Emerson Dixell XEV23D Installing And Operating Instructions

XEV23D
tEP
Model
LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)Sr(step/s)
0
Manual settings
Par
Par
Par
Par
Par
1
Alco EX4-EX5-EX6
5755010500
2
Alco EX7
10
1607525
500
3
Alco EX8 500
10
2608050
500
4
Danfoss ETS-25/50
7
2621010
300
5
Danfoss ETS-100
10
3531010
300
6
Danfoss ETS-250/400
11
3811010
300
7
Sporlan SEI 0.5-11
0
159165
200
8
Sporlan SER 1.5-20
0
159125
200
9
Sporlan SEI 30
0
319165
200
10
Sporlan SER(I) G,J,K
0
250125
200
11
Sporlan SEI 50
0
638165
200
12
Sporlan SEH(I) 100
0
638165
200
13
Sporlan SEH(I) 175
0
638165
200
Connection
numbering
ALCO EX
SPORLAN
SEI-SEH
DANFOSS
ETS
4
BLUE
WHITE
BLACK
2
BROWN
BLACK
WHITE
3
BLACK
RED
RED
1
WHITE
GREEN
GREEN
Connection
numbering
SPORLAN
SAGINOMIYA
4
ORANGE
ORANGE
2
RED
RED
3
YELLOW
YELLOW
1
BLACK
BLACK
5 – Common
GRAY
GRAY
DRIVER FOR STEPPER ELECTRONIC EXPANSION
VALVES
--- MANUAL FOR RELEASE 1.2 ---
1. GENERAL WARNING.........................................................................................................................1
2. GENERAL DESCRIPTION..................................................................................................................1
3. WIRING CONNECTIONS ...................................................................................................................1
4. VALVE CONNECTIONS AND CONFIGURATION.............................................................................1
5. ABSOLUTE MAXIMUM POWER........................................................................................................1
6. FRONT PANEL ...................................................................................................................................2
7. USER INTERFACE.............................................................................................................................2
8. PARAMETER LIST .............................................................................................................................2
9. DIGITAL INPUTS ................................................................................................................................3
10. FORCED OPENING............................................................................................................................3
11. ELECTRICAL CONNECTIONS...........................................................................................................3
12. RS485 SERIAL LINE...........................................................................................................................3
13. HOW TO: USE THE HOT-KEY...........................................................................................................3
14. DISPLAY MESSAGES........................................................................................................................4
15. TECHNICAL DATA..............................................................................................................................4
16. STANDARD VALUES .........................................................................................................................4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot
be used as a safety device.
Check the application limits before proceeding.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
The XEV23D module is able to drive a large variety of stepper electronic expansion valves. XEV23D permits to regulate the superheat (SH) of the fluid that runs into refrigerating unit in order to obtain optimized performance and a functioning of the evaporator independent by climatic or load conditions. XEV23D modules are equipped with two probe inputs, one for 4 to 20mA or 0 to 5V pressure transducer and another one for NTC-EU or NTC-US temperature probe. There are also two configurable digital inputs, the first one is free of voltage and the other ones is free of voltage to pass from the chilling to the heat-pump model. With the useful display it’s possible to see the value of superheat (SH), the degree of opening of the valve or the probe values, the local keyboard allows to program the instrument without any other devices. To complete instrument equipment, a RS485 serial link permits to connect XEV23D to dIXEL monitoring and supervising systems.
3. WIRING CONNECTIONS
The superheat regulation is performed only when the cooling digital input is enabled. The following scheme shows how the device takes the request of cooling:
4. VALVE CONNECTIONS AND CONFIGURATION
WARNINGS
1. To avoid possible problems, before connecting the valve configure the driver by making the right changes on the parameters. Select the kind of motor (tEU parameter) and check if the valve is present in tEP parameter table reported here below.
2. The max distance between an XM controller and a valve must not exceed 10 m. To avoid any problems, use only shielded cables with section greater than or equal to 0.325 mm² (AWG22).
If you can see your valve on the table, please select the valve through tEP parameter. In this way, you can be sure of a right configuration.
