Emerson Gedney User Manual

General Cable Support Information
NEC/CEC:
Listed for Ordinary Locations
Applications
• Used to support cables in vertical raceways or risers.
• Relieves the strain that would be placed on terminations, the interior of panels, or other devices to which the cables are connected.
Spacing for Conductor Supports
Size of Wire
18 AWG thru 8 AWG Not greater than 30 (100) 30 (100)
6 AWG thru 1/0 AWG Not greater than 60 (200) 30 (100)
2/0 AWG thru 4/0 AWG Not greater than 55 (180) 25 (80)
over 4/0 AWG - 350 kcmil Not greater than 41 (135) 18 (60)
over 350 kcmil - 500 kcmil Not greater than 36 (120) 15 (50)
over 500 kcmil - 750 kcmil Not greater than 28 (95) 12 (40)
over 750 kcmil Not greater than 26 (85) 11 (35)
Support of Conductors
in Vertical Raceways
Certifications and Compliances
• Requirements for Cable Supports in the National Electrical Code reads as follows: 300.19 Supporting Conductors in Vertical Raceways. (A) Spacing Intervals - Maximum. Conductors in vertical raceways shall be supported if the vertical rise exceeds the values in Table 300.19(A). One cable support shall be provided at the top of the vertical raceway or as close to the top as practical. Intermediate supports shall be provided as necessary to limit supported conductor lengths to
not greater than those specied in Table 300.19(A).
Example:
• A 10-story building contains a vertical conduit run from the
basement to the top oor, approx. 34 m (110 ft) in length. The raceway contains 4/0 copper conductors. Per Table 300.19(A),
the unsupported cable length cannot exceed 25 m (80 ft). Therefore, one cable support is required at or near the top of the vertical riser, and one intermediate support is required at or near the midpoint in the conduit run, assuring that any unsupported cable length does not exceed 25 m (80 ft).
Aluminum or Copper - Clad Aluminum
Meters (Feet)
Copper
Meters (Feet)
TWO or more wires - Indoors - at voltages to 600 Volt Type S
Retrofit - TWO or more wires - Indoors - at voltages to 600 Volt Type D
ONE or more wires - Indoors - at all voltages Type R
Retrofit - ONE or more wires - Indoors - at all voltages Type DR
Ventilating - ONE or more wires - Outdoors - at all voltages Type CMT
Ventilating - Bakelite - ONE or more wires - Outdoors - at all voltages Type V
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Non-ventilating - ONE or more wires - Outdoors - at all voltages Type C
Locking - Horizontal/Vertical - ONE or more wires - Indoors - at all voltages Type K
Space Maker - ONE or more wires - Indoors - at all voltages Type M
Pull Box - ONE or more wires - Outdoors at all voltages Type W
Conduit Ventilators Type KVF/KVM
Grounding Lugs Type G
Wire Armored Cable - In conduit or supported by structure Type F/FS/FT/SF1773
192
Application Recommended O-Z/Gedney™ Cable Supports
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
General Cable Support Information
NEC/CEC:
Listed for Ordinary Locations
Applications
• Two basic types of cable supports are offered for use with
non-armored cable. They both utilize the pOZi-grip™ Wedging
Plug. pOZi-grip™ is a unique manufacturing technique for lining the cable grooves with a coarse grain grit using a high strength epoxy adhesive. This grit improves the cable support holding
power and does not injure the jacket or insulation on the cable.
One Piece Plug Type "S"
• This type consists of a metal body having an insulating liner
with a knurled and tapered inside surface and a one piece
impregnated hardwood wedging plug having a groove for each wire. This type support is recommended for use with all types of non-armored cables 600 Volts or less, as it is the easiest to install, impossible to install incorrectly and it provides ventilation of the conduit. This design is used in our Types S and D Cable Supports. The basic principles of their assembly are illustrated below.
Type S
1. Screw body on the end of the conduit or connector in place of the regular insulating bushing.
Multiple Segment Plug Type "R"
• This type consists of an all metal body having a tapered inner
surface and a canvas bakelite multiple segment wedging plug
so constructed that each cable is supported between grooves in adjacent segments. This construction provides the uniform pressure distribution required by the softer types of insulations frequently used at higher voltages. This design is used in non-ventilating types R, DR, W, C, K and M, and Ventilating Compound Types CMT, and V. The basic principles of their assembly are illustrated below.
Type R
1. Screw body on the end of the conduit or connector in place of the regular insulating bushing.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
2. Pull wires and arrange temporary means of support.
3a. Remove all pulling compound from
wires in the area where they pass through the cable support.
3b. Place the plug between the wires
as close to the top of the body as
possible. Care should be taken
to locate each wire in the proper groove.
4. Tap the plug firmly into the support
body.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
2. Pull wires and arrange temporary means of support.
3a. Remove all pulling compound from
wires in the area where they pass through the cable support.
3b. Place the segments of the plug
around the wires. Where more than two segments are involved the top of each plug segment has numbers at each end and it is important that these are paired with the corresponding numbers on the adjacent plug segments.
4. Tap the plug segments evenly and
firmly into the support body.
193
Drill Chart for Type S and D Cable Supports
NEC/CEC:
Listed for Ordinary Locations
HOW TO USE THIS CHART FOR S AND D CABLE SUPPORTS
(1) Select your conduit size and measure your cable diameter(s) which must t within the min/max range corresponding to the quantity of
cables in the white area of this chart. (Note: S and D Cable Supports must be used with two or more cables, 600 volts maximum)
(2) Cable diameters that fall within the gray area of this chart cannot be accommodated. Therefore a 3" Cable Support has a cable range of
0.261" up to 1.130". Cables smaller or larger cannot be considered.
