• Used to support cables in vertical raceways or risers.
• Relieves the strain that would be placed on terminations, the
interior of panels, or other devices to which the cables are
connected.
• Properly designed cable supports must not only be capable
of supporting a given weight of cable with a good margin of
safety but must also support the cable without damaging the
insulation or excessively reducing the amount of insulation over
the conductor in the area where the cable is supported.
O-Z/Gedney™ has been furnishing Cable Supports to the
electrical industry for almost 100 years that meet these
requirements.
over 4/0 AWG - 350 kcmilNot greater than41 (135)18 (60)
over 350 kcmil - 500 kcmilNot greater than36 (120)15 (50)
over 500 kcmil - 750 kcmilNot greater than28 (95)12 (40)
over 750 kcmilNot greater than26 (85)11 (35)
Support of Conductors
in Vertical Raceways
Certifications and Compliances
• Requirements for Cable Supports in the National Electrical
Code reads as follows: 300.19 Supporting Conductors
in Vertical Raceways. (A) Spacing Intervals - Maximum.
Conductors in vertical raceways shall be supported if the
vertical rise exceeds the values in Table 300.19(A). One cable
support shall be provided at the top of the vertical raceway or
as close to the top as practical. Intermediate supports shall be
provided as necessary to limit supported conductor lengths to
not greater than those specied in Table 300.19(A).
Example:
• A 10-story building contains a vertical conduit run from the
basement to the top oor, approx. 34 m (110 ft) in length. The
raceway contains 4/0 copper conductors. Per Table 300.19(A),
the unsupported cable length cannot exceed 25 m (80 ft).
Therefore, one cable support is required at or near the top of the
vertical riser, and one intermediate support is required at or near
the midpoint in the conduit run, assuring that any unsupported
cable length does not exceed 25 m (80 ft).
Aluminum or Copper - Clad Aluminum
Meters (Feet)
Copper
Meters (Feet)
TWO or more wires - Indoors - at voltages to 600 VoltType S
Retrofit - TWO or more wires - Indoors - at voltages to 600 VoltType D
ONE or more wires - Indoors - at all voltages Type R
Retrofit - ONE or more wires - Indoors - at all voltagesType DR
Ventilating - ONE or more wires - Outdoors - at all voltagesType CMT
Ventilating - Bakelite - ONE or more wires - Outdoors - at all voltagesType V
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Non-ventilating - ONE or more wires - Outdoors - at all voltages Type C
Locking - Horizontal/Vertical - ONE or more wires - Indoors - at all voltagesType K
Space Maker - ONE or more wires - Indoors - at all voltagesType M
Pull Box - ONE or more wires - Outdoors at all voltagesType W
Conduit VentilatorsType KVF/KVM
Grounding LugsType G
Wire Armored Cable - In conduit or supported by structureType F/FS/FT/SF1773
192
ApplicationRecommended O-Z/Gedney™ Cable Supports
Visit our website at www.emerson.com or contact us at (800) 621-1506.
• Two basic types of cable supports are offered for use with
non-armored cable. They both utilize the pOZi-grip™ Wedging
Plug. pOZi-grip™ is a unique manufacturing technique for lining
the cable grooves with a coarse grain grit using a high strength
epoxy adhesive. This grit improves the cable support holding
power and does not injure the jacket or insulation on the cable.
One Piece Plug Type "S"
• This type consists of a metal body having an insulating liner
with a knurled and tapered inside surface and a one piece
impregnated hardwood wedging plug having a groove for each
wire. This type support is recommended for use with all types
of non-armored cables 600 Volts or less, as it is the easiest to
install, impossible to install incorrectly and it provides
ventilation of the conduit. This design is used in our Types S
and D Cable Supports. The basic principles of their assembly
are illustrated below.
Type S
1. Screw body on the end of the
conduit or connector in place of the
regular insulating bushing.
