Emerson Edco TER Installation Manual

Edco TER Series
Single Pair Medium Duty Low Voltage Zone/Horn/Strobe/Data
The Edco TER surge suppressor directly installs onto electronic circuit wiring terminal screws. This close proximity preserves Edco TER’s response time, clamping level and ground reference by eliminating lead lengths. The Edco TER’s miniature size fits directly inside fire or security panels, CCTV housings and other system electronic enclosures. These features maximize surge suppression performance while reducing hardware and labor costs to install.
General Technical Specifications
Operating Voltage 40 VDC
Clamping Voltage 43 VDC
Operating Current 2 A
Peak Pulse Current (10 x 1000 μs) 043 = 46.5 A
Frequency Range 0 to 20 MHz
Insertion Loss < 0.1 dB at 20 MHz
SPD Technology Silicon Avalanche Diode (SAD)
Connection Type Terminal block w/compression lugs
Terminals accept up to 12 AWG
Operating Temperature -40°C to +85°C
Dimensions (in / mm) 1.3˝ H x 0.4˝ W x 2.0˝ L
Weight (oz / kg) 0.6 oz [0.02 kg]
Certifications UL 497B
Warranty 5 years
Features
■ Fits Euro style and barrier strip
terminals
■ Automatic recovery
■ Single pair protection
■ High energy silicon avalanche
technology
■ UL 497B listed
■ Operating current > 2 Amps
■ Compact size:
1.3˝ H x 0.4˝ W x 2.0˝ L [33.02 x 10.16 x 50.8 mm]
Ordering Information
MODEL APPLICATIONS
TER-043 12 VDC, 24 VDC, 25 VAC Systems
Zone, Buss, Loop, Data, Receive, Bell, Horn, Strobe, Pan/Tilt & CCTV
■ 5 year warranty
Installation Instructions
1. Install zone or loop circuit wires (1 pair) at the vacant end of the Edco TER. Torque terminal screws to 3.5 in. lbs. max.
2. Slip the Edco TER’s Rigid Mounting Prongs into the panels designated Zone or Loop terminals and tighten.
3. Using a 16-12 AWG solid wire, attach all Edco TERs via the center ground terminal. Run this wire to your panel’s “single point” AC power ground or building approved ground. Torque terminal screws to 6.0 in. lbs. max.
Note:
A. Never install data wiring during a lightning storm. B. Disconnect data line before installing the protection
module.
C. These protectors are intended for indoor use on
communication loop circuits which have been isolated from the Public Switch Telephone Network.
D. The communication loop circuits shall not be
exposed to accidental contact with the electric light or power conductors. The protectors shall be installed per the applicable requirements of the National Electric Code, ANSI/NFPA 70.
Fits in series with circuit wires
at the terminal screws
DANGER!
V
Only qualified personnel should install or service this system. Electrical safety pre­cautions must be followed when installing or servicing this equipment. To prevent risk of electrical shock, turn off and lock out all power sources to the unit before making electrical connections or servicing.
Seulement le personnel qualifié doit installer ou maintenir ce systéme. Des précautions de sécurité en électricité doivent être suivis lors de l’installation ou de la maintenance de cet equipement. Pour eviter tout risque de choc électrique, débranchez et verouiller toutes les sources d’alimentation de cet equipement avant de.
Emerson Network Power Contact information
Surge Protection 100 Emerson Parkway Binghamton, NY 13905 T: (607) 721-8840 T: (800) 288-6169 F: (607) 722-8713 E: SurgeTech@Emerson.com
IO-50120 5/14 Rev. 5 Printed in USA
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
Emerson Network Power, the Emerson Network Power logo and Edco are trademarks
www.EmersonNetworkPower.com/Surge
and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.
Loading...