This guide provides basic guidelines for the Emerson Wireless 1410S Gateway. It does not
provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the
Emerson Wireless Gateway 1410S Reference Manual for more information and instructions. The
manuals and this guide are available electronically on Emerson.com/Rosemount.
WARNING
Explosion hazard
Do not make or break any connections to the gateway while circuits are live unless area is known to be
non-hazardous.
Risque d'explosion
N'établissez ni ne rompez aucune connexion à la passerelle lorsque les circuits sont sous tension, à
moins que la zone ne soit connue comme étant non dangereuse.
Explosions could result in death or serious injury
Installation of device in an explosive environment must be in accordance with appropriate local,
national, and international standards, codes, and practices. Review the Product Certifications section
for any restrictions associated with a safe installation.
Avoid contact with leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Les explosions peuvent entraîner la mort ou des blessures graves
L'installation de l'appareil dans un environnement explosif doit être conforme aux normes, codes et
pratiques locaux, nationaux et internationaux appropriés. Consultez la section Certifications du produit
pour toute restriction associée à une installation en toute sécurité.
Évitez tout contact avec les fils et les bornes. La haute tension qui peut être présente sur les câbles peut
provoquer un choc électrique.
Potential electrostatic charging hazard
The Emerson Wireless 1410S2 Gateway enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. The Emerson Wireless 1410S1 Gateway is housed in a polymeric enclosure that
may constitute an electrostatic hazard. Use care in handling and cleaning when in explosive
environments to avoid an electrostatic discharge.
Risque potentiel de charge électrostatique
Voir les instructions.
Repair/maintenance
The Emerson Wireless 1410S Gateway contains no user serviceable components. If the device is not
functioning properly, see the troubleshooting guide in the Emerson Wireless 1410S Gateway manual.
If these troubleshooting steps do not resolve the problem, contact the factory.
Physical access
Physical security is an important part of any security program and fundamental to protecting your
system. Unauthorized personnel may cause intentional or unintentional damage or misconfiguration
of the Emerson Wireless 1410S Gateway and connected field devices. Restrict physical access by
unauthorized personnel to protect end users’ assets
2Emerson.com
July 2022Quick Start Guide
CAUTION
Equipment conformance
Protection may be impaired if the device is used in a manner not specified by the manufacturer.
NOTICE
The 1410S1 needs an external IP54 that meets the requirements of CAN/CSA 60079-0.
Le 1410S1 a besoin d'un IP54 externe qui répond aux exigences de CAN/CSA 60079-0.
The gateway should be installed and functioning properly before power
modules are installed in any wireless field devices. Wireless field devices
should also be powered up in order of proximity from the gateway
beginning with the closest. This will result in a simpler and faster network
installation.
1.2Gateway redundancy
If the wireless gateway was ordered with redundancy (Gateway Redundancy
code RD), refer to Appendix D in the Emerson Wireless 1420 Gateway
Reference Manual for additional installation instructions.
1.3Gateway firmware compatability
The gateway firmware needs to be compatible with host connections being
made. Verify that gateway firmware and host firmware (e.g. Security Setup
Utility (SSU) and Plantweb Insight) are compatible before commissioning.
Quick Start Guide5
Quick Start GuideJuly 2022
2PC requirements
2.1Operating system (optional software only)
For security setup. Microsoft® supported Windows™ operating systems are
acceptable. Some examples are shown below:
• Microsoft Windows Server 2019 (Standard Edition), Service Pack 2
• Windows 10 Enterprise, Service Pack 1
2.2Applications
Configuration of the gateway is done through a secure web interface.
Recent versions of the following browsers are supported:
• Chrome™ browser
• Mozilla Firefox
• Microsoft Edge
2.3Hard disk space
• AMS Wireless Configurator: 1.5 GB
• Gateway Setup CD: 250 MB
®
6Emerson.com
July 2022Quick Start Guide
3Initial connection and configuration
To configure the gateway, a local connection between a computer and the
gateway needs to be established.