Multiple Segment Plug Type "R"
• This type consists of an all metal body having a tapered inner
surface and a canvas bakelite multiple segment wedging plug
so constructed that each cable is supported between grooves
in adjacent segments. This construction provides the uniform
pressure distribution required by the softer types of insulations
frequently used at higher voltages. This design is used in
non-ventilating types R, DR, W, C, K and M, and
Ventilating Compound Types CMT, and V. The basic
principles of their assembly are illustrated below.
Type R
1. Screw body on the end of the conduit
or connector in place of
the regular insulating bushing.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
2. Pull wires and arrange temporary
means of support.
3a. Remove all pulling compound from
wires in the area where they pass
through the cable support.
2. Pull wires and arrange temporary
means of support.
3a. Remove all pulling compound from
wires in the area where they pass
through the cable support.
3b. Place the segments of the plug
around the wires. Where more than
two segments are involved the top of
each plug segment has numbers at
each end and it is important that these
are paired with the corresponding
numbers on the adjacent plug
segments.
4. Tap the plug segments evenly and
firmly into the support body.
193
Drill Chart for Type S and D Cable Supports
NEC/CEC:
Listed for Ordinary Locations
HOW TO USE THIS CHART FOR S AND D CABLE SUPPORTS
(1) Select your conduit size and measure your cable diameter(s) which must t within the min/max range corresponding to the quantity of
cables in the white area of this chart. (Note: S and D Cable Supports must be used with two or more cables, 600 volts maximum)
(2) Cable diameters that fall within the gray area of this chart cannot be accommodated. Therefore a 3" Cable Support has a cable range of
0.261" up to 1.130". Cables smaller or larger cannot be considered.
(3) Example: A 3" Cable Support will be used for 3 cables at 1.051" and 1 cable at 0.384". Refer to the 3" Conduit Size column. We can t
4 cables between 1.011" to 1.070" therefore 3 at 1.051" will t. The fourth cable ts between 0.361" to 0.410" within the white area in
the 3" Conduit column. This drilling will work.
(4) Using the example above but the fourth cable is smaller at 0.216", this drilling will not work. The 0.216" cable falls into the 0.211" to
0.260" range which is within the gray shaded area of the 3" conduit column. In this case, we recommend using our Cable Supports with
R-type wedging plugs. See the R table below.
For combinations of cables that fall outside these parameters, please contact your local representative.
Conduit Size
Types S and D
Min/Max Cable OD
.180 - .2101015
.211 - .26081316
.261 - .3108111418
.311 - .36069121619
.361 - .41048111517
.411 - .4604610131517
.461 - .510458111416
.511 - .560457101214
.561 - .61025691113
.611 - .66024581012
.661 - .7104481011
.711 - .760447910
.761 - .810247810
.811 - .860468912
.861 - .910467811
.911 - .960457810
.961 - 1.01056710
1.011 - 1.0704679
1.071 - 1.130446911
1.131 - 1.19046811
1.191 - 1.25045710
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
1.251 - 1.31044710
1.311 - 1.370479
1.371 - 1.430468
1.431 - 1.490468
1.491 - 1.550458
1.551 -1.610247
1-1/2"2"2-1/2"3"3-1/2"4"5"6"
194
Visit our website at www.emerson.com or contact us at (800) 621-1506.
For Two or More Wires Already Installed in Conduit - Indoors - at Voltages to 600 Vac
Retrofit Type Split Bakelite Body with pOZi-grip™ "S-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit
risers.
Features
• Retrot type cable support can be installed after conductors are
pulled and terminated.
• Split body rests on existing bushing atop any conduit raceway.
• The two halves of the body are placed around the cables,
seated on the existing bushing and securely held together by
the steel band set in a groove around the body. The plug is then
wedged between the cables.
• Use with all types of insulations at voltages to and including
600 Volts.
• The tapered, knurled insulating inner body surface and pOZigrip
plug provide support well in excess of code requirements.
Material/Finish
• Bodies: two molded canvas bakelite halves. Inside surface is
knurled to grip cables
• Band: steel/zinc plated
• Bolts and nuts: stainless steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Impregnated Hardwood
pOZi-grip™ Wedging Plug
Shape and special gripping surface
of grooves in plug give maximum
support to cable.