(3) Example: A 3" Cable Support will be used for 3 cables at 1.051" and 1 cable at 0.384". Refer to the 3" Conduit Size column. We can t
4 cables between 1.011" to 1.070" therefore 3 at 1.051" will t. The fourth cable ts between 0.361" to 0.410" within the white area in the 3" Conduit column. This drilling will work.
(4) Using the example above but the fourth cable is smaller at 0.216", this drilling will not work. The 0.216" cable falls into the 0.211" to
0.260" range which is within the gray shaded area of the 3" conduit column. In this case, we recommend using our Cable Supports with R-type wedging plugs. See the R table below.
For combinations of cables that fall outside these parameters, please contact your local representative.
Conduit Size
Types S and D
Min/Max Cable OD
.180 - .210 10 15
.211 - .260 8 13 16
.261 - .310 8 11 14 18
.311 - .360 6 9 12 16 19
.361 - .410 4 8 11 15 17
.411 - .460 4 6 10 13 15 17
.461 - .510 4 5 8 11 14 16
.511 - .560 4 5 7 10 12 14
.561 - .610 2 5 6 9 11 13
.611 - .660 2 4 5 8 10 12
.661 - .710 4 4 8 10 11
.711 - .760 4 4 7 9 10
.761 - .810 2 4 7 8 10
.811 - .860 4 6 8 9 12
.861 - .910 4 6 7 8 11
.911 - .960 4 5 7 8 10
.961 - 1.010 5 6 7 10
1.011 - 1.070 4 6 7 9
1.071 - 1.130 4 4 6 9 11
1.131 - 1.190 4 6 8 11
1.191 - 1.250 4 5 7 10
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
1.251 - 1.310 4 4 7 10
1.311 - 1.370 4 7 9
1.371 - 1.430 4 6 8
1.431 - 1.490 4 6 8
1.491 - 1.550 4 5 8
1.551 -1.610 2 4 7
1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6"
194
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Type S Cable Supports
For Two or More Wires - Indoors - at Voltages to 600 Vac
For Rigid Conduit, IMC and EMT with pOZi-grip™ "S-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit risers.
Features
• Threaded for Rigid Conduit and IMC.
• Use with all types of insulations at voltages to and including 600 Volt.
• The fastest and easiest type cable support to install.
• The knurled insulating inner surface and one piece impregnated
hardwood pOZi-grip plug provide positive support well in excess of code requirements.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay-In­Lug grounding lug should be mounted on cable support body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
• For PVC Conduit, use a PVC terminal adapter.
Material/Finish
• Bodies: malleable or ductile iron with hot dip galvanized nish
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Optional Material/Finish
• For non-metallic bodies see Type D
For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for
use with cable supports.
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Illustrated Features
Impregnated Hardwood pOZi-grip™ Wedging Plug
Shape and special gripping surface of grooves in plug give maximum support to cable.
Malleable or Ductile Iron Body
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Tapered inside surface of insulating bushing is knurled to grip cable.
Dimensions in Millimeters
(Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
Conduit Size
(Inches)
1-1/2 66.8 (2.63) 60.4 (2.38) S-1500-1 S-1500-2 S-1500-BO SPLG-1500-1 SPLG-1500-2
2 79.5 (3.13) 66.8 (2.63) S-2000-1 S-2000-2 S-2000-BO SPLG-2000-1 SPLG-2000-2
2-1/2 95.3 (3.75) 76.2 (3.00) S-2500-1 S-2500-2 S-2500-BO SPLG-2500-1 SPLG-2500-2
3 114.3 (4.50) 79.5 (3.13) S-3000-1 S-3000-2 S-3000-BO SPLG-3000-1 SPLG-3000-2
3-1/2 130.3 (5.13) 88.9 (3.50) S-3500-1 S-3500-2 S-3500-BO SPLG-3500-1 SPLG-3500-2
4 143.0 (5.63) 3.88 (3.88) S-4000-1 S-4000-2 S-4000-BO SPLG-4000-1 SPLG-4000-2
5 174.8 (6.88) 114.3 (4.50) S-5000-1 S-5000-2 S-5000-BO SPLG-5000-1 SPLG-5000-2
6 212.9 (8.38) 139.7 (5.50) S-6000-1 S-6000-2 S-6000-BO SPLG-6000-1 SPLG-6000-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
Outside
Diameter
Overall
Height
2-4 Same Size Wires
Different Size
Wires or 5 or More
Same Size Wires Body Only
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
195
Type D Cable Supports
For Two or More Wires Already Installed in Conduit - Indoors - at Voltages to 600 Vac
Retrofit Type Split Bakelite Body with pOZi-grip™ "S-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit risers.
Features
• Retrot type cable support can be installed after conductors are
pulled and terminated.
• Split body rests on existing bushing atop any conduit raceway.
• The two halves of the body are placed around the cables, seated on the existing bushing and securely held together by the steel band set in a groove around the body. The plug is then wedged between the cables.
• Use with all types of insulations at voltages to and including 600 Volts.
• The tapered, knurled insulating inner body surface and pOZigrip
plug provide support well in excess of code requirements.
Material/Finish
• Bodies: two molded canvas bakelite halves. Inside surface is knurled to grip cables
• Band: steel/zinc plated
• Bolts and nuts: stainless steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Impregnated Hardwood pOZi-grip™ Wedging Plug
Shape and special gripping surface of grooves in plug give maximum support to cable.
Two molded Canvas Bakelite halves. Inside surface is knurled to grip cables.
Steel band, Zinc Plated. Bolts and nuts are Stainless Steel.
