Emerson CF788ORB00, CF788AP00, CF788CK00, CF788GBZ00 Owner's Manual

Page 1
Part No. F40BP74270002 Form No. BP7427-2
ETL Model No.: CF788
READ AND SAVE THESE INSTRUCTIONS
Damp Location
Ceiling Fan Owner's Manual
CF788AP00 - Antique Pewter CF788CK00 - Chalk CF788GBZ00 - Gilded Bronze CF788ORB00 - Oil Rubbed Bronze
Model Numbers
CARRERA GRANDE ECO
54”, 60” or 72” Fan Blades
Not Included
Net Weight: 17.2 Lbs.
Page 2
WARNING: To avoid fire, shock, and serious personal injury, follow these instructions.
Safety Instructions
1. Read your owner’s manual carefully and keep it for future reference.
2. Before servicing or cleaning unit, switch power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a warning device, such as a tag, to the service panel.
3. Be careful of the fan and blades when cleaning, painting, or working near the fan. Always turn off the power to the ceiling fan before servicing.
4. Do not put anything into the fan blades while they are turning.
5. Do not operate reversing switch until fan blades have come to a complete stop.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off at the fuse box before wiring, and do not operate fan without blades.
2. All wiring must be in accordance with the National Electrical Codes “ANSI/NFPA 70-2008” and Local Electrical Codes. Use the National Electrical Code if Local Codes do not exist. The ceiling fan must be grounded as a precaution against possible electrical shock. Electrical installation should be made or approved by a licensed electrician.
3. The outlet box and joist must be securely mounted and capable of reliably supporting at least 50 pounds. Use only U.L. outlet boxes listed as “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use the mounting screws provided with the outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
4. The downrod furnished with the fan provides the minimum recommended floor to fan blade clearance for an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least 7 feet from the floor to prevent accidental contact with the fan blades.
6. Follow the recommended instructions for the proper method of wiring your ceiling fan. If you do not know enough about electrical wiring, have your fan installed by a licensed electrician.
NOTE: This fan is suitable for use with solid-state speed controls.
WARNING: To reduce the risk of fire or electric shock, this fan should only be used with fan speed
control, Model No. FR-7861LMB manufactured by Rhine Electric Co., Ltd.
WARNING: To avoid fire, shock or injury, do not use an Emerson or any other brand of control not specifically approved for this fan.
WARNING: This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING: To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING: To reduce the risk of electrical shock, this fan must be installed with an isolating wall control/switch.
WARNING
2
!
DATE CODE:
The date code of this fan may be found on the box, stamped in ink on a white label.
You should record this data above and keep it in a safe place for future use.
ETL Model No.: CF788
Page 3
3
ETL Model No.: CF788
EMERSON QUICK START GUIDE
The Quick Start Guide covers the installation instructions common for ceiling fan operations. If additional assistance with wiring, alternate hanging systems, or lighting options, proceed to the complete instructions of this Owner’s Manual.
The Quick Start Guide sections include page numbers to correspond with the appropriate sections of the Owner’s Manual for detailed instructions.
* See Unpacking Instructions for a complete list of
parts for installation.
How to Put Your Ceiling Fan Together (page 6)
1. Unscrew and discard each
shipping retainer screw and retainer.
1. Disconnect electrical power to
the branch circuit at the circuit breaker or fuse box before attempting to install the ceiling fan hanger bracket on the outlet box.
2. The fan must be hung with at
least 7’ of clearance from floor to blades.
3. Attach the hanger bracket to
the outlet box.
4. Seat the hanger ball/downrod
assembly on the hanger bracket.
Hanging Your Ceiling Fan (page 10)
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
!
WARNING
2. Attach the blade flanges to
the fan blades.
3. Attach the blade/flange
assembly to the motor hub.
Installation of Downrod (page 8)
1. Remove the hanger ball from
the downrod.
2. Install the downrod to the
motor coupling using the clevis pin and hairpin clip.
3. Tighten the setscrews.
Installation of Ceiling Fan (pages 8 and 9)
1. Install the coupler cover and
ceiling cover onto the downrod.
2. Reinstall the hanger ball onto
the downrod, place the pin into the hanger ball and tighten the setscrew.
Installation of Switch Housing (page 7)
1. Tuck blue and white wires
carefeully under the switch housing cover and attach witht he three switch housing mounting screws.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse or circuit breaker box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
!
WARNING
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse or circuit breaker box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
!
WARNING
O
N
D
r
e
b
b
u
R
e
la
v
l
p
a
t
o
s
S
n
o
I
s
e
o
r
m
L
o
o
L
f
r
r
e
a
r
i
a
e
T
t
R
i
B
Y
u
!
e
d
Q
E
r
J
!
a
T
a
l
c
A
a
s
T
i
b
O
m
N
E
r
o
CEILING
AT LEAST
7'
FLOOR
Page 4
4
1. Connect the green grounding lead from the hanger ball and the
green grounding lead from the hanger bracket to the grounding conductor of supply (this may be a bare wire or wire with green colored insulation). Securely connect wires with wire connectors supplied.
