Emerson FTA2000 Brochures and Data Sheets

Medium Voltage Fire Pump Controllers
Firetrol® FTA2000 combined automatic and manual class E2 medium voltage controllers are intended for star ting squirrel cage motors driving listed fi re pumps.
The maximum controller ratings are as follows:
• 1500 HP (1119 kW) @ 2300 Volts
• 2000 HP (1492 kW) @ 3300 Volts
• 2500 HP (1865 kW) @ 4160 Volts
• 3000 HP (2238 kW) @ 5500 Volts
• 3000 HP (2238 kW) @ 6000 Volts
• 3250 HP (2425 kW) @ 6300 Volts
• 3500 HP (2611 kW) @ 6600 Volts
• 3500 HP (2611 kW) @ 6900 Volts
• 3500 HP (2611 kW) @ 7200 Volts
Approvals
Firetrol fi re pump controllers are listed by Underwriters Laboratories, Inc., in accordance with UL 218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equip­ment (cUL), and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, and NFPA 70, National Electrical Code.
Features
The Firetrol® Mark IIXG medium voltage fi re pump controller monitors, displays and records fi re pump system information. The system is standard on all Firetrol medium voltage electric re pump controllers. The standard USB host controller and port allows recording of events/alarms to a Flash Memory Disk. Depending on the capacity of the fl ash disk utilized, the amount of data saved could easily cover the lifetime of the controller. The data is recorded in text (.txt fi le) format and can easily be reviewed using popular software such as Microsoft
®
.
Excel Door mounted display/interface panel featuring a 128 x 64 pixel backlit LCD Graphical Display, Membrane Type User Control Push-buttons and easy to read LED Indicators for:
• Alarm • Phase Failure
• System Pressure Low • Phase Reversal
• Pump Running • Automatic Shutdown
• Deluge Open Disabled
• Remote Start • Overvoltage
• Interlock On • Undervoltage
• Fail To Start
• Motor Overload
Other features include:
• Isolating switch - NEMA rating, 7200 Volts, 400 Amps with external operating handle and both electrical and
®
Word® or
mechanical interlocks to prevent opening of the medium voltage compartment door with the isolating switch or the main contactor closed.
• Fuses - current limiting motor starting main fuses.
• Vacuum contactor - NEMA rating, 7200 Volts, 400 Amps.
• Control transformer with fused primary and secondary.
• Simultaneous 3 phase display of both voltage and current.
• Pressure display in PSI or Bars in 1 psi increments (0.1 bar)
• Operators for START, STOP, NORMAL-OFF-TEST and manual EMERGENCY RUN.
• Field connection remote alarm terminals for each of the following: Pump Operating, Power Available, Phase Reversal and Overcurrent Trip.
• Circuitry for start by remote deluge valve or other fi re protection equipment (requires normally closed, open to start remote contacts).
• Circuitry for remote start by push-button or other nor­mally open, closed to start device (requires manual stop at controller.
Options and Modifications
Refer to the controller Product Description sheet for a list of available Options and Modifi cations.
Medium voltage compartment (including vacuum contactor, main fuses, motor connection bus and mechanical emergency run mechanism).
Emerson Network Power - Global Headquarters
1050 Dearborn Drive Columbus, OH 43085 Tel +1 614 888 0246
EmersonNetworkPower.com
While every precaution has been taken to ensure accuracy and completeness herein, ASCO assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Information and specifications are subject to change without notice. Emerson, Consider It Solved., Emerson Network Power, the Emerson Network Power Logo, ASCO, Firetrol and the Firetrol Logo are trademarks or registered trademarks of Emerson Electric Co. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2013 Emerson Elec tric Co.
CB2000-50 (C)
ASCO Power Technologies - Firetrol Brand Products
111 Corning Road, Suite 120 Cary, NC 27518 Tel +1 1 460 5200 FaY +1 1 460 5250
Firetrol.com
Loading...