Emerson Gedney User Manual

General Cable Support Information
NEC/CEC:
Listed for Ordinary Locations
Applications
• Used to support cables in vertical raceways or risers.
• Relieves the strain that would be placed on terminations, the interior of panels, or other devices to which the cables are connected.
Spacing for Conductor Supports
Size of Wire
18 AWG thru 8 AWG Not greater than 30 (100) 30 (100)
6 AWG thru 1/0 AWG Not greater than 60 (200) 30 (100)
2/0 AWG thru 4/0 AWG Not greater than 55 (180) 25 (80)
over 4/0 AWG - 350 kcmil Not greater than 41 (135) 18 (60)
over 350 kcmil - 500 kcmil Not greater than 36 (120) 15 (50)
over 500 kcmil - 750 kcmil Not greater than 28 (95) 12 (40)
over 750 kcmil Not greater than 26 (85) 11 (35)
Support of Conductors
in Vertical Raceways
Certifications and Compliances
• Requirements for Cable Supports in the National Electrical Code reads as follows: 300.19 Supporting Conductors in Vertical Raceways. (A) Spacing Intervals - Maximum. Conductors in vertical raceways shall be supported if the vertical rise exceeds the values in Table 300.19(A). One cable support shall be provided at the top of the vertical raceway or as close to the top as practical. Intermediate supports shall be provided as necessary to limit supported conductor lengths to
not greater than those specied in Table 300.19(A).
Example:
• A 10-story building contains a vertical conduit run from the
basement to the top oor, approx. 34 m (110 ft) in length. The raceway contains 4/0 copper conductors. Per Table 300.19(A),
the unsupported cable length cannot exceed 25 m (80 ft). Therefore, one cable support is required at or near the top of the vertical riser, and one intermediate support is required at or near the midpoint in the conduit run, assuring that any unsupported cable length does not exceed 25 m (80 ft).
Aluminum or Copper - Clad Aluminum
Meters (Feet)
Copper
Meters (Feet)
TWO or more wires - Indoors - at voltages to 600 Volt Type S
Retrofit - TWO or more wires - Indoors - at voltages to 600 Volt Type D
ONE or more wires - Indoors - at all voltages Type R
Retrofit - ONE or more wires - Indoors - at all voltages Type DR
Ventilating - ONE or more wires - Outdoors - at all voltages Type CMT
Ventilating - Bakelite - ONE or more wires - Outdoors - at all voltages Type V
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Non-ventilating - ONE or more wires - Outdoors - at all voltages Type C
Locking - Horizontal/Vertical - ONE or more wires - Indoors - at all voltages Type K
Space Maker - ONE or more wires - Indoors - at all voltages Type M
Pull Box - ONE or more wires - Outdoors at all voltages Type W
Conduit Ventilators Type KVF/KVM
Grounding Lugs Type G
Wire Armored Cable - In conduit or supported by structure Type F/FS/FT/SF1773
192
Application Recommended O-Z/Gedney™ Cable Supports
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
General Cable Support Information
NEC/CEC:
Listed for Ordinary Locations
Applications
• Two basic types of cable supports are offered for use with
non-armored cable. They both utilize the pOZi-grip™ Wedging
Plug. pOZi-grip™ is a unique manufacturing technique for lining the cable grooves with a coarse grain grit using a high strength epoxy adhesive. This grit improves the cable support holding
power and does not injure the jacket or insulation on the cable.
One Piece Plug Type "S"
• This type consists of a metal body having an insulating liner
with a knurled and tapered inside surface and a one piece
impregnated hardwood wedging plug having a groove for each wire. This type support is recommended for use with all types of non-armored cables 600 Volts or less, as it is the easiest to install, impossible to install incorrectly and it provides ventilation of the conduit. This design is used in our Types S and D Cable Supports. The basic principles of their assembly are illustrated below.
Type S
1. Screw body on the end of the conduit or connector in place of the regular insulating bushing.
Multiple Segment Plug Type "R"
• This type consists of an all metal body having a tapered inner
surface and a canvas bakelite multiple segment wedging plug
so constructed that each cable is supported between grooves in adjacent segments. This construction provides the uniform pressure distribution required by the softer types of insulations frequently used at higher voltages. This design is used in non-ventilating types R, DR, W, C, K and M, and Ventilating Compound Types CMT, and V. The basic principles of their assembly are illustrated below.
Type R
1. Screw body on the end of the conduit or connector in place of the regular insulating bushing.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
2. Pull wires and arrange temporary means of support.
3a. Remove all pulling compound from
wires in the area where they pass through the cable support.
3b. Place the plug between the wires
as close to the top of the body as
possible. Care should be taken
to locate each wire in the proper groove.
4. Tap the plug firmly into the support
body.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
2. Pull wires and arrange temporary means of support.
3a. Remove all pulling compound from
wires in the area where they pass through the cable support.
3b. Place the segments of the plug
around the wires. Where more than two segments are involved the top of each plug segment has numbers at each end and it is important that these are paired with the corresponding numbers on the adjacent plug segments.
