Emerson Liebert NXL Installation Manual

Page 1
AC Power For Business-Critical Continuity™
Liebert® NXL
Installation Manual – 500-750, 60Hz, Three-Phase, Single-Module & Multi-Module
Page 2
To contact Liebert Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Emerson Network Power Liebert Services, the authorized distributor is responsible for providing qualified, factory-authorized service.
For Liebert Services to assist you promptly, please have the following information available:
Part numbers: _________________________________________________________________
Serial numbers:________________________________________________________________
Rating: _______________________________________________________________________
Date purchased: _______________________________________________________________
Date installed:_________________________________________________________________
Location: ______________________________________________________________________
Input voltage/frequency:________________________________________________________
Output voltage/frequency: ______________________________________________________
Battery reserve time:___________________________________________________________
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.1 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.2 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.3 Floor Installation/Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.0 UPS ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2.1 Power Cable Connection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Control Cable and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.2 Analog Load Bus Synch Connection to Non-Liebert NXL Equipment . . . . . . . . . . . . . . . . . . 11
2.3.3 Multi-Module Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3.4 Remote Input Breaker (RIB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3.5 Inverter Output Breaker (IOB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4 Digital LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5 Configuring Neutral and Ground Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.1 Four-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.2 Three-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5.3 Preferred Grounding Configuration, Battery Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.5.4 Multi-Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.0 OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.1 Single-Module System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.1 Matching Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.2 Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.3 Matching Liebert NXL Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.4 Matching Module Battery Disconnect—MBD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.5 Load Bus Synch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.1.6 Remote Alarm Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2 Communication and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.1 Alber Monitoring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
i
Page 4
FIGURES
Figure 1 Cabinet arrangement—Liebert NXL, battery cabinets, maintenance bypass cabinet . . . . . . . . . . 5
Figure 2 Cabinet grounding plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 3 Kick plate and filter locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 4 Low-voltage cable installation—top entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5 External Interface Board connections layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules . . . . . . . . . . . . . . . . . . . . 14
Figure 7 Remote Input Breaker diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 8 Remote Output Breaker diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 9 Inter-Module Communication Board wiring diagram—Digital LBS . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 10 Main components, 500kVA Liebert NXL 1+N multi-module or SMS with static bypass. . . . . . . 21
Figure 11 Outline drawing, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static bypass . . . 22 Figure 12 Output terminal details, Pg. 1, Liebert NXL 500kVA UPS 1+N multi-module or SMS with
static bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 13 Output terminal details, Pg. 2, Liebert NXL 500kVA UPS 1+N multi-module or SMS with
static bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 14 Base drawing, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static bypass . . . . . . 25
Figure 15 Main components, 750kVA Liebert NXL UPS without static bypass . . . . . . . . . . . . . . . . . . . . . . 26
Figure 16 Main components, 750kVA Liebert NXL UPS with static bypass (SMS OR 1+N) . . . . . . . . . . . . 27
Figure 17 Outline drawing, 750kVA Liebert NXL without static bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 18 Outline Drawing, 750kVA Liebert NXL 1+N multi-module or SMS with static bypass . . . . . . . 29
Figure 19 Base detail drawing, 750kVA Liebert NXL, N+1 multi-module without static bypass . . . . . . . . 30
Figure 20 Base Drawing, 750kVA Liebert NXL 1+N multi-module or SMS with static bypass. . . . . . . . . . 31
Figure 21 Input/output terminal detail, 750kVA Liebert NXL without static bypass. . . . . . . . . . . . . . . . . . 32
Figure 22 Detail 750kVA Liebert NXL with static bypass (SMS/1+N). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 23 Input/output terminal detail, 750kVA Liebert NXL without static bypass (continued) . . . . . . . . 34
Figure 24 Input/output terminal detail, 750kVA Liebert NXL with static bypass (SMS or
1+N) continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 25 Shipping split 750kVA Liebert NXL without static bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 26 Shipping Split, 750kVA Liebert NXL with static bypass (SMS/1+N) . . . . . . . . . . . . . . . . . . . . . . 37
Figure 27 Shipping Split, 750kVA Liebert NXL with static bypass (SMS/1+N) continued. . . . . . . . . . . . . . 38
Figure 28 Single-input wire cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 29 Control cable layout, UPS active analog load bus sync, 250-750kVA units . . . . . . . . . . . . . . . . . 40
Figure 30 Control cable layout, UPS passive analog load bus sync, 250-750kVA units . . . . . . . . . . . . . . . . 40
Figure 31 Control cable layout, UPS analog load bus sync, ELBS, 250-750kVA units . . . . . . . . . . . . . . . . . 41
ii
Page 5
TABLES
Table 1 UPS input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2 UPS control contacts with battery cabinet or module battery disconnect. . . . . . . . . . . . . . . . . . . 10
Table 3 UPS control contacts with maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 4 UPS control contacts to remote status panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 5 UPS control contacts with analog LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 6 Parallel from UPS module Inter-Module Communication Board to other Inter-Module
Communication Board in system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 7 RIB UV coil, aux. contacts from UPS RIB CB interface board to remote CB1 . . . . . . . . . . . . . . . 15
Table 8 Remote IOB contacts from remote breaker to UPS IOB CB interface board . . . . . . . . . . . . . . . . 17
Table 9 Wire size, length for digital LBS connection of UPS Inter-Module Communication
Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 10 Liebert NXL UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 11 Current ratings—rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 12 Current ratings—bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 13 Current ratings—output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 14 Current ratings—battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 15 Recommended conduit and cable sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 16 Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 17 Recommended torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
iii
Page 6
iv
Page 7
IMPORTANT SAFETY INSTRUCTIONS
!
!
!
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert NXL to your installation, before working with the UPS. Retain this manual for use by installing per-
sonnel.
UPS. Read this manual thoroughly, paying special attention to the sections that apply
WARNING
Risk of electrical shock. Can cause personal injury or death. This UPS has several circuits that are energized with high DC as well as AC voltages. Check
for voltage with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance. Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, SL-25425, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight is up to 13,200lb (5988kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the module cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or prepare unit for installation.
WARNING
Risk of electrical shock and fire. Can cause equipment damage, personal injury or death. Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections.
All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes.
One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.
1
Page 8
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.
2
Page 9
1.0 MECHANICAL INSTALLATION
!
1.1 Introduction
This section describes the requirements that must be taken into account when planning the position­ing and cabling of the Liebert NXL uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures.
WARNING
Risk of electrical shock. Can cause injury or death. Special care must be taken when working with the batteries associated with this equipment.
When they are connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal.
NOTE
All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation.
NOTICE
Three-phase input supply required. The standard Liebert NXL UPS is suitable for connection to three-phase, four-wire (+ Earth)
TN-C, TN-S, IT-G or IT-IG, or three-phase, three-wire plus ground IT-UG. If the unit is used with an IT power system, a 4-pole disconnect device must be included as
part of building installation.
Mechanical Installation
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
1.2 Preliminary Checks
Before installing the UPS, please carry out the following preliminary checks:
• Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the interior doors reporting the type, size and main calibration parameters of the UPS.
• Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
1.3 Environmental Considerations
1.3.1 UPS Room
The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air envi­ronment with adequate ventilation to keep the ambient temperature within the specified operating range (see Environmental Parameters in Table 10).
The Liebert NXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and pre­vent overheating or malfunctioning, do not cover the ventilation openings.
The Liebert NXL UPS is equipped with air filters located behind the front doors and kick plates. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions.
When bottom entry is used, the conduit plate must be installed.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
3
Page 10
1.3.2 Storage
!
Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and/or heat sources (see Environmental Parameters in Table 10).
1.4 Positioning
The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminal blocks and power switches is from the front.
The door can be opened to give access to the power connection bars, auxiliary terminal blocks and power isolators. Front door can be opened at 180 degrees, and interior doors can be removed for more flexibility in installations.
NOTE
The UPS must be placed a solid floor. There must be no openings in floor except those required for conduit landing areas. All provided kick plates must be installed.
1.4.1 Moving the Cabinets
The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
Ensure that the UPS weight is within the designated surface weight loading (kg/cm equipment. For weight details, see Table 10.
The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will sup­port the unit only if the forks are completely beneath the unit.
Handling with straps is not authorized.
Mechanical Installation
2
) of any handling
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Because the weight distribution in the cabinet is uneven, use extreme care while handling and transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weight is up to 13,200lb (5988kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
1.4.2 Clearances
The Liebert NXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24in (610mm) between the top of the UPS and any over­head obstacles to permit adequate circulation of air coming out of the unit.
1.4.3 Floor Installation/Anchoring
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal. Kick plates must be installed. If the unit is to be installed in a position that permits access to rear kick plates, then kick plates must be installed before the unit is placed in its final position.
4
Page 11
Mechanical Installation
Note: If a maintenance bypass cabinet is used, it must be installed on the right side of the Liebert NXL UPS
Liebert
NXL
UPS
Liebert
NXL
UPS
Maintenance
Bypass Cabinet
Battery
Cabinet
Liebert
NXL
UPS
Maintenance
Bypass Cabinet
Additional
Battery
Cabinet(s)
Battery
Cabinet
Liebert
NXL
UPS
Additional
Battery
Cabinet(s)
Battery
Cabinet
Liebert
NXL
UPS
Additional
Battery
Cabinet(s)
If the cabinets are to be bolted together, the side panels and hangers must be removed before beginning.
Note: Battery cabinets can be bolted to the right of the UPS. However, the cabling must be routed externally.
1.5 System Composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements: e.g., UPS cabinet, battery cabinet, maintenance bypass cabinet. In general, all the cabinets used in a particular installation are of the same height. Refer to the drawings provided in
4.0 - Installation Drawings for the positioning of the cabinets as shown in Figure 1.
1.6 Cable Entry
Cables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) section of the unit; see the figures in 4.0 - Installation Drawings.
Figure 1 Cabinet arrangement—Liebert NXL, battery cabinets, maintenance bypass cabinet
5
Page 12
2.0 UPS ELECTRICAL INSTALLATION
!
!
This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.
WARNING
Risk of electrical shock. Can cause injury or death. The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC
voltmeters before working within the UPS.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation.
2.1 External Protective Devices
For safety, it is necessary to install circuit breakers in the input AC supply and external battery sys­tem. Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed.
External overcurrent protection must be provided. See Table 10 - Liebert NXL UPS specifications for overload capacity.
UPS Electrical Installation
2.2 Power Cables
The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run separately from the power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.
The cable design must comply with the voltages and currents in Tables 11 through 14, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media), room temperature and conditions of installation of the cable and system’s overload capacity (see 5.0 - Specifications).
WARNING
Risk of electrical shock. Can cause injury or death. Before cabling the UPS, ensure that you are aware of the location and operation of the
external isolators that connect the UPS input/bypass supply to the power distribution panel. Check that these supplies are electrically isolated, and post any necessary warning signs to
prevent their inadvertent operation.
When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given in Table 14.
The following are guidelines only and are superseded by local regulations and codes of practice where applicable:
• Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non­linear loads. Refer to the values in Table 10.