Existing Bushing
Existing Conduit
Dimensions in Millimeters (Inches)
Conduit
Size
(Inches)
1-1/2 66.8 (2.63) 50.8 (2.00) 50.8 (2.00) 57.2 (2.25) 1.00 D-1502-1 D-1502-2 SPLG-1500-1 SPLG-1500-2
2 82.6 (3.25) 57.2 (2.25) 60.4 (2.38) 73.2 (2.88) 1.00 D-2002-1 D-2002-2 SPLG-2000-1 SPLG-2000-2
2-1/2 98.6 (3.88) 63.5 (2.50) 76.2 (3.00) 85.9 (3.38) 2.00 D-2502-1 D-2502-2 SPLG-2500-1 SPLG-2500-2
3 114.3 (4.50) 73.2 (2.88) 79.5 (3.13) 101.6 (4.00) 2.00 D-3002-1 D-3002-2 SPLG-3000-1 SPLG-3000-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
3-1/2 133.4 (5.25) 85.9 (3.38) 92.2 (3.63) 117.6 (4.63) 2.00 D-3502-1 D-3502-2 SPLG-3500-1 SPLG-3500-2
4 146.1 (5.75) 88.9 (3.50) 98.6 (3.88) 130.3 (5.13) 2.00 D-4002-1 D-4002-2 SPLG-4000-1 SPLG-4000-2
5 171.5 (6.75) 95.3 (3.75) 120.7 (4.75) 158.8 (6.25) 2.00 D-5002-1 D-5002-2 SPLG-5000-1 SPLG-5000-2
6 209.6 (8.25) 117.6 (4.63) 133.4 (5.25) 187.5 (7.38) 2.00 D-6002-1 D-6002-2 SPLG-6000-1 SPLG-6000-2
Outside
Diameter
Overall
Height
Approx. Turning
Radius R
Inside
Diameter
Number of
Straps
Complete Fitting
Catalog Number Plug Only Catalog Number
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same
Size Wires
2-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same
Size Wires
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
196
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Drill Chart for Type R, DR, CMT, V, C, K, M and W Cable Supports
NEC/CEC:
Listed for Ordinary Locations
For combinations of cables that fall outside these parameters, please contact your local representative.
Type R, DR, CMT, V, C, K, M, and W Cable Supports
Max. Diameter of Wire Permitted - Millimeters (Inches)
Conduit Size
(Inches)
1-1/2" 35.6 (1.40) 16.3 (0.64) 15.0 (0.59) 13.0 (0.51) 9.91 (0.39) 9.4 (0.37)
2" 46.7 (1.84) 21.8 (0.86) 20.1 (0.79) 17.5 (0.69) 13.5 (0.53) 13.5 (0.53)
2-1/2" 57.2 (2.25) 26.9 (1.06) 24.9(0.98) 21.6 (0.85) 16.8 (0.66) 16.3 (0.64)
3" 72.1 (2.84) 34.5 (1.36) 31.8 (1.25) 27.9 (1.1) 21.8 (0.86) 21.6 (0.85)
3-1/2" 84.1 (3.31) 40.6 (1.60) 37.3 (1.47) 33.0 (1.3) 25.9 (1.02) 24.4 (0.96)
1
Wire
2
Wires
3
Wires
4
Wires
5
Wires
6
Wires
4" 96.8 (3.81) 46.7 (1.84) 43.1 (1.7) 38.1 (1.5) 30.0 (1.18) 27.7 (1.09)
5" 122.2 (4.81) 59.4 (2.34) 54.6 (2.15) 48.3 (1.9) 38.6 (1.52) 35.6 (1.4)
6" 148.3 (5.84) 72.6 (2.86) 66.6 (2.62) 59.4 (2.34) 47.2 (1.86) 43.4 (1.71)
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
197
Type R Cable Supports
For One or More Wires - Indoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit risers.
• Due to the possibility of Magnetic Induction Heating, a single alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• The pOZi-grip wedging plug exerts uniform pressure around the cable, providing holding force in excess of that required by code without deforming cable insulation.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay- In-Lug™ grounding lug should be mounted on cable support body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Options
For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for use with cable supports.
For non-metallic bodies, see type DR.
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Illustrated Features
Canvas Bakelite pOZi-grip™ Wedging Plug For one wire type, the plug consists of two pieces. For two wires or more, there is one piece for each wire.
Shape and special gripping surface of grooves in plug give maximum support to each cable and distributes even pressure around its entire circumference.
Malleable or Ductile Iron Body
Inside tapered surface is machined to assure proper seating of the Wedging Plug.
Dimensions in Millimeters
(Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
Conduit Size
(Inches)
1-1/2 66.8 (2.63) 60.4 (2.38) R-1501-1 R-1501-2
2 76.2 (3.00) 66.8 (2.75) R-2001-1 R-2001-2
2-1/2 92.2 (3.63) 79.5 (3.13) R-2501-1 R-2501-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
3 104.9 (4.13) 85.9 (3.38) R-3001-1 R-3001-2
3-1/2 123.9 (4.88) 92.2 (3.63) R-3501-1 R-3501-2
4 143.0 (5.63) 95.3 (3.75) R-4001-1 R-4001-2
5 171.5 (6.75) 111.3 (4.38) R-5001-1 R-5001-2
6 200.2 (7.88) 133.4 (5.25) R-6001-1 R-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Outside
Diameter
Overall
Height
1-4 Same Size Wires
Different Size
Wires or 5 or More
Same Size Wires
198
Any Number of
Catalog Number
Body Only
R-1501-BO
R-2001-BO
R-2501-BO
R-3001-BO
R-3501-BO
R-4001-BO
R-5001-BO
R-6001-BO
Visit our website at www.emerson.com or contact us at (800) 621-1506.