Powering the Gateway
For the Emerson Wireless 1410S Gateway, bench top power will be needed
to power the Gateway by wiring a 10.5–30 VDC power source.
An Emerson Wireless 1410S Gateway can also be powered via Power over
Ethernet (PoE) and is compliant with the IEEE 802.3af standard.
Note
The Emerson Wireless 1410S2 Gateway hardware revision 1.0.0 configured
with Intrinsically Safe Outputs option “A” can only be powered by 24 VDC
power source. Check label to verify hardware revision.
A. Mounting plate
B. 781S terminal 1 power and data connections
C. 781S terminal 2 power and data connections
D. Ethernet port 1. When this port is activated, the factory IP address is
192.168.1.10.
E. Ethernet port 2. When this port is activated, the factory IP address is
192.168.2.10.
F. Emerson 1410S power and serial connections
G. 781S power terminals
H. 781S data terminals
I. 10.5 to 30 VDC power input
(1)
J. Serial modbus
K. External ground terminal
L. Internal ground terminal
WARNING
Conduit/cable entries for Emerson Wireless 1410S2 Gateway
The conduit/cable entries in the transmitter housing use a ½–14 NPT thread
form. When installing in a hazardous location, use only appropriately listed
or Ex certified plugs, glands, or adapters in cable/conduit entries.
Installer to ensure external conduit/cable fittings are Type 4X rated or better
(C22.2 No 94.2/UL 50E requirement).
(1) Emerson Wireless 1410S2 Gateway hardware revision 1.0.0 configured with
Intrinsically Safe Outputs option “A” can only be powered by 24 VDC power source.
Check label to verify hardware revision
Quick Start Guide9
Quick Start GuideJuly 2022
3.1Establishing a connection
Connect the PC/laptop to the Ethernet 1 (Primary) receptacle on the
gateway using an Ethernet cable.
For DeltaV Ready Gateways, commission the gateway to the Deltav system
first. Proceed to Section 3.5 for updating user information. Section 3.2-3.4
can be ignored for a DeltaV Ready Gateway.
3.2Windows 10
Procedure
1. Select the network icon in the lower right corner of the Windows 10
workspace.
2. Select the Network & Internet Settings link.
Figure 3-3: WiFi Connections Menu
10Emerson.com
July 2022Quick Start Guide
3. Select Change adapter options.
Figure 3-4: Network & Internet Settings
4. Right click the network interface connection that the gateway is
plugged into, and select Properties.
Quick Start Guide11
Quick Start GuideJuly 2022
5. Select Internet Protocol Version 4 (TCP/IPv4)→Properties.
Figure 3-5: Ethernet properties
Note
If the PC/laptop is from another network, record the current IP
address and other settings so the PC/laptop can be returned to the
original network after the gateway has been configured.
12Emerson.com
July 2022Quick Start Guide
6. Select the Use the following IP address button.
Figure 3-6: IP Address Properties
7. In the IP Address field, enter 192.168.1.11.
8. In the Subnet mask field, enter 255.255.255.0.
9. Select OK for both the Internet Protocol (TCP/IP) Properties window
and the Local Area Connection Properties window.
Note
Connecting to the gateway's secondary Ethernet port will require
different network settings.
Table 3-1: Network Settings
EthernetGatewayPC/laptop/
tablet
1192.168.1.10192.168.1.11255.255.255.0
2192.168.2.10192.168.2.11
Quick Start Guide13
Subnet
Quick Start GuideJuly 2022
3.3Disable proxies
This procedure may be necessary when using a Chrome browser with
Windows operating systems.
Procedure
1. Open web browser.
2. Navigate to Settings→Advanced.
3. In the System section, click Open proxy settings.
Example
Figure 3-7: Proxy settings menu. Only use if a proxy is needed.
14Emerson.com
July 2022Quick Start Guide
3.4Configure the Gateway
To complete initial configuration for the gateway, follow the steps below.
This will have to be done be done for both networks.