NOTE: If you are using an Emerson Light Fixture with your fan, see Light Fixture Owner’s Manual for wiring.
2. Securely connect the fan motor white wire to the supply white
(neutral) wire using wire connector supplied. Securely connect the fan motor black wire to the supply black (hot) wire using wire connector supplied. After connections have been made, turn leads upward and carefully push leads into the outlet box, with the white and green leads on one side of the outlet box and the black leads on the other side of the outlet box.
Wiring Ceiling Fan (page 11)
1. Remove faceplate and screws from existing wall control. Pull
control out from the wall box. Determine the “hot” wire and the “load” wire and disconnect these wires from control. Do not attempt to disconnect any wires not already connected to existing control.
2. Before installing wall control, place wall control in “OFF” mode
by pushing “ON/OFF” switch to the “OFF” position.
3. Connect one black wire of wall control to the “hot” wire.
Securely connect wires with wire connectors supplied.
4. Connect one black wire of wall switch to the “load” (black) wire
in wall box. Securely connect wires with wire connector supplied.
5. Screw wall control into wall box using the supplied screws.
Leave wall control in “OFF” mode until fan installation is completed.
6. The wall control is supplied with a white, ivory, and almond
color switch covers. Choose the finish that best suits your needs and snap the cover onto the wall control.
7. Install decorator wall plate using the two screws provided with
wall plate. Leave wall control in “OFF” mode until fan installation is completed.
Installation of Wall Control (pages 12, 13 & 14)
1. Separate the grounded white
neutral and green wires on one side of the outlet box from the ungrounded black and blue wires on the other side of the outlet box
2. Insert the grounded green
and white wires into one side of the outlet box, and the ungrounded black and blue wires into the other side of the outlet box.
3. Screw the two threaded studs
into the tapped holes in the hanger bracket.
Installation of Ceiling Cover (page 11)
Your wall control has code switches which must be set in one of 32 possible code combinations. The five levers (numbered 1, 2, 3, 4, and 5) on the switches are factory-set in the ON (up) position. Change the switch settings as follows:
1. Slide the five switch levers in the wall control to your choice of
ON (up) or down positions. Use a ball-point pen or small screwdriver and slide the levers firmly up or down.
2. When power is restored after installation of the wall control,
push and hold the fan OFF button ( ) for 3 to 5 seconds to set the code in the receiver.
3. The sixth switch marked ON and I is for dimming control of
lights: Set switch to ON to allow for dimming of the lights. Set switch to I for no dimming of the lights such as for fluorescent bulbs.
Programming Receiver (page 12)
EMERSON QUICK START GUIDE
4. Install the ceiling cover onto
the hanger bracket. using the studs, lock washers and knurled nuts supplied.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse or circuit breaker box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
!
WARNING
ETL Model No.: CF788
* For additional installation review full instructions on pages
13 and 14.
GROUND WIRE
LISTED WIRE CONNECTOR (3)
GREEN WIRE (GROUND) FROM HANGER BRACKET
GREEN WIRE (GROUND) FROM HANGER BALL
BLACK FAN WIRE
WHITE SUPPLY (NEUTRAL)
WHITE FAN WIRE
BLACK SUPPLY (HOT)
NOTE: CEILING COVER OMITTED FOR CLARITY.
ON
1
23
4
5I
BLK
HOT
T
O
1
2
0
E
V
A
C
C
S
R
O
U
T
O
L
O
D
A
D
N
BLACK
U
O
R
G
Page 5
Unpacking Instructions
THESE FAN MODELS ARE SUITABLE FOR DAMP LOCATIONS SUCH AS COVERED PORCHES,
COVERED PATIOS, AND COVERED DECKS... ANYWHERE THERE IS A ROOF OVERHEAD.
1. Check to see that you have received the following
parts:
NOTE: If you are uncertain of part description, refer to exploded view illustration.
a. Fan motor assembly b. One switch housing c. One ceiling cover d. Five blade flanges e. One hanger ball/4.5” downrod assembly f. One hanger bracket g. One motor coupling cover h. One transmitter control with
switch covers i. One receiver control j. One loose parts bag containing:
1. Twenty-one #10-24 x 12mm washer head blade screws
2. Twenty-one 16mm flat washers OD
3. One #8-32 X 12mm flat head screw
4. One 1/4-20 x 14mm pan head screw
5. One 6mm lockwasher
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
Tools Needed for Assembly
One Phillips head screwdriver One stepladder One wire stripper
MATERIALS
Wiring outlet box and box connectors must be of type required by the local code. The minimum wire would be a 3-conductor (2-wire with ground) of the following size:
5
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
Before assembly your ceiling fan, refer to section on proper method of wiring your fan (page 10). If you feel you do not have enough wiring knowledge or experience, have your fan installed by a licensed electrician.