• The grounding conductor should be sized according to the fault rating, cable lengths, type of pro­tection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.
• Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.
• AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields.
6
Page 13
2.2.1 Power Cable Connection Procedure
!
!
!
The rectifier input, bypass, output and battery power cables (all require lug-type terminations) are connected to busbars in the I/O sections (refer to 4.0 - Installation Drawings).
Equipment Ground The equipment ground busbar is in the I/O sections as shown in (refer to 4.0 - Installation Draw-
ings). The grounding conductor must be connected to the ground busbar and bonded to each cabinet
in the system. All cabinets and cabling should be grounded in accordance with local regulations.
NOTE
Proper grounding reduces problems in systems caused by electromagnetic interference.
WARNING
Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur.
All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Emerson Network Power. See the back page of this manual for contact information.
The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice.
Once the equipment has been positioned and secured, connect the power cables as described below (refer to the appropriate cable connection drawing in 4.0 - Installation Drawings):
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.
2. Open exterior and interior panels on the front of the I/O sections.
3. Connect the ground and any necessary main bonding jumper to the equipment ground busbar located in the I/O sections.
4. Make power connections and tighten the connections to the proper torque.
Ensure correct phase rotation.
UPS Electrical Installation
WARNING
Risk of electrical shock. Can cause injury or death. If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, ensure that the system output cables are safely isolated at their termination.
WARNING
Risk of electrical shock. Can cause injury or death. When connecting the cables between the battery extremities to the circuit breaker, always
connect the circuit breaker end of the cable first.
5. For control connection details, see 2.3 - Control Cable and Communication.
NOTE
If fault bracing brackets were removed during installation, they MUST be replaced.
6. Close and secure the interior and exterior doors.
7. Attach the cabinet grounding plates to the top of the UPS at each shipping split. See Figure 2.
8. Attach the kick plates and filters to the bottom of the unit. See Figure 3.
7
Page 14
Figure 2 Cabinet grounding plates
Note location of larger cutouts. Orient ground plate as shown.
A
Mounting Hardware (Supplied)
Installed at Each Shipping Split
Detail A
INSTALL M6X25 BOLT, LCKW AND WSHR (4) PLACES, FRONT SIDE
INSTALL M6X25 BOLT, LCKW AND WSHR (2) PLACES, EACH SIDE
FRONT
KICKPLATE
KICKPLATE
REAR
KICKPLATE
KICKPLATE
INSTALL M6X25 BOLT,
LCKW AND WSHR
(4) PLACES, REAR SIDE
INSTALL M6X60 BOLT, LCKW AND WSHR (2) PLACES, FRONT SIDE
D
DETAIL D
E
DETAIL E
G
DETAIL G
F
Low-voltage cables can be install through the top of each unit. The entry conduit landing plate is shipped inverted. To install, remove conduit plate, flip and reinstall. Removal of side plate is for access to pull wires.
REMOVE PLATES
FLIP PLATES
INSTALL
Figure 3 Kick plate and filter locations
UPS Electrical Installation
NOTE
Kick plates must be installed. If the unit is to be installed in a position that permits access to rear kick plates, then kick plates must be installed before the unit is placed in its final position.
Figure 4 Low-voltage cable installation—top entry
8
Page 15
2.3 Control Cable and Communication
P66C P99C
TB0823
EPO
STATUS
TB0829
EXTERNA L
CAN
TB1154B TB1154A
TB0825
TB0824
TB0826
TB0820
TB0818
TB0817
TB0819
TB0816
TB0830
TB035TB0821
P0801
TB0811
TB0810
TB0813
TB0812
TB0815
P0832
P0831
P0808
OPT
PS
INT BATT
CAN
EXT BATT
CAN
REPO
J4
REPO
FORM C
LBS VOLTAGE
EXTERNA L
CAN
MOB
MIB
RIB
MBB
BIB
KEY
STATUS
INV
CNTRLN
RECT CNTL
BYP CNTL
ON GEN
ACT FILT STATUS
BATT GND
FLT
ACT FILT
CNTL
MAINT BYP
ENABLE
AUX SPARE
TEMP
J5
BATT MTR
OP
TB1156
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker), communicate with a personal computer or provide alarm signaling to external devices, or for Remote Emergency Power Off (REPO). The External Interface Board, arranged for this purpose, is next to the option box in the Rectifier section (refer to 4.0 - Installation Drawings).
Figure 5 External Interface Board connections layout
UPS Electrical Installation
9
Page 16
2.3.1 Dry Contacts
NOTE
If connection to more than one module is required, use a separate contact for each module.
Table 1 UPS input dry contacts
Item
Remote EPO Input Form C
On Generator Input Form C
Table 2 UPS control contacts with battery cabinet or module battery disconnect
Item
CAN Bus and 24V Power Supply
Terminal
Block Pin
TB0824
TB0816
Terminal
Block Pin
TB1154A
Connects to
(Description of External Item)
1 REPO Switch, normally open contact
2 REPO Switch, common contact
REPO Switch, normally closed contact, set jumper
3
J5: 1-2 to enable, 2-3 to disable
1 On Generator switch, closed = On Generator
2 On Generator switch, common
On Generator switch,
3
closed = Not On Generator
Connects to
(Description of External Item)
1 Battery Interface Board TB1154-1
2 Battery Interface Board TB1154-2
3 Battery Interface Board TB1154-3
4 Battery Interface Board TB1154-4
UPS Electrical Installation
Wire Size/
Max Length
14AWG/
500ft.
Wire Size/
Max Length
18 AWG
1000ft.
Table 3 UPS control contacts with maintenance bypass
Terminal
Item
Maintenance Isolation Breaker (MIB) Form C
1
Maintenance Bypass Breaker (MBB) Form C
Maintenance Bypass Enable Form C
Remote EPO Input
1
1
1
Block Pin
TB0811
TB0813
TB0821
TB0825
(Description of External Item)
1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open 1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open
Maintenance Bypass Cabinet,
1
closed = load not on inverter
2 Maintenance Bypass Cabinet, common
Maintenance Bypass Cabinet,
3
closed = load on inverter 1 REPO Switch, normally open contact 2 REPO Switch, common contact 1 Key status switch, closed = key removed
Key Status Input Form C
TB0820
2 Key status switch, common
1
3 Key status switch, closed = key inserted
Module Output Breaker (MIB) Form C
2
Rectifier Input Breaker (RIB) Form C
TB0815
TB0810
1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open 1 CB aux. contact, closed = CB is closed 2 CB aux. contact, common 3 CB aux. contact, closed = CB is open 1 CB aux. contact, closed = CB is closed
Bypass Input Breaker (BIB) Form C
1. For 1+N systems with a maintenance Bypass, these Aux contacts must be run to each module from an isolated source.
2. For 1+N systems, these breaker Aux contact go to the UPS that it is associated with.
TB0812
2 CB aux. contact, common
CB or Switch aux. contact, 3
closed = CB or switch is open
Connects to
Wire Size/
Max Length
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
14AWG/500ft.
(152m)
10
Page 17
Table 4 UPS control contacts to remote status panel
Item
CAN Bus and 24V Power Supply
Terminal
Block Pin
TB0829
(Description of External Item)
1 Remote Status Panel TB-2
2 Remote Status Panel TB-1
3 Remote Status Panel TB-3
4 Remote Status Panel TB-4
Connects to
Wire Size/
Max Length
18 AWG/1000ft.
(304m)
2.3.2 Analog Load Bus Synch Connection to Non-Liebert NXL Equipment
Refer to Figures 29 through 31 for layouts.
Table 5 UPS control contacts with analog LBS
Terminal Designation
Signal Name Wire Range/Max LengthFrom To
ANALOG LBS SIGNALS FROM UPS POWER BUS BARS TO LBS TRANSFORMER BOX
V-OUT-A F72 CRITICAL BUS VOLTS PH A
V-OUT-C F74 CRITICAL BUS VOLTS PH C
V-BYP-A F69 BYPASS VOLTS PH A
V-BYP-C F71 BYPASS VOLTS PH C
ANALOG LBS SIGNALS FROM UPS LBS INTERFACE BOARD TO LBS TRANSFORMER BOX
TB0826-1 TB27-7 SYNCH PH A
TB0826-5 TB27-9 SYNCH PH C
UPS Electrical Installation
#14-22AWG/500FtV-OUT-B F73 CRITICAL BUS VOLTS PH B
#14-22AWG/500FtV-BYP-B F70 BYPASS VOLTS PH B
#14-22AWG/500FtTB0826-3 TB27-8 SYNCH PH B
ANALOG LBS SIGNALS FROM UPS LBS TRANSFORMER BOX ASSEMBLY TO LBS BOX - SYSTEM #1
TB27-7 TB4-4 SYNCH PH A
TB27-8 TB4-5 SYNCH PH B
TB27-9 TB4-6 SYNCH PH C
TB27-4 TB3-1 CRITICAL BUS VOLTS PH A
TB27-5 TB3-2 CRITICAL BUS VOLTS PH B
TB27-6 TB3-3 CRITICAL BUS VOLTS PH C
TB27-1 TB2-2 BYPASS VOLTS PH A (V&I BOARD IN LBS BOX)
TB27-2 TB2-5 BYPASS VOLTS PH B (V&I BOARD IN LBS BOX)
TB27-3 TB2-9 BYPASS VOLTS PH C (V&I BOARD IN LBS BOX)
TB27-11 TB1-1 LBS POWER SUPPLY
TB27-12 TB1-2 LBS POWER SUPPLY
ANALOG LBS SIGNALS FROM UPS INTER-MODULE COMMUNICATION BOARD TO LBS BOX - SYSTEM #1
P3105-3 TB1-1 SYNCH TO MASTER (LBS BOARD IN LBS BOX)
P3105-4 TB1-2 SYNCH TO MASTER RETURN (LBS BOARD IN LBS BOX)
P3107-2 TB5-5
P3107-1 TB5-4 SYSTEM ON BYPASS (N.C.) (V&I BOARD IN LBS BOX)
P3107-6 TB1-7
P3107-5 TB1-8
SYSTEM ON BYPASS (N.C.) RETURN (V&I BOARD IN LBS BOX)
TRANSFERRED TO BYPASS (LBS BOARD IN LBS BOX) ­FOR ACTIVE LBS OPTION
TRANSFERRED TO BYPASS RETURN (LBS BOARD IN LBS BOX) - FOR ACTIVE LBS OPTION
#14-22AWG/500Ft
#18AWG/500Ft
#14-22AWG/500Ft
#14-22AWG/500Ft
11
Page 18
Table 5 UPS control contacts with analog LBS (continued)
Terminal Designation
Signal Name Wire Range/Max LengthFrom To
Analog LBS Signals from UPS LBS Transformer Box Assembly to LBS Box - System #2
TB27-7 TB3-4 SYNCH PH A
TB27-8 TB3-5 SYNCH PH B
TB27-9 TB3-6 SYNCH PH C
TB27-4 TB4-1 CRITICAL BUS VOLTS PH A
TB27-5 TB4-2 CRITICAL BUS VOLTS PH B
TB27-6 TB4-3 CRITICAL BUS VOLTS PH C
TB27-1 TB3-1 BYPASS VOLTS PH A (V&I BOARD IN LBS BOX)
TB27-2 TB3-5 BYPASS VOLTS PH B (V&I BOARD IN LBS BOX)
TB27-3 TB3-10 BYPASS VOLTS PH C (V&I BOARD IN LBS BOX)
TB27-11 TB2-1 LBS POWER SUPPLY
TB27-12 TB2-2 LBS POWER SUPPLY
Analog LBS Signals from UPS Inter-Module Communication Board to LBS Box - System #2
P3105-3 TB2-1 SYNCH TO MASTER (LBS BOARD IN LBS BOX)
P3105-4 TB2-2 SYNCH TO MASTER RETURN (LBS BOARD IN LBS BOX)
P3107-2 TB5-2
P3107-1 TB5-1 SYSTEM ON BYPASS (N.C.) (V&I BOARD IN LBS BOX)
P3107-6 TB2-7
P3107-5 TB2-8
SYSTEM ON BYPASS (N.C.) RETURN (V&I BOARD IN LBS BOX)
TRANSFERRED TO BYPASS (LBS BOARD IN LBS BOX) ­FOR ACTIVE LBS OPTION
TRANSFERRED TO BYPASS RETURN (LBS BOARD IN LBS BOX) - FOR ACTIVE LBS OPTION
UPS Electrical Installation
#14-22AWG/500Ft
#18AWG/500Ft
#14-22AWG/500Ft
#14-22AWG/500Ft
Analog LBS Signals from UPS LBS Transformer Box Assembly to ELBS BOX
TB27-7 TB4-4 SYNCH PH A
TB27-8 TB4-5 SYNCH PH B
TB27-9 TB4-6 SYNCH PH C
TB27-4 TB3-4 CRITICAL BUS VOLTS PH A
TB27-5 TB3-5 CRITICAL BUS VOLTS PH B
TB27-6 TB3-6 CRITICAL BUS VOLTS PH C
TB27-1 TB2-2 BYPASS VOLTS PH A
TB27-2 TB2-5 BYPASS VOLTS PH B
TB27-3 TB2-9 BYPASS VOLTS PH C
TB27-11 TB1-1 LBS POWER SUPPLY
TB27-12 TB1-2 LBS POWER SUPPLY
Analog LBS Signals from UPS/SCC Inter-Module Communication Board to ELBS Box
P3105-3 TB1-1 SYNCH TO MASTER (LBS BOARD IN LBS BOX)
P3105-4 TB1-2 SYNCH TO MASTER RETURN (LBS BOARD IN LBS BOX)
P3107-2 TB5-5
SYSTEM ON BYPASS (N.C.) RETURN (V&I BOARD IN LBS BOX)
P3107-1 TB5-4 SYSTEM ON BYPASS (N.C.) (V&I BOARD IN LBS BOX)
#14-22AWG/500Ft
#18AWG/500Ft
#14-22AWG/500Ft
12
Page 19
2.3.3 Multi-Module Communication
Paralleling cables that connect the module to the system are connected to terminals P3101 and P3103 on the Inter-Module Communication (IMC) board (refer to 4.0 - Installation Drawings).