Procedure
1. Access the default web page for the gateway at https://
192.168.1.10.
a) Log on as Username: admin
b) Type in password: default
Note
If the gateway has been connected properly, a security
certificate alert will be displayed in the web browser. Proceed
to the gateway web interface and log-in using the following
default credentials. Password should be changed after initial
sign-in. See Section 3.5 for changing username and
passwords.
Figure 3-8: User Name and Password
2. Navigate to System Settings → Gateway → Ethernet
Communication to enter the Network Settings.
a) Configure a static IP Address or set for DHCP and enter a Host
Name.
Quick Start Guide15
Quick Start GuideJuly 2022
Figure 3-9: Ethernet Communication
Note
IP addresses will need to be user defined. See Figure 3-9
contains example IP addresses.
b) Restart application at System Settings→Gateway→
Backup and Restore→Restart Apps.
Note
Resetting applications will temporarily disable communications with
field devices.
3. Disconnect the power and Ethernet cable from the gateway.
3.5
16Emerson.com
Changing username and passwords
Procedure
1. Navigate to System Settings→Users→User Accounts to change
passwords and add users with the following steps.
a) For DeltaV Ready Gateways, access gateway web interface
from DeltaV Explorer
2. Change admin, operator, maintenance, and executive passwords to a
secure password that adheres to user’s password requirements.
July 2022Quick Start Guide
Figure 3-10: Navigating to User Accounts page
NOTICE
Changing passwords is HIGHLY SUGGESTED before installing the
gateway for full use.
WARNING
There is no way to recover lost passwords. The only way to access a
gateway that no longer has known credentials is to factory reset the
gateway. Doing a factory reset will clear all user settings.
Figure 3-11: User Accounts page for updating changing
passwords
Quick Start Guide17
Quick Start GuideJuly 2022
4Physical installation
4.1Emerson 1410S mounting
Find a location where the gateway has convenient access to the host system
network (process control network).
4.1.11401S1 DIN-rail mounting
The Emerson Wireless 1410S1 Gateway can be snapped onto a DIN TS35/7.5
or TS35/15 rail system. To clip the gateway onto the DIN rail, see Figure 4-1.
Prerequisites
• DIN-rail for mounting gateway
• Emerson Wireless 1410S1 Gateway
Procedure
1. Press down on the upper release tab of the gateway to release the
mounting clip.
2. Align top teeth on top of DIN-rail and rotate bottom teeth into
bottom of DIN-rail.
3. Release upper tab to secure the gateway to the DIN-rail.
4. To remove, press down on upper tab to release the gateway from the
DIN-rail.
NOTICE
When mounting the unit in an electrical enclosure or other location,
comply with the appropriate local and national installation codes.
Verify that the installer, associated hardware, and installation
equipment used have the proper certifications for the specific type of
installation being performed. Before installation, verify if local codes
require a permit and/or an inspection before energizing. When
planning the installation, account for routing the antenna cable
within the enclosure.
Note
Do not mount the antenna within a metal enclosure. To avoid
damage to sensitive RF components, do not remove protective cap
from the gateway SMA connector until ready to install the antenna.
18Emerson.com
July 2022Quick Start Guide
Figure 4-1: Emerson 1410S1 Mounting
Quick Start Guide19
Quick Start GuideJuly 2022
4.1.21410S2 Pipe mount
Prerequisites
The following hardware and tools are needed to mount the gateway to a 20in. pipe:
• Two 5/16-in. u-bolts kits (supplied with gateway)
• 2-in. mounting pipe
• 1/2-in. wrench
Procedure
1. Insert one u-bolt around the pipe, through the top mounting holes of
the gateway mounting plate, and through the washer plate.
2. Use a 1/2-in. wrench to fasten the nuts to the u-bolt.
3. Repeat for the second u-bolt and the lower mounting holes.
Figure 4-2: Emerson 1410S2 Mounting
4.1.31410S2 Surface mount
The following hardware and tools are needed to surface mount the gateway
to a support bracket:
Prerequisites
• Four appropriate fasteners for preferred mounting method
• Mounting plate (supplied with gateway)
• Drill (not supplied)
• Wrench (not supplied)
20Emerson.com
July 2022Quick Start Guide
Mount the gateway using the following procedure:
Procedure
Install gateway into surface as shown in Figure 4-3. Screws shown as
example.
