g. All the UPS breakers—CB1, CB2, BFB and DC source—will open. The message “Open all
MOB’s” will appear.
h. Open all the MOB breakers to isolate the UPS units from each other
Liebert® NXL
™
50
Page 59
i.To isolate the system, open all MOB breakers and utility feeds to the bypass and rectifier
inputs.
Figure 46 1+N System Shutdown menu commands
Operation
51Liebert® NXL
™
Page 60
2.16Automatic Operations
150%
125%
110%
1 min
10 min
60min
85min
105%
The Liebert NXL UPS system is designed to function while unattended by an operator. The system
control logic monitors the performance of the UPS, the availability of power sources and the current
required by the critical load.
The system control logic:
• Determines what overload conditions can be sustained without a transfer to bypass.
• Initiates an automatic transfer to bypass to sustain an overload or when selected UPS faults
occur.
• Can initiate an automatic retransfer to the UPS after an overload has been cleared.
• Initiates an automatic transfer to bypass and emergency module shutdown when specified UPS
faults occur.
2.16.1 Overloads (Without Transfer)
The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload
conditions that remain within (under) the current versus time curve of overload capacity (Figure 47).
Note that the time scale is not linear.
For high current demands of short duration (momentary overloads) the critical load is supplied
simultaneously by both the UPS system and the bypass line. Whenever an overload condition occurs,
you should determine the cause of the overload. If an overload condition exceeds the overload
capacity, the UPS system initiates an automatic load transfer to the bypass line.
For overloads above the Input Current Limit, a DC source, such as a battery system or a generation
source, must be available. The Input Current limit has a default setting of 125% rated output current.
Operation
Figure 47 Current-versus-time curves of overload capacity
Liebert® NXL
™
52
Page 61
2.16.2 Automatic Transfers to Bypass (Overload Condition)
The UPS system will initiate an automatic load transfer to the bypass line if an overload condition
exceeds the current-versus-time curve of overload capacity or if specified UPS system faults occur.
Load On Bypass is illustrated in Figure 30.
The Overload Transfer and Output Undervoltage alarm messages will initiate an automatic transfer
to bypass and the Load On Bypass message will be displayed. The active event window will display
the Automatic Transfer to Bypass message. Other UPS system faults will initiate an automatic
transfer to bypass followed immediately by the shutdown and isolation of the UPS system. Refer to
2.16.3 - Automatic Transfers to Bypass, UPS System Faults.
In an automatic transfer to bypass the output and bypass circuit breakers do not overlap as they do in
a manual transfer. The static bypass switch is fired (closed), the output circuit breaker is opened, and
the bypass circuit breaker is closed. Bypass power is supplied to the critical load through the static
bypass switch during the short time while both circuit breakers are open.
NOTE
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass
is initiated. If the OK to Transfer condition is present, the load transfer will be uninterrupted.
If the Static Switch Unable alarm message is present for any reason, the automatic transfer
will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS components,
an interrupted load transfer is a very unlikely occurrence.
2.16.3 Automatic Transfers to Bypass, UPS System Faults
For specified UPS system faults, the control logic will initiate an automatic transfer to bypass
followed immediately by a shutdown and isolation of the UPS system. The output, DC source (MBD)
and input circuit breakers are open. The bypass breaker will be closed if the bypass line is available.
Note that the bypass line is usually not available during Low Battery Shutdown. The circuit diagram
is the same as illustrated in Figure 34 for Emergency Module Off.
Operation
The following UPS system faults will initiate an automatic transfer to bypass:
• DC Overvoltage Shutdown
• Inverter Fault
• Low-Battery Shutdown
• Output Overvoltage and Undervoltage
• Overload Shutdown
• Equipment Overtemperature
• Rectifier Fuse Blown
Refer to Table 10 for more information about these alarm messages.
NOTE
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass
is initiated and the bypass line is available. If the OK to Transfer condition is present, the load
transfer will be uninterrupted. If the Static Switch Unable alarm message is present for any
reason, the automatic transfer will be interrupted for 40 to 120 milliseconds. Because of the
reliability of the UPS components, an interrupted load transfer is a very unlikely occurrence.
Some installations may include a Remote Emergency Power Off mode that can be initiated
automatically by a contact closure in the critical load equipment. Refer to 2.14.6 - Remote Emergency Power Off.
53Liebert® NXL
™
Page 62
2.16.4 Automatic Retransfers to UPS
In an automatic retransfer, the two circuit breakers (bypass and inverter output) are both closed
simultaneously for a short period of time (overlap).
The following critical bus conditions must be present to initiate an automatic retransfer of the critical
load from the bypass source to the UPS inverter:
1. Critical load was initially transferred to the bypass source due to a system overload only. A
manual retransfer from bypass is required if the transfer to bypass was caused by any condition
other than output overload.
2. Overload has since dropped below 100% of the rated load.
3. Both the Input and the DC source (MBD) circuit breakers have remained closed since the
overload transfer.
4. OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of
the system overload transfer. A manual retransfer from bypass is required for overloads lasting 5
minutes or more.
5. Cyclic-type overloads, which occur up to five (select range is 0 to 5) times in 60 minutes, are
automatically returned to the inverter for each event including the Nth overload.
NOTE
If you do not want the UPS system to initiate any automatic retransfers, this can be set during
the initial commissioning or by calling your local Liebert Services representative.
Operation
Liebert® NXL
™
54
Page 63
3.0OPTIONS
NOTE
These items must be enabled by service before they become functional. If a feature is disabled,
the feature will not be available and the menu item will not be displayed.
3.1Input Contact Isolator Board
The Input Contact Isolator Board (ICI) provides a Liebert NXL module interface for up to eight
external user alarm or message inputs to be routed through the NXL’s alarm network. The eight
contacts are normally open dry contacts. When a contact closes, an event is triggered.
NOTE
Up to two (2) ICI’s can be installed in a Liebert NXL.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box,
which is accessed from the Internal Option Settings under Config dialog box on the HMI touchscreen
display. The Input Contact Isolator dialog box contains eight choices to match the eight channel input
board. You can label each button to identify the event associated with the contact. When the dialog
box is accessed, each button flashes to display the Input Contact Isolator number and the user
entered label. This label also appears in the Display Panel when an event related to an Input Isolator
Connector is triggered.
The Input Contact Isolator dialog box allows you to:
• Label the input contact assignments for your setup.
• Set the delay for an external event triggering an alarm.
• Review the isolator contact assignments, once the labels are entered.
The delay allows setting the number of seconds that a condition must exist before it will trigger an
alarm. To configure the Input Contact Isolator relays:
1. Press Internal Option Settings from the Config menu.
2. Press which Input Contact Isolator is to be configured. The Input Contact Isolator dialog box is
displayed.
1.Customer control wiring connection points are terminals 1 through 16 (see
Table 2).
2.Customer provided normally open dry contacts for user alarm messages.
3.All control wiring (by others) must be run separate from power wiring.
Control wiring runs should not be combined in the same conduit.
4.Signal voltage: 100mA @ 12VDC.
5.Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded
cable.
6.All wiring must be in accordance with national and local electrical codes.
• Delay, sec—0 to 99.9 (default: 0)
• Message—Custom: 0-19 characters
3. To assign labels for each channel:
a. Press Pre-assigned for default labels on Channels 1-6 (See Table 1)
b. For Custom labels
1. Press Custom to unique labels.
2. Click on Input Contact XX button. A keyboard is displayed to allow naming alarms.
3. Enter the name of the alarm set for that input. For example, a fan problem could be
indicated by naming the button FAN.
4. Press OK on the keyboard to keep your label.
4. Press DELAY.
a. A keypad is displayed prompting you for a delay time, in seconds, for a condition to exist
before the alarm is triggered.
b. Enter the delay value. The range for the values are from 0 (zero) to 99.9 seconds.
c.Press OK on the keypad to keep your setting. The value you entered is displayed in the field
adjacent to the corresponding input contact.
5. Repeat Steps 3 and 4 for each input contact.
6. Press SAVE after you have configured all input contacts.
Be sure to press Save even if you have accessed this dialog only to change a setting.
7. This information is not saved if control power is removed.
1.Customer control wiring connection points are terminals 1 through 15. (Pin 16 not used on J71, J72, and
J73.)
2.Programmable Relay Board option includes eight signal channels with two Form-C dry contacts per
channel (see Table 3).
3.All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be
combined in the same conduit.
4.Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A
5.Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable.
6.All wiring must be in accordance with national and local electrical codes.
The Programmable Relay Board (PRB) provides a means to trigger an external device when an event
occurs in the Liebert NXL. Each PRB has eight channels. Each channel has Form-C dry contacts
rated at 1A @ 30VDC or 125VAC @ 0.45A.
Any alarm/event can be programmed to any channel or channels. Up to four (4) events can be
programmed to a relay. If multiple events are grouped to one relay, group the events logically to
simplify troubleshooting when an event is triggered. The same alarm/event can be programmed to
more than one channel. Up to two Programmable Relay Boards can be installed in the Liebert NXL
for a total of 16 channels. Programming is performed through the HMI touchscreen display.
NOTE
Up to two (2) PRB’s can be installed in the Liebert NXL.
Figure 50 Control wiring, Programmable Relay Board
Options
Table 3Programmable Relay Board pinout
Terminal
BlockChannelPin No.Common
CH1
J71
J72
TB3
J74B1-3123
Note: Pin 16 not used on J71, J72, and J73.
CH2
CH3
CH4
CH5
CH6
CH7
CH8
A1-31 23
B4-64 56
A7-97 89
B10-12101112
A13-15131415
B1-31 23
A4-64 56
B7-97 89
A10-12101112
B13-15131415
A1-31 23
B4-64 56
A7-97 89
B10-12101112
A13-15131415
Normally
Closed
57Liebert® NXL
Normally
Open
™
Page 66
3.2.1Configuring the Programmable Relay Board Settings
1. Press Internal Option Settings from the Config menu.
2. Press which Programmable Relay Board will be configured. The Programmable Relay Board
dialog box is displayed.
3. Press the Relay channel
4. Press up to four (4) events. Selected events will show up under Relay 1 Assignment.
NOTE
To deselect an event, click on the event.
5. Repeat Steps 3 and 4 for each relay.
6. Press SAVE to keep the settings.
Figure 51 Programmable relay board dialog box
Options
• Assignment—0 to 4 event (default: 0)
• Delay, sec—0 to 99.9 (default: 0)
Liebert® NXL
™
58
Page 67
3.3Remote Alarm Status Panel RAS
The Remote Alarm Status Panel (RAS) uses LED status indicators that allow the operator to monitor
the UPS.
The main purpose of the Remote Alarm Status Panel option is to report the status of the load and the
UPS. To interpret the LED indicators, see Table 4.