Do not install or use fan if any part is damaged or missing. Call Toll-Free:
1-800-654-3545
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
WARNING
!
WARNING
!
WARNING
!
6. Three wire connectors
7. Two #8-32 x 1-1/4” threaded studs
8. Two #8-32 knurled knobs
9. Two #8 external tooth lockwashers
10. One clevis pin
11. One hairpin clip
12. One balance kit
NOTE: Place the parts from the loose parts bags in a small container to keep them from being lost. If any parts are missing, contact your local retailer or catalog outlet for replacement before proceeding.
2. Remove the fan assembly from the protective
plastic bag. Place the fan assembly into the upper foam pad with the bottom of the motor facing up. The upper foam pad serves as a holder for the fan during the first stages of assembly.
ETL Model No.: CF788
J. LOOSE PARTS BAG
D. BLADE FLANGES
C. CEILING COVER
G. MOTOR COUPLING COVER
I. RECEIVER CONTROL
A. FAN MOTOR ASSEMBLY
E. HANGER BALL/ DOWNROD ASSEMBLY
B. SWITCH HOUSING
H. WALL CONTROL
F. HANGER BRACKET
Page 6
Electrical Requirements
How to Put Your Ceiling Fan Together
6
Figure 2
Figure 1
If your fan is to replace an existing ceiling light fixture, turn electricity off at the main fuse box at this time and remove the existing light fixture.
Your new ceiling fan will require a grounded electrical supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of withstanding a load of at least 50 pounds.
To avoid fire or shock, follow all wiring instructions carefully. Any electrical work not described in these instructions should be done or approved by a licensed electrician.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
WARNING
!
WARNING
!
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
WARNING
!
ETL Model No.: CF788
2. Mount blade flanges (supplied with fan) to fan
blades (sold separately) using four #10-24 x 12mm washer head blade screws and four 16mm flat washers (supplied with fan) (Figure 2).
NOTE: Some accessory blades available are supplied with shorter screws. These shorter screws MUST be used to assemble the blades to flanges.
1. Rotate the motor hub to align the hub notch area
over each of the five screws which is holding the shipping retainer to the motor assembly. One by one unscrew each screw and discard screw and shipping retainer (Figure 1).
MOTOR HUB
REMOVE SHIPPING RETAINER BY REMOVING 5 SCREWS
r
e
b
b
u
l
a
R
t
s
e
n
v
I
S
o
e
s
r
m
o
o
e
f
L
R
e
r
a
!
r
a
B
i
t
E
i
T
d
u
T
r
Y
a
Q
O
e
c
!
N
J
s
A
i
a
T
D
l
a
O
b
N
m
E
d
n
A
s
t
n
u
o
M
g
n
i
k
a
r
a
c
P
a
a
.
P
o
i
t
a
l
o
p
o
o
L
r
n
m
o
i
c
o
a
.
l
a
G
t
n
s
e
n
I
D
a
L
s
e
e
t
D
r
s
e
t
n
A
s
#10-24 x 12mm WASHER HEAD BLADE SCREW (4 per blade/flange)
BLADE FLANGE
FLAT WASHER 16 mm OD (4 per blade/flange)
FAN BLADE
Page 7
7
Figure 4
4. The blade flanges have an interlocking feature that
must be fully engaged before tightening the screw. Make sure all the flanges are properly engaged and then tighten the flange screws. If one of the flanges does not seat properly on the motor hub, loosen the adjacent flange screws, re-engage and reseat the flanges, then tighten the screws again.
Figure 3
5. Remove and retain the three switch housing
mounting screws (Figure 4) from the switch housing plate. Tuck the blue and white fan wire carefully under the switch housing cover as shown in Figure 4.
6. Position the switch housing assembly on the
switch housing plate and align the holes in the switch housing assembly with the holes in the plate. Secure the switch housing assembly by installing the three #8-32 x 12mm flat head screws (supplied) (Figure 5).
Figure 5
To avoid possible fire or shock, do not pinch wires between the switch cup assembly and the switch cup plate.
WARNING
!
ETL Model No.: CF788
To reduce the risk of personal injury, do not bend the blade flange when installing the blade flanges, balancing the blades or cleaning the fan. Do not insert foreign objects in between rotating fan blades.
WARNING
!
3. Loosely attach one blade/flange assembly to the
motor hub by securing the two 1/4-20 x 14mm captive pan head screws. Make sure the screws are NOT tightened (Figure 3). Repeat this procedure for other four blade assemblies.
How to Put Your Ceiling Fan Together (continued)
NOTE: Take care not to scratch fan housing when installing blades.