Table 6 Parallel from UPS module Inter-Module Communication Board to other Inter-Module
Communication Board in system
Terminal Designation
Primary Connections
P3101-1 P3101-1 Share CAN +24V
P3101-2 P3101-2 Share CAN common
P3101-3 P3101-3 System CAN +24V
P3101-4 P3101-4 System CAN common
P3101-5 P3101-5 SER synch CAN+24V
P3101-6 P3101-6 SER synch CAN common
P3101-7 P3101-7 Ground
P3101-14 P3101-14 Ground
P3101-8 P3101-8 PWM synch CAN +24V
P3101-9 P3101-9 PWM synch CAN common
P3101-10 P3101-10 MMS synch CAN +24V
P3101-11 P3101-11 MMS synch CAN common
P3101-12 P3101-12 LBS synch CAN +24V
P3101-13 P3101-13 LBS synch CAN common
Redundant Connections
P3103-1 P3103-1 Redundant share CAN +24V
P3103-2 P3103-2 Redundant share CAN common
P3103-3 P3103-3 Redundant system CAN +24V
P3103-4 P3103-4 Redundant system CAN common
P3103-5 P3103-5 Redundant SER synch CAN +24V
P3103-6 P3103-6 Redundant SER synch CAN common
P3103-7 P3103-7 Ground
P3103-14 P3103-14 Ground
P3103-8 P3103-8 Redundant PWM synch CAN +24V
P3103-9 P3103-9 Redundant PWM synch CAN common
P3103-10 P3103-10 Redundant MMS synch CAN +24V
P3103-11 P3103-11 Redundant MMS synch CAN common
P3103-12 P3103-12 Redundant LBS synch CAN +24V
P3103-13 P3103-13 Redundant LBS synch CAN common
1. Must only use Belden 8106 or Belden 8102.
2. Each cable group should be run in a separate grounded conduit to ensure redundancy.
3. The maximum lengths must include all the parallel cables from the first module to the last module. The primary and redundant cable lengths can be counted separately. The ground pins on the Inter-Module Communication Board (pins 7 and 14) are connected together on the board. If using cable with only one (1) drain wire, then connect to the ground to pin 7.
4. If using (4) Belden 8102 cables, all (4) cables must be run in the same conduit.
Signal Name
UPS Electrical Installation
Wire Size/
Max LengthFrom To
#18AWG/
1000ft
#18AWG/
1000ft
13
Page 20
Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules
UPS 1 UPS 2
UPS 3
P3103
P3101
P3103
P3101
P3103
P3101
IMC
02-806730-xx
IMC
02-806730-xx
IMC
02-806730-xx
A
B
C
E
RIB
10A 10A 10A
IN_LINE_A
IN_LINE_B
IN_LINE_C
INPUT EMI
FILTER
IN_LOAD_A
IN_LOAD_B
IN_LOAD_C
A
B
C
A
B
C
LIN E LOAD
V_IN_R_A
V_IN_R_B
V_IN_R_C
4 CB1_COIL_RTN
3_CB1_NO(CBCLOSED )
2_CB1_NC(CB OPEN)
5CB1_COIL
1_CB1_COM
Inside UPS Cabinet
RIB UVR Coil (48VDC)
RIB Status Contacts
120-240VAC
Close
RIB
RCB1
Elect ric al
Operator
120-240 Vac (suppl ied by
swit chgear vendor )
5_M TR_OP_ CLOSE
2_M TR_OP_ ENA BLE
Circuit Breaker
Interface
Board
02-806711- 01
Inside Switchgear
To Customer
Input
Terminals
121212
RIB-1
1
1
Fuses should be 10A class CC or J type time delay fuse
2
Electrical operator power provided by switchgear vendor and shall be powered from line side of RIB
TB1
TB1-1
TB1-2
TB1-3
2
TB1101
TB1102
2.3.4 Remote Input Breaker (RIB)
For systems that use Remote Input Breakers (RIB), the controls for the Aux contacts, UVR, Motor Operator (optional) and voltage sense will go between the Remote breaker and the UPS Input I/O sec­tion. See Figure 7.
Figure 7 Remote Input Breaker diagram
UPS Electrical Installation
14
Page 21
UPS Electrical Installation
RIB must be Listed UL 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Cir­cuit Breaker) that are required to be used in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating not exceeding 480 Volts at 150K Amperes, for 5 cycles.
See Table 11 for required current ratings.
Table 7 RIB UV coil, aux. contacts from UPS RIB CB interface board to remote CB1
Terminal Designation
Signal Name
TB1101-1 RIB aux. common
TB1101-2 RIB aux. N.C. (closed = CB is open)
Remote Breaker
Contacts
Remote RIB motor operator control contacts from remote breaker to UPS RIB CB interface
Remote Breaker Motor
Operator Contacts
Remote RIB voltage sense from remote breaker to UPS
Remote Breaker
Voltage Sense
TB1101-3 RIB aux. N.O. (closed = CB is closed)
TB1101-4 RIB trip coil (-)
TB1101-5 RIB trip coil (+)
board (optional)
TB1102-2 AC line
TB1102-5 Motor operator close
TB1-1 Voltage sense PH A
TB1-2 Voltage sense PH B
TB1-3 Voltage sense PH C
Wire Size/
Max LengthFrom To
#14AWG/
500ft
#14AWG/
500ft
#14AWG/
500ft
15
Page 22
2.3.5 Inverter Output Breaker (IOB)
A
B
C
E
IOB
5A 5A 5A
OUT_LINE_A
OUT_LINE_B
OUT_LINE_C
OUTPUT EMI
FILTER
OUT_L OAD_A
OUT_L OAD_B
OUT _LOAD_C
A
B
C
A
B
C
LIN E LOAD
V_CB_A
V_CB_B
V_CB_C
TB1101
TB1102
4 CB2_ COI L_R TN
3_CB2_NO (CB CLOSED)
2_C B2_N C (CB OPEN )
5 CB2_ COI L
1_C B2_C OM
Inside UPS Cabinet
IOB UVR
Coil
(48VDC)
Circ uit Break er Interface
Board
02- 806711 -01
Inside Switchgear
To UPS
Output Customer
Connections
1212
1
2
IOB-1
N
1
1
Fuses should be 5A class CC or J type time delay fuse
OUT _LOAD_N
OUT_LINE_N
N
2
Electrical operator power pr ovided by switchgear vendor and shall be powered from UPS side of IOB
N
120 -240 Vac
Close
IOB-x
IOB Electr ical Operator
120 -240 Vac
(suppli ed by
swi tchgear v endor )
5_M TR_O P_C LOSE
2_M TR_O P_EN ABLE
TB2
TB2-1
TB2-2
TB2-3
TB2-4
2
IOB Status
Contact s
For systems that use Inverter Output Breakers (IOB), the controls for the Aux contacts, UVR, Motor Operator (optional) and voltage sense will go between the Remote breaker and the UPS Output I/O section. See Figure 8.
IOB must be Listed UL 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Cir­cuit Breaker) that are required to be used in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating not exceeding 480 Volts at 150K Amperes, for 5 cycles.
Figure 8 Remote Output Breaker diagram
UPS Electrical Installation
See Table 12 for required current ratings.
16
Page 23
Table 8 Remote IOB contacts from remote breaker to UPS IOB CB interface board
Terminal Designation
Remote Breaker
Contacts
Remote IOB contacts from remote breaker to UPS IOB CB interface board
Remote Breaker Motor
Operator Contacts
Remote IOB contacts from remote breaker to UPS IOB CB interface board
Remote Breaker
Voltage Sense
2.4 Digital LBS
The Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or when supplied by unsynchronized input sources.