1-4 Same Size Wires
RPLG-1501-1 RPLG-1501-2
RPLG-2001-1 RPLG-2001-2
RPLG-2501-1 RPLG-2501-2
RPLG-3001-1 RPLG-3001-2
RPLG-3501-1 RPLG-3501-2
RPLG-4001-1 RPLG-4001-2
RPLG-5001-1 RPLG-5001-2
RPLG-6001-1 RPLG-6001-2
Different Size
Wires or 5 or More
Same Size Wires
© January 2021
Type DR Cable Supports
For One or More Wires Already Installed in Conduit - Indoors - at all Voltages
Retrofit Type Split Bakelite Body with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Application
• For supporting non-armored electrical cables in vertical conduit risers.
Features
• Retrot type cable support can be installed after conductors are
pulled and terminated.
• Split body rests on existing bushing atop any conduit raceway.
• Use with all types of insulations at all voltages.
• The pOZi-grip™ wedging plug exerts uniform pressure around the cable, providing holding force in excess of that required by code without deforming cable insulation.
Material/Finish
• Bodies: two molded canvas bakelite halves
• Wedging plug: canvas bakelite pOZi-grip
• Band: steel/zinc plated
• Bolts and nuts: stainless steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Canvas Bakelite pOZi-grip™ Wedging Plug For one wire type, the plug consists of two pieces. For two wires or more, there is one piece for each wire.
Shape and special gripping surface of grooves in plug give maximum support to each cable and distributes even pressure around its entire circumference.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Two molded Canvas Bakelite halves. Inside surface is knurled to grip cables.
Steel band, Zinc Plated. Bolts and nuts are Stainless Steel.
Existing Bushing
Existing Conduit
Dimensions in Millimeters (Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
Conduit
Size
(Inches)
1-1/2 66.8 (2.63) 50.8 (2.00) 50.8 (2.00) 57.2 (2.25) 1 DR-1502-1 DR-1502-2 RPLG-1501-1 RPLG-1501-2
2 82.6 (3.25) 57.2 (2.25) 60.4 (2.38) 73.2 (2.88) 1 DR-2002-1 DR-2002-2 RPLG-2001-1 RPLG-2001-2
2-1/2 98.6 (3.88) 63.5 (2.50) 76.2 (3.00) 85.9 (3.38) 2 DR-2502-1 DR-2502-2 RPLG-2501-1 RPLG-2501-2
3 114.3 (4.50) 73.2 (2.88) 79.5 (3.13) 101.6 (4.00) 2 DR-3002-1 DR-3002-2
3-1/2 133.4 (5.25) 85.9 (3.38) 92.2 (3.63) 117.6 (4.63) 2 DR-3502-1 DR-3502-2 RPLG-3501-1 RPLG-3501-2
4 146.1 (5.75) 88.9 (3.50) 98.6 (3.88) 130.3 (5.13) 2 DR-4002-1 DR-4002-2 RPLG-4001-1 RPLG-4001-2
5 171.5 (6.75) 95.3 (3.75) 120.7 (4.75) 158.8 (6.25) 2 DR-5002-1 DR-5002-2 RPLG-5001-1 RPLG-5001-2
Outside
Diameter
Overall Height
Approx. Turning
Radius R
Inside
Diameter
Number of
Straps
1-4 Same Size Wires
Different Size
Wires or 5 or
More Same
Size Wires
1-4 Same Size Wires
RPLG-3001-1
Any Number of
Different Size
Wires or 5 or
More Same
Size Wires
RPLG-3001-2
6 209.6 (8.25) 117.6 (4.63) 133.4 (5.25) 187.5 (7.38) 2 DR-6002-1 DR-6002-2 RPLG-6001-1 RPLG-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
199
Type CMT Cable Supports
Ventilating, Compound, Threaded Type. For One or More Wires - Outdoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Rated for Ordinary Locations
Application
• To support non-armored electrical cables in vertical conduit risers, furnish a weatherproof seal and provide ventilation at the top of the conduit.
• Due to the possibility of Magnetic Induction Heating, a single alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• This device not only supports the cable, but furnishes a weatherproof seal and provides ventilation at the top of the conduit riser.
• The temperature in a conduit riser can be reduced +8 °C to 11 °C (15 °F to 20 °F) with proper venting. To obtain full effect of this decrease, the lower end of the conduit must be open or vented by use of the conduit ventilators.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay- In-Lug™ grounding lug should be mounted on cable support body.
• For threadless rigid conduit, threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
• For PVC conduit, use a PVC terminal adapter.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Illustrated Features
Compound Chamber
Cable Support Body
Ventilating Ports
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Recommended Compound Chamber Material
For insulating compound, use 3M Scotchcast Electrical Insulating Resin 4 with solid and synthetic cable insulations and jackets to insulate between conductors operating up to 8kV.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
Dimensions in Millimeters
(Inches)
Conduit Size
(Inches)
2 79.5 (3.13) 88.9 (3.50) 0.25 CMT-2000-1 CMT-2000-2 CMT-2000-BO RPLG-2001-1 RPLG-2001-2
2-1/2 98.6 (3.88) 101.6 (4.00) 0.33 CMT-2500-1 CMT-2500-2 CMT-2500-BO RPLG-2501-1 RPLG-2501-2
3 114.3 (4.50) 111.3 (4.38) 0.50 CMT-3000-1 CMT-3000-2 CMT-3000-BO RPLG-3001-1 RPLG-3001-2
3-1/2 127.0 (5.00) 120.7 (4.75) 0.75 CMT-3500-1 CMT-3500-2 CMT-3500-BO RPLG-3501-1 RPLG-3501-2
4 139.7 (5.50) 127.0 (5.00) 1.00 CMT-4000-1 CMT-4000-2 CMT-4000-BO RPLG-4001-1 RPLG-4001-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
5 181.1 (7.13) 143.0 (5.63) 1.75 CMT-5000-1 CMT-5000-2 CMT-5000-BO RPLG-5001-1 RPLG-5001-2
6 209.6 (8.25) 171.5 (6.75) 3.50 CMT-6000-1 CMT-6000-2 CMT-6000-BO RPLG-6001-1 RPLG-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Outside
Diameter
Overall
Height
Compound
Required
Pints
200
Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
1-4 Same Size Wires
Different Size
Wires or 5 or More
Same Size Wires Body Only
Visit our website at www.emerson.com or contact us at (800) 621-1506.