Two molded Canvas Bakelite halves.
Inside surface is knurled to grip cables.
Steel band, Zinc Plated. Bolts and
nuts are Stainless Steel.
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Applications
• For supporting non-armored electrical cables in vertical conduit
risers.
• Due to the possibility of Magnetic Induction Heating, a single
alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• The pOZi-grip wedging plug exerts uniform pressure around the
cable, providing holding force in excess of that required by code
without deforming cable insulation.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
• If mounting on a non-metallic/non-grounded conduit, a Lay-
In-Lug™ grounding lug should be mounted on cable support
body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the
body can be attached to the male threads of a set-screw or
compression connector.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Options
• For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for
use with cable supports.
• For non-metallic bodies, see type DR.
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Illustrated Features
Canvas Bakelite pOZi-grip™ Wedging Plug
For one wire type, the plug consists of two
pieces. For two wires or more, there is one
piece for each wire.
Shape and special gripping surface of
grooves in plug give maximum support to
each cable and distributes even pressure
around its entire circumference.
Malleable or Ductile Iron Body
Inside tapered surface is
machined to assure proper
seating of the Wedging Plug.
Dimensions in Millimeters
(Inches)Complete Fitting Catalog Number Plug Only Catalog Number
Any Number of
Conduit Size
(Inches)
1-1/266.8 (2.63)60.4 (2.38)R-1501-1R-1501-2
276.2 (3.00)66.8 (2.75)R-2001-1R-2001-2
2-1/292.2 (3.63)79.5 (3.13)R-2501-1R-2501-2
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
3104.9 (4.13)85.9 (3.38)R-3001-1R-3001-2
3-1/2123.9 (4.88)92.2 (3.63)R-3501-1R-3501-2
4143.0 (5.63)95.3 (3.75)R-4001-1R-4001-2
5171.5 (6.75)111.3 (4.38)R-5001-1R-5001-2
6200.2 (7.88)133.4 (5.25)R-6001-1R-6001-2
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Outside
Diameter
Overall
Height
1-4 Same
Size Wires
Different Size
Wires or 5 or More
Same Size Wires
198
Any Number of
Catalog Number
Body Only
R-1501-BO
R-2001-BO
R-2501-BO
R-3001-BO
R-3501-BO
R-4001-BO
R-5001-BO
R-6001-BO
Visit our website at www.emerson.com or contact us at (800) 621-1506.
For One or More Wires Already Installed in Conduit - Indoors - at all Voltages
Retrofit Type Split Bakelite Body with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Listed for Ordinary Locations
Application
• For supporting non-armored electrical cables in vertical conduit
risers.
Features
• Retrot type cable support can be installed after conductors are
pulled and terminated.
• Split body rests on existing bushing atop any conduit raceway.
• Use with all types of insulations at all voltages.
• The pOZi-grip™ wedging plug exerts uniform pressure around
the cable, providing holding force in excess of that required by
code without deforming cable insulation.
Material/Finish
• Bodies: two molded canvas bakelite halves
• Wedging plug: canvas bakelite pOZi-grip
• Band: steel/zinc plated
• Bolts and nuts: stainless steel
™
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
• CSA Standard: C22.2 No.18.3
• CSA Certied: 011584
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Canvas Bakelite pOZi-grip™ Wedging Plug
For one wire type, the plug consists of two
pieces. For two wires or more, there is one
piece for each wire.
Shape and special gripping surface of
grooves in plug give maximum support to
each cable and distributes even pressure
around its entire circumference.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Two molded Canvas Bakelite halves.
Inside surface is knurled to grip cables.
Steel band, Zinc Plated. Bolts and
nuts are Stainless Steel.
Existing Bushing
Existing Conduit
Dimensions in Millimeters (Inches)Complete Fitting Catalog Number Plug Only Catalog Number
Ventilating, Compound, Threaded Type. For One or More Wires - Outdoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Rated for Ordinary Locations
Application
• To support non-armored electrical cables in vertical conduit
risers, furnish a weatherproof seal and provide ventilation at the
top of the conduit.
