Micro Motion™ ELITE™ Coriolis Flow and
Density Sensors
October 2020
Safety messages
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully
before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the configuration
manual. Product data sheets and manuals are available from the Micro Motion web site at www.emerson.com.
Return policy
Follow Micro Motion procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Micro Motion employees. Micro Motion will not accept
your returned equipment if you fail to follow Micro Motion procedures.
Return procedures and forms are available on our web support site at www.emerson.com, or by phoning the Micro Motion
Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America
United States800-522-6277U.K. and Ireland0870 240 1978Australia800 158 727
This document provides information on planning, mounting, wiring, and grounding the
ELITE sensor.
The information in this document assumes that users understand basic transmitter and
sensor installation, configuration, and maintenance concepts and procedures.
1.2Hazard messages
This document uses the following criteria for hazard messages based on ANSI standards
Z535.6-2011 (R2017).
DANGER
Serious injury or death will occur if a hazardous situation is not avoided.
WARNING
Serious injury or death could occur if a hazardous situation is not avoided.
CAUTION
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a
situation is not avoided. There is no credible risk of physical injury.
Physical access
NOTICE
Unauthorized personnel can potentially cause significant damage and/or misconfiguration
of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access to protect users' assets. This is true for all
systems used within the facility.
Installation Manual5
Before you beginInstallation Manual
October 202020002158
1.3Related documentation
You can find all product documentation on the product documentation DVD shipped with
the product or at www.emerson.com.
See any of the following documents for more information:
• The hazardous area approvals documentation shipped with the sensor or available at
www.emerson.com/flowmeasurement.
• Micro Motion ELITE Coriolis Flow and Density Meters Product Data Sheet
• Micro Motion 9-Wire Flow Meter Cable Preparation and Installation Guide
• The transmitter installation and configuration and use guides
6Micro Motion ELITE
Installation Manual
20002158October 2020
Planning
2Planning
2.1Installation checklist
□ If you plan to mount the transmitter in a hazardous area:
WARNING
Make sure that the hazardous area specified on the approval tag is suitable for the
environment in which the meter will be installed.
□ Verify that the local ambient and process temperatures are within the limits of the
meter.
□ If your sensor has an integral transmitter, no wiring is required between the sensor and
transmitter. Follow the wiring instructions in the transmitter installation manual for
signal and power wiring.
□ If your transmitter has remote-mounted electronics, follow the instructions in this
manual for wiring between the sensor and the transmitter, and then follow the
instructions in the transmitter installation manual for power and signal wiring.
Table 2-1: Maximum lengths for Micro Motion cable
Cable typeTo transmitterMaximum length
Micro Motion 9-wire9739 MVD transmitter1,000 ft (305 m)
All other MVD transmitters60 ft (18 m)
Micro Motion 4-wireAll 4-wire MVD transmitters— 1,000 ft (305 m) without
Ex-approval
— 500 ft (152 m) with IIC
rated sensors
— 1,000 ft (305 m) with IIB
rated sensors
Table 2-2: Maximum lengths for user-supplied 4-wire cable
Wire functionWire sizeMaximum length
Power (VDC)22 AWG (0.326 mm²)300 ft (91 m)
20 AWG (0.518 mm²)500 ft (152 m)
18 AWG (0.823 mm²)1,000 ft (305 m)
Signal (RS-485)22 AWG (0.326 mm²) or larger 1,000 ft (305 m)
□ For optimal performance, install the sensor in the preferred orientation. The sensor will
work in any orientation as long as the flow tubes remain full of process fluid.
Installation Manual7
Planning
October 202020002158
Table 2-3: Preferred sensor orientation
Installation Manual
Process
Liquids & slurries
Gases
Primary preferred
orientation
Liquid with bubblesWet gas
Secondary preferred
orientation
Alternate suitable
orientation
Two-phase
□ Install the meter so that the flow direction arrow on the sensor case matches the actual
forward flow of the process. (Flow direction is also software-selectable.)
2.2Best practices
The following information can help you get the most from your sensor.
• There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe
upstream or downstream are unnecessary.
• If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward
through the sensor. Gases should flow downward.
• Keep the sensor tubes full of process fluid.
• For halting flow through the sensor with a single valve, install the valve downstream
from the sensor.
8Micro Motion ELITE
Installation ManualPlanning
20002158October 2020
• The sensor does not require external supports. The flanges will support the sensor in
any orientation. (Some sensor models installed in very small, flexible pipeline have
optional installation instructions that allow for external supports.)