Signal Name
TB1101-1 IOB aux. common
TB1101-2 IOB aux. N.C. (closed = CB is open)
TB1101-3 IOB aux. N.O. (closed = CB is closed)
TB1101-4 IOB trip coil (-)
TB1101-5 IOB trip coil (+)
TB1102-2 AC line
TB1102-5 Motor operator close
TB1-1 Voltage sense PH A
TB1-2 Voltage sense PH B
TB1-3 Voltage sense PH C
UPS Electrical Installation
Wire Size/
Max LengthFrom To
#14AWG/
500ft
#14AWG/
500ft
#14AWG/
500ft
Digital LBS cables that connect the module to the system are connected to terminals P3108 and P3109 on the Inter-Module Communication (IMC) board. See Figure 9.
Table 9 Wire size, length for digital LBS connection of UPS Inter-Module Communication
Boards
Terminal Designation
Signal Name
Digital LBS from UPS Inter-Module Communication Board to other UPS Inter-Module Communication Board
P3108-1 P3108-1 LBS SYNCH CANH
P3108-2 P3108-2 LBS SYNCH CANL
P3108-3 P3108-3 GROUND
P3108-4 P3108-4 GROUND
Redundant Digital LBS from UPS Inter-Module Communication Board to Other UPS Inter-Module Communication Board
P3109-1 P3109-1 REDUNDANT LBS SYNCH CANH
P3109-2 P3109-2 REDUNDANT LBS SYNCH CANL
P3109-3 P3109-3 GROUND
P3109-4 P3109-4 GROUND
1. Must only use Belden 8104 or (2) Belden 8102.
2. Each cable group should be run in a separate grounded conduit to ensure redundancy.
3. The maximum lengths must include all the LBS cables from the first module to the last module.
4. The primary and redundant cable lengths can be counted separately.
5. If using (2) Belden 8102 cables, all (2) cables must be run in the same conduit.
Wire Size/
Max LengthFrom To
#18AWG/1000ft
(300m)
#18AWG/1000ft
(300m)
17
Page 24
Figure 9 Inter-Module Communication Board wiring diagram—Digital LBS
!
UPS 1 UPS 2
UPS 3
P3108
P3109
P3108
P3109
P3108
P3109
IMC
02-806730-xx
IMC
02-806730-xx
IMC
02-806730-xx
2.5 Configuring Neutral and Ground Connections
Improper grounding is the largest single cause of UPS installation and startup problems. Grounding techniques vary significantly from site to site, depending on several factors.
Proper grounding should be based on NEC Section 250, but safe and proper equipment operation requires further enhancements. The following pages detail recommendations for grounding various system configurations to ensure optimal UPS system performance.
NOTE
Some UPS modules are equipped with input isolation transformers. However, these transformers have no effect upon any system grounding considerations. These modules will be grounded exactly as shown in Figures 1 through 9.
UPS Electrical Installation
CAUTION
The UPS ground lug must be solidly connected to the service entrance ground by an appropriately sized wire conductor per NEC Article 250. Each conduit or raceway containing phase conductors must also contain a ground wire, both for UPS input and output, which are solidly connected to the ground terminal at each termination point. Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding conductor for UPS applications may degrade UPS performance and cause improper UPS operation.
2.5.1 Four-Wire Input connections
The UPS module main input and bypass input are connected to a grounded service. In this configura­tion, the UPS module is not considered a separately derived source. The UPS module output neutral is solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment.
Advantages of this configuration include:
• A measure of common-mode noise attenuation, since the isolation (common-mode rejection) occurs as close to the load as practical (i.e., at the PDU).
• The UPS module can be located remotely from the PDU without compromising common-mode noise performance.
• By using UPS modules with 480VAC input and output and creating 208VAC at the PDU, smaller and less costly power feeders can be used and less voltage drop (as a percent of nominal) occurs.
18
Page 25
2.5.2 Three-Wire Input connections
This configuration must NOT be used when single-phase loads are directly connected to the UPS.
The UPS output transformer is considered a separately derived source. The UPS module neutral is bonded to the UPS ground, which is connected to a local grounding electrode in accordance with NEC 250-26. Please note that this configuration represents a price/performance trade-off. Whenever the UPS module transfers to or from bypass, two AC sources (input and bypass) are briefly connected together and circulating current must flow. In this configuration, the current flows through the ground path, possibly tripping ground fault interrupters (GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping. The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation.
CAUTION
Failure to set the ground fault interrupters properly could cause loss of power to the critical load.
2.5.3 Preferred Grounding Configuration, Battery Systems
Open-rack battery systems, depending on local code requirements and customer preference, are nor­mally:
• Floating (ungrounded)
• Center-tapped and floating or
• Center tapped and grounded
UPS Electrical Installation
Battery cabinet systems must be connected as floating (ungrounded) systems.
Center-tapped or grounded battery systems are not possible with battery cabinet systems.
Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus.
2.5.4 Multi-Module Systems
For both N+1 and 1+N systems, the neutrals of all UPS modules in the system must be connected together inside the switchgear or parallel cabinet. The neutral conductors must be rated for 50% of phase conductor current minimum. Site and load conditions will determine if larger neutrals are required.
For Multi-Module systems using a 3-wire bypass, the Neutral-Ground bond must be made at the com­mon neutral connection point in the switchgear or parallel cabinet.
19
Page 26
3.0 OPTIONAL EQUIPMENT
3.1 Single-Module System Options
3.1.1 Matching Maintenance Bypass Cabinet
A matching Liebert NXL Maintenance Bypass cabinet is available. See Maintenance Bypass Cabinet Installation Manual (SL-24532) for more details.
3.1.2 Battery Temperature Sensor
The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board.
3.1.3 Matching Liebert NXL Battery Cabinet
The optional matching Liebert NXL Battery Cabinet can be used to obtain the desired autonomy time. The battery cabinets are designed to be either attached to the UPS or installed in a separate battery room (for details, see the Liebert NXL Battery Cabinet installation manual, SL-25430, avail­able at Emerson Network Power’s Liebert Web site: www.liebert.com).
3.1.4 Matching Module Battery Disconnect—MBD
The optional Module Battery Disconnect (MBD) can be used as a battery disconnect between a battery system and the Liebert NXL UPS. The battery cabinets are designed to be either attached to the UPS or battery cabinet or installed in a separate battery room (for details, see the Liebert NXL Battery Cabinet installation manual, SL-24530, available at Emerson Network Power’s Liebert Web site:
www.liebert.com).
Optional Equipment
3.1.5 Load Bus Synch
An optional Load Bus Synch (LBS) system can be used to synchronize two Liebert NXL UPS units or a Liebert NXL UPS to a Liebert Series 610 UPS.
3.1.6 Remote Alarm Panel
The remote alarm panel has LED alarm lights. An audible alarm sounds upon any alarm condition. The surface- or flush-mounted NEMA 1 enclosed panel indicates: Load on UPS, Load on Bypass, Bat­tery Discharging, Low Battery Warning, Overload Warning, Ambient Overtemp Warning, UPS Alarm Condition, New Alarm Condition (For a Second UPS Alarm Condition).
3.2 Communication and Monitoring
• Liebert IntelliSlot® Web Card - SNMP/HTTP Network Interface Card
• Liebert IntelliSlot
• Remote Monitoring Services IntelliSlot Card
• RS485/422 Protocol Converter IntelliSlot Card
• Programmable Relay Board
• Input Contact Isolator Board
3.2.1 Alber Monitoring System
The matching Liebert NXL Battery Cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical bat­tery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Addi­tional capabilities include automatic internal DC resistance tests and trend analysis, providing the ability to analyze performance and aid in troubleshooting.
®
485 Web Card - Modbus, J-bus, IGM Net
20
Page 27
Installation Drawings
U40-5C-2000 Rev. 0
OPTION BOX
(6 SLOTS)
LIEBERT INTELLISLOT
HOUSINGS
MAIN INPUT
CIRCUIT BREAKER
(CB1)
MODULE OUTPU T CIRCUIT BREAKER (CB2)
BACK FEED CIRCUIT BREAKER (BFB)
INPUT
BUS BARS
DOORS AND INNER SKINS REMOVED
FRONT DOORS REMOVED
KEYLOCK OR
EMO BUTTON
(OPTIONAL)
HMI SCREEN
INTER-MODULE COMMUNIC ATION BOARD, LOCATED
BEHIND HMI SCREEN
BUSBARS
BYPASS
INPUT
GROUND
OUTPUT GROUND
BUSBARS
OUTPUT
DC (+)
INPUT
DC (-)
INPUT
4.0 INSTALLATION DRAWINGS
Figure 10 Main components, 500kVA Liebert NXL 1+N multi-module or SMS with static bypass
21
Page 28
Installation Drawings
U40-5C-2001 Rev. 0
NOTES:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Aluminum and copper-clad aluminum cables are not recommended.
8. All wiring is to be in accordance with national and local electrical codes.
9. Depth dimension includes front door and rear panel.
10. Width dimensions include side panels. Subtract 1.4" (35mm) when removing both side panels.
INVERTER SPLI T (PART B)
LEFT SIDE VIEW FRONT VIEW
RECTIFIER SPLI T (PART A)
RIGHT SIDE VIEW
.0
.0
DETAIL B
SECTION A-A
BOTTOM VIEW
AA
TOP VIEW
25.5
[647mm]
32.3"
[820mm]
49.2" [1250mm] 62.4" [1585mm]
111.6 [2835mm]
39.6 [1005mm]
76.8"
[1950mm]
35.7"
[906mm]
14.9"
[379mm]
69.8"
[1773mm]
25.8"
[654mm]
10.8"
[273mm]
96.8" [2458mm]
10.8"
[274mm]
14.6"
[370mm]
1.25"
[31.9mm]
10.8"
[275mm]
2.92"
[74mm]
15.6"
[396mm]
10.6
[269mm]
RECTIFIER / DC
CABLE ENTRY
CONTRO L CABLE ENTRY/EXIT
BYPASS/OUTPUT
CABLE ENTRY/EXIT
CABLE ENTRY
BYPASS/OUTPUT
CABLE ENTRY/EXIT
RECTIFIER CENTER OF GRAVITY
INVERTER CENTER OF
GRAVITY
0.6 [15mm]
PANEL WIDTH
FRONT MOST
EDGE OF FRAME
OUTER EDGE
CORNER POS T
Figure 11 Outline drawing, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static bypass
22
Page 29
Installation Drawings
NOTES:
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduit.
3. Aluminum and copper-clad aluminum cables are not recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. See page 2 of 2, drawing number: U40-5E-3201
CB1-3
CB1-3
DUAL LUG CONNECTION DETA IL
Do not double stack lugs (two lugs on sameS ide of busbar). This is to prevent the cablesF rom coming into contact with other busbars.