MOTOR HUB
MOTOR HUB NOTCHED AREA
1/4-20 x 14mm CAPTIVE PAN HEAD SCREW (2 per blade/flange assembly)
BLADE/FLANGE ASSEMBLY
SWITCH HOUSING ASSEMBLY
#8-32 x 12mm FLAT HEAD SCREW (3)
#8-32 x 12mm FLAT HEAD SCREW (3)
SWITCH HOUSING ASSEMBLY
Page 8
8
8. Remove the hanger ball by loosening the setscrew
in the hanger ball until the ball falls freely down the downrod (Figure 6). Remove the pin from the downrod, then remove the hanger ball. Retain the pin and hanger ball for reinstallation in Step 9.
9. Separate, untwist and unkink the two 80” motor
leads. Route the motor lead wires through the downrod. Remove the upper setscrew from the motor coupling. Align the clevis pin holes in the downrod with the holes in the motor coupling. Install the clevis pin and secure with the hairpin clip (Figure 7). The clevis pin must go through the holes in the motor coupling and the holes in the downrod. Be sure to push the straight leg of the hairpin clip through the hole near the end of the clevis pin until the curved portion of the hairpin clip snaps around the clevis pin. The hairpin clip must be properly installed to prevent the clevis pin from working loose. Pull on the downrod to make sure the clevis pin is properly installed. Reinstall the upper setscrew in the motor coupling. Check that the lower setscrew is tightened securely (Figure 7).
HANGER
Figure 6
7. Carefully turn partially assembled fan upside down
and place in styrofoam form carton, in preparation for final installation.
How to Put Your Ceiling Fan Together (continued)
It is critical that the clevis pin in the motor coupling is properly installed and the setscrews securely tightened. Failure to verify that the pin and setscrews are properly installed could result in the fan falling.
WARNING
!
NOTE: The setscrews must be properly installed as described above, or fan wobble could result.
Figure 7
10. Remove and retain the three #8-32 x 12mm
screws from the upper motor housing.
11. Make sure the grommet is properly installed in the
coupling cover, then slide the coupling cover on the downrod until it rests on the motor housing. Place the ceiling cover over the downrod. Be sure that the ceiling cover and the coupling cover are both oriented correctly (Figure 8). Secure the coupling cover by reinstalling the three previous removed #8-32 x 12mm screws.
Figure 8
ETL Model No.: CF788
BALL
DOWNROD
SETSCREW
CLEVIS PIN
MOTOR COUPLING
HAIRPIN CLIP
CLEVIS PIN
DOWNROD
UPPER SETSCREW
PIN
CLEVIS PIN
SETSCREW
HAIRPIN CLIP
RUBBER GROMMET
MOTOR COUPLING COVER
DOWNROD
CEILING COVER
COUPLING COVER SCREW (3)
Page 9
How to Put Your Ceiling Fan Together (continued)
Figure 9
It is critical that the pin in the hanger ball is properly installed and the setscrew securely tightened. Failure to verify that the pin and setscrew are properly installed could result in the fan falling.
WARNING
!
13. The fan comes with black and white leads that
are 80” long. Before installing fan, measure up approximately 6 to 9-inches above top of hanger ball/downrod assembly. Cut off excess leads and strip back insulation 1/2-inch from end of leads.
14. You have now completed the assembly of your
new ceiling fan. You can now proceed with hanging and wiring your fan.
9
12. Reinstall the hanger ball (Figure 9) on the
downrod as follows. Route the two 80” motor leads through the hanger ball. Position the pin through the two holes in the downrod and align the hanger ball so the pin is captured in the groove in the top of the hanger ball. Pull the hanger ball up tight against the pin and securely tighten the setscrew in the hanger ball. A loose setscrew could create fan wobble.
ETL Model No.: CF788
PIN
HANGER BALL
SETSCREW
CEILING COVER
Page 10
10
How to Hang Your Ceiling Fan
The fan must be hung with at least 7' of clearance from floor to blades (Figure 10).
Figure 10
WARNING
!
The outlet box and joist must be securely mounted and capable of supporting at least 50 lbs. Use only a U.L. outlet box listed as “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”.
WARNING
!
To reduce the risk of fire, electric shock, or personal injury, mount fan to outlet box marked “Acceptable for Fan Support of 22.7 kg. (50 lbs.) or less”, and use screws supplied with outlet box. Most outlet boxes commonly used for support of light fixtures are not acceptable for fan support and may need to be replaced. Consult a qualified electrician if in doubt.
WARNING
!
ETL Model No.: CF788
NOTE: CEILING COVER OMITTED FOR CLARITY.
Figure 12
To avoid possible fire or shock, do not pinch wires between the hanger ball/downrod assembly and hanger bracket.
WARNING
!
Hanger bracket must seat firmly against outlet box. If the outlet box is recessed, remove wall board until bracket contacts box. If bracket and/or outlet box are not securely attached, the fan could wobble or fall.
Failure to seat tab in groove could cause damage to electrical wires and possible shock or fire hazard.