• Due to the possibility of Magnetic Induction Heating, a single
alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• This device not only supports the cable, but furnishes a
weatherproof seal and provides ventilation at the top of the
conduit riser.
• The temperature in a conduit riser can be reduced +8 °C
to 11 °C (15 °F to 20 °F) with proper venting. To obtain full effect
of this decrease, the lower end of the conduit must be open or
vented by use of the conduit ventilators.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
• If mounting on a non-metallic/non-grounded conduit, a Lay-
In-Lug™ grounding lug should be mounted on cable support
body.
• For threadless rigid conduit, threadless IMC, or EMT, the
body can be attached to the male threads of a set-screw or
compression connector.
• For PVC conduit, use a PVC terminal adapter.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Illustrated Features
Compound Chamber
Cable Support Body
Ventilating Ports
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Recommended Compound Chamber Material
• For insulating compound, use 3M Scotchcast Electrical
Insulating Resin 4 with solid and synthetic cable insulations and
jackets to insulate between conductors operating up to 8kV.
Ventilating, Compound, Setscrew type. For One or more wires - Outdoors - at all voltages
All Bakelite Cable Support For Threadless Rigid Conduit and IMC with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• To support non-armored electrical cables in vertical conduit
risers, furnish a weatherproof seal and provide ventilation at the
top of the conduit.
Features
• Use with all types of insulations at all voltages.
• A special cable support made of canvas bakelite. This support
furnishes a weatherproof seal and provides ventilation at the top
of the conduit riser. The temperature in a riser can be reduced
+8 °C to 11 °C (15 °F to 20 °F) with proper venting. To obtain
full effect of this decrease, the lower end of the conduit must be
open or vented by use of the conduit ventilators.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
• Body can also be mounted on EMT in trade sizes 2-1/2 thru 4.
Material/Finish
• Body and plug: canvas bakelite
Recommended Compound Chamber Material
• For insulating compound, use 3M Scotchcast Electrical
Insulating Resin 4 with solid and synthetic cable insulations and
jackets to insulate between conductors operating up to 8kV.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
Illustrated Features
Cable Support Plug
Setscrew
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Compound Chamber
Cable Support Body
Ventilating Ports
Existing Conduit
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Dimensions in Millimeters
(Inches)Complete Fitting Catalog Number Plug Only Catalog Number
Conduit Size
(Inches)
2
2-1/2
3
3-1/2
4
5
6
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Compound: Non-Ventilating. For One or More Wires Outdoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ “R-style” Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• To seal the end of conduit and support non-armored electrical
cables in vertical conduit risers.
• Due to the possibility of Magnetic Induction Heating, a single
alternating current conductor should not be used in iron ttings.
Features
• Threaded for rigid conduit and IMC.
• Use with all types of insulations at all voltages.
• This device not only supports the cable, but furnishes a
watertight seal at the top of a conduit riser.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
• If mounting on a non-metallic/non-grounded conduit, a Lay-
In-Lug™ grounding lug should be mounted on cable support
body.
• For threadless rigid conduit, Threadless IMC, or EMT, the
body can be attached to the male threads of a set-screw or
compression connector.
• For PVC conduit, use a PVC terminal adapter.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Recommended Compound Chamber Material
• For insulating compound, use 3M Scotchcast Electrical
Insulating Resin 4 with solid and synthetic cable insulations and
jackets to insulate between conductors operating up to 8kV.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
Illustrated Features
Compound Chamber
Cable Support Body
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Dimensions in Millimeters
(Inches)Complete Fitting Catalog Number Plug Only Catalog Number
Locking Style: Horizontal or Inverted - One or More Wires - Indoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ “R-style” Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• Can be installed in horizontal or inverted position.
• For supporting non-armored electrical cables in conduit.
• Due to the possibility of Magnetic Induction Heating, a single
alternating current conductor should not be used in iron ttings.
Features
• Threaded for Rigid Conduit and IMC.
• Use with all types of insulations at all voltages.