Table 4RAS indicators
LED Name
Load on UPSGreen
Load on Bypass AlarmRed
Battery Discharge AlarmRedThe DC source is providing power to the UPS.
Low Battery Reserve AlarmRedDC source capacity is low and has reached the low-battery alarm setting.
OverloadRedSystem load has exceeded the system rating.
Ambient OvertempRedUPS inlet cooling air temperature has exceeded the specified limits.
System Summary AlarmRedAn alarm has occurred at the UPS.
New Alarm ConditionRed
LED ColorMeaning
The load is fully protected and no alarm conditions are present. The UPS
is supplying uninterrupted power to the load.
Power to the load is bypassing the UPS. The UPS is no longer supplying
power to the load.
A second alarm has occurred at the UPS. The New Alarm Condition LED
lights when the UPS Alarm Condition LED has been triggered and has
not been reset.
Options
The RAS also includes:
1. An audible alarm
2. Lamp Test/Reset push button to test the LED indicators
3. Audio Reset push button to silence an audible alarm
3.3.1Lamp Test/Reset Push button
The Lamp Test/Reset push button is used to verify that each LED indicator is in working condition
and to reset an LED indicator that has been triggered by a condition at the load or UPS.
To test the LEDs, press the Lamp Test/Reset push button. This lights all of the LED indicators for
visual inspection.
If an LED indicator does not respond to the lamp test, contact your local Emerson Network Power
representative for assistance.
To reset an activated LED, press the Lamp Test/Reset push button.
3.3.2Audio Reset Push button
The Audio Reset push button is used to silence an audible alarm that has been triggered and reset the
alarm to activate on the next alarm condition.
After correcting the alarm condition, press the push button to reset the audible alarm.
3.4Digital Load Bus Sync
3.4.1System Description
Liebert’s Load Bus Sync
Power Systems in synchronization, even when the systems are operating from different power
sources. The Liebert LBS works by synchronizing the Designates Slave System (DSS) to the output of
the Designated Master System (DMS). There are no other connections between the logic or controls of
either UPS. This ensures maximum system independence and reliability.
™
(LBS) option keeps the output of two or more independent Uninterruptible
59Liebert® NXL
™
Page 68
3.4.2LBS Configurations
• Load Bus Sync – Enable or Disabled (default: Disable)
• LBS Master Select - Master or Slave (default: Slave)
NOTE
The LBS settings permit proper operation with only one UPS set as the Master unit.
• LBS Slave Priority – 0 to 7 (default: 0)
NOTE
Setting of ‘0’ will disable LBS Slave Priority
3.4.3Normal Operations
The LBS will synchronize the Designated Slave Systems (DSS) to the Designated Master System
(DMS). The DSS will synchronize to the DMS output if the DMS is in Normal, Battery, Bypass or
Maintenance Bypass Mode
If the DSS transfers to Bypass Mode or Maintenance Bypass mode, the DMS will then synchronize to
the output bus of the DSS. This re-selection of master will be accomplished automatically.
3.4.4Slave Priority
When Slave Priority is enabled, the LBS system will work the same as Normal operations (See 3.4.2 LBS Configurations except when the DMS disqualifies it bypass source. If the DMS’s bypass is
disqualified, the LBS system will synchronize to the output of the DSS with the lowest Slave Priority
number that has a qualified bypass. The LBS system will synchronize back to the DMS when the
DMS’s bypass is qualified or all DSS’s bypass are disqualified.
If a DSS LBS Slave Priority is set to “0”, it will not assume the synchronization of the system if the
DMS disqualifies its bypass.
Options
Figure 52 LBS configuration
3.4.5Master System
The unit designated at power-up/reset to be the Master will monitor the LBS Sync Pulse line.
If two units are designated as Master, the second designated Master Unit to come on-line will inhibit
the LBS and synch to its own bypass.
The LBS Master will monitor the LBS Sync Pulse continuously; if the LBS Master detects that
another unit has transferred to bypass, the LBS Master will follow the unit on bypass.
• Slave can no longer follow the Master; the Master must follow the Slave.
When the Master unit is following a Slave LBS Sync Signal, it will generate the LBS Active event.
If the Slave LBS Sync Pulse stops, the Master will resume generating the LBS Sync Pulse.
Liebert® NXL
™
60
Page 69
3.4.6Slave System
Any unit designated as the Slave upon power-up / reset will monitor and lock to the Master LBS Sync
Pulse.
When the Slave unit is on bypass, the Slave will generate the LBS Sync Pulse.
• The Slave will slew to be locked to its own bypass source. The inverter in the LBS Slave system
will follow the local bypass.
• When the Slave unit is on UPS, the Slave will stop generating the LBS Sync Pulse.
When more than one Slave unit goes to bypass:
• All systems on UPS will follow the first Slave’s LBS Sync Pulse
• All other Slave systems on Bypass will follow their own local Bypass Source.
3.5ECO Mode
ECO Mode improves the overall efficiency by powering the critical bus from the bypass static switch
instead from the inverter.
3.5.1ECO Mode Setup
ECO Mode Operation—To enable or disable ECO mode via the front touchscreen.
• Enable, Disable
• Default: Disabled
Options
Maximum Auto Suspensions—Used to specify how many times the system is allowed to
automatically reactivate ECO Mode before the current ECO Mode session is terminated and
Excessive ECO Mode Suspension event is set.
• Min., 1; Max., 5; Iteration, 1
•Default, 3
Restart Delay—Used to specify how long the conditions to activate must be satisfied before
reactivating ECO Mode. Once Automatic Reactivation has been satisfied, the conditions must remain
satisfied for the full Restart Delay before ECO Mode is active.
When any Conditions to Suspend have been satisfied, the inverter(s) will power the load and the
bypass will be turned off. When the Conditions to Activate ECO Mode (Section 3.5.4) have been met,
the system will automatically return to ECO Mode.
3.5.6Conditions to Terminate ECO Mode
The system will terminate ECO Mode when at least one of the following conditions is true:
1. ECO Mode - Stop command is received.
2. Scheduling stop time is reached.
3. Excessive ECO Mode Suspension event is set.
4. ECO Mode Operation setting is disabled.
5. System transfers to bypass, either automatically or manually.
6. Backfeed Breaker Open event is active.
7. Bypass Static Switch Unable event is active (SCR Short, SCR Open).
8. Inverter Output Breaker (CB2/IOB) Open event is active.
9. Module Output Breaker (MOB) Open event is active.
10. Critical Bus Voltage Disqualification is satisfied.
11. Bypass Line Fault or Critical Bus Load Fault detected.
When any Conditions to Terminate have been satisfied, the inverter(s) will power the load and the
bypass will be turned off. ECO Mode will not turn on until the next Start command - either manually
or automatically if scheduled.
63Liebert® NXL
™
Page 72
3.6Intelligent Paralleling
Intelligent Paralleling is intended to increase system efficiency and reduce operating hours on the
modules. Intelligent Paralleling will put one or more paralleled modules into standby operation when
the number of redundant modules is above the user specified threshold.
3.6.1Intelligent Paralleling Setup
Operation
• Enable, Disable
• Default: Disabled
Minimum System Redundancy—Permits setting the redundancy threshold at which Intelligent
Paralleling will operate. This is the minimum Number of Redundant Modules that the system will
allow before bringing one or more modules back to normal operation and terminating Intelligent
Paralleling.
• Min: 0; Max: Number of Modules - 1; Iteration: 1
•Default: 1
Maximum Time Module In Standby—Permits cycling a module that has had Intelligent
Paralleling active the longest with another module currently in normal operation after the selected
amount of time. After the cycle is successful, the new module that has had Intelligent Paralleling
active the longest will go into standby mode. Disable this feature by selecting 0 days.
• Min: 0 Days; Max: 30 Days; Iteration: 1 Day
• Default: 30 Days
Options
Shutdown Delay—Permits choosing how long a module should wait before Intelligent Paralleling is
active and module is in standby.
• Min. 5 minutes; Max. 60 minutes; Iteration 1 minute
• Default: 5 minutes
NOTE
These are global settings. The settings only have to be configured from one module.
Figure 55 Intelligent Paralleling settings
Liebert® NXL
™
64
Page 73
3.6.2Intelligent Paralleling Target Area
The Intelligent Paralleling Target Area is the Number of Redundant Modules that fall between the
Minimum System Redundancy setting and the internal Maximum System Redundancy (Minimum
System Redundancy + 1.25).
• The Maximum Number of Redundant modules is designed to provide hysteresis so that modules
are not started and stopped when the load oscillates a few percentage points.
• When the Number of Redundant Modules goes above the Target Area, the system puts one or
more modules into standby operation until the Number of Redundant Modules is inside the
Target Area.
• When the Number of Redundant Modules goes below the Target Area, the system puts one or
more modules back into normal operation until the Number of Redundant Modules is inside the
Target Area or all available modules are supporting the load.
3.6.3Conditions to Activate Intelligent Paralleling
All of the following conditions must be true for the system to activate Intelligent Paralleling
• Intelligent Paralleling is enabled.
• The Number of Redundant Modules is above the Intelligent Paralleling Target Area for longer
than the Shutdown Delay setting.
• The Critical Load is on UPS.
• The module is part of the collective.
• No modules are on DC source.
• The module is selected as the next module to activate Intelligent Paralleling.
• Input Contact Interface 2 (Channel 7) event is not active
Options
3.6.4Conditions to Suspend Intelligent Paralleling
Suspend Intelligent Paralleling for a Module
At least one of the conditions below must be true for the module to terminate Intelligent Paralleling
at a module and return the module to normal operation:
• Intelligent Paralleling is disabled.
• The Number of Redundant Modules is below the Intelligent Paralleling Target Area.
• One or more modules is on DC source.
• Module is removed or user has issued a UPS/System shutdown.
Any of the following conditions will terminate Intelligent Paralleling and place all modules in normal
operation:
• All modules transfer to bypass
• System overload
• One or more modules go on DC source
3.6.5Intelligent Paralleling Module Selection
Intelligent Paralleling Module Activation
The next module chosen to activate Intelligent Paralleling and put into standby operation will be
done by cycling through the Module Numbers, starting with Module 1.
• The module chosen to be next must be a part of the collective (load on UPS). Otherwise, this
module will be skipped.
• When the last Module Number is chosen, the next module will be Module 1 (start cycle over).
Intelligent Paralleling Module Termination
The next module chosen to terminate Intelligent Paralleling normally and put back into normal
operation will be done by selecting the module that has had Intelligent Paralleling active the longest.
65Liebert® NXL
™
Page 74
3.6.6Module Standby Rotation
Module Standby Rotation will limit the time a module is in standby operation when the Number of
Redundant Modules doesn't change for a long period.