Figure 4-3: Emerson 1410S2 Surface Mounting
Quick Start Guide21
Quick Start GuideJuly 2022
4.2Wiring the Emerson 1410S to Power and 781S Smart
Antenna(s)
Prerequisites
• Compatible cable
• Screwdriver
• Wire strippers
• For the Emerson Wireless 1410S1 Gateway, the connectors require a
12-30 AWG cable that meets the ambient temperature requirements of
the end installation. Screws on the connector must be secured with a
torque of 4.4 - 5.3 in-lbs.
• For the Emerson Wireless 1410S2 Gateway, the internal antenna
terminal connections on the shroud require 14 AWG cable or smaller.
The cable must be rated for an ambient temperature of 100 °C. Terminal
screws must be secured with a torque of 7 in-lbs at installation and
maximum torque of 10 in-lbs.
• For the internal and external grounding, screws should be installed with a
torque of 7 in-lbs.
4.2.1Connecting power to the Emerson Wireless 1410S Gateway
Procedure
1. Strip the insulation back a minimum of 0.14 inches.
2. Attach positive and negative wires to appropriate terminals on 1410S
Gateway (see wiring diagrams in Figure 4-4 and Figure 4-5).
4.2.2Connecting 781S antenna to the Emerson 1410S Gateway
Prerequisites
781S is provided with up to 9 m (30 ft) of Belden 3084A cabling. If additional
cabling is required, user must supply field junction box with compatible
terminals and shielded, twisted pair cable such as Belden 3084A.
Recommended cable specifications are an ambient temperature rating of at
least 100°C and 18-24 AWG.
Maximum cable length between 1410S and 781S is 400 m (1312 ft) using
these cable specs.
Procedure
1. Strip the insulation back a minimum of 0.14 inches.
2. Attach 781S Smart Antenna wires to appropriate terminals on
Emerson 1410S Gateway (see wiring diagram in Figure 4-4 and
Figure 4-5).
22Emerson.com
July 2022Quick Start Guide
Note
781S shield must be connected at gateway.
Figure 4-4: Emerson 1410S1 Wiring diagram with 781S smart
antenna
A. Emerson Wireless 1410S1 Gateway
B. Terminal connections
C. Shielded, twisted pair cable
D. Emerson Wireless 781S Smart Antenna
E. 781S power terminals
F. 781S data terminals
G. 10.5 to 30 VDC power input
H. Serial Modbus
I. 781S terminal 1 power and data connections
J. 781S terminal 2 power and data connections
(3)
Quick Start Guide23
Quick Start GuideJuly 2022
Figure 4-5: Emerson 1410S2 Wiring Diagram with 781S Smart
Antenna
A. Emerson Wireless 1410S2 Gateway
B. Terminal connections
C. Shielded, twisted pair cable
D. Emerson Wireless 781S Smart Antenna
E. 781S power terminals
F. 781S data terminals
G. 10.5 to 30 VDC power input
(2)
H. Serial Modbus
I. 781S terminal 1 power and data connections
J. 781S terminal 2 power and data connections
(3)
K. External ground terminal
L. Internal ground terminal
Note
Wire colors are typical of Belden 3084a cable or equivalent
(2) Emerson Wireless 1410S2 Gateway hardware revision 1.0.0 configured with
Intrinsically Safe Outputs option “A” can only be powered by 24 VDC power source.
Check label to verify hardware revision.
(3) Second antenna can be connected to terminal 2, Wiring is same as terminal 1
antenna.