2.3Temperature limits
Sensors can be used in the process and ambient temperature ranges shown in the
temperature limit graphs. For the purposes of selecting electronics options, temperature
limit graphs should be used only as a general guide. If your process conditions are close to
the gray area, consult with your Micro Motion representative.
Note
• In all cases, the electronics cannot be operated where the ambient temperature is
below -40 °F (-40.0 °C) or above 140 °F (60.0 °C). If a sensor is to be used where the
ambient temperature is outside of the range permissible for the electronics, the
electronics must be remotely located where the ambient temperature is within the
permissible range, as indicated by the shaded areas of the temperature limit graphs.
• Temperature limits may be further restricted by hazardous area approvals. Refer to the
hazardous area approvals documentation shipped with the sensor or available at
www.emerson.com/flowmeasurement.
• The extended-mount electronics option allows the sensor case to be insulated without
covering the transmitter, core processor, or junction box, but does not affect
temperature ratings. When insulating the sensor case at elevated process
temperatures above 140 °F (60.0 °C), ensure electronics are not enclosed in insulation
as this may lead to electronics failure.
• For the CMFS007 sensor, the difference between the process fluid temperature and the
average temperature of the case must be less than 210 °F (99 °C)
Installation Manual9
140 (60)
–40 (–40)
113
(45)
–148 (–100)
–400
(–240)
400
(204)
140
(60)
T amb
T proc
A
B
B
C
-148
(-100)
PlanningInstallation Manual
October 202020002158
Ambient and process temperature limits for CMFS007, CMFS025–CMFS150
B
113
(45)
Tamb
–40 (–40)
140 (60)
140 (60)
A
B
–148 (–100)
–58 (–50)400 (204)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options
B= Remote mount electronics only
Ambient and process temperature limits for CMF***M/L/H/P (excludes special order
cryogenic modifications) and CMFS010-015
Tproc
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options
B = Remote mount electronics only
C = Recommend special order cryogenic sensor options when operating at a process
temperature below -148 °F (-100 °C)
10Micro Motion ELITE
Installation ManualPlanning
20002158October 2020
Ambient and process temperature limits for special order cryogenic ELITE meters
140 (60)
Tamb
–40 (–40)
A
B
–148 (–100)
–400
(–240)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
Tproc
A = All available electronic options
B= Remote mount electronics only
Ambient and process temperature limits for high temperature ELITE meters
140 (60)
176
(80)
Tamb
–40 (–40)
–148 (–100)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A = All available electronic options
B= Remote mount electronics only
–58
(–50)
A
B
Tproc
662
(350)
Installation Manual11
PlanningInstallation Manual
October 202020002158
Ambient and process temperature limits for super duplex ELITE meters
140 (60)
140 (60)
B
113
(45)
Tamb
–40 (–40)
–148 (–100)
–40 (–40)400 (204)
T
= Ambient temperature °F (°C)
amb
T
= Process temperature °F (°C)
proc
A
B
Tproc
A = All available electronic options
B= Remote mount electronics only
Note
For super duplex models operating above 351 °F (177.2 °C), consult the factory before
purchase.
2.4Recommendations for hygienic and selfdraining applications
CMFS sensors are certified EHEDG TYPE EL CLASS I for hygienic applications when installed
vertically with the process fitting and gasket combinations listed in the Position Paper of
the EHEDG Test Methods Subgroup (available at https://www.ehedg.org). Other process
connections/gasket combinations may be used provided they have been evaluated and
successfully tested for in-place cleanability according to the latest edition of EHEDG
Document 2. Refer to the ELITE Product Data Sheet for further information about fitting
options.
For optimal cleanability and drainability:
• If possible, install the sensor in a vertical pipeline with the process fluid flowing upward
through the sensor.
• If the sensor must be installed in a horizontal pipeline, drainage is accomplished by air
purge evacuation of the pipeline circuit.
• For clean-in-place (CIP) applications, Micro Motion recommends using the generally-
accepted flow velocity of at least 1.5 m/s for cleaning the sensor.
• The gap between the electronics housing and sensor body should be inspected
periodically. Manually clean this gap when necessary.
12Micro Motion ELITE
A
B
C
Installation ManualPlanning
20002158October 2020
Figure 2-1: Installation for self-draining applications
A. Process pipeline
B. Direction of normal process flow
C. Direction of drainage
Installation Manual13
Loading...
+ 29 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.