About the connection, please pay attention to the following table to have a quick reference on the connection mode for valves of different manufacturer. In any case, the unique and valid reference has
to be considered the datasheet made by manufacturer of the valve:
4 WIRES VALVES (BIPOLAR)
5-6 WIRES VALVES (UNIPOLAR)
Please see the following scheme to make the right wirings. With "First Level" are indicated the connections on the floor of the 4 DIN module and, of course, with "Second Level" the connections of the 1st floor that are only for the stepper motor of the valve and for HOT-KEY.
AFTER MAKING THE CONNECTION, PLEASE SWITCH OFF AND ON THE XEV CONTROLLER IN ORDER TO BE SURE OF THE RIGHT POSITIONING OF THE VALVE.
5. ABSOLUTE MAXIMUM POWER
XEV23D is able to drive a wide range of stepper valves, in the following table are indicated the maximum values of current that the actuator can supply to the stepper wiring. The dIXEL transformer to use is the TF20D.
1592025930 XEV23D GB r1.0 07.10.2011.doc XEV23D 1/4
NOTE: the electrical power absorption of the valve can be unrelated to refrigeration power that valve
VALVE
TYPE
BIPOLAR VALVES
(4 wires)
Maximum Current 0.9A
UNIPOLAR VALVES
(5-6 wires)
Maximum Current 0.33A
To display and to modify the set point. In programming mode it selects a parameter or it confirms a value.
By pressing and releasing this key, it’s possible to see the values of the probes. In programming mode it slides the codes of the parameters or it increases their values.
In programming mode it slides the codes of parameters or it decreases their values.
KEYS COMBINATIONS
+
To lock or to unlock the keyboard
+
To enter programming mode.
LED
MODE
Function
ON
Low pressure alarm
ON
Maximum Operating Pressure alarm
OFF
Valve is completely closed
BLINKING
Valve is moving
ON
Valve is completely opened
BLINKING
Serial communication present
OFF
Serial communication absent
ON
Superheat alarm
To enter in “Pr1” level menu:
1) Pressing SET+ DOWN buttons for about 3 seconds.
2) Instruments shows first parameter in Pr1 menu
To enter to “Pr2” parameters list:
1. Enter to “Pr1”.
2. Select “Pr2” parameter and press SET.
3. The “PAS” label will be shown, then “0--” with 0 blinking.
4. Insert “321” password through UP and DOWN buttons, then press SET to confirm.
To change the parameter’s value operate as follows:
1. Enter the Programming mode by pressing the Set and DOWN button for about 3s.
2. Select the required parameter.
3. Press the SET button to display the value.
4. Use UP or DOWN to change the value.
5. Press SET to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 30s without pressing any button.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
SEt
SH Set point in Chill mode (0,0 ÷ 24,0°C - 0 ÷ 43 °F)
St2
SH Set point in Heat Pump mode (0,0 ÷ 24,0°C - 0 ÷ 43 °F)
FtY
Kind of gas: (R22, 134, 404, 407, 410, 507, CO2) type of gas used by plant. This is a
fundamental parameter for correct functioning of all system.
PEo
Probe Error opening percentage: (0 to 100%) if a temporary probe error occurs, valve
opening percentage is PEo until PEd time is elapsed. If PEO is different from 0 it assures cooling also with probe error, because even if the device cannot calculate superheat the valve can work at PEo percentage.
PEd
Probe Error delay before stopping regulation: (0 to 239sec; 240=On=unlimited) if
probe error duration is higher than PEd, valve will close completely and “Pf” message will be showed. With PEd=on, valve opening is PEo until probe error finishes.
tEU
Type of Stepper motor: (UP; bP) it permits to select the kind of valve. UP = 5-6 wires
unipolar valves; bP = 4 wires bipolar valves. !!!!! WARNING !!!!! by changing this parameter the valve has to be reinitialized.
tEP
Predefined valve selection: (0 to 13) if tEP=0 the user has to modify all the parameters
of configuration in order to use the valve. If tEP is different from 0 the device performs a fast configuration of the following parameters: LSt, USt, Sr, CPP, CHd. To select the right number please read the following table:
tEP
Model
LSt
(steps*10)
uSt
(steps*10)
CPP
(mA*10)
CHd
(mA*10)Sr(step/s)
0
Manual settings
Par
Par
Par
Par
Par
1
Alco EX4-EX5-EX6
5755010500
2
Alco EX7
10
1607525
500
3
Alco EX8 500
10
2608050
500
4
Danfoss ETS-25/50
7
2621010
300
5
Danfoss ETS-100
10
3531010
300
6
Danfoss ETS-250/400
11
3811010
300
7
Sporlan SEI 0.5-11
0
159165
200
8
Sporlan SER 1.5-20
0
159125
200
9
Sporlan SEI 30
0
319165
200
10
Sporlan SER(I) G,J,K
0
250125
200
11
Sporlan SEI 50
0
638165
200
12
Sporlan SEH(I) 100
0
638165
200
13
Sporlan SEH(I) 175
0
638165
200
If tEP is different from 0, previous configuration of LSt, uSt, Sr, CPP and CHd will be overwritten.