4. Tap the plug segments evenly and
firmly into the support body.
193
Drill Chart for Type S and D Cable Supports
NEC/CEC:
Listed for Ordinary Locations
HOW TO USE THIS CHART FOR S AND D CABLE SUPPORTS
(1) Select your conduit size and measure your cable diameter(s) which must t within the min/max range corresponding to the quantity of
cables in the white area of this chart. (Note: S and D Cable Supports must be used with two or more cables, 600 volts maximum)
(2) Cable diameters that fall within the gray area of this chart cannot be accommodated. Therefore a 3" Cable Support has a cable range of
0.261" up to 1.130". Cables smaller or larger cannot be considered.
(3) Example: A 3" Cable Support will be used for 3 cables at 1.051" and 1 cable at 0.384". Refer to the 3" Conduit Size column. We can t
4 cables between 1.011" to 1.070" therefore 3 at 1.051" will t. The fourth cable ts between 0.361" to 0.410" within the white area in the 3" Conduit column. This drilling will work.
(4) Using the example above but the fourth cable is smaller at 0.216", this drilling will not work. The 0.216" cable falls into the 0.211" to
0.260" range which is within the gray shaded area of the 3" conduit column. In this case, we recommend using our Cable Supports with R-type wedging plugs. See the R table below.
For combinations of cables that fall outside these parameters, please contact your local representative.
Conduit Size
Types S and D
Min/Max Cable OD
.180 - .210 10 15
.211 - .260 8 13 16
.261 - .310 8 11 14 18
.311 - .360 6 9 12 16 19
.361 - .410 4 8 11 15 17
.411 - .460 4 6 10 13 15 17
.461 - .510 4 5 8 11 14 16
.511 - .560 4 5 7 10 12 14
.561 - .610 2 5 6 9 11 13
.611 - .660 2 4 5 8 10 12
.661 - .710 4 4 8 10 11
.711 - .760 4 4 7 9 10
.761 - .810 2 4 7 8 10
.811 - .860 4 6 8 9 12
.861 - .910 4 6 7 8 11
.911 - .960 4 5 7 8 10
.961 - 1.010 5 6 7 10
1.011 - 1.070 4 6 7 9
1.071 - 1.130 4 4 6 9 11
1.131 - 1.190 4 6 8 11
1.191 - 1.250 4 5 7 10
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
1.251 - 1.310 4 4 7 10
1.311 - 1.370 4 7 9
1.371 - 1.430 4 6 8
1.431 - 1.490 4 6 8
1.491 - 1.550 4 5 8
1.551 -1.610 2 4 7
1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6"
194
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Type S Cable Supports
For Two or More Wires - Indoors - at Voltages to 600 Vac
For Rigid Conduit, IMC and EMT with pOZi-grip™ "S-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit risers.
Features
• Threaded for Rigid Conduit and IMC.
• Use with all types of insulations at voltages to and including 600 Volt.
• The fastest and easiest type cable support to install.
• The knurled insulating inner surface and one piece impregnated
hardwood pOZi-grip plug provide positive support well in excess of code requirements.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay-In­Lug grounding lug should be mounted on cable support body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
• For PVC Conduit, use a PVC terminal adapter.
Material/Finish
• Bodies: malleable or ductile iron with hot dip galvanized nish
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Optional Material/Finish
• For non-metallic bodies see Type D
For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for
use with cable supports.
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Illustrated Features
Impregnated Hardwood pOZi-grip™ Wedging Plug
Shape and special gripping surface of grooves in plug give maximum support to cable.
Malleable or Ductile Iron Body
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Tapered inside surface of insulating bushing is knurled to grip cable.
Dimensions in Millimeters
(Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
Conduit Size
(Inches)
1-1/2 66.8 (2.63) 60.4 (2.38) S-1500-1 S-1500-2 S-1500-BO SPLG-1500-1 SPLG-1500-2
2 79.5 (3.13) 66.8 (2.63) S-2000-1 S-2000-2 S-2000-BO SPLG-2000-1 SPLG-2000-2
2-1/2 95.3 (3.75) 76.2 (3.00) S-2500-1 S-2500-2 S-2500-BO SPLG-2500-1 SPLG-2500-2
3 114.3 (4.50) 79.5 (3.13) S-3000-1 S-3000-2 S-3000-BO SPLG-3000-1 SPLG-3000-2
3-1/2 130.3 (5.13) 88.9 (3.50) S-3500-1 S-3500-2 S-3500-BO SPLG-3500-1 SPLG-3500-2
4 143.0 (5.63) 3.88 (3.88) S-4000-1 S-4000-2 S-4000-BO SPLG-4000-1 SPLG-4000-2
5 174.8 (6.88) 114.3 (4.50) S-5000-1 S-5000-2 S-5000-BO SPLG-5000-1 SPLG-5000-2
6 212.9 (8.38) 139.7 (5.50) S-6000-1 S-6000-2 S-6000-BO SPLG-6000-1 SPLG-6000-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
Outside
Diameter
Overall
Height
2-4 Same Size Wires
Different Size
Wires or 5 or More
Same Size Wires Body Only
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
195
Type D Cable Supports
For Two or More Wires Already Installed in Conduit - Indoors - at Voltages to 600 Vac
Retrofit Type Split Bakelite Body with pOZi-grip™ "S-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit risers.