• The module selected as the next to terminate Intelligent Paralleling per Module Selection -
Termination, (see Intelligent Paralleling Module Termination on page 65), will not be in
standby operation for longer than Maximum Time Module In Standby (see 3.6.1 - Intelligent Paralleling Setup).
• When this time expires, the module will terminate Intelligent Paralleling and come back online.
• The next module selected to activate Intelligent Paralleling will be put into standby operation.
NOTE
When Maximum Time Module In Standby setting is 0, Module Standby Rotation is disabled.
Options
Liebert® NXL
™
66
Page 75
Figure 56 Module standby rotation
Load
UPS1UPS2UPS3UPS4UPS5
UPS1UPS2
Load
UPS3UPS4UPS5
Load
UPS1UPS2UPS3UPS4UPS5
Load
UPS1UPS2UPS3UPS4UPS5
Load
UPS1UPS2UPS3UPS4UPS5
After Maximum Time
Module in Standby
setting time
After Maximum Time
Module in Standby
setting time
After Maximum Time
Module in Standby
setting time
After Maximum Time
Module in Standby
setting time
Options
67Liebert® NXL
™
Page 76
4.0MAINTENANCE
!
!
4.1Safety Precautions
Observe the safety precautions in Battery Cabinet Precautions inside the front cover.
NOTE
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations as well as with manufacturers’
specifications.
Observe ALL of the WARNINGS below before performing ANY maintenance on the UPS System and
associated equipment. Also observe the manufacturer’s safety precautions pertaining to the DC
source, along with the DC source safety precautions in this section.
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
Extreme caution is required when performing maintenance.
Be constantly aware that the UPS system contains high DC as well as AC voltages. With
input power off and the DC source disconnected, high voltage at filter capacitors and power
circuits should be discharged within 5 minutes. However, if a power circuit failure has
occurred, you should assume that high voltage may still exist after shutdown. Check with a
voltmeter before making contact.
AC voltage will remain on the bypass and output circuit breakers and the static bypass
switch, unless associated external circuit breakers are opened.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the UPS system is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the UPS chassis frame by using rubber
mats.
Some components within the cabinets are not connected to chassis ground.
Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential
oscilloscopes when measuring a floating circuit.
Exercise caution that the test instrument exterior does not make contact, either physically or
electrically, with earth ground.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in fighting electrical fires.
Maintenance
Liebert® NXL
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
Always identify connecting wiring prior to disconnecting any wiring.
Do not substitute parts except as authorized by Emerson
Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.
Contact Liebert Services if you are not sure of the procedures to follow or if you are not
familiar with the circuitry.
™
68
®
.
Page 77
4.2Liebert Services
Startup, UPS maintenance, DC source maintenance and training programs are available for the
Liebert NXL UPS through your Liebert sales representative.
4.2.1Professional Startup
UPS Startup—Liebert’s customer engineers perform a thorough non-powered inspection of the units
and will then conduct a complete electrical checkout. The DC source installation is also inspected and
placed on an initialization charge to ensure cell equalization. Customer Operation training will be
conducted during DC source charge time.
Load bank testing and full site acceptance testing are additional services that can be performed
during a UPS startup. One preventive maintenance service call can be added to the initial UPS
startup agreement.
Battery Installation/Startup—When purchased with a UPS Startup, this Agreement provides
consistent, professional service for your entire UPS system. This one-source approach avoids conflicts
that may occur during a multisource installation. Note that Liebert requires a mandatory installation
inspection for all batteries not installed by Liebert customer engineers.
Battery IEEE Certification Inspection—The Battery Specialist will perform a detailed inspection
of the entire battery system to ensure it meets current IEEE standards.
Maintenance Agreements: The Signature Program
UPS Service Agreements—Liebert Services has a variety of available maintenance agreements,
depending on specific site needs. Choose the level of support appropriate for each installation.
Maintenance
Mission-critical sites can have the standard parts-and-labor, around-the-clock coverage for their UPS,
with or without scheduled preventive maintenance visits. Other sites can benefit from a variety of
money-saving options.
Emerson
®
recommends two preventive maintenance visits per year for the UPS. The first can be
conducted with the UPS operational and includes an infrared scan of key UPS components.
The annual visit will require taking the UPS off-line for a thorough non-powered inspection.
These visits are in addition to the general housekeeping tasks (changing air filters, etc.) that can be
performed by customer personnel.
Battery Service Agreements—The same flexible Signature Program can also be applied to
contracts for battery maintenance. Again, the coverage needed will depend on the type of battery
purchased and the degree of support required from Liebert Services.
Training
Customer training courses include the proper operation of the system, emergency procedures,
preventive maintenance and some corrective maintenance.
Warranties
Contact Liebert Services if you have any questions regarding the warranty on your Liebert NXL UPS
or the batteries.
69Liebert® NXL
™
Page 78
4.3Routine Maintenance
You should become thoroughly familiar with the equipment, but at no time should you go beyond the
specific procedures in this manual while performing maintenance or correcting a malfunction.
If you have any doubt as to what must be done, call Liebert Services at 1-800-LIEBERT for further
instructions.
NOTE
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations as well as with manufacturers’
specifications.
The UPS is designed for unattended operation, but does require some common-sense maintenance.
• Keep good records—Troubleshooting is easier if you have historical background.
• Keep it clean—Maintain the UPS free of dust and any moisture.
• Keep it cool—Battery systems must be kept in the range of 72-77°F (22-26°C) in order to meet
design specifications for capacity and longevity.
The UPS will reliably meet all performance specifications and design life at temperatures up to
104°F (40°C). However, performance and longevity will be optimized when the UPS is operated at
the same temperature as the batteries. Contact your local Liebert sales representative or call
1-800-LIEBERT for further details.
• Keep connections tight—Tighten all connections at installation and at least annually
thereafter (see torque requirements, Table 7.)
• Keep it inspected—Periodically inspect external upstream and downstream circuit breakers to
assure that the trip current settings are correct.
Become familiar with typical ambient conditions surrounding equipment so that abnormal
conditions may be more quickly recognized. Know what typical meter readings are and where
adjustable settings should be.
Maintenance
4.3.1Record Log
Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered parameter indications including phase readings, alarm
messages, UPS mode of operation, air filter replacement date and observation notes. A second log
should be maintained for the DC source as directed by the DC source manufacturer.
A periodic walk-through inspection of the UPS and DC source rooms is advised to check for visible
and audible indications of problems. Log the inspection, metered parameter indications and any
discrepancies.
4.3.2Air Filters
The air filters must be inspected and serviced on a regular schedule. The period between inspections
will depend upon environmental conditions. Under normal conditions, the air filters will require
cleaning or replacement approximately every two months. Abnormal or dusty conditions will require
more-frequent cleaning and replacement of air filters. Inspect installations in new buildings more
often, then extend the inspection period as experience dictates.
All NXL models have a replaceable air filter located inside the front doors. These filters can be
changed while the UPS is in operation.
Liebert® NXL
™
70
Page 79
4.3.3Limited Life Components
!
The Liebert NXL UPS has a design life well in excess of 10 years. Well-maintained units can continue
to provide economic benefits for 20 years or more. Long-life components are used in the UPS wherever
practical and cost-effective. However, due to the currently available component material,
manufacturing technology limitations and the general function and use of the component, a few
components in your Liebert UPS will have a shorter life cycle and require replacement in less than 10
years.
The following components utilized in your UPS system have a limited life cycle and are specifically
exempt from warranty. To prevent a wear-out failure of one of these components affecting your
critical load operations, Liebert recommends these components be periodically inspected and replaced
before the expected expiration of their life cycle. The expected life of each component listed below is
simply an estimate and is not a guarantee. Individual users may have site-specific requirements,
maintenance and other environmental conditions that affect the length of the component's useful life
cycle.
Table 5UPS component service life
ComponentExpected LifeReplace in:
Power AC filter capacitors> 7 years (~62,000 hours)5 to 6 years
Power DC filter capacitors> 7 years (~62,000 hours)5 to 6 years
Low-profile fans> 7 years (~62,000 hours)5 to 6 years
Air filters1 to 3 yearsCheck four times per year
Battery, lithium logic memory
backup
Battery, storage
Lead-acid wet-cell (user selection)10 to 20 years12 to 15 years
Valve-regulated, lead-acid (VRLA)
Maintenance
10 years (~87,600 hours)8 to 9 years
5 years2 to 3 years
10 years4 to 5 years
20 years8 to 12 years
In most cases, replacement components must exactly match the original component specifications.
These replacement components are not readily available from third-party component distributors.
For assistance with your specific component specifications, replacement component selection and
sourcing, call 1-800-LIEBERT. For customers using Liebert Services’ preventive maintenance
services, periodic inspection of these components is part of this service, as well as recommending
component replacement intervals to customers to avoid unanticipated interruptions in critical load
operations.
4.4Battery Maintenance
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
These maintenance procedures will expose hazardous live parts. Refer servicing to properly
trained and qualified personnel working in accordance with applicable regulations as well as
with manufacturers’ specifications.
DC fuses operate at the rated battery voltage at all times. A blown DC bus fuse indicates a
serious problem. Serious injury or damage to the equipment can result if the fuse is replaced
without knowing why it failed. Contact Liebert Services for assistance.
71Liebert® NXL
™
Page 80
4.4.1Battery Safety Precautions
!
!
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, use the same number and type of batteries.
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and
recycled or discarded in accordance with federal, state and local regulations. Because lead is a
toxic substance, lead-acid batteries must be recycled rather than discarded.
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It is toxic.
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
The following precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine whether the battery is grounded. If it is grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and
maintenance.
Maintenance
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition, the
electrical connections must be protected against accidental short circuits which can cause sparks. The
following procedures should be followed:
• DO NOT SMOKE when near batteries.
• DO NOT cause flame or spark in battery area.
• Discharge static electricity from body before touching batteries by first touching a grounded metal
surface.
• After replacing battery jars in a battery cabinet, replace the retaining straps that hold the jars in
place on the shelves. This will limit accidental movement of the jars and connectors should the
cabinet ever need to be repositioned or relocated.
Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery
and terminal voltages, specific gravity and connection resistance should be made. Strictly follow the
procedures outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.
Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although
maintenance of electrolyte levels is not required, visual inspections and checks of battery voltage and
connection resistance should be made.
NOTICE
Risk of equipment damage. Batteries should be cleaned with a dry cloth or a cloth lightly
moistened with water. Do not use cleaners on the batteries. Solvents can make the battery
cases brittle.
Because individual battery characteristics are not identical and may change over time, the UPS
module is equipped with circuitry to equalize battery cell voltages. This circuit increases charging
voltage to maintain flooded type battery cells at full capacity.
Liebert® NXL
™
72
Page 81
Maintenance
!