• The design of this support is similar to the Type R except that
is it is equipped with a locking collar which securely holds the
pOZi-grip™ wedging plug in place. This permits the support to
be installed in any position and provides holding force against
pull in either direction.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
• If mounting on a non-metallic/non-grounded conduit, a Lay- InLug™ grounding lug should be mounted on cable support body.
• For Threadless Rigid Conduit, Threadless IMC, or EMT, the
body can be attached to the male threads of a set-screw or
compression connector.
• For PVC Conduit, use a PVC terminal adapter.
Material/Finish
• Body and locking collar: malleable or ductile iron with hot dip
galvanized nish
Illustrated Features
Cable Support Plug
Bakelite Bushing
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Cable Support
Body
Existing Conduit
Options
• For Lay-in-Lug, see O-Z/Gedney™ Lay-In-Lug Grounding Lugs
for use with cable supports.
NEC Certifications and Compliances
• UL Standard: ANSI/UL 514B
• UL Listed: E-11853
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Space-Maker Style - One or More Wires - Indoors - at all Voltages
For Rigid Conduit, IMC and EMT with pOZi-grip™ "R-style" Wedging Plug.
NEC:
Listed for Ordinary Locations
Application
• Use where there is insufcient room for a cable support inside
a junction box. For supporting non-armored electrical cables in
vertical conduit risers.
• Due to the possibility of Magnetic Induction Heating, a single
alternating current conductor should not be used in iron ttings.
Illustrated Features
Locknut
Features
• Use with all types of insulations at all voltages.
• This tting is similar to the Type R support, except that it is
threaded at the top to allow fastening to a cabinet (1/4 max.
thickness) with standard locknuts or threading into tapped (NPT)
openings.
• Body Only can be ordered separately, for installation prior to
wire pulling. Plug Only can be ordered later, once wires are in
place.
Material/Finish
• Body: malleable or ductile iron with hot dip galvanized nish
Locknut
Existing Conduit
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Options
• For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for
use with cable supports.
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
For Threadless Rigid Conduit, Threadless IMC, or EMT, the body can be attached to the male threads of a set-screw or compression connector.
For PVC Conduit, use a PVC terminal adapter. If mounting on a non-metallic/non-grounded conduit, a Type G grounding lug should be mounted on cable
support body.
Cable support plugs will not be supplied undrilled. See Drill Chart for wire fill information.
Includes two locknuts.
204
Visit our website at www.emerson.com or contact us at (800) 621-1506.
Pull Box Style - Raintite Enclosed - For One or More Wires - at all Voltages
For Threaded Rigid Conduit and IMC with pOZi-grip™ "R-style" Wedging Plug.
NEC/CEC:
Rated for Ordinary Locations
Applications
• For all types of insulations at all voltages.
• Provides intermediate support of non-armored conductors in an
indoor/outdoor vertical conduit run where a junction box and/or
pull point is unavailable.
Features
• Meets NEC Section 300.19(A) requirements for intermediate
supports at midpoints in vertical conduit risers.
• Requires less space in conduit run than rectangular junction
box. May be mounted side-by-side or staggered in multiple
conduit runs.
• Type W cable support is essentially a modied type R cable
support mounted within a pull box tting.
• Lay-In-Lug grounding lug can be mounted on pull box end
tting.
Material/Finish
• Cable support body and pull box end ttings: malleable or
ductile iron
• Oversize sleeve: steel
• Hot dip galvanized nish
Options
• For Lay-In-Lug, see O-Z/Gedney™ Type G Grounding Lugs for
use with cable supports.
Illustrated Features
TO ORDER SPECIFY:
1. Catalog Number
2. Number of conductors in conduit
3. Outside diameters of each conductor
Existing
Conduit
Oversize
Sleeve
Type R Cable
Support
Set Screws
Existing
Conduit
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
• To provide for the ow of cooling air through a conduit riser.
Features
• The Type KVF conduit ventilators when used at the bottom
of a vertical conduit riser which is properly vented at the top,
provides for the movement of cooling air through the riser.
