LIEBERT® NX™ 3-PHASE UPS: 40-200KVA, 60HZ, 480VAC - SITE PLANNING DATA
General Specifications
INPUT
Vol tag e 480VAC, 60Hz, 3-phase 3-wire plus ground
Voltage Range w/o derating +15%, -20%
Frequency Range 57-63Hz
Current Distortion 3% maximum reflected THD at full load
Current Limit 125% of full load input current
Power Factor >0.99 lagging at full load; >0.98 lagging at half load
Surge Protection Sustains input surges without damage, per criteria listed in IEC 61000-4-5
OUTPUT
Voltage 480VAC, 60Hz, 3-phase 3-wire plus ground
Voltage Adjustment Range ±5%
Voltage Regulation 1% for balanced load 2% for 100% unbalanced load
Dynamic Regulation ±5% deviation for 100% load step; ±1% for loss or return of AC input
Transient Response Time Recover to ±5% of output voltage within 1/2 cycle
Voltage Distortion For linear loads, 1% THD; Less than 4% THD for 100% nonlinear loads without kVA/kW derating
Phasing Balance 120° ±0.5° for balanced load; 120° ±1° for 100% unbalanced load
Frequency Regulation ±0.05% single module; ±0.25% paralleled modules
Load Power Factor Range 0.5 lagging to 1.0 without derating
Overload 125% of full load for 10 minutes; 150% for 1 minute, with true sinusoidal waveform
ENVIRONMENTAL
Operating Temperature UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C)
Non-Operating Temperature -13° to 158°F (-25° to 70°C)
Relative Humidity 0-95% non-condensing
Operating Altitude Up to 6,500 ft. (2,000m) without derating
Acoustical Noise (full load)
80kVA <67dB at 80-104°F (27-40°C) ambient; <61dB below 80°F (27°C) ambient
120kVA <69dB at 80-104°F (27-40°C) ambient; <63dB below 80°F (27°C) ambient
200kVA <74dB at 80-104°F (27-40°C) ambient; <68dB below 80°F (27°C) ambient
STANDARDS
Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation.
The Liebert NX is a true on-line,
double conversion, three-phase
UPS system that delivers
complete, centralized power
protection for mission-critical
systems.
1

Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC
Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC
UPS Rating Voltage AC Input Battery AC Output Mechanical Data
Input
kVA kW
40 36 480 480 48 60 80 480 106 225 48 70
60 54 480 480 71 89 110 / 125 480 157 225 72 100 15,400 (4.5) 620 (1050)
80 72 480 480 94 118 150 480 208 225 96 125 20,600 (6.0) 620 (1050)
80 72 480 480 94 118 150 480 205 350 96 125
100 90 480 480 117 147 175 480 258 350 120 150 24,300 (7.1) 920 (1550)
120 108 480 480 140 175 225 480 307 350 144 200 28,700 (8.4) 920 (1550)
160 144 480 480 186 233 300 480 411 500 192 250
200 180 480 480 234 293 350 480 511 600 241 300 47,000 (13.8) 1590 (2700)
See Notes for Table (below): 1 2,3,7,11 5 4 1,3,7,11 1,3,7,11 5 12, 13 12 — —
Nom.
Output
Nom.
Current (A)
Nom. Max. Nom. OCPD BTU/hr (kWH) CFM (m3/hr)
Rec.
OCPD
Nom.
VDC
Max.
Discharge
Battery
Disconnect
Rating
Current (A) Dimensions
W x D x H
in. (mm)
25.5 x 39.0 x 78.7
(648 x 990 x 2000)
41.0 x 39.0 x 78.7
(1040 x 990 x 2000)
64.4 x 39.0 x 78.7
(1636 x 990 x 2000)
Weight
lb. (kg)
1290
(585)
1422
(645)
2201
(1000)
Heat Dissipation Cooling Airflow
12,200 (3.6) 620 (1050)
19,700 (5.8) 920 (1550)
35,900 (10.5) 1590 (2700)
Notes for Table
1. Nominal (Nom) current is based on full rated output load at nominal input
voltage.
2. Maximum (Max) current is short duration for battery recharge conditions.
3. UPS input cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC
output overcurrent protection represents 125% of nominal full load current
(continuous) plus 100% of recharge current (non-continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended.
7. Wiring requirements: AC Input: 3-phase, 3-wire, plus ground
AC Output: 3-phase, 3-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.
9. Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above
the UPS.
10. Top or bottom cable entry through removable access plates. Punch plate to
suit conduit size, then replace.
11. Control wiring and power wiring must be run in separate conduit.
12. Dimensions and weights in table do not include external battery cabinet.
13. 80-200kVA UPS dimensions include UPS wiring section for installation
without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX
BDC will be used.
Additional Notes
• Input and output wiring and breakers for a Liebert NX with Softscale
technology should be sized for the maximum scalable capacity. For example, a
40kVA Liebert NX that is scalable to 80kVA should be installed with wiring
and breakers rated for an 80kVA configuration.
• If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a
UPS application. Generator options would typically include an isochronous
governor (generator frequency regulation) and a UPS-compatible regulator
(generator voltage regulation). Consult generator manufacturer for required
generator options and sizing.
• It is recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit,
it should be noted that utility AC input might not be in phase with the UPS AC
output. Consult an Emerson Network Power sales representative or applications engineer.
• The UPS must be fed from a solidly grounded wye or delta AC source. Not for
use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed
between the AC feed and the UPS.
2

Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC
Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC
UPS Rating Voltage AC Input Bypass Input Battery AC Output Mechanical Data
Input
kVA kW Nom. Max. Nom. Nom. OCPD BTU/hr (kWH) CFM (m3/hr)
40 36 480 480 48 60 80 48 70 480 106 225 48 70
60 54 480 480 71 89 110 /125 72 110 480 157 225 72 110 15,400 (4.5) 620 (1050)
80 72 480 480 94 118 150 96 125 480 208 225 96 125 20,600 (6.0) 620 (1050)
80 72 480 480 94 118 150 96 125 480 205 350 96 125
100 90 480 480 117 147 175 120 150 480 258 350 120 150 24,300 (7.1) 920 (1550)
120 108 480 480 140 175 225 144 200 480 307 350 144 200 28,700 (8.4) 920 (1550)
160 144 480 480 186 233 300 192 250 480 411 500 192 250
200 180 480 480 234 293 350 241 300 480 511 600 241 300 47,000 (13.8) 1590 (2700)
See Notes for Table (below): 1 2,3,7,11 5 — — 4 1,3,7,11 1,3,7,11 5 12, 13 12 — —
Nom.
Out-
put
Nom.
Current
(A)
Rec.
OCPD
Current
(A)
Rec.
OCPD
Nom.
VDC
Max.
Dis-
charge
Battery
Dis-
connect
Rating
Current
(A) Dimensions
W x D x H
in. (mm)
25.5x39.0x78.7
(648x990x2000)
41.0x39.0x78.7
(1040x990x2000)
64.4x39.0x78.7
(1636x990x2000)
Weight
lb.
(kg)
1290
(585)
1422
(645)
2201
(1000)
Heat
Dissipation
12,200 (3.6) 620 (1050)
19,700 (5.8) 920 (1550)
35,900 (10.5) 1590 (2700)
Cooling
Airflow
Notes for Table
1. Nominal (Nom) current is based on full rated output load at nominal input
voltage.
2. Maximum (Max) current is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output
cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC
output overcurrent protection represents 125% of nominal full load current
(continuous) plus 100% of recharge current (non-continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended.
7. Wiring requirements: AC Input: 3-phase, 3-wire, plus ground
AC Output: 3-phase, 3-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.
9. Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above
the UPS.
10. Top or bottom cable entry through removable access plates. Punch plate to
suit conduit size, then replace.
11. Control wiring and power wiring must be run in separate conduit.
12. Dimensions and weights in table do not include external battery cabinet.
13. 80-200kVA UPS dimensions include UPS wiring section for installation
without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX
BDC will be used.
Additional Notes
• Input and output wiring and breakers for a Liebert NX with Softscale
technology should be sized for the maximum scalable capacity. For example, a
40kVA Liebert NX that is scalable to 80kVA should be installed with wiring
and breakers rated for an 80kVA configuration.
• If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a
UPS application. Generator options would typically include an isochronous
governor (generator frequency regulation) and a UPS-compatible regulator
(generator voltage regulation). Consult generator manufacturer for required
generator options and sizing.
• It is recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit,
it should be noted that utility AC input might not be in phase with the UPS AC
output. Consult an Emerson Network Power sales representative or applications engineer.
• The UPS must be fed from a solidly grounded wye or delta AC source. Not for
use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed
between the AC feed and the UPS.
3

External Battery Cabinet
External Battery Cabinet
Battery
Mfr.
Enersys
Battery
Typ e
HX-205FR
HX-300FR
Dimensions Weight
in. (mm) lb. (kg.) 40 60 80 80 100 120 160 200
33.5 x 39.0 x 78.7
(850 x 990 x 2000)
2620 (1188)
3502 (1589)
HX-330FR 3942 (1788)
48.8 x 39.0 x 78.7
(1240 x 990 x 2000)
HX-400FR 4302 (1952)
HX-500FR 5502 (2496)
Qty. Battery
Battery Run Time in Minutes by kVA
Cabinets
1 1810 6 —————
2 452718—————
3 724632—————
4 100 65 46 — — — — —
13016101176——
2 72453131211812 9
3 111 73 51 52 39 33 21 16
4 156102737455463323
1 36211414985—
2 9353373728231611
3 149 95 65 65 49 38 27 20
4 207135969672543830
1 412517171210 6 —
2 101 64 41 45 33 27 19 14
3 159103737455453223
4 221 146 103 104 79 66 45 35
1 63382626191610 7
2 142 90 65 66 50 38 27 20
3 222 144 103 103 78 66 46 34
4 318 202 145 146 110 92 66 49
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.