24Emerson.com
July 2022Quick Start Guide
4.3Emerson 1410S grounding
4.3.1Emerson 1410S1 grounding
The Emerson Wireless 1410S1 Gateway is grounded through the DIN-rail
mounting plate on the back of the gateway. The DIN-rail should always be
grounded in accordance with national and local electrical codes. Ensure
proper contact between gateway's mounting plate and DIN-rail for
grounding.
4.3.2Emerson 1410S2 grounding
The gateway's enclosure case should always be grounded in accordance with
national and local electrical codes using either the internal or external
grounding provisions. The most effective grounding method is a direct
connection to earth ground with minimal impedance. The ground should be
connected with a conductor larger than 11AWG. Ensure the ground screw is
securely tightened. The internal and external ground screws should be
installed with a torque of 7 in-lbs. The connection should be 1Ω or less. See
wiring diagrams in Figure 4-5 above for identifying internal and external
ground terminals.
Note
Always make sure cable is rated for ambient temperature of the end
installation.
4.4
4.5
4.6
Quick Start Guide25
Terminating resistors
Three DIP switches are provided to enable termination and biasing resistors
to the serial Modbus connection.
See 1410S Reference Manual for more information.
Connect to the host system
Connect the Gateway’s Ethernet 1 (Primary) or serial Modbus Output
connection to the Host System Network or Serial I/O.
Refer to 1410S Reference Manual for additional instruction on host
connections.
Best practice
Twisted shielded pair cable is generally used to wire the serial connection,
and it is standard practice to ground the shield on the serial host side leaving
the shield floating on the gateway side. Insulate the shield to avoid
grounding issues.
Quick Start GuideJuly 2022
4.6.1Security best practices
For security best practices, please see Emerson Wireless Security
Whitepaper. User is solely responsible for the security of their system and
products installed on such systems. These recommendations are in addition
to user’s product and cybersecurity policies.
26Emerson.com
July 2022Quick Start Guide
5Software installation (optional)
Install Security Setup Utility (only required for secure host connections or
OPC-DA communications) and AMS Wireless Configurator as needed. See
Reference Manual for further information.
The gateway firmware needs to be compatible with host connections being
made. Verify that gateway firmware and host firmware (e.g. Security Setup
Utility (SSU) and Plantweb Insight) are compatible before commissioning.
Quick Start Guide27
Quick Start GuideJuly 2022
6Verify operations
Operation is verified through the web interface by opening a web browser
from any PC on the host system network and entering the gateway IP
address or DHCP host name in the address bar.
Log in using credentials set in Section 3-5.
Procedure
1. Ensure field devices to be used with each network have the Network
ID and Join Key that can be found on the gateway’s Network Settings
Page.
2. Verify field devices are joined to the network and displayed on the
Devices page of the gateway web interface.
3. Verify host system is receiving field device data.
28Emerson.com
July 2022Quick Start Guide
7Product certifications
7.1Emerson Wireless 1410S1 Gateway
Rev: 1.0
7.1.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com.
7.1.2Ordinary location certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.1.3Installing equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
7.1.4USA
N5 U.S.A. Division 2 with Intrinsically Safe Outputs
Certificate
Standards
Markings with
Intrinsically Safe into
Division 1 or Zone 0
Markings with
Intrinsically Safe into
Division 2 or Zone 2
Temperature code
Special Conditions for Safe Use(X)
1. Warning: Potential electrostatic charging hazard - See instructions.
Quick Start Guide29
80009647 (CSA)
UL 60079-0: 2019, UL 60079-7: 2017, UL
60079-11: 2014, FM 3600: 2011, FM 3610:2018,
FM 3611:2004, FM 3616:2011, UL 61010-1-12 Ed
3
Class I Division 2, Groups A, B, C, D; Intrinsically
Safe outputs to Class I, Division 1, Groups A, B, C,
D; Class I, Zone 2 AEx ec [ia Ga] IIC T4 Gc
Class I Division 2, Groups A, B, C, D; Intrinsically
Safe outputs to Class I, Division 2, Groups A, B, C,
D; Class I, Zone 2 AEx ec [ic] IIC T4 Gc
T4 (-40 °C ≤ Ta ≤ 70 °C)
Quick Start GuideJuly 2022
2. Warning: The equipment is not capable of withstanding the 500V
electrical strength test as defined in Clause 6.1 of UL 60079-7:2017
and 6.3.13 of UL 60079-11:2014. This must be taken into account
during installation.