1-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
© January 2021
Type V Cable Supports
Ventilating, Compound, Setscrew type. For One or more wires - Outdoors - at all voltages
All Bakelite Cable Support For Threadless Rigid Conduit and IMC with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• To support non-armored electrical cables in vertical conduit risers, furnish a weatherproof seal and provide ventilation at the top of the conduit.
Features
• Use with all types of insulations at all voltages.
• A special cable support made of canvas bakelite. This support
furnishes a weatherproof seal and provides ventilation at the top of the conduit riser. The temperature in a riser can be reduced +8 °C to 11 °C (15 °F to 20 °F) with proper venting. To obtain full effect of this decrease, the lower end of the conduit must be open or vented by use of the conduit ventilators.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• Body can also be mounted on EMT in trade sizes 2-1/2 thru 4.
Material/Finish
• Body and plug: canvas bakelite
Recommended Compound Chamber Material
For insulating compound, use 3M Scotchcast Electrical Insulating Resin 4 with solid and synthetic cable insulations and jackets to insulate between conductors operating up to 8kV.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
Illustrated Features
Cable Support Plug
Setscrew
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Compound Chamber
Cable Support Body
Ventilating Ports
Existing Conduit
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Dimensions in Millimeters
(Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Conduit Size
(Inches)
2
2-1/2
3
3-1/2
4
5
6
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
Outside
Diameter
82.6 (3.25) 95.3 (3.75) 0.25
95.3 (3.75) 104.9 (4.13) 0.33
111.3 (4.38) 114.3 (4.50) 0.50
127.0 (5.00) 127.0 (5.00) 0.75
136.7 (5.38) 136.7 (5.38) 1.00
174.8 (6.88) 152.4 (6.00) 1.75
206.5 (8.13) 177.8 (7.00) 3.50
Overall
Height
Compound
Required
Pints
1-4 Same Size Wires
V-2005-1 V-2005-2 V-2005-BO RPLG-2001-1 RPLG-2001-2
V-2505-1 V-2505-2 V-2505-BO RPLG-2501-1 RPLG-2501-2
V-3005-1 V-3005-2 V-3005-BO RPLG-3001-1 RPLG-3001-2
V-3505-1 V-3505-2 V-3505-BO RPLG-3501-1 RPLG-3501-2
V-4005-1 V-4005-2 V-4005-BO RPLG-4001-1 RPLG-4001-2
V-5005-1 V-5005-2 V-5005-BO RPLG-5001-1 RPLG-5001-2
V-6005-1 V-6005-2 V-6005-BO RPLG-6001-1 RPLG-6001-2
Wires or 5 or More
Any Number of
Different Size
Same Size Wires Body Only
1-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
201
Type C Cable Supports
Compound: Non-Ventilating. For One or More Wires Outdoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ “R-style” Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• To seal the end of conduit and support non-armored electrical cables in vertical conduit risers.
• Due to the possibility of Magnetic Induction Heating, a single alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• This device not only supports the cable, but furnishes a watertight seal at the top of a conduit riser.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay- In-Lug™ grounding lug should be mounted on cable support body.
• For threadless rigid conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
• For PVC conduit, use a PVC terminal adapter.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Recommended Compound Chamber Material
For insulating compound, use 3M Scotchcast Electrical Insulating Resin 4 with solid and synthetic cable insulations and jackets to insulate between conductors operating up to 8kV.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
Illustrated Features
Compound Chamber
Cable Support Body
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Dimensions in Millimeters
(Inches) Complete Fitting Catalog Number Plug Only Catalog Number
Conduit Size
(Inches)
2 79.5 (3.13) 88.9 (3.50) 0.25 C-2004-1 C-2004-2 C-2004-BO RPLG-2001-1 RPLG-2001-2
2-1/2 98.6 (3.88) 101.6 (4.00) 0.33 C-2504-1 C-2504-2 C-2504-BO RPLG-2501-1 RPLG-2501-2
3 114.3 (4.50) 111.3 (4.38) 0.50 C-3004-1 C-3004-2 C-3004-BO RPLG-3001-1 RPLG-3001-2
3-1/2 127.0 (5.00) 120.7 (4.75) 0.66 C-3504-1 C-3504-2 C-3504-BO RPLG-3501-1 RPLG-3501-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
4 139.7 (5.50) 127.0 (5.00) 1.00 C-4004-1 C-4004-2 C-4004-BO RPLG-4001-1 RPLG-4001-2
5 181.1 (7.13) 143.0 (5.63) 1.75 C-5004-1 C-5004-2 C-5004-BO RPLG-5001-1 RPLG-5001-2
6 209.6 (8.25) 171.5 (6.75) 3.50 C-6004-1 C-6004-2 C-6004-BO RPLG-6001-1 RPLG-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Outside
Diameter
Overall Height
Compound
Required
Pints
1-4 Same Size Wires
202
Any Number of
Different Size
Wires or 5 or More
Same Size Wires Body Only
Visit our website at www.emerson.com or contact us at (800) 621-1506.
1-4 Same
Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
© January 2021
Type K Cable Supports
Locking Style: Horizontal or Inverted - One or More Wires - Indoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ “R-style” Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• Can be installed in horizontal or inverted position.