WARNING
Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment
damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery
manufacturer’s manual, available on the manufacturer’s Web site, for specific information
about equalize charging.
Matching Battery Cabinets—Optional
Although the individual battery cells are sealed (valve-regulated) and require only minimal
maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks
should be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS
operating, measure and record battery float voltage. With the DC circuit breaker open, measure and
record the nominal (open circuit) voltage. Both these measurements should be made across the final
positive and negative terminal lugs. Compare these values with those shown below. The recorded
nominal voltage should be no less than the value shown; while the recorded float voltage should be
within the range shown. If a discrepancy is found, contact Liebert Services.
Table 6Battery voltage, nominal and float
Battery Voltage, VDC
Number of Cells
240480527 - 552
NominalFloat
Power Connections: Check for corrosion and connection integrity. Inspect wiring for discolored or
cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 7.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and
tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more
than the retorque value. Table 7 shows battery retorque values.
If the system uses a different model battery, contact Liebert Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
73Liebert® NXL
™
Page 82
Other DC Sources
If the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the DC source as recommended in the DC source manufacturer’s maintenance
manual, available on the manufacturer’s Web site.
4.5Detecting Trouble
It is important that the operator check the instrument readings if abnormal equipment performance
is suspected. Any metered value that differs appreciably from normal could mean an impending
malfunction and should be investigated.
Items to check include:
• If the UPS has not operated on battery power during the last 10 hours, the batteries should
require little charging current. Battery mimic should indicate normal DC voltage with the battery
charge current no more than 1% of maximum discharge current.
• Input current on each phase should be within 10% of the average input current.
• Alarm messages indicate malfunction or impending malfunction. A daily check of the Display
Screen will help to provide an early detection of problems. Refer to Table 10 for information
about interpreting alarm messages.
• Tracing a problem to a particular section is facilitated by alarm messages and the metered
parameter indications.
NOTICE
Maintenance
If the UPS system has an open fuse, the cause should be determined before replacing the fuse.
Contact Liebert Services for assistance.
4.6Reporting a Problem
If a problem occurs within the UPS, review all alarm messages along with other pertinent data.
Contact Liebert Services at 1-800-LIEBERT to report a problem or to request assistance.
4.7Corrective Actions
The recommended corrective action for each alarm message on the Display Screen is in Table 10.
During normal UPS operations, short-term overload current demand from the bypass source may
reach 10 times the UPS output current rating. This overload current demand may be caused by the
magnetizing inrush current of one or more downstream transformers (i.e., power distribution units)
or faults on downstream branch circuits. The instantaneous trip point(s) of the upstream bypass
feeder breaker(s) must be set to support these temporary overloads. The magnitude of short-term
overload bypass current demand is typically six to eight times the UPS current rating, but must be
determined by analysis on a per-site basis. This analysis, generally known as an End-to-End Fault
Coordination Study, must be done by a registered professional engineer experienced in this activity
and familiar with local codes and related requirements.
Emerson
settings, as well as the module input (rectifier) feeder breaker trip settings, to ensure that they are
correct. For a variety of reasons, although typically during circuit breaker maintenance procedures by
others, trip settings have been known to be inadvertently left improperly set. Correct trip setting of
these circuit breakers is most important to achieving high-availability from your Liebert UPS system.
For further information regarding proper trip settings for your feeder breakers, call 1-800-LIEBERT.
®
highly recommends periodic inspections of the bypass feeder breaker instantaneous trip
Liebert® NXL
NOTE
The instantaneous trip setting of the breaker feeding the UPS bypass input should be high
enough to accommodate short-duration overloads. The bypass static switch power path inside
the UPS can draw up to 10 times the system’s rated current for up to three cycles.
NOTE
While Emerson
settings outside the Liebert-manufactured UPS equipment resides with the owner. Contact
Liebert Services at 1-800-LIEBERT for further details.
™
®
can provide typical guidelines, the responsibility for the proper breaker trip
74
Page 83
5.0SPECIFICATIONS
5.1DC Sources
5.1.1Battery Operation
The separate battery manufacturer’s manual, available on the manufacturer’s Web site, provides the
necessary information for the installation, operation and maintenance of the battery. Use the battery
manual in conjunction with this manual.
The float charge voltage for a battery is equal to the number of cells in series making up the battery
multiplied by the charge voltage for each cell.
Because the charging voltage level is critical to proper battery operation, refer to your battery
manual, available on the manufacturer’s Web site, for information about your system.
For models with nominal 240-cell battery, the DC bus nominal float voltage range is 2.15 to 2.30VPC.
Maximum equalize voltage is 2.45VPC. The number of battery cells required ranges from 228 to 246,
depending on the application.
5.2Other DC Sources
The separate DC source manufacturer’s manual, available on the manufacturer’s Web site, provides
the necessary information for the installation, operation and maintenance of the DC source. Use the
DC source manual in conjunction with this manual.
5.3Environmental Conditions
Table 8Environmental specifications
ParameterSpecification
Enclosure
Recommended Operating
Temperature, °F (°C)
Maximum Operating
Temperature, °F (°C)
Minimum Operating
Temperature, °F (°C)
Storage Temperature, °F (°C)-13 to 158 (-25 to 70)
Typical Battery
Temperature Requirements
Relative Humidity0 to 95% without condensation
Operating ElevationSea level to 4900 ft. (1500m) without derating
Storage ElevationSea level to 50,000 ft. (15,240m)
The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor
use only and is not to be subjected to falling objects or precipitation.
77 (25) ambient
104 (40) ambient (design temperature) without derating; (see Notes 2 and 3).
0°C
Average annual temperature must not exceed 80°F (27°C). Peak temperature
must not exceed 109°F (43°C). See battery manufacturer’s recommendations.
Specifications
Audible Noise,
5 Feet (1.5m) from Unit
68 dBA typical
Notes on Environmental Specifications
1. This category of electronic equipment is agency rated for use in an atmosphere free of conductive
particles. Some industrial facilities may require a room air filtration system to keep the UPS free
of excess moisture and contaminants.
2. The UPS system is designed to operate continuously at 104°F (40°C). However, design equipment
life expectancy will be extended with lower temperatures (25°C is recommended).
3. Ambient temperature is the maximum ambient temperature during any 24-hour period. For
operation at higher temperatures, consult your Liebert sales representative or call Liebert
Services at 1-800-LIEBERT.
4. Exercise care during installation to ensure unimpeded airflow through the UPS.
5. For operation at higher elevations, consult your Liebert sales representative or call Liebert
Services at 1-800-LIEBERT.
75Liebert® NXL
™
Page 84
Table 9Electrical specifications
Input Parameters
Input Voltage to Rectifier, VAC,
3-phase, 3-wire
Input Voltage to Bypass, VAC, 3-phase,
3- or 4-wire
Input Voltage Range, VAC+10% to -30%
Input Frequency, Hz60
Permissible Input Frequency Range,
Hz
Reflected Input THDi at nominal
voltage at full load, %
Rectifier Power Walk-In, sec1 to 30 (selectable) in 1 sec. Increments
DC Parameters
Battery TypeVRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid)
Nominal DC Bus, VDC480V
DC Float Voltage, VDC540V
End-Cell Voltage, VDC384–502 (for VRLA / FLA)
DC Ripple Voltage in Float and Const V
Ch. mode, %
Output Parameters
Inverter TypeIGBT-based Sine-Sine PWM Controlled
Output Voltage, 3-phase, 4-wire480V/575V/600V
Output Voltage Regulation, %< 1% (3-phase RMS average)
Output Voltage Regulation (Unb. Load)< 2% (3-phase RMS average)
Output Frequency, Hz60
Output Frequency Regulation, %± 0.1
Output THDu at Nominal Voltage
(Linear Load), %
Output THDu at nominal voltage
Including a 100kVA Non Linear Load
per EN 62040-3, %
Capacity to Handle Step Load, %0-100 or 100-0
Transient Recovery
(Linear Loads),
, msec
%
within 5% peak to peak in one-line cycle
Capacity to Handle Leading PF Load
0.9 lag to UnitySubject to maximum kW rating
at 0.95 LeadSubject to maximum. kW rating
at 0.9 LeadSubject to 12,5% kW derate or same rating and 10°C temp. derate
Voltage Displacement, ° el120° ±1° el (with unbalanced load)
Compliance to
Overload Conditions, % FL
(with DC source available)
Liebert NXL Model Size
FCC Class-AStandard
105% for 85 minutes; 110% for 60 minutes;
125% for 10 minutes; 150% for 1 minute
2503004005006257501100
Physical Parameters & Standards, in (mm)
1
with Static Bypass
Width
Width
without Static Bypass
Depth
Height
71.8
(1823)
1
———
33.5
2
(850)
76.8
(1950)
78.5
(1993)
33.5
(850)
76.8
(1950)
480V/575V/600V
480V/575V/600V
55 to 65
250-400kVA: <10%
500-1100kVA: <5%
<1 (RMS value) < 3.4% Vpp
<2%
2.5% (max)
78.5
(1993)
111.6
(2835)
140.5
(3569)
111.6
39.4
(1000)
76.8
(1950)
(2835)
39.4
(1000)
76.8
(1950)
(3175)
(1000.7)
(1950)
125
39.4
76.8
Specifications
140.5
(3569)
125
(3175)
39.4
(1000)
76.8
(1950)
228.3
(5799)
197.5
(5016.5)
46.1
(1170.9)
78.7
(1999)
Liebert® NXL
™
76
Page 85
Table 9Electrical specifications (continued)
Weight, unpackaged, lb (kg) approx.
3965
with Static Bypass (SMS)
with Static Bypass (1+N)
without Static Bypass (N+1)
Front Door Opening (for serviceability)More than 180°
Degree of Protection for UPS
Enclosure
Standards & Conformities
1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions with both side panels removed.
2. The depth dimensions include the front door and rear panel.
(1798)
4,040
(1,833)
———
4840
(2195)
4,915
(2,229)
6280
(2849)
6,380
(2,894)
IP 20 (with and without front door open)
IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3
10,310
(4677)
10,410
(4,722)
10,210
(4,631)
UL 1778, 4th Edition
CSA 22.2 107.3
FCC Part 15, Class A
ISTA Procedure 1H
WEEE
13,650
13,100
13,800
(6192)
(5942)
(6260)
13,650
(6192)
13,100
(5942)
13,800
(6260)
Specifications
21,450
(9730)
21,800
(9888)
20,050
(9095)
Disclosures with Regard to Embedded Software Licensed from Nokia, Inc., (“Sublicensed
Software”)
1. Limits on Use, Distribution and Derivative Works: User is not given any rights to modify or
create derivative works based on Sublicensed Software, or reproduce Sublicensed Software, or
distribute any copies of Sublicensed Software, or disclose any Sublicensed Software to any third
party, or decompile, disassemble or otherwise reverse engineer Sublicensed Software, or use any
information learned therefrom. User acknowledges that Nokia, Inc., and its licensors own the
copyrights and other intellectual property in and to the Sublicensed Software.