3. The 1410S1 needs an external IP54 that meets the requirements of
UL 60079-0.
7.1.5Canada
N6 Canada Division 2 with Intrinsically Safe Outputs
Certificate
Standards
80009647 (CSA)
CAN/CSA C22.2 No 60079-0:2019, CAN/CSA
C22.2 No 60079-7:2016, CAN/CSA C22.2 No
60079-11:2014, CAN/CSA C22.2 No.25:2014,
CAN/CSA C22.2 No.61010-1-12 3rd Edition
Markings with
Intrinsically Safe into
Division 1 or Zone 0
Markings with
Intrinsically Safe into
Division 2 or Zone 2
Temperature code
Class I Division 2, Groups A, B, C, D; Intrinsically
Safe outputs to Class I, Division 1, Groups A, B, C,
D; Class I, Zone 2 Ex ec [ia Ga] IIC T4 Gc
Class I Division 2, Groups A, B, C, D; Intrinsically
Safe outputs to Class I, Division 2, Groups A, B, C,
D; Class I, Zone 2 Ex ec [ic] IIC T4 Gc
T4 (-40 °C ≤ Ta ≤ 70 °C)
Special Conditions for Safe Use(X)
1. Warning: Potential electrostatic charging hazard - See instructions.
AVERTISSEMENT - RISQUE D'EXPLOSION. NE PAS DÉBRANCHER
PENDANT QUE LE CIRCUIT EST SOUS TENSION.
2. Warning: The equipment is not capable of withstanding the 500V
electrical strength test as defined in Clause 6.1 of CAN/CSA
60079-7:2016 and 6.3.13 of CAN/CSA 60079-11:2014. This must be
taken into account during installation.
Avertissement: L'équipement n'est pas capable de résister au test de
résistance électrique de 500V tel que défini dans la clause 6.1 de
CAN / CSA 60079-7:2016 et 6.3.13 de CAN / CSA 60079-11:2014.
Ceci doit être pris en compte lors de l'installation.
3. The 1410S1 needs an external IP54 that meets the requirements of
CAN/CSA 60079-0.
Le 1410S1 a besoin d'un IP54 externe qui répond aux exigences de
CAN/CSA 60079-0.
30Emerson.com
July 2022Quick Start Guide
7.2Emerson Wireless 1410S2 Gateway
Rev: 3.0
7.2.1European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com.
7.2.2Ordinary location certification
As standard, the transmitter has been examined and tested to determine
that the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
7.2.3Installing equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
7.2.4USA
N5 U.S.A. Division 2 with Intrinsically Safe Outputs
Certificate
Standards
Markings with
Intrinsically Safe
Outputs into
Division 1 or Zone 0
Markings with
Intrinsically Safe
into Division 2 or
Zone 2
Temperature Code
Quick Start Guide31
80009647 (CSA)
UL 60079-0: 2019, UL 60079-7: 2017, UL 60079-11:
2014, UL 60079-31: 2015, FM 3600: 2011, FM
3610:2018, FM 3611:2004, FM 3616:2011, UL
61010-1-12 Ed 3
Class I, II, III, Division 2, Groups A, B, C, D, F, G;
Intrinsically Safe outputs to Class I, Division 1,
Groups A, B, C, D; Class I, Zone 2 AEx ec [ia Ga] IIC
T4 Gc; Class I, Class II, Zone 22 AEx tc [ia Ga] IIIC T90
Dc
Class I, II, III, Division 2, Groups A, B, C, D, F, G;
Intrinsically Safe outputs to Class I, Division 2,
Groups A, B, C, D; Class I, Zone 2 AEx ec [ic] IIC T4
Gc; Class II, Zone 22 AEx tc [ic Gc] IIIC T90 Dc
Rev 1 (-40 °C ≤ Ta ≤ 65 °C ), Rev 2 T4 (-40 °C ≤ Ta ≤ 70
°C)
Quick Start GuideJuly 2022
Special Conditions for Safe Use (X):
1. Warning: Potential electrostatic charging hazard - See instructions.
2. Warning: The equipment is not capable of withstanding the 500V
electrical strength test as definded in Clause 6.1 of UL 60079-7:2017
and 6.3.13 of UL 60079-11:2014. This must be taken into account
during installation.