2. Carefully lift the fan and seat the hanger
ball/downrod assembly on the hanger bracket that was just attached to the outlet box (Figure 12). Be sure the groove in the ball is lined up with tab on the hanger bracket (Figure 11).
WARNING
!
WARNING
!
1.Securely attach the hanger bracket to the outlet box
using the two screws supplied with the outlet box. (Figure 11.)
TWO SCREWS SUPPLIED WITH OUTLET BOX
HANGER BRACKET
TAB
OUTLET BOX
Figure 2
Figure 11
AT LEAST
7'
CEILING
FLOOR
NOTE: CEILING COVER, SUPPLY WIRES AND FAN WIRES OMITTED FOR CLARITY.
OUTLET BOX
HANGER BRACKET
HANGER BALL/ DOWNROD ASSEMBLY
Page 11
11
ETL Model No.: CF788
How to Wire Your Ceiling Fan
If you feel that you do not have enough electrical wiring knowledge or experience, have your fan installed by a licensed electrician.
1. Connect the green grounding lead from the hanger
ball and the green grounding lead from the hanger bracket to the grounding conductor of supply (this may be a bare wire or wire with green colored insulation). Securely connect wires with wire connectors supplied.
NOTE: If you are using an Emerson Light Fixture with your fan, see Light Fixture Owner’s Manual for wiring.
2. Securely connect the fan motor white wire to the
supply white (neutral) wire using wire connector supplied (Figure 13). Securely connect the fan motor black wire to the supply black (hot) wire using wire connector supplied (Figure 13). After connections have been made, turn leads upward and carefully push leads into the outlet box, with the white and green leads on one side of the outlet box and the black leads on the other side of the outlet box.
To avoid possible electrical shock, be sure electricity is turned off at the main fuse box before wiring.
NOTE: If you are not sure if the outlet box is grounded, contact a licensed electrician for advice, as it must be grounded for safe operation.
Check to see that all connections are tight, including ground, and that no bare wire is visible at the wire connectors, except for the ground wire. Do not operate fan until blades are in place. Noise and fan damage could result.
Figure 13
WARNING
!
WARNING
!
3. Screw the two threaded studs (supplied) into the
tapped holes in the hanger bracket.
4. Lift the ceiling cover up to the threaded studs and
turn until studs protrude through the holes in the ceiling cover (Figure 14).
5. Secure the ceiling cover in place by sliding
lockwashers over the threaded studs and installing the two knurled knobs (supplied). (Figure 14). Tighten the knurled knobs securely until the ceiling cover fits snugly against the ceiling and the hole in the ceiling cover is clear of the downrod. Your fan is now wired to be turned on and off from the fan switch.
To avoid possible fire or shock, make sure that the electrical wires are completely inside the outlet box and not pinched between the ceiling cover and the ceiling.
Figure 14
WARNING
!
GROUND WIRE
LISTED WIRE CONNECTOR (3)
BLACK FAN WIRE
WHITE SUPPLY (NEUTRAL)
GREEN WIRE (GROUND) FROM HANGER BRACKET
GREEN WIRE (GROUND) FROM HANGER BALL
WHITE FAN WIRE
BLACK SUPPLY (HOT)
NOTE: CEILING COVER OMITTED FOR CLARITY.
CEILING COVER
THREADED STUDS (2)
KNURLED KNOBS (2)
LOCKWASHERS (2)
Page 12
Wall Control Installation (continued)
Wall Control Procedures
12
ETL Model No.: CF788
SINGLE-POLE INSTALLATION
CAUTION: To reduce the risk of electrical shock, disconnect the electrical supply circuit before installing the fan, light kit or receiver.
General
Your Emerson Ceiling Fan/Light Control consists of wall mounted transmitter and a receiver which is mounted under the fan ceiling cover. The remote control is designed to separately control your ceiling fan speed and light intensity.
Code switches in the transmitter and receiver may be set in 32 different positions. If your fan and light go on and off without using your control, you may be getting interference from other remote units such as garage door openers, car alarms or security systems. To remedy this situations, simply change the combination code in your transmitter and receiver.
Your wall control has code switches which must be set in one of 32 possible code combinations (Figure
15). The five levers (numbered 1, 2, 3, 4, and 5) on the switches are factory-set in the ON (up) position. Change the switch settings as follows:
1. Slide the five switch levers in the wall control to
your choice of ON (up) or down positions. Use a ball-point pen or small screwdriver and slide the levers firmly up or down.
2. When power is restored after installation of the wall
control, push and hold the fan OFF button ( ) for 3 to 5 seconds to set the code in the receiver.
3. The sixth switch marked ON and I is for dimming
control of lights: Set switch to ON to allow for dimming of the lights. Set switch to I for no dimming of the lights such as for fluorescent bulbs.
Figure 15
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse or circuit breaker box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
WARNING
!