2. Responsibility of User: The Sublicensed Software is not designed, intended or licensed for use
in or with systems, devices or products intended for surgical implant into the body or other
applications intended to support or sustain life or for any aviation or nuclear reactor. It is User's
responsibility to ascertain the suitability of Sublicensed Software for any situation or application.
77Liebert® NXL
™
Page 86
Specifications
Liebert® NXL
™
78
Page 87
UPS Alarm and Status Messages
APPENDIX A-UPS ALARMAND STATUS MESSAGES
Table 10 shows alarm and status messages as they appear in the Liebert NXL’s touchscreen and in
the history log, along with a description and recommended actions, if any.
If the recommended action fails to correct the condition, contact your factory-authorized service provider.
The “Service Telephone Number” can be found by pressing “CONFIG,” “Ratings,” “More>>” on the
menu bar.
NOTE
In Event log, take the number for the “Data” Column. Convert that number from Decimal to
Hex. Each digit will explain the reason for the Inhibit signals.
Example: Data = 512d =0200h->“Removing Module will cause Overload or Drop the Load”
Table 10Liebert NXL alarm and status messages
Event MessageEvent DefinitionRecommended Action
An Automatic Restart was enabled, but has
failed to complete.
With Automatic Restart enabled, the unit
automatically restarts after an End of Discharge
(EOD) event. This alarm means that one of the
auto restart requirements was true, but failed
before the restart sequence completed.
Auto Restart Fail
Auto Rexfer
Failed
Bat Mon 1 CriticalBattery Monitor 1 is reporting a critical alarm.
Bat Mon 1 Maint
Batt CB“#” Open
For example, one conditional requirement for
Automatic Restart to occur is that the Rectifier
Input Voltage must be within acceptable limits. If,
during the restart sequence, the input voltage
drops out of tolerance, the Automatic Restart will
fail.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The condition that caused the system to
automatically disconnect the inverter from the
critical bus has failed to clear within a specified
time delay.
An example of a recoverable condition (one
which the controls may attempt to recover from
automatically) is an overload that exceeded the
overload capability.
Battery Monitor 1 has an active Maintenance
Alarm.
Battery Circuit Breaker “#” is open.
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
Press “SILENCE” to silence the audible alarm.
Check the active events to determine the status of
the UPS.
If “Auto Restart Fail” is the only alarm present,
attempt a manual start of the unit by pressing
“Startup,” “Manual Start,” then following the
prompts to attempt to place the unit back online.
If the manual start fails, or if there are other alarms
present that won’t clear, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear active events.
This does not clear the “Auto Retransfer Failed”
alarm.
If all other alarm conditions are clear, for a single
module system attempt a manual transfer to
Inverter by pressing “Transfer,” “UPS.” For a multimodule system attempt to manually reconnect this
inverter by pressing “Transfer,” “Connect This
Inverter.”
If successful, press “RESET” to clear this alarm
from the Active Event Window. If the UPS fails
connect the inverter to the critical bus and the
active messages do not explain the reason,
contact your factory-authorized service provider.
Check the Battery Monitor Module for more details
on this condition.
Contact your factory-authorized service
representative for service.
Check the Battery Monitor Module for more details
on this condition.
Contact your factory-authorized service
representative for service.
Press “SILENCE” to silence the audible alarm.
Check the status of Battery Circuit Breaker 1. If it is
open, the alarm is normal.
If Battery Circuit Breaker 1 is closed, contact your
factory-authorized service provider.
79Liebert
®
NXL
™
Page 88
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Observe the One-Line Display. If the input line is
orange, black, or gray, the battery discharging
condition is normal.
If the input line on the One-Line Display is green,
check the Active Event Window for potential fault
conditions that could explain why the UPS is on
battery. An example of this could be “Rectifier
Fault.”
Monitor the UPS during the battery discharge. The
display shows the discharge curve of the battery.
When the Battery Voltage Line touches the End of
Discharge Line, the UPS shuts down.
Check the bypass line on the One-Line Display. If
the line feeding the Static Bypass Switch (BPSS) is
green, the unit can be transferred to bypass by
pressing “Transfer,” “Bypass” to transfer the load
to the bypass source. Note that transferring to
bypass could expose the load to an outage if the
bypass source fails.
If the battery is discharging because of a fault such
as “Rectifier Fault” in the Active Event Window
rather than an actual power outage, transfer to
bypass if available, and contact your factoryauthorized service provider.
In normal operation, no user response is required.
Equalize charge can be terminated at any time by
pressing “Battery Management,” “Manual Battery
Equalize,” “Stop.”
Press “SILENCE” to silence the audible alarm.
Are any Battery Circuit Breakers tripped?
Perform a visual inspection of the batteries in the
tripped string(s). Look for signs of leaking battery
acid or excessively corroded battery terminals.
If there are no visible signs of defective batteries,
press “RESET” to try and clear the alarm.
Close any open breakers one at a time, pressing
“RESET” after each one to see which string is
causing the alarm. The string reporting the fault,
when online, will not allow the alarm to reset.
Once the location is identified, or if the battery
string tests are inconclusive, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Wait 30 minutes and check to see if the alarm has
cleared.
If the alarm does not clear 15 minutes after the
battery test, but does clear within 30 minutes after
the battery test, check the condition of the batteries
(contact your factory-authorized service provider).
If the alarm is still present 30 minutes after the
battery test concluded, check the Event Log by
pressing “Status Reports,” “Event Log” for
additional information and contact your factoryauthorized service provider.
Batt Discharging
Batt Equalizing
Batt Ground Fault
Batt Not Charging
The UPS is on Battery.
The most common reason for going to battery is
a loss of Rectifier input power (power outage).
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The Batteries are being equalized.
Battery equalization stops automatically based
on the Equalize Time Setting.
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
Detected Battery ground current exceeds the trip
setting.
A possible symptom that could cause this alarm
is a leaking battery.
This alarm has a higher detection setpoint than
“Battery Ground Fault Current Warning,” and if
present, means that the Battery Ground Fault
Current is excessive.
This alarm could cause Battery Breakers to trip if
the “Battery Ground Fault Trip Enable” setting is
enabled.
The UPS just passed a Manual or Automatic
Battery Test and the float voltage has not yet
returned to normal.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Liebert® NXL
™
80
Page 89
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Observe the One-Line Display. To identify which
battery cabinet is reporting the temperature
condition, press the “Battery Box” on the One-Line
Display to cycle through each battery compartment
or string. The temperature display is located under
the voltage reading in the Battery Box.
If the Common Battery Disconnect and/or the
individual battery cabinet or string reporting the
over temperature condition is tripped, check the
following settings.
Press “User Settings,” “Battery Management,”
“Battery Temperature” to check the current Battery
Temperature Setpoints. If none of the Battery
Boxes on the One-Line Display exhibit a
temperature in excess of the temperature setpoint
in the user settings, contact your factoryauthorized service provider.
If the over temperature limit is being reported
correctly, investigate potential causes such as
faulty air conditioning, or air flow blockage and
resolve. Otherwise, contact your factory-authorized
service provider.
Press “SILENCE” to silence the audible alarm.
Observe the One-Line Display. To identify which
battery cabinet is reporting the temperature
condition, press the “Battery Box” on the One-Line
Display to cycle through each battery compartment
or string. The temperature display is located under
the voltage reading in the Battery Box.
Press “User Settings,” “Battery Management,”
“Battery Temperature” to check the current Battery
Temperature Setpoints. If none of the Battery
Boxes on the One-Line Display exhibit a
temperature in excess of the temperature setpoint
in the user settings, contact your factoryauthorized service provider.
If the over temperature warning is being reported
correctly, investigate potential causes, such as
faulty air conditioning or air flow blockage and
resolve. Otherwise, contact your factory-authorized
service provider.
During normal operation, no user response is
required.
The battery test can be terminated at any time by
the user by pressing “Batt Mgt,” “Manual Battery
Test,” “Stop.”
Press “SILENCE” to silence the audible alarm.
Try to identify which sensor has failed by observing
the temperature reading inside the Battery Box on
the One-Line Display. Cycle through all connected
batteries by pressing the Battery Box on the
display.
Contact your factory-authorized service provider.
Batt Ovtemp Limit
Batt Ovtemp
Warning
Batt Self Test
Batt Sensor Fail
One or more of the Battery Temperature
Sensors is reporting a temperature above the
limit setpoint.
There are two user adjustable Battery
Temperature Setpoints: Battery Over
Temperature Warning and Battery
Overtemperature Limit. The temperature in one
or more battery compartments has risen above
the limit setpoint.
Depending on user settings, the controls may trip
the battery breaker associated with the over
temperature condition.
One or more of the Battery Temperature
Sensors is reporting a temperature above the
warning setpoint.
There are two user adjustable Battery
Temperature Setpoints: Battery Over
Temperature Warning and Battery
Overtemperature Limit. This alarm means the
temperature in one or more battery
compartments has risen above the warning
setpoint.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The UPS is performing a battery self test.
The battery self test terminates automatically at
the end of the test.
Battery test settings are adjustable and can be
accessed by pressing “Config,” “User Settings,”
“Batt Mgt,” “Battery Test.”
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
The controls are sensing a failed Battery
Temperature Sensor.
If a sensor reports a value outside the normal
operating range of the sensor, it is considered
failed.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
81Liebert
®
NXL
™
Page 90
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
To attempt to identify which sensor is reporting an
inconsistent temperature or an overheating
battery, observe the temperature reading inside
With more than one Battery Temperature Sensor
Batt Temp
Imbalance
installed, the controls are detecting too great a
temperature difference between the individual
sensors.
An Automatic or Manual Battery Test Failed. The
battery “Test Duration” is adjustable. The battery
test fail criteria were met before the end of the
Batt Test Failed
timed battery test.
For example, there must be at least 25% load to
run the battery test. If, during the battery test the
load drops below 25%, the test fails.
The conditions required to perform an automatic
battery test are not met.
When the battery test is inhibited, the system
delays the test for 7 days. If conditions are
Batt Test Inhibit
satisfied after 7 days, the UPS performs the
battery test at that time.
Examples of conditions required to run the
automatic battery test are at least 25% load, all
battery breakers closed, normal operation, etc.
Batt Test PassedThe Battery Test passed.
The Backfeed Breaker is open.
The Backfeed Breaker feeds the Static Bypass
Switch (BPSS). The physical location of the
breaker depends on unit configuration. It may be
located in the UPS, or it may be located external
to the UPS.