LUGS
BUS BAR
BOLT
U40-5E-3200 Rev. 0
LEFT SIDE (PART A) LEFT FRONT (PART A)
GROUND BUS
DC INPUT
INPUT
PHASES
CBA
D
C
(
+
)
I
N
P
U
T
D
C
(
-
)
I
N
P
U
T
.0
29.5 (749)
42.4
(1077)
45.6
(1158)
48.8 (1240)
54.6 (1387)
59.2 (1504)
1.75 (44)
TYP
1.75 (44)
TYP
Ø0.50
(13) TYP
DC INPUTS
GROUND
Ø0.50
(13)
TYP
1.75 (44)
TYP
1.75 (44)
TYP
INPUT PHASES
1.75 (44) TYP
Ø0.50
(13) TYP
1.75 (44) TYP
3.0
(76)
3.0
(76)
3.0 (76)
76.8(1950)
Figure 12 Output terminal details, Pg. 1, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static
bypass
23
Page 30
Installation Drawings
Figure 13 Output terminal details, Pg. 2, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static
bypass
1.75 (44)
Ø0.50
(13) TYP
TYP
2.56 (65) TYP
2.56 (65)
TYP
8.7
(220)
OUTPUT, BYPASS & NEUTRAL
76.8 (1950)
59.2 (1504)
44.7 (1135)
31.1 (790)
13.8
(350)
OUTPUT
GROUND
BYPASS &
NEUTRAL
OUTPUT & NEUTRAL
Ø0.50
1.75 (44)
TYP
OUTPUT GROUND
FRONT
ABCN
ABCN
(13) TYP
2.36 (60) TYP
2.36 (60)
TYP
NOTES:
1.All dimensions are in inches (mm).
3. Aluminum and copper-clad aluminum cables are not recommended.
4. All wiring is to be in accordance with national and local electrical codes.
5. See page 1 of 2 , drawing number: U40-5E-3200
CB1-3
CB1-3
Do not double stack lugs (two lugs on same side of busbar). This is to prevent the cables from coming into contact with other busbars.
LUGS
BUSBAR
BYPASS PHASES & NEUTRAL BUS
BOLT
DUAL LUG
CONNECTION DETAIL
OUTPUT PHASES & NEUTRAL BUS
RIGHT FRONT (PART B)
.0
(0)
RIGHT SIDE (PART B)
U40-5E-3201 Rev. 0
24
Page 31
Installation Drawings
U40-5L-1000 Rev. 0
BRACKET MOUNTING LOC ATIONS
(M10 HEXSERTS)
FOOTPRIN T SPACING
LIFT CLEARANCE
SHIPPING SPLIT
RECTIFIER SECTION
(PART A)
NOTES:
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate for forklift handling.
INVERTER SECTION
(PART B)
BOTTOM CABLE ENTRY PANELS
PILLARS REMOVED FOR CLARIT Y
RECTIFIER SECTION
(PART A)
INVERTER SECTION
(PART B)
BOTTOM INPUT (PART A)
BOTTOM OUTPUT (PART B)
FRONT VIEW
RIGHT SIDE
BOTTOM VIEW
FRONT VIEW
RIGHT SIDE
2.2
[56]
33.3
[845]
10.9
[276]
DETAIL A
27.2
[691]
3.9
[99]
4.7 [120] TYP.
3.9 [100] TYP.
7.9 [200] TYP.
37.2
[945]
PILLAR
SPACING
36.7
[931]
FOOT
SPACING
.75
[19]
TYP.
2.4
[61]
21.0
[535]
1.7
[42]
21.0
[535]
4.8
[122]
12.1
[307]
1.7
[42]
13.9
[354]
1.7 [42]
13.9 [354]
1.7
[42]
12.1 [307]
FORKLIFT OPENINGS
3.9
[99]
48.6
[1234]
FORKLIFT OPENINGS
61.8
[1570]
3.9
[100]
9.0
[229]
10.9
[276]
9.0
[229]
18.0
[457]
18.0
[457]
REAR
FRONT
SEE A
8.0 [202]
8.0 [202]
Figure 14 Base drawing, Liebert NXL 500kVA UPS 1+N multi-module or SMS with static bypass
25
Page 32
Figure 15 Main components, 750kVA Liebert NXL UPS without static bypass
Liebert IntelliSlot Housings
HMI Screen
Inter-Module Communication Board (IMC) (behind door)
EMO Button (Optional)
Option Box (6 Slots)
Main Input Circuit Breaker (CB1)
Module Output Circuit Breaker (CB2)
Output
CB2/IOB Circuit Breaker Board
Busbars
Neutral
Output Ground
DC Input
External Interface Board (EIB)
Input Busbars
Input Ground
CB1/RIB Circuit Breaker Board
FRONT DOORS REMOVED
DOORS AND INNER SKINS REMOVED
Installation Drawings
26
Page 33
Figure 16 Main components, 750kVA Liebert NXL UPS with static bypass (SMS OR 1+N)
OPTION BOX
(6 SLOTS)
LIEBERT INTELLISLOT HOUSINGS
MAIN INPUT
CIRCUIT BREAKER
(CB1)
MODULE OUTPUT CIRCUIT BREAKER (CB2)
BACK FEED CIRCUIT BREAKER (BFB)
KEYLOCK OR EMO BUTTON
(OPTIONAL)
INPUT
GROUND
INPUT
BUS BARS
DC INPUT
OUTPUT BUS BARS
BYPASS BUS BARS
FRONT DOORS REMOVED
DOORS AND INNER SKINS REMOVED
HMI SCREEN
CB2/IOB CIRCUIT BREAKER INTERFACE BOARD
CB1/RIB
CIRCUIT BREAKER
INTERFACE BOARD
EXTERNAL INTERFACE
BOARD (EIB)
pxqc;INTER-MODULE COMMUNICATION BOARD (LOCATED BEHIND HMI SCREEN)
Installation Drawings
27
Page 34
Figure 17 Outline drawing, 750kVA Liebert NXL without static bypass
U40-7d-2001
NOTES:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Aluminum and copper-clad aluminum cables are not recommended.
8. All wiring is to be in accordance with national and local electrical codes.
9. Depth dimension includes front door and rear panel.
10. Width dimensions include side panels. Subtract 1.4" (35mm) when removing both side panels.
11. See technical data drawing for shipping split weights.
Rectifier / DC
Cable Entry
Control Cable Entry \ Exit
Bypass \ Output Cable Exit
Rectifier / DC Cable Entry
Control Cable Entry / Exit
Outer Edge Corner Post
Front Most Edge Of Frame
Bypass \ Output Cable Exit.
Rectifier
Center of
Inverter
71.6
[1819]
62.4
[1585]
62.4
[1585]
Inverter Split (Part B)
15.8
[402]
3.7
[94]
17.6
[447]
.0
(0)
.0
(0)
3.3
[85]
14.8
[376]
2.1
[53]
19.1
[486]
24.6
[626]
15.2
[385]
4.1
[105]
.0
(0)
0
.6
[15]
Panel Width
76.8
[1950]
14.4
[367]
11. 6
[294]
109.9 (2791)
10.6
[269]
1.6
[40]
17.7
[449]
23.6
[600]
12.3
[312]
24.6
[625]
31.5
[800]
36.3
[922]
26.0
[660]
31.5
[800]
23.8
[605]
Section A-A
Bottom View
B
Detail B
AA
Gravity
Center of
Gravity
125 (3175)
39.4 (1000)
Right Side View
Left Side View
To p Vi ew
Front View
Rectifier Split (Part A)
16.6
[423]
Installation Drawings
28
Page 35
Installation Drawings
RECTIFIER
CENTER OF
62.5 [1587]
78.0 [1981]
INVERTER SPLIT (PART B)
24.6
[625]
31.5
[800]
36.3
[922]
29.1
[739]
A
GRAVITY
140.5
[3568]
LEFT SIDE VIEW FRONT VIEW
RECTIFIER SPLIT (PART A)
A
INVERTER
76.8 [1950]
34.1
[866]
23.8
[605]
CENTER OF
GRAVITY
39.4
[1000]
RIGHT SIDE VIEW
OUTER EDGE
CORNER POST
FRONT MOST
EDGE OF FRAME
.0
(0)
.0
(0)
.6
[15]
PANEL WIDTH
DETAIL B
RECTIFIER / DC
CABLE ENTRY
CONTROL CABLE
ENTRY \ EXIT
71.6 [1819]
15.8
[402]
3.7
[94]
17.6
[447]
TOP VIEW
16.6
[423]
11. 9
[302]
34.3
[871]
BYPASS \ OUTPUT
CABLE EXIT
RECTIFIER / DC
CABLE ENTRY
CONTROL CABLE
ENTRY / EXIT
.0
(0)
.0
(0)
3.3
[85]
14.8
[376]
2.1
[53]
19.1
[486]
24.6
[626]
15.2
[385]
4.1 [105]
SECTION A-A
BOTTOM VIEW
B
9.2 [233]
34.3
[872]
BYPASS \ OUTPUT
CABLE EXIT.
126.8
[3220]
1.6
[40]
Figure 18 Outline Drawing, 750kVA Liebert NXL 1+N multi-module or SMS with static bypass
29
Page 36
Installation Drawings
Bracket Mounting Locations (M10 Hexserts)
Footprint Spacing
Lift Clearance
Shipping Split
Rectifier Section
(Part A)
Pillars Removed For Clarity
Bottom Cable Entry Panels
Front
Inverter Section
(Part B)
Front Of Unit
Forklift Openings
Forklift Openings
Rectifier Section
(Part A)
Inverter Section
(Part B)
Notes:
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate for forklift handling.
Bottom Input (Part A) Bottom Output (Part B)
Front View
Right Side
Bottom View
Front View
2.4 [61]
27.7 [403]
27.7 [403] 27.7 [403]
27.7 [403]
1.7 [42]
1.7 [42]
4.8
[122]
Right Side
2.1 [53]
33.3 [845]
24.6
[625]
10.9
[276]
9.0
[229]
9.0
[229]
10.9
[276]
10.9
[276]
9.0
[229]
3.9
[100]
Typ
4.7
[120]
Typ
7.9
[200]
Typ
27.2 [691]
3.9 [99]
61.8 [1570]
61.8 [1570]
3.9
[100]
6.0 (152.4)
8.0 (203.2)
37.2
[945]
U40-7L-2000
Figure 19 Base detail drawing, 750kVA Liebert NXL, N+1 multi-module without static bypass
30
Page 37
Installation Drawings
Figure 20 Base Drawing, 750kVA Liebert NXL 1+N multi-module or SMS with static bypass
6.0 (152.4)
REAR
A
33.3
2.2
10.7
27.7
27.7
[845]
[56]
[271]
4.8
[703]
1.7
[703]
RIGHT SIDE
[122]
[42]
(M10 HEXSERTS)
FRONT VIEW
BRACKET MOUNTING LOCATIONS
0.75
[19]
(PART B)
INVERTER SECTION
DETAIL A
FRONT
OF UNIT
77.3 [1963]
FORKLIFT OPENINGS
NOTES:
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate
for forklift handling.