Features
• Retrot type cable support can be installed after conductors are
pulled and terminated.
• Split body rests on existing bushing atop any conduit raceway.
• The two halves of the body are placed around the cables, seated on the existing bushing and securely held together by the steel band set in a groove around the body. The plug is then wedged between the cables.
• Use with all types of insulations at voltages to and including 600 Volts.
• The tapered, knurled insulating inner body surface and pOZigrip
plug provide support well in excess of code requirements.
Material/Finish
• Bodies: two molded canvas bakelite halves. Inside surface is knurled to grip cables
• Band: steel/zinc plated
• Bolts and nuts: stainless steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Impregnated Hardwood pOZi-grip™ Wedging Plug
Shape and special gripping surface of grooves in plug give maximum support to cable.
Two molded Canvas Bakelite halves. Inside surface is knurled to grip cables.
Steel band, Zinc Plated. Bolts and nuts are Stainless Steel.
Existing Bushing
Existing Conduit
Dimensions in Millimeters (Inches)
Conduit
Size
(Inches)
1-1/2 66.8 (2.63) 50.8 (2.00) 50.8 (2.00) 57.2 (2.25) 1.00 D-1502-1 D-1502-2 SPLG-1500-1 SPLG-1500-2
2 82.6 (3.25) 57.2 (2.25) 60.4 (2.38) 73.2 (2.88) 1.00 D-2002-1 D-2002-2 SPLG-2000-1 SPLG-2000-2
2-1/2 98.6 (3.88) 63.5 (2.50) 76.2 (3.00) 85.9 (3.38) 2.00 D-2502-1 D-2502-2 SPLG-2500-1 SPLG-2500-2
3 114.3 (4.50) 73.2 (2.88) 79.5 (3.13) 101.6 (4.00) 2.00 D-3002-1 D-3002-2 SPLG-3000-1 SPLG-3000-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
3-1/2 133.4 (5.25) 85.9 (3.38) 92.2 (3.63) 117.6 (4.63) 2.00 D-3502-1 D-3502-2 SPLG-3500-1 SPLG-3500-2
4 146.1 (5.75) 88.9 (3.50) 98.6 (3.88) 130.3 (5.13) 2.00 D-4002-1 D-4002-2 SPLG-4000-1 SPLG-4000-2
5 171.5 (6.75) 95.3 (3.75) 120.7 (4.75) 158.8 (6.25) 2.00 D-5002-1 D-5002-2 SPLG-5000-1 SPLG-5000-2
6 209.6 (8.25) 117.6 (4.63) 133.4 (5.25) 187.5 (7.38) 2.00 D-6002-1 D-6002-2 SPLG-6000-1 SPLG-6000-2
Outside
Diameter
Overall
Height
Approx. Turning
Radius R
Inside
Diameter
Number of
Straps
Complete Fitting
Catalog Number Plug Only Catalog Number
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same
Size Wires
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same
Size Wires
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
196
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Drill Chart for Type R, DR, CMT, V, C, K, M and W Cable Supports
NEC/CEC:
Listed for Ordinary Locations
For combinations of cables that fall outside these parameters, please contact your local representative.
Type R, DR, CMT, V, C, K, M, and W Cable Supports
Max. Diameter of Wire Permitted - Millimeters (Inches)
Conduit Size
(Inches)
1-1/2" 35.6 (1.40) 16.3 (0.64) 15.0 (0.59) 13.0 (0.51) 9.91 (0.39) 9.4 (0.37)
2" 46.7 (1.84) 21.8 (0.86) 20.1 (0.79) 17.5 (0.69) 13.5 (0.53) 13.5 (0.53)
2-1/2" 57.2 (2.25) 26.9 (1.06) 24.9(0.98) 21.6 (0.85) 16.8 (0.66) 16.3 (0.64)
3" 72.1 (2.84) 34.5 (1.36) 31.8 (1.25) 27.9 (1.1) 21.8 (0.86) 21.6 (0.85)
3-1/2" 84.1 (3.31) 40.6 (1.60) 37.3 (1.47) 33.0 (1.3) 25.9 (1.02) 24.4 (0.96)
1
Wire
2
Wires
3
Wires
4
Wires
5
Wires
6
Wires
4" 96.8 (3.81) 46.7 (1.84) 43.1 (1.7) 38.1 (1.5) 30.0 (1.18) 27.7 (1.09)
5" 122.2 (4.81) 59.4 (2.34) 54.6 (2.15) 48.3 (1.9) 38.6 (1.52) 35.6 (1.4)
6" 148.3 (5.84) 72.6 (2.86) 66.6 (2.62) 59.4 (2.34) 47.2 (1.86) 43.4 (1.71)
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
197
Loading...
+ 13 hidden pages