BFB Open
The purpose of the Backfeed Breaker is to
prevent leakage current through the bypass
circuit during an outage.
This status message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the status event
reverts to normal.
BPSS is OnThe Bypass Static Switch is On.
The Bypass Static Switch (BPSS) was turned Off
due to an extended overload.
While the BPSS can sustain an overload greater
than the Inverter and for a longer period of time,
BPSS Ovld
Exceeded
there are still limits on the amplitude and duration
of overload that the BPSS can handle. This
alarm indicates the overload was greater in
amplitude and time than the BPSS can handle,
and therefore shut Off to prevent damage to the
equipment.
the Battery Box on the One-Line Display. Cycle
through all connected batteries by pressing the
Battery Box.
If it appears this alarm is due to a specific cabinet
or battery string being warmer than the others,
verify through investigation whether the string is
actually getting warmer than the others, or if the
sensor appears to be reporting incorrectly.
Contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Contact your factory-authorized service provider.
Check the Active Event Window and investigate
other events to further analyze.
If there are other active events in the Active Event
Window, press “RESET” to clear the events.
Check the One-Line display to verify the UPS is
online.
Check the Module Output Meter and verify the kW
load is between 25%-100%.
Press the Battery Box on the One-Line Display and
verify all battery strings show at least 96% charged
and all battery breakers are closed.
If the issue cannot be resolved, contact your
factory-authorized service provider.
This status message is informational. If the breaker
was not opened intentionally, or if the breaker is
actually closed and this message is active, contact
your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Once the overload source is isolated, restart the
UPS by pressing “Startup,” “Manual Start” and
follow the prompts.
If the overload condition does not clear, or the
overload is cleared but the UPS does not restart,
contact your factory-authorized service provider.
Liebert® NXL
™
82
Page 91
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
When starting the module BPSS's in a 1+N
BPSS Start Inhibit
BPSS Unable
Breaker Close
Fail
Breaker Open
Fail
Byp
Overload
Ph A
Byp
Overload
Ph B
system without a MBB, there are not enough
module BPSS's ready with their MOB closed to
support the rated capacity.
This alarm is a latching alarm that must be
cleared at each module after enough Bypass
Static Switches are available to support the
system load.
A problem has been detected in the Bypass
Static Switch.
This is a summary event that informs the user
that a circuit breaker that was either signaled to
close or was manually closed failed to report a
closed status.
The Breaker Close Fail event indicates a
mismatch between the expected state of a
breaker and the reported state of the breaker.
This is a summary event that informs the user a
circuit breaker that was either signaled to open
or was manually opened failed to report an open
status.
The Breaker Open Fail event indicates a
mismatch between the expected state of a
breaker and the reported state of the breaker.
The critical load is greater than 110% while the
UPS is on bypass. The controls may shut the
unit down if the overload condition does not clear
within the allotted time. Allotted time is variable,
and is inversely proportional to the amplitude of
the overload, i.e., the greater the amplitude of
the overload, the less time the unit continues to
support the load.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The critical load is greater than 110% while the
UPS is on bypass. The controls may shut the
unit down if the overload condition does not clear
within the allotted time. Allotted time is variable,
and is inversely proportional to the amplitude of
the overload, i.e., the greater the amplitude of
the overload, the less time the unit continues to
support the load.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Press “SILENCE” to silence the audible alarm.
Contact your factory-authorized service provider if
there are enough Bypass Static Switches available
to support the existing system load.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear the fault.
Contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the One-Line Display and the Active Event
Window to determine which breaker or switch is
open.
If the open breaker cannot be reset or closed, or if
all breakers are closed but the One-Line Display
does not agree, or the alarm cannot be cleared,
contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the One-Line Display and the Active Event
Window to determine which breaker or switch that
should be open is still closed.
If a breaker that should be open shows closed, or if
the breaker in question actually is open but the
fault is still present, attempt to clear the fault by
pressing “RESET.”
If the event does not reset, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Observe the calculated load percentage on A
phase displayed on the Module Output Meter. If
the A phase steady state load percentage exceeds
110%, perform the following:
If Maintenance Bypass is available, follow
Standard Operating Procedures to transfer the
load to Maintenance Bypass.
Investigate the overload condition.
If the Module Output Meter does not indicate an
overload condition, perform the previous steps and
contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Observe the calculated load percentage on B
phase displayed on the Module Output Meter. If
the B phase steady state load percentage exceeds
110%, perform the following:
If Maintenance Bypass is available, follow
Standard Operating Procedures to transfer the
load to Maintenance Bypass.
Investigate the overload condition.
If the Module Output Meter does not indicate an
overload condition, perform the previous steps and
contact your factory-authorized service provider.
83Liebert
®
NXL
™
Page 92
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Observe the calculated load percentage on C
phase displayed on the Module Output Meter. If
the C phase steady state load percentage exceeds
110%, perform the following:
If Maintenance Bypass is available, follow
Standard Operating Procedures to transfer the
load to Maintenance Bypass.
Investigate the overload condition.
If the Module Output Meter does not indicate an
overload condition, perform the previous steps and
contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Observe the One-Line Display. The bypass power
line feeding the static switch is green when bypass
power is within normal operating range. If the line
feeding the static switch is orange, gray, or black,
bypass voltage is out of tolerance. Also check the
bypass voltage readings on the Bypass Meter.
When the bypass returns to normal, this alarm
clears automatically. If all indications checked
above are normal and the alarm is still present,
contact your factory-authorized service provider.
If there is a problem indicated with the bypass
voltage, investigate and resolve the issue.
Examples of conditions which could cause this
alarm: Unstable generator voltage; or, Bypass
Feeder Breaker tripped.
Press “SILENCE” to silence the audible alarm.
Check the frequency on the Bypass Meter. If the
frequency is outside the synchronization range,
investigate and resolve the issue.
This alarm is commonly the result of an
uncalibrated generator, or power anomalies on the
utility feed. Check bypass power for nominal limits.
If bypass frequency appears normal, contact your
factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to reset the fault.
Contact your factory-authorized service provider
If the alarm does not clear, or if the alarm condition
returns, contact your factory-authorized service
provider.
Press “SILENCE” to silence the audible alarm.
Byp
Overload
Ph C
Bypass Breaker
(SBB) Open
Bypass
Not Avail
Bypass OF/UF
Controller Error
Controls
Comm Fail
Controls
Reset
Required
The critical load is greater than 110% while the
UPS is on bypass. The controls may shut the
unit down if the overload condition does not clear
within the allotted time. Allotted time is variable,
and is inversely proportional to the amplitude of
the overload, i.e., the greater the amplitude of
the overload, the less time the unit continues to
support the load.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The bypass circuit breaker indicates that it is in
the open position.
This summary event indicates a problem with the
detected bypass voltage. If bypass is not
available, transfers to bypass are disabled.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The bypass frequency has exceeded the bypass
frequency limit of ± 5 Hz of nominal. If this alarm
is active, transfers to bypass are disabled.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
This is a summary event that indicates a DSP
communication error.
The Controller Error event is a fault condition that
indicates a loss of communications in the
controls.
The Controls Communication Failure event
indicates a loss of communications between the
Controls and Human Machine Interface (HMI).
The Controls Communication Failure event is
displayed when the HMI detects a loss of
communication with Controls on the Controller
Area Network (CAN).
An infrequent occurrence that resets
immediately is probably not serious.
This alarm means one or more critical settings
have been changed by user during UPS
operation.
The change(s) will not take effect until after a
UPS Controls reset. This operation should only
be performed by an authorized service
personnel.
This alarm is cleared after UPS Controls reset.
Liebert® NXL
™
84
Page 93
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Press “RESET” to clear the fault.
Perform a visual inspection of the batteries. Look
for signs of leaking battery acid or excessively
corroded battery terminals.
If there are no visible signs of defective batteries,
open one Battery Breaker. Press “RESET” and see
if the condition clears. If the condition clears, you
have isolated the problem to that battery string.
If the condition will not clear, repeat the test with
each connected battery string.
Once the location is identified, or if the battery
string tests are inconclusive, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to clear the fault.
Perform a visual inspection of the batteries. Look
for signs of leaking battery acid or excessively
corroded battery terminals.
If there are no visible signs of defective batteries,
open one Battery Breaker. Press “RESET” and see
if the condition clears. If the condition clears, you
have isolated the problem to that battery string.
If the condition will not clear, repeat the test with
each connected battery string.
Once the location is identified, or if the battery
string tests are inconclusive, contact your factoryauthorized service provider.
Under normal circumstances, none.
Perform ECO Mode setup and operation by
pressing “CONFIG,” “User Settings,” “ECO Mode”
from the Menu Bar. ECO Mode can be manually
controlled under the “Operation” submenu, or
configured to run automatically under the
“Schedule” submenu.
If this message is active, and there is no clear
reason why the UPS is in ECO Mode, contact your
factory-authorized service provider.
Under normal circumstances, none.
DC Link
Gnd Fault-
DC Link
Gnd Fault+
ECO Mode
Active
The negative DC Bus has a ground fault.
The UPS controls monitor the DC Bus negative
half for a voltage imbalance caused by current
flow to ground. This fault means excessive
ground current is detected.
In normal operation, with the batteries
connected, the most likely cause of a current
path to ground is a leaking battery.
If your system includes an optional Battery
Ground Fault Monitor, check if the Battery
Ground Fault message is present also.
The positive DC Bus has a ground fault.
The UPS controls monitor the DC Bus positive
half for a voltage imbalance caused by current
flow to ground. This fault means excessive
ground current is detected.
In normal operation, with the batteries
connected, the most likely cause of a current
path to ground is a leaking battery.
If your system includes an optional Battery
Ground Fault Monitor, check if the Battery
Ground Fault message is present also.
This event indicates that ECO Mode operation is
active.
The ECO Mode feature improves the overall
efficiency of the UPS system by powering the
critical bus from the bypass static switch instead
of the inverter. If the critical bus goes out of
tolerance (voltage, frequency or slew rate), the
BPSS is turned Off and the inverter quickly
assumes powering the critical bus. The inverter
is always ready to take the load in the event that
the bypass source fails.
The user has the ability to start and stop ECO
Mode manually via the user interface or
automatically based on a user-defined schedule.
ECO Mode
Suspended
This event indicates that ECO Mode operation is
suspended.
When the ECO Mode feature is enabled and
active, the UPS system powers the critical bus
from the bypass static switch instead of the
inverter. But if the critical bus goes out of
tolerance (voltage, frequency or slew rate), ECO
mode is temporarily suspended (or “inhibited.”)
The BPSS is turned Off and the inverter quickly
assumes powering the critical bus.