3.9
[99]
27.2
[691]
LIFT CLEARANCE
RIGHT SIDE
3.9 [100]
7.6 [193]
9.0 [229]
10.9
[276]
10.9
[276]
SHIPPING SPLIT
FRONT VIEW
9.0 [229]
37.2
[945]
PILLAR
6.0 (152.4)
SPACING
BOTTOM OUTPUT (PART B)
BOTTOM INPUT (PART A)
REAR
BOTTOM VIEW
7.9
TYP
[200]
PILLARS REMOVED FOR CLARITY
BOTTOM CABLE ENTRY PANELS
FOOTPRINT SPACING
(PART B)
INVERTER SECTION
4.8
[703]
1.7
[703]
[61]
[122]
[42]
27.7
27.7
2.4
(PART A)
RECTIFIER SECTION
61.8 [1570]
3.900
FORKLIFT OPENINGS
31
9.0
10.9
[229]
[276]
24.6
[625]
36.7
[931]
FOOT
SPACING
4.7
3.9
TYP
[120]
TYP
[100]
(PART A)
RECTIFIER SECTION
Page 38
Notes:
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. Aluminum and copper-clad aluminum cables are not recommended.
4. All wiring is to be in accordance with national and local electrical codes.
DC (-)
Input
Input
Ground
DC (+) Input
Input
Phases
DO NOT DOUBLE STACK LUGS (TWO LUGS ON SAME SIDE OF BUSBAR). THIS IS TO PREVENT THE CABLES FROM COMING INTO CONTACT WITH OTHER BUSBARS.
LEFT FRONT
A
B
LEFT SIDE (INPUT)
DC Inputs
Input Phases
Input Ground
O
.56
(14
)
TYP
2.00 (51)
TYP
1.75
(44)
TYP
O
.56
(14)
TYP
2.00
(51)
TYP
1.75
(44)
TYP
O
.56
(14)
TYP
1.26
(32)
TYP
1.75
(44)
TYP
.0
(0)
23.5
( 598
)
32.4
(824)
36.2
(920)
40.0
(
1016)
51.3
(1303)
3.5
(90
)
3.5 (90)
76.8
(1950 )
CB1-3
CB1-3
Figure 21 Input/output terminal detail, 750kVA Liebert NXL without static bypass
Installation Drawings
32
Page 39
Figure 22 Detail 750kVA Liebert NXL with static bypass (SMS/1+N)
NOTES:
1. ALL DIMENSIONS ARE IN inches (mm).
2. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUITS.
3. ALUMINUM AND COPPER-CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.
4. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONALAND LOCAL ELECTRICAL CODES.
DO NOT DOUBLE STACK LUGS (TWO LUGS ON SAME SIDE OF BUSBAR). THIS IS TO PREVENT THE CABLES FROM COMING INTO CONTACT WITH OTHER BUSBARS.
LEFT FRONT (PART A)
LEFT SIDE (PART A)
DC INPUTS
INPUT PHASES
INPUT GROUND
DUAL LUG CONNECTION DETAIL
DC (-)
INPUT
INPUT
GROUND
DC (+) INPUT
INPUT
PHASES
LUGS
BUSBAR
BOLT
A
B
C
DIA. .56
[14]
TYP
2.00 [51]
TYP
1.75 [44]
TYP
DIA. .56
[14]
TYP
2.00 [51]
TYP
1.75 [44]
TYP
DIA. .56
[14]
TYP
1.26 [32]
TYP
1.75 [44]
TYP
.0
(0)
23.5
( 598 )
32.4
( 824 )
36.2
( 920 )
40.0
( 1016 )
51.3
( 1303 )
3.5
[90]
3.5
[90]
76.8
( 1950 )
CB1-3
CB1-3
Installation Drawings
33
Page 40
Installation Drawings
Figure 23 Input/output terminal detail, 750kVA Liebert NXL without static bypass (continued)
.56
5 Places
O
(14) Typ 20 Places
NEUTRAL
1.75 (44 ) Typ
O
Typ 5 Places
1.75 (44) Typ
76.8
(1950 )
53.2
(1352 )
39.4
(1002 )
32.0
( 813)
1.75
(44) Typ
(Top Entry)
C
B
A
Output
Phases
Neutral
Output
Ground
1.38 X .56 Slot
Each Busbar
OUTPUT PHASES
1.38 X .56 Slot 10 Places
1.75
(44)
(Bottom
Typ
Entry)
(Top Entry)
.56 (14 )
(Bottom Entry)
.0
(0)
RIGHT FRONT
NOTES:
1. All dimensions are in inches (mm)
2. Control wiring and power wiring must be run in separate conduits.
3. Aluminum and copper-clad aluminum cables are not recommended.
4. All wiring is to be in accordance with national and local electrical codes.
RIGHT SIDE (OUTPUT)
CB1-3
CB1-3
DO NOT DOUBLE-STACK LUGS
1.75 (44 ) Typ
.56
O
(14)
Typ
1.57 (40) Typ
OUTPUT GROUND
34
Page 41
Installation Drawings
NOTES:
1. ALL DIMENSIONS ARE IN inches (mm).
2. CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUITS.
3. ALUMINUM AND COPPER-CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.
4. ALL WIRING IS TO BE INACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
BREAKERS AND FRONT POST REMOVED FOR CLARITY
CBANCBA
OUTPUT
GROUND
(TOP ENTRY)
OUTPUT
GROUND
1.75 (44)
TYP
.56 DIA.
(14)
TYP
1.75 (44)
TYP
76.8 (1950)
30.4 (772)
33.9 (860)
.0 (0)
56.4 (1432)
BYPASS / OUTPUT NEUTRAL
1.49 (37.7)
TYP
BYPASS NEUTRAL BUS
OUTPUT NEUTRAL BUS
(BOTTOM
ENTRY)
RIGHT SIDE (PART B)
RIGHT FRONT (PART B)
BYPASS / OUTPUT PHASES
OUTPUT GROUND
1.38 X .56 SLOT 6 PLACES EACH BUSBAR
1.75 (44) TYP
OUTPUT PHASES, APPROX.
3.0" SPACING BETWEEN BUSBARS
BYPASS PHASES, APPROX.
3.0" SPACING BETWEEN BUSBARS
.56 DIA.
(14) TYP
28 PLACES
.56 DIA.
(14)
TYP
20 PLACES
1.30 (33) TYP
1.75 (44) TYP
OUTPUT NEUTRAL
BYPASS NEUTRAL
DO NOT DOUBLE-STACK LUGS
CB1-3
CB1-3
Figure 24 Input/output terminal detail, 750kVA Liebert NXL with static bypass (SMS or 1+N) continued
35
Page 42
Figure 25 Shipping split 750kVA Liebert NXL without static bypass
(+) DC Busbar
(-) DC Busbar
M10 Flat Washer
M10 Ribbed Washer (2x)
M10 Hex Head Bolt
Low-Voltage Wire Connections Between Part A and Part B
Wires are coiled and tied in Part A. Uncoil, route and connect wires in finish part as shown. Use wire label as guide for "to" component, connection ID and wire part number. Tie wires away from sharp edges, busbar and electronic components.
02-806716-
02-806704­Phase A
02-806704­Phase B
02-806704­Phase C
02-806707-
Hardware for Detail A Included in This Box
Loosen hardware to allow busbar to move to join to Part B Busbar. Retighten and torque to 27 N-m (240 in-lb)
Note: See Page 2 of 2, drawing # U40-7g-2001
Part A (Rectifier) - Wire Starting Point
531985GI
531988G2
531983G1
A
531985G2
531985G3
532061G1
Detail A
DC Power Connection Between Part A and Part B
Hardware Provided With Part B: 4 Bolts Total Torque Connection To 27 N-m (240 In-lbs)
U40-7g-2000 Pg. 1, Rev. 01
Part B (Inverter) - Wire Finishing Point
02-806708-
Low Voltage Wire Connections Between Part B and Part A
Wires are coiled and tied in Part B. Uncoil, route and connect wires in finish part as shown. Use wire label as guide for "to" component, connection ID and wire part number. Tie wires away from sharp edges, busbar and electronic components.
02-806710-
NOTE: See Page 1 of 2, drawing # U40-7G-2000
Part A (Rectifier) - Wire Finishing Point
532049G1
532065G1
532063G1
532065G1
U40-7G-2001 Rev. 1
Part B (Inverter) - Wire Starting Point
Installation Drawings
36
Page 43
Figure 26 Shipping Split, 750kVA Liebert NXL with static bypass (SMS/1+N)
PART A - WIRE STARTING POINT PART B - WIRE FINISHING POINT
Hardware Provided With Part B.
(4) Bolts Total.
Torque Connection to 27 N-m (240 in-lb).
M10 FLAT WASHER
M10 RIBBED WASHER (x2)
M10 HEX HEAD BOLT
Low Voltage Wire Connections Between Parts A and B
Wires are coiled and tied in Part A. Uncoil, route and connect wires in finish part as shown. Use wire label as gu ide for “TO” component, connection ID and wire part number. Tie wires away from sharp edges, busbar and electronic components.
DC Power Connection Between Parts A and B
(+) DC BUSBAR
LOOSEN HARDWARE TO ALLOW
BUSBAR TO MOVE TO JOIN TO
PART B BUSBAR.
RETIGHTEN AND TORQUE TO
27 N-m (240 in-lbs)
02-806704-
PHASE A
02-806704-
PHASE B
02-806704-
PHASE C
02-806707-
02-806705-
02-806716-
F42 & F43
(-) DC BUSBAR
531988G2
531985G1
531983G1
531985G2
531984G1
531985G3
531988G1
532061G1
532062G1
Detail A
DETAIL A
Installation Drawings
37
Page 44
Figure 27 Shipping Split, 750kVA Liebert NXL with static bypass (SMS/1+N) continued
Low Voltage Wire Connections Between Parts B and A
Wires are coiled and tied in Part B. Uncoil, route and connect wires in finish part as shown. Use wire label as guide for “TO” component, connection ID and wire part number. Tie wires away from sharp edges, busbar and electronic components.
PART A - WIRE FINISHING POINT. PART B - WIRE STARTING POINT.