• For supporting non-armored electrical cables in conduit.
• Due to the possibility of Magnetic Induction Heating, a single alternating current conductor should not be used in iron ttings.
Features
• Threaded for Rigid Conduit and IMC.
• Use with all types of insulations at all voltages.
• The design of this support is similar to the Type R except that
is it is equipped with a locking collar which securely holds the
pOZi-grip™ wedging plug in place. This permits the support to be installed in any position and provides holding force against pull in either direction.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
• If mounting on a non-metallic/non-grounded conduit, a Lay- In­Lug™ grounding lug should be mounted on cable support body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
• For PVC Conduit, use a PVC terminal adapter.
Material/Finish
• Body and locking collar: malleable or ductile iron with hot dip galvanized nish
Illustrated Features
Cable Support Plug
Bakelite Bushing
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Cable Support
Body
Existing Conduit
Options
For Lay-in-Lug, see O-Z/Gedney™ Lay-In-Lug Grounding Lugs for use with cable supports.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Dimensions in Millimeters (Inches)
Conduit Size
(Inches)
1-1/2 73.2 (2.88) 69.9 (2.75) K-1503-1 K-1503-2 K-1503-BO RPLG-1501-1 RPLG-1501-2
2 85.9 (3.38) 79.5 (3.13) K-2003-1 K-2003-2 K-2003-BO RPLG-2001-1 RPLG-2001-2
2-1/2 01.6 (4.00) 88.9 (3.50) K-2503-1 K-2503-2 K-2503-BO RPLG-2501-1 RPLG-2501-2
3 114.3 (4.50) 95.3 (3.75) K-3003-1 K-3003-2 K-3003-BO RPLG-3001-1 RPLG-3001-2
3-1/2 130.3 (5.13) 101.6 (4.00) K-3503-1 K-3503-2 K-3503-BO RPLG-3501-1 RPLG-3501-2
4 158.8 (6.25) 111.3 (4.38) K-4003-1 K-4003-2 K-4003-BO RPLG-4001-1 RPLG-4001-2
5 187.5 (7.38) 123.9 (4.88) K-5003-1 K-5003-2 K-5003-BO RPLG-5001-1 RPLG-5001-2
6 212.9 (8.38) 146.1 (5.75) K-6003-1 K-6003-2 K-6003-BO RPLG-6001-1 RPLG-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information. Includes Locking Collar and Bushing.
Outside
Diameter
Overall
Height
Complete Fitting
Catalog Number
1-4 Same
Size Wires
Any Number of
Different Size
Wires or 5 or More
Same Size Wires Body Only
1-4 Same Size Wires
Plug Only
Catalog Number
Any Number of
Different Size
Wires or 5 or More
Same Size Wires
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
203
Type M Cable Supports
Space-Maker Style - One or More Wires - Indoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• Use where there is insufcient room for a cable support inside
a junction box. For supporting non-armored electrical cables in vertical conduit risers.
• Due to the possibility of Magnetic Induction Heating, a single alternating current conductor should not be used in iron ttings.
Illustrated Features
Locknut
Features
• Use with all types of insulations at all voltages.
• This tting is similar to the Type R support, except that it is threaded at the top to allow fastening to a cabinet (1/4 max. thickness) with standard locknuts or threading into tapped (NPT)
openings.
• Body Only can be ordered separately, for installation prior to wire pulling. Plug Only can be ordered later, once wires are in place.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Locknut
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Options
• For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for use with cable supports.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: 11853
Dimensions in Millimeters (Inches)
Conduit
(Inches)
1 - 1/2 2 25.4 (1.00) 66.8 (2.63) 57.2 (2.25) M-1520-1 M-1520-2 M-1520-BO RPLG-1501-1 RPLG-1501-2
2-1/2 3 31.8 (1.25) 92.2 (3.63) 73.2 (2.88) M-2530-1 M-2530-2 M-2530-BO RPLG-2501-1 RPLG-2501-2
3-1/2 4 38.1 (1.50) 123.9 (4.88) 85.9 (3.38) M-3540-1 M-3540-2 M-3540-BO RPLG-3501-1 RPLG-3501-2
Knockout
Size
2 2-1/2 28.7 (1.13) 76.2 (3.00) 66.8 (2.63) M-2025-1 M-2025-2 M-2025-BO RPLG-2001-1 RPLG-2001-2
3 3-1/2 35.1 (1.38) 104.9 (4.13) 79.5 (3.13) M-3035-1 M-3035-2 M-3035-BO RPLG-3001-1 RPLG-3001-2
4 5 41.4 (1.63) 143.0 (5.63) 95.3 (3.75) M-4050-1 M-4050-2 M-4050-BO RPLG-4001-1 RPLG-4001-2
5 6 41.4 (1.63) 171.5 (6.75) 104.9 (4.13) M-5060-1 M-5060-2 M-5060-BO RPLG-5001-1 RPLG-5001-2
Size
(Inches)
Top Thread
Length
Outside
Diameter
Overall
Height
Complete Fitting
Catalog Number
1-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same Size
Wires Body Only
Plug Only
Catalog Number
1-4 Same Size Wires
Any Number of
Different Size
Wires or 5 or
More Same Size
Wires
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
For PVC Conduit, use a PVC terminal adapter. If mounting on a non-metallic/non-grounded conduit, a Type G grounding lug should be mounted on cable support body.
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information. Includes two locknuts.
204
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Type W Cable Supports
Pull Box Style - Raintite Enclosed - For One or More Wires - at all Voltages
For Threaded Rigid Conduit and IMC with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Rated for Ordinary Locations
Applications
• For all types of insulations at all voltages.
• Provides intermediate support of non-armored conductors in an indoor/outdoor vertical conduit run where a junction box and/or pull point is unavailable.