7.2.5Canada
N6 Canada Division 2 with Intrinsically Safe Outputs
Certificate
Standards
80009647 (CSA)
CAN/CSA C22.2 No 60079-0:2019, CAN/CSA C22.2
No 60079-7:2016, CAN/CSA C22.2 No
60079-11:2014, CAN/CSA C22.2 No
60079-31:2016, CAN/CSA C22.2 No.25:2014,
CAN/CSA C22.2 No.61010-1-12 3rd Edition
Markings with
Intrinsically Safe
Outputs into
Division 1 or Zone 0
Markings with
Intrinsically Safe
Outputs into
Division 2 or Zone 2
Temperature code
Class I, II, III, Division 2, Groups A, B, C, D, F, G;
Intrinsically Safe outputs to Class I, Division 1,
Groups A, B, C, D; Class I, Zone 2 Ex ec [ia Ga] IIC T4
Gc; Class II, Zone 22 Ex tc [ia Ga] IIIC T90 Dc
Class I, II, III, Division 2, Groups A, B, C, D, F, G;
Intrinsically Safe outputs to Class I, Division 2,
Groups A, B, C, D; Class I, Zone 2 Ex ec [ic] IIC T4 Gc;
Class II, Zone 22 Ex tc [ic Gc] IIIC T90 Dc
Rev 1 (-40 °C ≤ Ta ≤ 65 °C ), T4 (-40 °C ≤ Ta ≤ 70 °C)
Special Conditions for Safe Use (X):
1. Warning: Potential electrostatic charging hazard - See instructions.
AVERTISSEMENT - RISQUE D'EXPLOSION. NE PAS DÉBRANCHER
PENDANT QUE LE CIRCUIT EST SOUS TENSION.
2. Warning: The equipment is not capable of withstanding the 500V
electrical strength test as defined in Clause 6.1 of CAN/CSA
60079-7:2016 and 6.3.13 of CAN/CSA 60079-11:2014. This must be
taken into account during installation.
Avertissement: L'équipement n'est pas capable de résister au test de
résistance électrique de 500V tel que défini dans la clause 6.1 de
CAN / CSA 60079-7: 2016 et 6.3.13 de CAN / CSA 60079-11: 2014.
Ceci doit être pris en compte lors de l'installation.
32Emerson.com
July 2022Quick Start Guide
7.2.6Europe
N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 0
Certificate
Markings
Standards
SGS20ATEX0036X
II 3(1)G Ex ec [ia Ga] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 0 (For
use only with the Cisco Outdoor Access Point Model IW-6300H-AC-x-K9)
Certificate
Markings
Standards
SGS20ATEX0036X
II 3(1)G Ex ec nA [ia Ga] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
Special Conditions for Safe Use (X):
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 2
Certificate
Markings
Standards
SGS20ATEX0057X
II 3G Ex ec [ic] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
N1 ATEX Increased Safety with Intrinsically Safe Outputs to Zone 2 (For
use only with the Cisco Outdoor Access Point Model IW-6300H-AC-x-K9)
Certificate
Markings
Standards
SGS20ATEX0057X
II 3G Ex ec nA [ic] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
Quick Start Guide33
Quick Start GuideJuly 2022
Special Conditions for Safe Use (X):
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The non-intrinsically safe Supply, Modbus RTU & Ethernet Port
connections of the equipment must be supplied from either safety
extra low-voltage (SELV) or protective extra low-voltage (PELV)
circuits, for example equipment complying with the requirements of
either the IEC 60950 series, IEC 61010-1 or a technically equivalent
standard.
3. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
ND ATEX Dust-Ignition Proof with Intrinsically Safe Outputs to Zone 0
Certificate
Markings
SGS20ATEX0036X
II 3D (1G) Ex tc [ia IIC Ga] IIIC T90 °C Dc (-40 °C ≤ Ta ≤ +65
°C)
Standards
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
Special Conditions for Safe Use (X):
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
ND ATEX Dust-Ignition Proof with Intrinsically Safe Outputs to Zone 2
Certificate
Markings
SGS20ATEX0036X
II 3D (3G) Ex tc [ic IIC Gc] IIIC T90 °C Dc (-40 °C ≤ Ta ≤ +65
°C)
Standards
EN IEC 60079-0: 2018, EN IEC 60079-7:2015+A1:2018, EN
60079-11: 2012, EN 60079-15:2010, EN 60079-31:2014
34Emerson.com
July 2022Quick Start Guide
Special Conditions for Safe Use (X):
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The non-intrinsically safe Supply, Modbus RTU & Ethernet Port
connections of the equipment must be supplied from either safety
extra low-voltage (SELV) or protective extra low-voltage (PELV)
circuits, for example equipment complying with the requirements of
either the IEC 60950 series, IEC 61010-1 or a technically equivalent
standard.
3. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
7.2.7International
N7 IECEx Increased Safety with Intrinsically Safe Output to Zone 0
Certificate
Markings
Standards
IECEx BAS.20. 0022X
Ex ec [ia Ga] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
Quick Start Guide35
Quick Start GuideJuly 2022
N7 IECEx Increased Safety with Intrinsically Safe Output to Zone 2
Certificate
Markings
Standards
IECEx BAS.20. 0027X
Ex ec [ic] IIC T4 Gc (-40 °C ≤ Ta ≤ +65 °C)
IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The non-intrinsically safe Supply, Modbus RTU & Ethernet Port
connections of the equipment must be supplied from either safety
extra low-voltage (SELV) or protective extra low-voltage (PELV)
circuits, for example equipment complying with the requirements of
either the IEC 60950 series, IEC 61010-1 or a technically equivalent
standard.
3. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of EN 60079-7:2015+ A1:2018
and 6.3.13 EN 60079-11:2012. This must be taken into account
during installation.
NF IECEx Dust-Ignition Proof with Intrinsically Safe Outputs to Zone 0
Certificate
Markings
Standards
IECEx BAS.20. 0022X
Ex tc [ia IIC Ga] IIIC T90 °C Dc (-40 °C ≤ Ta ≤ +65 °C)
IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
36Emerson.com
July 2022Quick Start Guide
2. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of IEC 60079-7:2015+ A1:2017.
This must be taken into account during installation.
NF IECEx Dust-Ignition Proof with Intrinsically Safe Outputs to Zone 2
Certificate
Markings
Standards
IECEx BAS.20. 0027X
Ex tc [ic IIC Gc] IIIC T90 °C Dc (-40 °C ≤ Ta ≤ +65 °C)
IEC 60079-0: 2017, IEC 60079-7:2015+A1:2017, IEC
1. The enclosure’s polyurethane paint finish may constitute an
electrostatic hazard. Care should be taken to protect it from external
conditions conducive to the build-up of electrostatic charge on such
surfaces. The equipment must only be cleaned with a damp cloth.
2. The non-intrinsically safe Supply, Modbus RTU & Ethernet Port
connections of the equipment must be supplied from either safety
extra low-voltage (SELV) or protective extra low-voltage (PELV)
circuits, for example equipment complying with the requirements of
either the IEC 60950 series, IEC 61010-1 or a technically equivalent
standard.
3. The equipment is not capable of withstanding the 500V electrical
strength test as defined in clause 6.1 of IEC 60079-7:2015+ A1:2017.
This must be taken into account during installation.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
Emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.