02-806710-
02-806708-
Fig12A-ShippingSplit750kVANXLwStaticBypass-SMS1plusNcontd
532065G1
532049G1
532065G1
532063G1
Installation Drawings
38
Page 45
Figure 28 Single-input wire cabinet
M6 hardware for Ground Plate provided in shipped-loose bag inside Wire Cabinet
Remove Side Panels From Left Side of Rectifier Cabinet
and Install on Left Side of Wire Cabinet
M10 Hardware Provided in Shipped-Loose Bag Inside Wire Cabinet
Kickplate is provided as a shipped-loose item inside the Wire Cabinet on inverter-side the UPS
Cabinet-to-Cabinet Connection Hardware
DETAIL A
538307
Reference of Rectifier Corner Post See Detail A
Remove upper and lower internal panels before attaching wire cabinet to UPS
Reference of Wire Cabinet Corner Post See Detail A
Rectifier Cabinet Corner Posts
Wire Cabinet Corner Posts
Rectifier ( Not All Components Shown)
Wire Cabinet
This hardware provided on Rectifer Cabinet. Reuse hardware to mount ground plate
1 Ground Plate
Bolt and Washer
Bolt and Washer
Bolt and Washer
DETAIL B
B
COMPLETE ASSEMBLY
Installation Drawings
39
Page 46
Figure 29 Control cable layout, UPS active analog load bus sync, 250-750kVA units
U40-CQ-1560 Rev. 1
SYSTEM #1 SYSTEM #2
UPS
TB27-7
ANALOG LBS BOX
TB27-8
TB27-9
INTER-MODULE
COMMUNICATIONS
02-806730-00
TB4-4
TB27-4
TB27-5
TB27-6
TB27-1
TB27-2
TB27-3
TB27-11
TB27-12
TB4-5
TB4-6
TB3-1
TB3-2
TB3-3
TB2-2
TB2-5
TB2-9
TB1-1
TB1-2
TB1-7
TB1-8
P3107-4
P3107-5
Bypass Volts Phase A
Bypass Volts Phase B
Bypass Volts Phase C
120 Volts AC
Ground
Return
Transferred To Bypass
Synch Phase C
Synch Phase B
Synch Phase A
V & I
BOARD
LBS
BOARD
TB1-1
TB1-2
P3105-3
P3105-4
Return
Synch To Master
Critical Bus Volts Phase A
Critical Bus Volts Phase B
Critical Bus Volts Phase C
CG #14A
CG #14B
F70
F69
F71
V-BYP-A
V-BYP-C
V-BYP-B
F73
F72
F74
V-OU T-A
V-OU T-C
V-OU T-B
TB27-8
TB27-7
TB27-9
TB0826-1
TB0826-5
TB0826-3
External Interface Board
LBS Transformer Box
CG #13
TB5-5
TB5-4
P3107-2
P3107-1
Common
V & I
BOARD
System Is On Bypass (N.C.)
ANALOG LBS BOX
UPS
TB27-7
TB27-8
TB27-9
INTER-MODULE
COMMUNICATIONS
02-806730-00
TB3-4
TB27-4
TB27-5
TB27-6
TB27-1
TB27-2
TB27-3
TB27-11
TB27-12
TB3-5
TB3-6
TB4-1
TB4-2
TB4-3
TB3-1
TB3-5
TB3-10
TB2-1
TB2-2
TB2-7
TB2-8
P3107-4
P3107-5
Synch Phase C
Synch Phase B
Synch Phase A
Critical Bus Volts Phase B
Critical Bus Volts Phase A
Critical Bus Volts Phase C
Bypass Volts Phase A
Bypass Volts Phase B
Bypass Volts Phase C
120 Volts AC
Ground
Transferred To Bypass
Return
V & I
BOARD
LBS
BOARD
TB2-1
TB2-2
P3105-3
P3105-4
Synch To Master
Return
CG #14C
CG #14D
LBS Transformer Box
F70
F69
F71
V-BYP-A
V-BYP-C
V-BYP-B
F73
F72
F74
V-OU T-A
V-OU T-C
V-OU T-B
TB27-8
TB27-7
TB27-9
TB0826-1
TB0826-5
TB0826-3
External
Interface
Board
CG #13
TB5-2
TB5-1
P3107-2
P3107-1
System Is On Bypass (N.C.)
Common
V & I
BOARD
NOTES:
1. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.
2. All wiring must be in accordance with national and local electrical codes.
3. UPS can be wired either as System #1 or System #2.
ANALOG LBS BOX
TB27-7
TB27-8
TB27-9
INTER-MODULE
COMMUNIC ATIONS
02-806730-00
TB3-4
TB27-4
TB27-5
TB27-6
TB27-1
TB27-2
TB27-3
TB27-11
TB27-12
TB3-5
TB3-6
TB4-1
TB4-2
TB4-3
TB3-1
TB3-5
TB3-10
TB2-1
TB2-2
TB5-2
TB5-1
P3107-2
P3107-1
Synch Phase C
Synch Phase B
Synch Phase A
Critical Bus Volts Phase B
Critical Bus Volts P hase A
Critical Bus Volts Phase C
Bypass Volts Phase A
Bypass Volts Phase B
Bypass Volts Phase C
120 Volts AC
Ground
V & I
BOARD
LBS
BOARD
TB2-1
TB2-2
P3105-3
P3105-4
Synch To Master
Return
CG #14C
CG #14D
LBS Transformer Box
F70
F69
F71
V-BYP-A
V-BYP-C
V-BYP-B
F73
F72
F74
V-OU T-A
V-OU T-C
V-OU T-B
TB27-8
TB27-7
TB27-9
TB0826-1
TB0826-5
TB0826-3
External
Interface
Board
CG #13
V & I
BOARD
Common
System Is On Bypass (N. C.)
UPS
TB27-7
ANALOG LBS BOX
TB27-8
TB27-9
INTER-MODULE
COMMUNIC ATIONS
02-806730-00
TB4-4
TB27-4
TB27-5
TB27-6
TB27-1
TB27-2
TB27-3
TB27-11
TB27-12
TB4-5
TB4-6
TB3-1
TB3-2
TB3-3
TB2-2
TB2-5
TB2-9
TB1-1
TB1-2
TB5-5
TB5-4
P3107-2
P3107-1
Bypass Volts Phase A
Bypass Volts Phase B
Bypass Volts Phase C
120 VoltsAC
Ground
Common
Synch Phase C
Synch Phase B
Synch Phase A
V & I
BOARD
LBS
BOARD
TB1-1
TB1-2
P3105-3
P3105-4
Return
Synch To Master
Critical Bus Volts P hase A
Critical Bus Volts P hase B
Critical Bus Volts P hase C
CG #14A
CG #14B
F70
F69
F71
V-BYP-A
V-BYP-C
V-BYP-B
F73
F72
F74
V-OU T-A
V-OU T-C
V-OU T-B
TB27-8
TB27-7
TB27-9
TB0826-1
TB0826-5
TB0826-3
External Interface Board
LBS Transformer Box
CG #13
System Is On Bypass (N. C.)
V & I
BOARD
SYSTEM #1 SYSTEM #2
UPS
NOTES:
1. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.
2. All wiring must be in accordance with national and local electrical codes.
3. UPS can be wired either as System #1 or System #2.
U40-CQ-1540 Rev. 2
Installation Drawings
Figure 30 Control cable layout, UPS passive analog load bus sync, 250-750kVA units
40
Page 47
Figure 31 Control cable layout, UPS analog load bus sync, ELBS, 250-750kVA units
U40-CQ-1562 Rev. 0
NOTES:
1. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.
2. All wiring must be in accordance with national and local electrical codes.
UPS
TB27-7
ANALOG LBS BOX
TB27-8
TB27-9
INTER-MODULE
COMMUNICATIONS
02-806730-00
TB4-4
TB27-4
TB27-5
TB27-6
TB27-1
TB27-2
TB27-3
TB27-11
TB27-12
TB4-5
TB4-6
TB3-4
TB3-5
TB3-6
TB2-2
TB2-5
TB2-9
TB1-1
TB1-2
V & I
BOARD
LBS
BOARD
TB1-1
TB1-2
P3105-3
P3105-4
Return
SynchTo Master
Bypass Volts Phase A
Bypass Volts Phase B
Bypass Volts Phase C
120 Volts AC
Ground
Synch Phase C
Synch Phase B
Synch Phase A
Critical Bus Volts Phase A
Critical Bus Volts Phase B
Critical Bus Volts Phase C
CG #30A
CG #30B
F70
F69
F71
V-BYP-A
V-BYP-C
V-BYP-B
F73
F72
F74
V-O UT-A
V-O UT-C
V-O UT-B
TB27-8
TB27-7
TB27-9
TB0826-1
TB0826-5
TB0826-3
EXTERNAL INTERFACE BOARD
LBS Transformer Box
CG #13
TB5-5
TB5-4
P3107-2
P3107-1
Common
V & I
BOARD
System is on Bypass (N.C.)
Installation Drawings
41
Page 48
5.0 SPECIFICATIONS
Table 10 Liebert NXL UPS specifications
Model Size 500kVA 750kVA
Input Parameters
Input Voltage to Rectifier, VAC 480V 3-phase, 3-wire
Input Voltage to Bypass, VAC 480V 3-phase, 3-wire or 4-wire
Input Voltage Range, VAC +10% to -15; -15% to -20%*; -20% to -30%**; <-30%***
Input Frequency, Hz 60
Permissible Input Frequency Range, Hz 55 to 65
Reflected Input THDi, Nominal Voltage, Full Load, % <5% with 12-Pulse & Passive Filter
Input THDi at Nominal Voltage at Full Load, %
Power Walk-In, sec 1 to 30 (selectable) in 1 sec. Increment
Neutral Current up to 1.7 times full-phase current
Battery & DC Parameters
Nominal Battery Bus, VDC 480V
Battery
Float Voltage, VDC 540V
Minimum End of Discharge Voltage, VDC 384V (for VRLA / Flooded Lead Acid)
DC Ripple Voltage in Float & Const V Ch. Mode, % <1 (RMS value) < 3,4% Vpp
Temperature Compensated Battery Charging Optional (with temperature probe)
Output Parameters
Output Power, kW 450 675
Output Voltage, VAC 480V 3-ph, 4-w
Output Voltage Regulation, % < 1% (3-phase RMS average)
Output Voltage Regulation (100% Unb. Load) < 2% (3-phase RMS average)
Output Frequency, Hz 60
Output Frequency Regulation, % ± 0.1
Output THDu Linear Load at Nominal Voltage, % <2%
Including a 100kVA Non Linear Load per EN 62040-3, %
Capacity to Handle High Crest Factor Load 3:1
Step Load Transient Recovery (linear loads), % Within 5% peak-to-peak in one line cycle.
Output THDu at Nominal Voltage
Capacity to handle Step Load, % 0-100 or 100-0
Unbalance Loads Current Capacity 100% of nominal phase current
Capacity to Handle Leading PF Load
Voltage Displacement, ° el 120° ±1° el (with 100% unbalanced load)
Battery Type VRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid)
Inverter Type IGBT-based Sine-Sine PWM Controlled
0.9 lag to Nom Subject to Max. kW rating
at 0.95 Lead Subject to Max. kW rating
at 0.9 Lead
<5% with 12-Pulse & Passive Filter; <10% with 12-Pulse Without
Passive Filter
2.5% (max)
Subject to 12.5% kW derate or same Rating and 10°C Temp.