85Liebert
Typically ECO Mode operation will resume soon
after the bypass source becomes qualified again,
unless the ECO Mode session is terminated due to
a manual or scheduled 'Stop' command or if
excessive ECO Mode suspensions occur.
Perform ECO Mode setup and operation by
pressing “CONFIG,” “User Settings,” “ECO Mode”
from the Menu Bar. ECO Mode can be configured
via the “Settings” submenu and manually
controlled under the “Operation” submenu.
If this message is active, and there is no clear
reason why ECO Mode is inhibited, contact your
factory-authorized service provider.
®
NXL
™
Page 94
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Resolve the issue that precipitated the EMO.
For safety, the UPS latches an EPO event. To
clear the latch, press the EMO Reset push button
on the External Interface Board (EIB).
Verify the EMO is cleared by pressing “RESET”
and observing that the EPO alarm in the Active
Event Window is gone.
Restart the UPS by pressing “Startup,” “Manual
Start,” and follow the prompts.
Press “SILENCE” to silence the audible alarm.
Resolve the issue that precipitated the EPO.
For safety, the UPS latches an EPO event. There
are two ways to clear the latch:
1. Press the EPO Reset push button on the
External Interface Board (EIB).
2. From HMI front panel display, press OK button
when “Press OK to Reset EPO Latched signal”
message is displayed in a dialog box.
Verify the EPO is cleared by observing the EPO
alarm in the Active Event Window is gone.
Restart the UPS by pressing “Startup,” “Manual
Start,” and follow the prompts.
Investigate possible causes for a rising
temperature condition, such as loss of air
conditioning, airflow obstructions, etc. If the
ambient temperature is high due to loss of air
conditioning and cannot be addressed
immediately, perform the following:
Press “Transfer,” “Bypass” to transfer the UPS to
bypass.
Press “SILENCE” to silence the audible alarm.
Wait at least 15 minutes, then attempt to reset the
alarm by pressing “RESET.”
If the alarm clears and proper cooling has been
restored to the UPS, press “Transfer,” “UPS” to
transfer back to UPS.
If this alarm is present and no external factors are
affecting proper cooling of the UPS, contact your
factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the One-Line Display for system status:
UPS Off
If external Maintenance Bypass is available, close
the Maintenance Bypass Breaker (MBB) to restore
power to the load. Do not attempt to restart the
UPS without first contacting your factoryauthorized service provider.
UPS On
Bypass
Verify the bypass line is green. If it is not, contact
your factory-authorized service provider
immediately and prepare to shut down the load.
If external Maintenance Bypass is available, close
the Maintenance Bypass Breaker (MBB) to place
the load on Maintenance Bypass. Do not attempt
to re-transfer to UPS without first contacting your
factory-authorized service provider.
U
PS On Battery
Verify the bypass line is green. If it is not, contact
your factory-authorized service provider
immediately and prepare to shut down the load.
If the bypass line is green, press “Transfer”,
“Bypass,” to transfer the load to bypass.
EMO
Shutdown
EPO
Shutdown
Equip
Ovtemp
Equip
Ovtemp
Limit
An Emergency Module Off (EMO) command has
been detected.
The EMO signal means the front panel EMO
button was pressed. A Remote EMO would
display the “REMO Shutdown” alarm.
In response to an EMO, the UPS transfers to
Bypass and shuts Off.
The UPS shuts down in response to an active
Emergency Power Off (EPO) command.
This summary event indicates the UPS is
nearing an over temperature condition.
Depending on which sensor is reporting the high
temperature, the UPS may do one of three things
once the limit is reached: shut down, transfer to
bypass, or transfer to battery operation. This is a
potentially serious event.
This summary event occurs when one or more
internal temperatures have exceeded the
maximum temperature setpoint. This is the
second of two over temperature alarms. The
first, “Equipment Overtemperature Warning,”
sets when the detected temperature is near the
limit.
The controls react to this condition in various
ways, depending on which sensor is reporting
the over temperature condition.
Liebert® NXL
™
86
Page 95
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
The UPS has tried to reconnect the inverter to
the critical bus too many times. For a single
module system, the load will be on the bypass
static switch. For multi-module systems the load
will be supported by the other modules.
The UPS will attempt to automatically recover
and reconnect the Inverter to the critical bus, if
Excess
Auto
Rexfers
the reason that caused it to disconnect has
cleared and the event is recoverable; for
example, a temporary overload.
The number of times the UPS attempts to
recover is limited. When the number of attempts
exceed the allowable number (default is 5
attempts per hour), the inverter will remain
disconnected from the critical bus and this event
will be displayed.
An example of a condition that could cause this
alarm is a cycling load on the UPS where the
peak load exceeds the overload capability. If the
cycling load exceeds the overload capability for
more than the allowable number, the UPS will
have to be put online manually by selecting
“Transfer,” “UPS.”
This event indicates that ECO Mode operation
has been terminated due to an excessive
number of suspensions.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to clear any active faults or alarms.
Provided there are no alarms or faults still present
that could prevent a transfer, press “Transfer,”
“UPS,” to reconnect the Inverter to the critical bus.
If successful, press “RESET” to clear the alarm.
Otherwise, contact your factory-authorized service
provider.
This event will clear the next time ECO Mode is
initiated by a manual or scheduled 'start'
command.
Excess ECO
Suspends
Excess
Paralleling
Fuse Fail
When the ECO Mode feature is enabled and
active, the UPS system powers the critical bus
from the bypass static switch instead of the
inverter. But if the critical bus goes out of
tolerance (voltage, frequency or slew rate), ECO
mode is temporarily inhibited (or “suspended.”)
This event is generated when ECO mode is
repeatedly suspended and exceeds the user
setting for the maximum number of automatic
suspensions allowed.
When the controls detect a high amplitude, short
duration overload condition on the output, the
static switch is turned on momentarily in parallel
with the Inverter to attempt to clear the condition.
If the fault clears, the controls turn Off the static
switch and the load remains on Inverter. This
fault condition indicates the UPS pulse paralleled
too many times and is now locked on bypass
(auto re-transfers to Inverter are inhibited).
This is a summary event that indicates a fuse
has opened. There are several fuses that can
cause this fault.
The Fuse Failure event is caused by one or more
fuses reporting a failed status. The UPS may or
may not transfer to bypass as a result of the
failed fuse.
Perform ECO Mode setup and operation by
pressing “CONFIG,” “User Settings,” “ECO Mode”
from the Menu Bar. ECO Mode can be configured
via the “Settings” submenu and manually
controlled under the “Operation” submenu.
If this message is active, and there is no clear
reason why excessive ECO Mode suspensions are
occurring, contact your factory-authorized service
provider.
Press “SILENCE” to silence the audible alarm.
Check the Module Output Meter and verify the
output currents are normal, the kVA/kW
percentages are less than 100%, and the Rexfer
Time out is 00:00.
Verify the Inverter box on the One-Line Display is
green.
Investigate any other active alarms or faults before
attempting to clear this fault.
Press “RESET” to clear the fault.
If the Event Window is clear, press “Transfer,”
“UPS” to transfer the load back to Inverter.
If the “UPS” button is grayed out, or pressing the
“UPS” button does not transfer the unit back to
Inverter, or if the UPS immediately transfers back
to bypass, contact your factory-authorized service
provider.
Press “SILENCE” to silence the audible alarm.
Check the One-Line Display and other indicators to
determine the state of the unit and take appropriate
action.
Contact your factory-authorized service provider.
87Liebert
®
NXL
™
Page 96
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Press “SILENCE” to silence the audible alarm.
Check the Inlet Air Temperature on the One-Line
Display and verify the reading is accurate, i.e. is
the room temperature warmer than normal?
If the room temperature is warmer than normal,
investigate and resolve the issue.
If the room temperature is normal, and the Inlet Air
Temp reading on the One-Line Display is higher
than normal, contact your factory-authorized
service provider.
Press “SILENCE” to silence the audible alarm.
Verify correct phase rotation at the input.
If the phase rotation is correct, contact your
factory-authorized service provider.
Check the wires landed on Input Contact Isolator
#X.
If this signal is not active, or if no signal wires are
present, contact your factory-authorized service
provider.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to attempt to clear the alarm
condition.
If the alarm clears, press “Startup,” “Device
Control,” “Close Trap” to manually close the filter
contactor.
If the contactor remains closed, check the Input
Meter and verify the input currents are balanced.
If the contactor re-opens and the “Input Current
Imbalance” returns, silence the alarm, leave the
filter contactor open, and contact your factoryauthorized service provider.
Inlet
Ovtemp
Inp Phase
Rotation
Input Breaker
(BIB) Open
Input Breaker
(RIB) Open
Input
Contact
“XY”
Input
Current
Imbal
The air flowing into the UPS is too warm.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The correct input phase rotation should be
clockwise, or A-B-C. This alarm indicates the
sensed input phase rotation is counterclockwise. If this alarm occurs on an operational
unit, it typically indicates upstream work was
performed (input side) and the input wiring was
connected incorrectly.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The bypass isolation breaker indicates that it is in
the open position.
The rectifier isolation breaker indicates that it is
in the open position.
The displayed text for this alarm depends on
settings.
In response to this alarm, the user may see any
of four possible messages:
No message at all, but the help icon is present;
A custom message programmed by the user;
“Input Contact XY” if the contact is unconfigured;
“Stop Batt Charge” if the contact is programmed
as Pre-assigned.
If this event is active, an external signal is wired
into channel Y of Input Contact Isolator #X.
If the display shows Case 1 above (blank
message), it means the contact channel is set to
default but the default message was erased.
If the display shows Case 2, the userprogrammed event is active and the displayed
text is customer defined.
If the display shows Case 3, the contact is active
but was not pre-programmed (default condition).
If the display shows Case 4, the controls disable
Battery charging operation.
This alarm message is self-clearing. When the
condition is no longer present, the message and
any control activity tied to the alarm will revert to
normal.
The detected input currents are not balanced.
This latching alarm indicates a potential problem
in the input filter. The controls automatically open
the filter contactor in response to this condition.
The filter contactor must be manually closed
once it opens in response to this alarm.
Liebert® NXL
™
88
Page 97
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
An active Input Current Limit alarm means the
Press “SILENCE” to silence the audible alarm.
Observe the meters on the One-Line Display for
input voltage level, battery charge/discharge
current, and output load percentage kW.
Investigate any abnormal readings.
If the reason for the alarm cannot be determined,
contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Attempt to manually close the disconnect by
pressing “Startup,” “Device Control,” “Close Trap.”
If the condition which caused the filter disconnect
to lock open is still present, it re-opens.
If the disconnect cannot be manually closed or the
alarm cannot be cleared, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Examine the One-Line Display. The Rectifier input
line feeding the Input Breaker should be green. If
not, investigate source power to the UPS.