Figure 16
Preset Memory Feature
Your Emerson receiver is equipped with a preset memory feature. If the AC supply to the receiver is powered through a wall switch, when the switch is turned OFF, the control will remember the light intensity and fan speed. When the switch is turned back ON the light and fan will resume operation as they were prior to the switch being turned OFF.
Setting Operating Frequency of Wall Control
WALL CONTROL CODE SWITCHES
ON
1
23
4
5I
WALL CONTROL
CODE SWITCHES
HOT BLK
NEUTRAL
RECEIVER LOCATED ON TOP OF THE CEILING FAN
HI
MED
LOW
FAN OFF
EMERSON
LIGHT
®
ONOFF
FAN/LIGHT WALL CONTROL
BLACK
BLACK
LOAD
GROUND
Page 13
Wall Control Installation (continued)
NOTE: Make all wiring connections using wire connectors (supplied). Make sure that all connections are tight, including ground, and that no bare wire is visible at the wire connectors, except for the ground wire.
1. Disconnect electrical power to the branch circuit at
the circuit breaker or fuse box before attempting to install the ceiling fan wall control into the outlet box.
2. Remove faceplate and screws from existing wall
control. Pull control out from the wall box. Determine the “hot” wire and the “load” wire and disconnect these wires from control. Do not attempt to disconnect any wires not already connected to existing control.
3. Before installing wall control, place wall control in
“OFF” mode by pushing “ON/OFF” switch to the “OFF” position.
4. Connect one black wire of wall control to the “hot”
wire. Securely connect wires with wire connectors supplied (Figure 17).
5. Connect one black wire of wall switch to the “load”
(black) wire in wall box. Securely connect wires with wire connector supplied.
6. Screw wall control into wall box using the supplied
screws. Leave wall control in “OFF” mode until fan installation is completed.
13
ETL Model No.: CF788
Do not connect any neutral (white) wire to this control. Incorrect wiring will damage this control.
WARNING
!
Check to see that all connections are tight and that no bare wires are visible at the wire connectors.
WARNING
!
7. The wall control is supplied with a white, ivory, and
almond color switch covers. Choose the finish that best suits your needs and snap the cover onto the wall control (Figure 17).
8. Install decorator wall plate using the two screws
provided with wall plate. Leave wall control in “OFF” mode until fan installation is completed (Figure 17).
Figure 17
3-WAY INSTALLATION
(One fan controlled by two different wall controls) (See Figures 18 and 19.)
1. Disconnect electrical power to the branch circuit at
the circuit breaker or fuse box before attempting to install the ceiling fan wall control into the outlet box.
Turning off wall switch is not sufficient. To avoid possible electrical shock, be sure electricity is turned off at the main fuse or circuit breaker box before wiring. All wiring must be in accordance with National and Local codes and the ceiling fan must be properly grounded as a precaution against possible electrical shock.
WARNING
!
Do not connect any neutral (white) wire to this control. Incorrect wiring will damage this control.
WARNING
!
2. At all wall box locations remove faceplates and
screws from existing controls. Pull controls out from wall boxes and determine which wall box contains the “hot” lead and which wall box contains the “load” wire. Also, identify traveler wires which are common to both wall boxes. Disconnect wires from existing controls only. Do not attempt to disconnect any wires not already connected to existing controls.
3. Before installing wall control, place wall control in
“OFF” mode by pushing “ON/OFF” switch to the “OFF” position.
4. Install a wall control in the wall box containing the
“hot” wire first. Connect the black wire of the wall control to the “hot” wire. Securely connect wires with wire connectors supplied.
5. Connect one black wire of the wall control to both
remaining traveler wires in the wall box and secure with wire connector supplied.
NOTE: Retrofit 3-way installations are likely to include two traveler wires between the two wall boxes. In new construction, only one traveler wire Is required (See Figure 19).
SCREWS (2)
BLK
HOT
T
O
DECORATIVE WALL PLATE
SWITCH COVER
1
T
O
BLACK
FAN/LIGHT WALL CONTROL
2
0
V
A
C
L
D
A
O
G
C
R
U
S
O
D
N
U
O
R
WALL BOX
E
Page 14
Wall Control Installation (continued)
6. Screw wall control into wall box using the supplied
screws. Leave wall control in “OFF” mode until fan installation is completed.
7. The wall control is supplied with a white, ivory, and
almond color switch covers. Choose the finish that best suits your needs and snap the cover onto the wall control (Figure 18).
8. Next, install the other wall control into the wall box
containing the load wire. Connect the black wire of the wall control to the traveler wire(s) already connected to the black wire (in the other wall box). Secure with wire connectors supplied.
9. Connect one black wire of the wall control to the
“load” (black) wire and secure with wire connector supplied.
14
ETL Model No.: CF788
Check to see that all connections are tight and that no bare wires are visible at the wire connectors.
WARNING
!