Features
• Meets NEC Section 300.19(A) requirements for intermediate supports at midpoints in vertical conduit risers.
• Requires less space in conduit run than rectangular junction box. May be mounted side-by-side or staggered in multiple conduit runs.
• Type W cable support is essentially a modied type R cable support mounted within a pull box tting.
• Lay-In-Lug grounding lug can be mounted on pull box end
tting.
Material/Finish
• Cable support body and pull box end ttings: malleable or
ductile iron
• Oversize sleeve: steel
• Hot dip galvanized nish
Options
For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for use with cable supports.
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Existing Conduit
Oversize
Sleeve
Type R Cable
Support
Set Screws
Existing Conduit
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Sleeve Furnished
With Fitting
Conduit
Size
(Inches)
1-1/2 63.5 (2.50) 12" 85.9 (3.38) 393.7 (15.50) 26 W-1508-1-OS W-1508-1-LS W-1508-2-OS W-1508-2-LS
2 76.2 (3.00) 15" 01.6 (4.00) 476.3 (18.75) 32 W-2008-1-OS W-2008-1-LS W-2008-2-OS W-2008-2-LS
2-1/2 88.9 (3.50) 15" 17.6 (4.63) 488.9 (19.25) 32 W-2508-1-OS W-2508-1-LS W-2508-2-OS W-2508-2-LS
3 101.6 (4.00) 15" 130.3 (5.13) 488.9 (19.25) 32 W-3008-1-OS W-3008-1-LS W-3008-2-OS W-3008-2-LS
3-1/2 114.3 (4.50) 18" 146.1 (5.75) 571.5 (22.50) 38 W-3508-1-OS W-3508-1-LS W-3508-2-OS W-3508-2-LS
4 127.0 (5.00) 18" 158.8 (6.25) 571.5 (22.50) 38 W-4008-1-OS W-4008-1-LS W-4008-2-OS W-4008-2-LS
5 177.8 (7.00) 18" 212.9 (8.38) 596.9 (23.50) 39 W-5008-1-OS W-5008-1-LS W-5008-2-OS W-5008-2-LS
6 203.2 (8.00) 18" 241.3 (9.50) 615.9 (24.25) 39 W-6008-1-OS W-6008-1-LS W-6008-2-OS W-6008-2-LS
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
Trade Size
(Inches) Length
Dimensions in Millimeters (Inches)
Overall Length
Maximum
Diameter Fitting Closed
Fitting
Open
(Min.) L
Size Wires
Fitting
With Sleeve
1-4 Same
Without Sleeve
Fitting
5 or More Wires
or Different Size Wires
Fitting
With Sleeve
Without Sleeve
Fitting
205
Type KVM and Type KVF Conduit Ventilators
For Threaded Rigid Conduit and IMC.
NEC/CEC:
Rated for Ordinary Locations
Applications
• To provide for the ow of cooling air through a conduit riser.
Features
• The Type KVF conduit ventilators when used at the bottom of a vertical conduit riser which is properly vented at the top, provides for the movement of cooling air through the riser. The temperature in a riser can thus be reduced -9 °C to -6 °C (+15 °F to +20 °F) improving the service life of the cable and increasing its load-carrying capacity.
• The Type KVM conduit ventilator has a male threaded nipple at the top and is used in conjunction with a cable terminator or other device having a female thread where ventilation is desired.
Material/Finish
• Bodies of ttings are cast Aluminum.
• Type KVM nipple is steel, zinc electroplated.
Optional Material
• KVM nipple: available in aluminum. Add sufx -A to catalog number.
Illustrated Features
Existing Conduit
A
Ventilating
Ports
Existing Conduit
Type KVF
Male
Nipple
B
A
Type KVF Type KVM Dimensions in Millimeters (Inches)
Conduit Size
(Inches)
1-1/2 11/2 KVF-1515 1-1/2 69.9 (2.75) 44.5 (1.75) 25.4 (1.00) KVM-1515
2 2” KVF-2020 2 82.6 (3.25) 44.5 (1.75) 28.7 (1.13) KVM-2020
2-1/2 21/2 KVF-2525 2-1/2 98.6 (3.88) 57.2 (2.25) 35.1 (1.38) KVM-2525
3 3” KVF-3030 3 114.3 (4.50) 57.2 (2.25) 38.1 (1.50) KVM-3030
3-1/2 31/2 KVF-3535 3-1/2 127.0 (5.00) 63.5 (2.50) 38.1 (1.50) KVM-3535
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
4 4” KVF-4040 4 139.7 (5.50) 63.5 (2.50) 41.4 (1.63) KVM-4040
5 5” KVF-5050 5 184.2 (7.25) 73.2 (2.88) 41.4 (1.63) KVM-5050
6 6” KVF-6060 6 209.6 (8.25) 73.2 (2.88) 44.5 (1.75) KVM-6060
Trade Size Top
Female Thd. Catalog Number
Ventilating
Ports
Existing Conduit
Type KVM
Trade Size Top
Male Thd. Max Dia. A. B. Approx. Catalog Number
206
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Type G Lay-In-Lug Grounding Lugs
Factory Installed. For mounting on O-Z/Gedney™ fittings. Copper Plus™ Lay-In-Lug Grounding Wire Connectors.
NEC/CEC:
Listed for Ordinary Locations
Application
• Provides a compact means of attaching a grounding or bonding conductor to an O-Z/Gedney™ tting.
Features
• Highly conductive tin-plated copper saddle for use with copper
or aluminum conductors.
• Connector opening allows easy insertion of grounding conductor for thru or end connection.
• Low grounding connector prole.
• Spring action design maintains positive rm contact on
grounding conductor.