Derate
Compliance to FCC Class-A Standard
105% for 85 minutes
Overload Conditions, % FL
* The UPS will operate at full load, but the battery charge will either be reduced or off (depending on input current). ** The UPS will operate at full load, but UPS may source share with the batteries (depending on input current). *** UPS will be in Battery mode
110% for 60 minutes 125% for 10 minutes
150% for 1 minute
480V 3-phase, 3-wire 575V 3-phase, 3-wire 600V 3-phase, 3-wire
480V 3-phase, 3-wire or 4-wire 575V 3-phase, 3-wire or 4-wire
600V3-phase, 3-wire or 4-wire
480V 3-ph, 4-w 575V 3-ph, 4-w 600V 3-ph, 4-w
Specifications
42
Page 49
Specifications
Table 10 Liebert NXL UPS specifications (continued)
Model Size 500kVA 750kVA
Physical Parameters and Standards, in (mm)
Width, With Static Bypass 111.6 (2835) 140.5 (3568)
Width, without Static Bypass N/A 125 (3175)
Depth 39.4 (1000) 39.4 (1000)
Height 76.8 (1950) 76.8 (1950)
Weight, Unpackaged, lb (kg) approx., with Static Bypass
(SMS)
9450 (4286) 13,200 (6000)
Weight, Unpackaged, lb (kg) approx., with Static Bypass (1+N) 9550 (4332) 13,350 (6055)
Weight, Unpackaged, lb (kg) approx., without Static Bypass
(N+1)
Max heat Dissipation, Full Load, BTU/hr 141,658
Cooling Air CFM 8113 15,760
9250 (4196) 12,500 (5670)
480V: 213,587
575V: 215,790 600V: 200,173
Color Black (ZP-7021)
Front Door Opening (for serviceability) More than 180°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
Minimum Clearance, Top, in (mm) 24 (610)
Minimum Clearance, Back, in (mm) 0
Minimum Clearance, Sides, in (mm) 0
Location of Cable Entrance Top or Bottom
UL 1778, 4th Ed.
CSA 22.2 107.3
FCC Part 15, Class A
IEC62040-2, Level 4, Criteria A
Standards and Conformities
EN61000-4-3, Level 3, Criteria A EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3
ISTA Procedure 1H
WEEE
Environmental Parameters
Storage Temperature Range, °F (°C) -13 to 158 (-25 to 70)
Operating Temperature Range, °F (°C) 32 to 104 (0 to 40) (UPS)
Relative Humidity
Maximum Altitude Above MSL, ft (m)
Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. Depth dimensions include the front door and rear panel.
Non-Condensing (Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) - 1% Max kW derate / 328
rise between 4921-9842 (100m rise between 1500-3000m)
95% or less
43
Page 50
Specifications
Table 11 Current ratings—rectifier input
UPS Rating Voltage, VAC
Rectifier
Type
500 450 480 480 480 12P + Filter 650 812 900 1000
750 675 480 480 480 12P + Filter 975 1219 1600 1600
750 675 575 575 575 12P + Filter 815 1018 1200 1600
750 675 600 600 600 12P + Filter 759 949 1000 2000
Nominal
Current
Maximum
Current
External
100% Breaker
Trip, Amps
External
80% Breaker
Trip, AmpskVA kW Input Bypass Output
Table 12 Current ratings—bypass input
UPS Rating Voltage, VAC
500 450 480 480 480 12P + Filter 601 752 800
750 675 480 480 480 12P + Filter 902 1128 1200
750 675 575 575 575 12P + Filter 753 941 1000
750 675 600 600 600 12P + Filter 722 902 1000
Rectifier
Type
Nominal
Current
10 Minute
Overload
External Breaker
Trip, AmpskVA kW Input Bypass Output
Table 13 Current ratings—output
UPS Rating Voltage, VAC
500 450 480 480 480 12P + Filter 601 752 800
750 675 480 480 480 12P + Filter 902 1128 1200
750 675 575 575 575 12P + Filter 753 941 1000
750 675 600 600 600 12P + Filter 722 902 1000
Rectifier
Type
Nominal
Current
10 Minute
Overload
External Breaker
Trip, AmpskVA kW Input Bypass Output
Table 14 Current ratings—battery
UPS Rating Voltage, VAC
500 450 480 480 480 12P + Filter 480 1241 1600
750 675 480 480 480 12P + Filter 480 1845 2000
750 675 575 575 575 12P + Filter 480 1851 2000
750 675 600 600 600 12P + Filter 480 1845 2000
Rectifier
Type Nominal VDC
Max Battery
Current at EOD
External Breaker
Trip, AmpskVA kW Input Bypass Output
Notes on Tables
1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input current is controlled by the current limit setting which is adjustable. Values shown are for maximum setting of 125%. Standard factory setting is 125%. If a smaller input feed breaker is used, the input current limit must be adjusted accordingly.
2. Recommended bypass external overcurrent protection is based on 125% overload capacity for 10 minutes.
3. All recommended external overcurrent protections are based on 80% rated breakers.
4. Nominal battery voltage is shown at 2.0 volts / cell.
44
Page 51
Specifications
Table 15 Recommended conduit and cable sizes
Rectifier Input
UPS Rating Voltage (VAC)
Rectifier Type
500 450 480 480 480 12P+Filter
750 675 480 480 480 12P+Filter
750 675 575 575 575 12P+Filter
750 675 600 600 600 12P+Filter
Bypass Input
UPS Rating Voltage (VAC)
Rectifier Type
500 450 480 480 480 12P+Filter
750 675 480 480 480 12P+Filter
750 675 575 575 575 12P+Filter
750 675 600 600 600 12P+Filter
Output
UPS Rating Voltage (VAC)
Rectifier Type
500 450 480 480 480 12P+Filter
750 675 480 480 480 12P+Filter
750 675 575 575 575 12P+Filter
750 675 600 600 600 12P+Filter
Battery
UPS Rating Voltage (VAC)
Rectifier Type
500 450 480 480 480 12P+Filter
750 675 480 480 480 12P+Filter
750 675 575 575 575 12P+Filter
750 675 600 600 600 12P+Filter
Bonding
UPS Rating Voltage (VAC)
Main Bonding Jumper/Grounding
Rectifier Type
500 450 480 480 480 12P+Filter (1) #4/0AWG/ (1) #4/0AWG
750 675 480 480 480 12P+Filter (1) 250kcmil/ (1) 250kcmil
750 675 575 575 575 12P+Filter (1) 250kcmil/ (1) 250kcmil
750 675 600 600 600 12P+Filter (1) 250kcmil/ (1) 250kcmil
1. Recommended cable sizes are 75°C (THW) wire at 30°C ambient.
2. For continuos operations not at 30°C, recommend that the site planner choose the appropriate cable type based on the particular installation requirements.
Nominal Selection
(#) Conduit Size, Ph, G
(3) 3.5C, 3-500kcmil,
#2/0AWG
(4) 3.5C, 3-600kcmil,
#4/0AWG
(3) 3.5C, 3-600kcmil,
#4/0AWG
(3) 3.5C, 3-600kcmil,
#4/0AWG
Nominal Selection
(#) Conduit Size, Ph, N, G
(3) 4C, 3-500kcmil,
2-250kcmil, #1/0AWG
(4) 4C, 3-500kcmil,
2-350kcmil, #4/0AWG
(4) 4C, 3-500kcmil,
2-250kcmil, #2/0AWG
(4) 4C, 3-500kcmil,
2-250kcmil, #2/0AWG
Nominal Selection
(#) Conduit Size, Ph, N, G
(3) 4C, 3-500kcmil,
2-250kcmil, #1/0AWG
(4) 4C, 3-500kcmil,
2-350kcmil, #4/0AWG
(4) 4C, 3-500kcmil,
2-250kcmil, #2/0AWG
(4) 4C, 3-500kcmil,
2-250kcmil, #2/0AWG
Nominal Selection
(#) Conduit Size, Ph, G
(4) 3C, 2-600kcmil,
#4/0AWG
(5) 3C, 2-600kcmil,
250kcmil
(5) 3C, 2-600kcmil,
250kcmil
(5) 3C, 2-600kcmil,
250kcmil
Electrode Conductor kVA kW Input Bypass Output
Alternate Selection
(#) Conduit Size, Ph, G kVA kW Input Bypass Output
(4) 3C, 3-250kcmil,
#2/0AWG
(5) 3.5C, 3-500kcmil,
#4/0AWG
(4) 3C, 3-350kcmil,
#4/0AWG
(4) 3C, 3-350kcmil,
#4/0AWG
Alternate Selection
(#) Conduit Size, Ph, N, G kVA kW Input Bypass Output
(4) 3C, 3-250kcmil,
2-#4/0AWG, #1/0AWG
(5) 3.5C, 3-350kcmil,
2-#4/0AWG, #4/0AWG
(5) 3C, 3-250kcmil,
2-#4/0AWG, #2/0AWG
(5) 3C, 3-250kcmil,
2-#4/0AWG, #2/0AWG
Alternate Selection
(#) Conduit Size, Ph, N, G kVA kW Input Bypass Output
(4) 3C, 3-250kcmil,
2-#4/0AWG, #1/0AWG
(5) 3.5C, 3-350kcmil,
2-#4/0AWG, #4/0AWG
(5) 3C, 3-250kcmil,
2-#4/0AWG, #2/0AWG
(5) 3C, 3-250kcmil,
2-#4/0AWG, #2/0AWG
Alternate Selection
(#) Conduit Size, Ph, G kVA kW Input Bypass Output
(5) 3C, 2-500kcmil,
#4/0AWG
(6) 3C, 2-500kcmil,
250kcmil
(6) 3C, 2-500kcmil,
250kcmil
(6) 3C, 2-500kcmil,
250kcmil
45
Page 52
Table 16 Recommended lug sizes
T&B Series 54000
Cable Size
One Hole
#8 AWG 54930BE 54850BE
#6 AWG 54905BE 256-30695-868
#4 AWG 54906BE 256-30695-733
#2-3 AWG 54942BE 54811BE
#1 AWG 54947BE 54857BE
#1/0 AWG 54950BE 256-30695-593
#2/0 AWG 54951BE 54862BE
#3/0 AWG 54965BE 54864BE
#4/0 AWG 54970BE 54866BE
250kcmil 54913BE 54868BE
300kcmil 54914BE 54870BE
350kcmil 54915BE 54872BE
400kcmil 54916BE 54874BE
500kcmil 54918BE 54876BE
600kcmil 54920BE 54878BE
750kcmil 54922BE 54880BE
Use the T&B crimping tools recommended for these types of lugs.
T&B Series 54000
Two Hole
Specifications
Table 17 Recommended torque values
Grade 5 Steel: Unified Thread System Torque lbf.*in. Class 8.8 Steel: Metric Thread System Torque N*m
Fastener Finish Plain Steel Zinc Plating Fastener Finish Plain Steel Zinc Plating
Size
1/4
5/16
3/8
7/16
1/2
9/16
Threads/
Inch, T
pi
No Washer/
Flat Washer
20 101 91
28 116 104 0.5 6.9 6.2
18 209 188
24 231 208 0.75 11 10
16 370 333
24 420 378 1 27 24
14 593 534
20 662 596 1.25 53 47
13 904 814
20 1,020 918 1.25 95 86
12 1,305 1,175
18 1,456 1,310 1.5 151 136
No Washer/
Flat Washer Size
M5
M6
M8
M10
M12
M14
Thread
Pitch, T
p
No Washer/
Flat Washer
No Washer/
Flat Washer
0.8 6.1 5.5
110 9
1.25 25 23
1.5 50 45
1.75 87 78
2139125
46
Page 53
NOTES
Specifications
47
Page 54
Specifications
48
Page 55
Page 56
Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2009 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-25434_REV4_06-10
Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
Emerson Network Power. The global leader in enabling Business-Critical Continuity
AC Power
Connectivity DC Power
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.
Embedded Computing Embedded Power Infrastructure Management & Monitoring
Outside Plant Power Switching & Controls Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...