HFS
Kind of motor movement: (HAF; FUL)
HAF = half step. Use this setting for the unipolar valve. FUL = half step. Use this setting for the bipolar valve.
LSt
Minimum number of steps: (0 to USt (*10)) it permits to select the minimum number of
steps. At this number of steps the valve should be closed. So it’s necessary the reading of manufacturer datasheet to set correctly this parameter. It’s the minimum number of steps to stay in advised range of functioning. !!!!! WARNING !!!!! after changing this
parameter the valve will have to be reinitialized. The device performs this procedure automatically and restarts its normal functioning when the programming mode ends.
USt
Maximum number of steps: (LSt to 800 (*10)) it permits to select the maximum number
of steps. At this number of steps the valve should be completely opened. Read the datasheet provided by manufacturer of the valve to set correctly this parameter. It’s the maximum number of steps to stay in advised range of functioning. !!!!! WARNING !!!!!
after changing this parameter the valve will have to be reinitialized. The device performs this procedure automatically and restarts its normal functioning when the programming mode ends.
ESt
Extra step in closing phase: (0 to 255 (*10)) it sets the number of extra steps the
controller performs, when the valve is closed at start up, to force the closure of the valve.
Sr
Step rate: (10 to 600 step/sec) it is the maximum speed to change step without losing
precision (=losing steps). It’s advised to stay under the maximum speed.
CPP
Current per phase (only bipolar valves): (0 to 100 (*10mA)) it is the maximum current per phase used to drive valve. It’s used only with bipolar valves.
CHd
Holding current per phase (only bipolar valves): (0 to 100 (*10mA)) it is the current per phase when the valve is stopped for more than 4 minutes. It’s used only with bipolar valves.
oPE
Start opening Percentage: (0 to 100%) opening valve percentage when start function is active and during post defrost phase. This phase duration is SFd time.
SFd
Start Function duration: (0.0 to 42min 00s, res. 10s) it sets start function duration and post-defrost duration. During this phase the alarms are neglected.
MnF
Maximum opening percentage at normal Functioning: (0 to 100%) during regulation
it sets the maximum valve opening percentage.
has. Before using the actuator, please read the technical manual of the valve supplied by the manufacturer and check the maximum current used to drive the valve in order to verify that they are lower than those indicated below.
6. FRONT PANEL
6.1 XEV23D LEDS
On display there are some luminous dots. Their meaning is described in the following table:
7.6 HOW TO: CHANGE A PARAMETERS VALUE
8. PARAMETER LIST
NOTE: All pressure parameters are relatives or absolutes depending on the PrM parameter
REGULATION
7. USER INTERFACE
7.1 HOW TO: SEE THE READ-ONLY VALUES
1) Press and release UP button.
2) First read-only label is showed;
3) Brows parameter labels with UP or DOWN buttons.
4) Press SET to see read-only value. To change parameter, press SET.
5) To leave the fast access menu, press and release SET+UP or wait for time-out to expire (about 3 minutes).
7.2 HOW TO: SEE THE SET POINT
1) Press the SET buttons until the set point will be showed.
2) To come back to see temperature, wait about 5s or press newly SET key.
7.3 HOW TO: MODIFY THE SET POINT
To change the set point value operate as follows:
1) Press the SET button until the set point will be showed.
2) Use UP or DOWN buttons to change its value.
3) Press SET button to store the new value.
7.4 HOW TO: ENTERING “PR1” PARAMETER MENU
7.5 HOW TO: ENTERING “PR2” PARAMETER MENU
1592025930 XEV23D GB r1.0 07.10.2011.doc XEV23D 2/4
Loading...
+ 2 hidden pages