• These grounding wire connectors are used on the specication
insulated grounding bushings.
• Grounding lugs not sold separately.
Material/Finish
• Grounding Saddle/Tin Plated Copper
• Clamping Tension Body/Stainless Steel
• Screws/Stainless Steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B, 467
• UL Listed: E-24264
• CSA Standard: C22.2 No. 18, 41
• CSA Certied: 11584
Note:
1. Type G Grounding Lugs are only furnished factory-mounted to O-Z/Gedney™ fittings.
2. Grounding Lugs are not sold separately.
3. Type G Grounding Lugs are not compatible with all O-Z/Gedney™ fitting
in this catalog. Please review specific fittings catalog page to insure compatibility. If unsure, please contact your local representative before ordering.
Mounted on Cable Support Mounted on PK Clamp
TO ORDER:
Place the order for each grounding lug on the next order line immediately after the fitting that the lug will be attached to. See Note prior to ordering.
Ordering Example:
Item #
1
2
Quantity Description Part Number
5 Cable Termination PK-200
5 Grounding Lug G-04S
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Grounding
Min.
14 4 CU only 1/2 — 6 G-04S
8 2/0 AL-CU 1/2 — 6 G-22S
6 4/0 AL-CU 2-1/2 — 6 G-24S
250 500 CU only 2-1/2 — 6 G-25S
Solid or stranded for No. 10 AWG or smaller; stranded for No. 8 or larger Indicates trade sizes of fitting to which grounding lug can be mounted.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
Wire Size
Max.
Lug
Rating
Trade Size
(Inches)
Part
Number
207
Type F Cable Supports
Unthreaded Conduit
For Wire Armored Cable
NEC/CEC:
Rated for Ordinary Locations
Applications
• For supporting wire armored cable in a vertical rise. Also used for supporting submarine cables up to 10,000 lbs.
Material/Finish
• Steel/Hot dip galvanized
Illustrated Features
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Max. Conduit Size
4 3 203.2 (8.00) 120.7 (4.75) F-4030
5 4 228.6 (9.00) 120.7 (4.75) F-5040
Max. Cable Dia. over Wire
Armor A
Upper end of cable, supported by Type F Cable
Type F – For Use with Unthreaded Conduit
Dimensions in Millimeters (Inches)
B.
Approx. Catalog Number
No minimum cable O.D.
208
Visit our website at www.emerson.com or contact us at (800) 621-1506.
© January 2021
Type FT and FS Cable Supports
FT: Threaded Conduit, FS: Structure Mount
For Wire Armored Cable
NEC/CEC:
Rated for Ordinary Locations
Illustrated Features
Type FT
Max. Conduit Size
Type FS
Type FT – For Use with Threaded Conduit Type FS – For Mounting on an Existing Structure
Dimensions in Millimeters (Inches)
Max. Cable Dia. over
Wire Armor A
4 3 203.2 (8.00) 73.2 (2.88) FT-4030
5 4 228.6 (9.00) 73.2 (2.88) FT-5040
Dimensions in Millimeters (Inches)
A
228.6 (9.00)
254.0
(10.00)
279.4
11.00)
304.8
(12.00)
B.
Approx. C D Catalog Number
177.8 (7.00) 63.5 (2.50) 63.5 (2.50) FS-0720
203.2 (8.00) 63.5 (2.50) 88.9 (3.50) FS-0830
228.6 (9.00) 63.5 (2.50) 114.3 (4.50) FS-0940
254.0 (10.00) 88.9 (3.50) 139.7 (5.50) FS-1050
B.
Approx. Catalog Number
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
No minimum cable O.D.
Visit our website at www.emerson.com or contact us at (800) 621-1506. © January 2021
209
Type SF 1773 Cable Supports
For Wire Armored Cable
NEC/CEC:
Rated for Ordinary Locations
Auxiliary Supports
Special auxiliary support specied for use at the lower end of
a conduit riser may be provided as an added factor of safety up to 10,000 lbs. Similar types are often used as intermediate supports when armored cable is run exposed. Contact your local representative for price and availability.
Notes
• All parts to be Hot Dip Galvanized except as noted.
• All Dimensions are nominal and may vary according to normal Foundry and Manufacturing Tolerances.
Illustrated Features
Type SF 1773
Dimension When
Chain is Fully
Extended
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
25.4 (1.00) Approx.
B
(NPT) Thread D
279.4 (11) APPROX.
A
114.3 (4.5)
38.1 (1.50)
19.05 (1.00) Approx.
Section B-B
273.05
(10.75)
B
DIA.
View A-A
DIA.
A
C
Existing Conduit
Existing Wire Armored Cable
Clamp body - Malleable Iron Clamp Wedge - Malleable Iron
(With Epoxy Base Organic Zinc Coating)
(4) 3/4 - 10 HEX HD
B
Steel Bolts, Nuts and Lockwashers Electro Galvanized
19.05 (.75) Eye Bolt
* Flange - Malleable Iron
or Steel
Eye Bolt and Chain
Assembly Electro
Galvanized
A
Ridges or Serrations on Inside
Surface of Wedge to Grip Cable
Dimensions in Millimeters (Inches)
Conduit Size
(Inches)
Max. Cable
DIA C
Min. Cable
DIA C
Max. Conduit
THD in Flange D
DIA
A
B
DIA
5 4 3 127.0 (5.00) 231.9 (9.13) 196.9 (7.75) SF1773-L4050
6 4 3 152.4 (6.00) 276.4 (10.88) 196.9 (7.75) SF1773-L4060
Supports are available less Flange for mounting to structure - Specify Catalog Number less the last two numerals. ie: SF1773L40.
210
Visit our website at www.emerson.com or contact us at (800) 621-1506.
Catalog
Number
© January 2021
Loading...