If input power is good, and this alarm is active,
contact your factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Press “RESET” to clear the alarm.
If the alarm cannot be reset, or if the alarm
condition returns, contact your factory-authorized
service provider.
Press “SILENCE” to silence the audible alarm.
Check the Module Output Meter and note the A
phase load percentage.
If possible, reduce A phase loading.
If the steady state load remains above 105%, allow
the UPS to transfer to bypass and contact your
factory-authorized service provider.
If the displayed load percentage is less than 100%
and the alarm is still active, contact your factoryauthorized service provider.
Input
Current
Limit
Input Filter
Cycle
Input Not
Avail
Internal
Comm
Error
Inv Overload
Ph A
detected input current (RMS) exceeds the limit
setpoint (default is 125%). This may be normal
depending on various operating conditions, such
as input voltage level, output load level, and
whether the batteries have recently discharged.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The Input Filter Disconnect is locked open.
The Input Filter Disconnect Cycle counter has
exceeded the setpoint. The Input Filter
Disconnect opens automatically as determined
by the disconnect settings, or because of an
unusual condition.
An example of a setting would be to
automatically open the filter disconnect under
light load conditions to improve the input power
factor. An example of an unusual condition
would be unbalanced currents on the input,
possibly because of a suspect component in the
filter itself.
This summary alarm means there is a problem
with input power. It is not acceptable to the
Rectifier.
If the unit is running normally when this event
occurs, the UPS goes to battery.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal
This is a summary event caused by an
interruption in communication between the
controls and a device on the Controller Area
Network (CAN).
The Internal Communication Error event
indicates a loss of communications between the
controls and an external device.
The Internal Communication Error is displayed
when the controls detect a loss of
communication to a device on the Controller
Area Network (CAN).
An infrequent occurrence that resets
immediately is probably not serious.
An overload condition is active on A phase.
A phase load condition exceeds 105%.
A countdown timer is displayed on the One-Line
Display in response to this alarm, and indicates
the time remaining until a transfer to bypass
occurs. The length of time remaining until
transfer is directly proportional to the severity of
the overload.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
89Liebert
®
NXL
™
Page 98
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
Inv Overload
Ph B
Inv Overload
Ph C
Inv Ovld
Exceeded
Inverter
Fault
Inverter Output
Breaker (CB2)
Open
An overload condition is active on B phase.
B phase load condition exceeds 105%.
A countdown timer is displayed on the One-Line
Display in response to this alarm, and indicates
the time remaining until a transfer to bypass
occurs. The length of time remaining until
transfer is directly proportional to the severity of
the overload.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
An overload condition is active on C phase.
C phase load condition exceeds 105%.
A countdown timer is displayed on the One-Line
Display in response to this alarm, and indicates
the time remaining until a transfer to bypass
occurs. The length of time remaining until
transfer is inversely proportional to the severity
of the overload.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
This message is displayed in response to an
overload on one or more output phases.
When an overload occurs, the controls display a
countdown timer that displays the time remaining
until a transfer to bypass occurs. The length of
the timer is inversely proportional to the
amplitude of the overload. When the timer
reaches zero, the UPS transfers to bypass and
populates the Active Event Window with this
alarm.
This fault is non-latching. When the underlying
condition is no longer present, this fault and any
control activity tied directly to this fault reverts to
normal.
This summary event indicates a potentially
serious problem in the Inverter.
The controls react to an Inverter fault in different
ways depending on the root event that caused
the fault. If bypass is available, the controls
transfer to static bypass.
A restart may or may not be possible.
The inverter output breaker indicates that it is in
the open position.
Press “SILENCE” to silence the audible alarm.
Check the Module Output Meter and note the B
phase load percentage.
If possible, reduce B phase loading.
If the steady state load remains above 105%, allow
the UPS to transfer to bypass and contact your
factory-authorized service provider.
If the displayed load percentage is less than 100%
and the alarm is still active, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the Module Output Meter and note the C
phase load percentage.
If possible, reduce C phase loading.
If the steady state load remains above 105%, allow
the UPS to transfer to bypass and contact your
factory-authorized service provider.
If the displayed load percentage is less than 100%
and the alarm is still active, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Observe the load percentages for each phase on
the Module Output Meter. If the load is less than
100%, attempt to transfer back to Inverter by
pressing “Transfer,” “UPS.”
If the transfer is successful, investigate the reason
for the overload and take appropriate action.
If the transfer is unsuccessful, contact your factoryauthorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the One-Line Display to determine the state
of the UPS. If both the Rectifier and Inverter are
shut Off, press “RESET” to attempt to clear any
latched alarms or faults.
Attempt a restart by pressing “Startup,” “Manual
Start,” and follow the prompts to place the UPS
back in service.
If the startup fails, contact your factory-authorized
service provider.
If the Rectifier and Inverter appear to be running,
press “RESET” to attempt to clear any latched
alarms or faults, then attempt a transfer by
pressing “Transfer,” “UPS.” If the transfer is
successful, contact your factory-authorized service
provider.
If the transfer is unsuccessful, contact your factoryauthorized service provider.
Liebert® NXL
™
90
Page 99
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
This UPS system has been enabled as the
functional Master Load Bus Synchronization
(LBS) system.
The functional Master is sending the LBS sync
LBS Active Master
pulse.
This status message is self-clearing when the
LBS is disabled or this system is no longer
selected as the LBS Master. When the condition
is no longer present, the message and any
control activity tied to the status event reverts to
normal.
With LBS operation enabled, conditions required
to allow LBS operation are not met.
Voltage or Frequency differences sensed by the
LBS
Inhibited
LBS control are preventing the ability of LBS to
function correctly.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
With a load of 80% or greater, the controls have
calculated the output Power Factor to be less
than 0.95 leading.
Leading
Pwr
Factor
Leading Power Factors result in wasted energy.
If the Power Factor is less than 0.95 leading, the
UPS output is de-rated to compensate for output
losses.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
Load Bank
Breaker (LBB)
Open
Load on
Bypass
Load on
Maint Byp
The load bank breaker indicates that it is in the
open position.
The load is being supplied by bypass.
The load is on Maintenance Bypass
Load on UPSThe load is being supplied by the Inverter
The multi-module system has less than one
redundant module online. The number of
redundant modules is calculated by taking the
number of modules online minus the numbers of
modules of load, rounded down to the nearest
whole number (i.e., 3 Modules Online - 1.75
Loss of
Redundancy
Modules of Load = 1 redundant modules online).
This is a “notification only” type alarm, meaning
the UPS takes no action other than sounding an
audible alarm based on this setpoint.
The alarm is self-clearing.
The alarm condition can be permanently
terminated by selecting NO in the Paralleling
Modules selection of the Service Settings
located in the configuration screen.
A module in a multi-module system has detected
a loss of the sync pulse.
Loss of
Sync Pulse
The system shall change sync master in an
attempt to correct the loss of sync pulse.
If operating normally, the SCC always posts this
event.
Under normal circumstances, none.
If this message is active, and there is no clear
reason why the LBS circuit should be active,
contact your factory-authorized service provider
Press “SILENCE” to silence the audible alarm.
Check both Systems and verify normal operation:
Both Systems running online on inverter;
Neither System in Maintenance Bypass;
No Bypass, Input, or Synchronization errors
present on either system.
If the cause of the alarm cannot be determined by
checking both Systems, contact your
factory-authorized service provider.
Press “SILENCE” to silence the audible alarm.
Check the Output Meter readings and verify the
Output Power Factor. If the displayed power factor
is less than 0.95 leading, and the load is greater
than 80%, reduce the load or investigate.
Contact your factory-authorized service
representative.
Press “SILENCE” to silence the audible alarm.
Check the system load and verify that the system
is non-redundant.
To enable/disable the setting for the Loss of
Redundancy you must select YES/NO (Enable/
Disable) in the Parallelling Modules selection
located in the User Settings of the Configuration
Press “SILENCE” to silence the audible alarm.
Contact your factory-authorized service provider.
91Liebert
®
NXL
™
Page 100
UPS Alarm and Status Messages
Table 10Liebert NXL alarm and status messages (continued)
Event MessageEvent DefinitionRecommended Action
One or more battery circuit breakers are open.
Low Batt
Capacity
Low Batt
Shutdown
Low Battery
Warning
Low
Power
Factor
This alarm applies if the system includes more
than one battery circuit breaker, and at least one
is closed, but one or more are open.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The Battery has reached End of Discharge
(EOD).
There is no longer enough energy left in the
battery to run the Inverter with the current load.
If bypass is available, the UPS attempts to
transfer the load to bypass at EOD.
The battery is nearly depleted, and the unit shuts
down very soon.
The Low Battery Warning setpoint is adjustable
under User Settings. This alarm means the
calculated time remaining on battery is now less
than the Low Battery Warning setpoint.
This alarm is self-clearing. When the condition is
no longer present, the alarm and any control
activity tied to the alarm reverts to normal.
The output power factor is low.
The output power factor is less than 70% leading
or lagging. A simplified explanation of power
factor is the ratio of energy being supplied to
energy being used by the load. For a given load,
the current output of the UPS goes up as power
factor decreases.
This results in the UPS output being derated.
For example, study the following:
Load = 100 kw @ 480V
amps = kW X 1000 / volts X power factor X 1.73
(square root of 3)
100kW X 1000 = 100000
480V X 0.9PF X 1.73 = 747.36
100000/747.36 = 133.8A
Now, replace the 0.9 power factor (typical
computer load power factor) with 0.7 power
factor:
100kW X 1000 = 100000
480V X 0.7PF X 1.73 = 581.28
100000/581.28 = 172A
The load remains the same, but the current
required to supply it is roughly 30% higher. The
extra current is wasted energy that can result in
nuisance trips of breakers, overheating of
cables, and other unwanted conditions. The UPS
cannot control the output power factor.
This alarm is notification to the user that the load
should be evaluated.
Press “SILENCE” to silence the audible alarm.
To clear this alarm, verify all battery breakers are
closed. Investigate any open breakers.
Press “SILENCE” to silence the audible alarm.
Once power is restored, attempt a normal restart of
the UPS.
If the restart fails, contact your factory-authorized
service provider.
Check to see if bypass is available by observing
the One-Line Display. Acceptable bypass voltage
is indicated by a green power line feeding the
Static Bypass Switch (BPSS) box.
If bypass is available, press “Transfer,” “Bypass” to
transfer to bypass. If the bypass is qualified, the
UPS transfers to the bypass source.
If bypass is not available, prepare to shut down
critical loads, or remove non-essential loads in
order to extend battery run time so that critical
loads may be shut down in an orderly manner.
Press “SILENCE” to silence the audible alarm.
Evaluate the load on the UPS. For more
information, contact your factory-authorized
service provider
Liebert® NXL
™
92
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.