3-WAY WIRING DIAGRAM: NEW CONSTRUCTION
STANDARD WIRING FOR EXISTING 3-WAY CONTROLS
Figure 18
Figure 19
3-WAY WIRING DIAGRAM: RETROFIT
IMPORTANT: The following steps must be completed immediately following the frequency programming of the ceiling fan.
1. Press the ( ) speed button until all 6 LED
indicators are lit. Let the fan operate on high speed for 2 minutes without interruption.
2. After 2 minutes, press the reverse ( ) button and
allow the fan to operate uninterupted for 2 minutes at high speed.
3. High speed conditioning is now complete.
High Speed Conditioning of Fan Control
HOT
BLACK
NEUTRAL RECEIVER LOCATED
ON TOP OF THE CEILING FAN
HI
LIGHT
MED
LOW
FAN OFF
®
EMERSON
ONOFF
SW605
FAN/LIGHT
WALL
CONTROL
TRAVELER
WIRE
MED
LOW
FAN OFF
EMERSON
BLK
HI
LIGHT
®
ONOFF
BLK
LOAD BLACK
GROUND
EXISTING
HOT
BLK
WALL CONTROL
TRAVELER WIRES
BLK
HOT BLK
FAN/LIGHT WALL CONTROL
FAN OFF
EMERSON
HI
LIGHT
MED
LOW
®
ONOFF
TRAVELER WIRES
BLK
HI
MED
LOW
FAN OFF
EMERSON
LIGHT
®
ONOFF
BLACK
LOAD
BLK
BLACK
LOAD
Page 15
15
ETL Model No.: CF788
Using Your Ceiling Fan
Maintenance
Accessories
Fan installation must be completed, including the installation of the fan blades, before testing the remote control.
WARNING
!
Your wall control has full control of your fan and light.
1.To set the desired fan speed, press the ( ) button
to decrease the speed and the ( ) to increase the speed. The LED display will light up to indicate the new speed selected.
2.To turn the light on and off, press and release the
LIGHT ( ) button. To set the light intensity, press and hold the LIGHT ( ) button. The light will turn on at the light intensity previously selected.
3.Your wall control comes complete with your choice
of three wall cover plates; ivory, white and light almond.
4. If airflow is desired in the opposite direction, press
the ( ) button on the wall control. The fan must be operating at any speed for the reverse button to function. The blades will turn in the opposite direction and reverse the airflow.
Figure 20
IMPORTANT CARE INSTRUCTIONS
for your Ceiling Fan
Periodic cleaning of your new ceiling fan is the only maintenance that is needed.
When cleaning, use only a soft brush or lint free cloth to avoid scratching the finish.
Abrasive cleaning agents are not required and should be avoided to prevent damage to finish.
Do not use water when cleaning your ceiling fan. It could damage the motor or the blades and create the possibility of an electrical shock.
WARNING
!
This product is designed to use only those parts supplied with this product and/or any accessories designated specifically for use with this product by Emerson Electric Co. Substitution of parts or accessories not designated for use with this product by Emerson Electric Co. could result in personal injury or property damage.
The use of any other control not specifically approved for this fan could result in fire, shock and personal injury.
1. Ceiling Fan Light Kits (see store or catalog).
2. Ceiling Fan/Light Controls (see store or catalog).
3. Downrod Extension Kits (see store or catalog).
4. Ceiling Fan Blades (see store or catalog).
WARNING
!
WARNING
!
POWER INDICATOR LIGHT
FAN DIRECTION
LIGHT BUTTON
FAN BUTTON
HIGH TO LOW SPEED BUTTONS
ON/OFF SWITCH O = OFF / — = ON
Page 16
Energy Efficient Use of Ceiling Fans
Control Trouble Shooting
INSTRUCTION TO THE USER (if device contains a digital device)
16
This equipment has been tested and found to comply with the limits for a class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help. This equipment has been certified to comply with the limits for a class B computing device, pursuant to FCC
Rules. In order to maintain compliance with FCC regulations, shielded cables must be used with this equipment. Operation with non-approved equipment or unshielded cables is likely to result in interference to radio and TV reception. The user is cautioned that changes and modifications made to the equipment without the approval of manufacturer could void the user’s authority to operate this equipment.
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Fan/Light Fails to Operate
• Check that the speed switch on the fan is set to ( ) or ( ) speed.
• Check that the light switch is on.
• Check that the battery is good (blue indicator light should light when any button is pressed).
• Check that the receiver is wired properly.
• Check that code switches in the remote control and receiver are set in the same position.
Short Range
• If the remote control operates the fan when close to it, but does not operate it at a distance of 40 feet, try placing the antenna wire outside of the ceiling cover.
ETL Model No.: CF788
Ceiling fan performance and energy savings rely heavily on the proper installation and use of the ceiling fan. Here are a few tips to ensure quality and product performance.