The temperature in a riser can thus be reduced -9 °C to -6 °C
(+15 °F to +20 °F) improving the service life of the cable and
increasing its load-carrying capacity.
• The Type KVM conduit ventilator has a male threaded nipple
at the top and is used in conjunction with a cable terminator or
other device having a female thread where ventilation is desired.
Material/Finish
• Bodies of ttings are cast Aluminum.
• Type KVM nipple is steel, zinc electroplated.
Optional Material
• KVM nipple: available in aluminum. Add sufx -A to catalog
number.
Illustrated Features
Existing
Conduit
A
Ventilating
Ports
Existing
Conduit
Type KVF
Male
Nipple
B
A
Type KVFType KVMDimensions in Millimeters (Inches)
Factory Installed. For mounting on O-Z/Gedney™ fittings. Copper Plus™ Lay-In-Lug Grounding Wire Connectors.
NEC/CEC:
Listed for Ordinary Locations
Application
• Provides a compact means of attaching a grounding or bonding
conductor to an O-Z/Gedney™ tting.
Features
• Highly conductive tin-plated copper saddle for use with copper
or aluminum conductors.
• Connector opening allows easy insertion of grounding
conductor for thru or end connection.
• Low grounding connector prole.
• Spring action design maintains positive rm contact on
grounding conductor.
• These grounding wire connectors are used on the specication
insulated grounding bushings.
• Grounding lugs not sold separately.
Material/Finish
• Grounding Saddle/Tin Plated Copper
• Clamping Tension Body/Stainless Steel
• Screws/Stainless Steel
NEC/CEC Certifications and Compliances
• UL Standard: ANSI/UL 514B, 467
• UL Listed: E-24264
• CSA Standard: C22.2 No. 18, 41
• CSA Certied: 11584
Note:
1. Type G Grounding Lugs are only furnished factory-mounted to
O-Z/Gedney™ fittings.
2. Grounding Lugs are not sold separately.
3. Type G Grounding Lugs are not compatible with all O-Z/Gedney™ fitting
in this catalog. Please review specific fittings catalog page to insure
compatibility. If unsure, please contact your local representative before
ordering.
Mounted on Cable SupportMounted on PK Clamp
TO ORDER:
Place the order for each grounding
lug on the next order line immediately
after the fitting that the lug will be
attached to. See Note prior to ordering.
Ordering Example:
Item #
1
2
QuantityDescriptionPart Number
5Cable TerminationPK-200
5Grounding LugG-04S
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
Grounding
Min.
144CU only1/2 — 6G-04S
82/0AL-CU1/2 — 6G-22S
64/0AL-CU2-1/2 — 6G-24S
250500CU only2-1/2 — 6G-25S
Solid or stranded for No. 10 AWG or smaller; stranded for No. 8 or larger
Indicates trade sizes of fitting to which grounding lug can be mounted.
Special auxiliary support specied for use at the lower end of
a conduit riser may be provided as an added factor of safety
up to 10,000 lbs. Similar types are often used as intermediate
supports when armored cable is run exposed. Contact your
local representative for price and availability.
Notes
• All parts to be Hot Dip Galvanized except as noted.
• All Dimensions are nominal and may vary according to normal
Foundry and Manufacturing Tolerances.
Illustrated Features
Type SF 1773
Dimension When
Chain is Fully
Extended
COMMERCIAL AND INDUSTRIAL FITTINGS: RIGID AND IMC CONDUIT FITTINGS
25.4 (1.00)
Approx.
B
(NPT) Thread D
279.4 (11)
APPROX.
A
114.3 (4.5)
38.1 (1.50)
19.05 (1.00)
Approx.
Section B-B
273.05
(10.75)
B
DIA.
View A-A
DIA.
A
C
Existing Conduit
Existing Wire Armored Cable
Clamp body - Malleable Iron
Clamp Wedge - Malleable Iron
(With Epoxy Base Organic Zinc
Coating)
(4) 3/4 - 10 HEX HD
B
Steel Bolts, Nuts and
Lockwashers
Electro Galvanized