Choosing the Appropriate Mounting Location.
Ceiling fans should be installed, or mounted, in the middle of the room and at least 7 feet above the floor and 18 inches from the walls. If ceiling height allows, install the fan 8 - 9 feet above the floor for optimal airflow. Consult your Emerson Retailer for optional mounting accessories.
Using the Ceiling Fan Year Round. In the summer, use the ceiling fan in the counter-clockwise direction. The airflow produced by the ceiling fan creates a wind-chill effect, making you "feel" cooler. Select a fan speed that provides a comfortable breeze, lower speeds consume less energy. In the winter, reverse the motor and operate the ceiling fan at low speed in the clockwise direction. This produces a gentle updraft, which forces warm air near the ceiling down into the occupied space. Remember to adjust your thermostat when using your ceiling fan - additional energy and dollar savings could be realized with this simple step!
Turn Off When Not in the Room. Ceiling fans cool people, not rooms. If the room is unoccupied, turn off the ceiling fan to save energy.
Page 17
17
ETL Model No.: CF788
Trouble Shooting
WARNING: For your own safety, turn off power at fuse box or circuit breaker before trouble shooting your fan.
TROUBLE PROBABLE CAUSE SUGGESTED REMEDY
1. Fan will not start. 1. Fuse or circuit breaker blown. 1. Check main and branch circuit fuses or circuit
breakers.
2. Loose power line connections to the fan, 2. Check line wire connections to fan and switch
or loose switch wire connections in the wire connections in the switch housing.
switch housing.
WARNING: Make sure main power is
turned OFF.
3. Reversing switch in neutral position. 3. Make sure reversing switch position is all the
way to one side.
4. Fan Wall Control is OFF. 4. Turn ON Fan Wall Control.
2. Fan sounds noisy. 1. Blades not attached to fan. 1. Attach blades to fan before operating.
2. Loose screws in motor housing. 2. Check to make sure all screws in motor housing
are snug (not over-tight).
3. Screws securing fan blade flanges to 3. Check to make sure the screws which attach
motor hub are loose. the fan flanges to the motor hub are tight.
4. Wire connectors inside switch housing 4. Check to make sure wire connectors in switch
rattling. housing are not rattling against each other or
against the interior wall of the switch housing.
WARNING: Make sure main power is
turned OFF.
5. Screws holding blades to flanges 5. Tighten screws securely.
are loose.
3. Fan wobbles 1. Setscrew in motor coupling is loose. 1. Tighten both setscrews securely in the motor
excessively. coupling.
2. Setscrew in hanger ball/downrod 2. Tighten the setscrew in the hanger ball/
assembly is loose. downrod assembly.
3. Screws securing fan blade flanges to 3. Check to be sure screws which attach the fan
motor are loose. blade flanges to the motor are tight.
4. Fan blade flanges not seated properly. 4. Check to be sure the fan blade flanges seat
firmly and uniformly to the surface of the motor.
If flanges are seated incorrectly, loosen the
flange screws and retighten according to the
procedure in the section on "How to Put
Your Ceiling Fan Together".
5. Hanger bracket and/or ceiling outlet 5. Tighten the hanger bracket screws to the outlet
box is not securely fastened. box, and/or secure outlet box.
6. Fan blades out of balance. 6. Interchanging an adjacent (side-by-side) blade
pair can redistribute the weight and result in
smoother operation.
!
!
!
Page 18
18
ETL Model No.: CF788
Repair Parts
20
1
15
4
12
13 14
2
3
16
17
BLADES SOLD SEPARATELY
19
5
6
21
7
8
9
10
11
18
7
Page 19
19
ETL Model No.: CF788
Repair Parts Listing
Key
Model Numbers
No. Description CF788AP00 CF788CK00 CF788GBZ00 CF788ORB00
* Hanger Ball Assembly, 761655-34 761655-23 761655-77 761655-32
Consisting of:
1 Hanger Bracket
2 Hanger Ball
3 Downrod (4.5”)
* Parts Bag Containing: 764086 76408-1 764086 764086
4 Wire Connector (3)
5 Pin, Clevis
6 Clip, Hairpin
7 Screw, Flat Head #8-32 x 12mm (1)
8 Screw, Pan Head
#10-24 x 12mm (21)
9 Flat Washer 16mm OD (21)
10 Screw, Washer Head 1/4-20 x 14mm
11 Lockwasher 6mm (1)
12 Threaded Stud #8-32 x 1-1/4” (2)
13 Lockwasher, #8 External Tooth (2)
14 Knurled Knob, #8-32 (2)
15 Balancing Kit (1)
16 Canopy, Ceiling (1) 763785-AP 763785-CK 763785-GBZ 763785-ORB
17 Motor Coupling Cover (1) 764083-AP 764083-CK 764083-GBZ 764083-ORB
18 Switch Housing (1) 764127-AP 764127-CK 764127-GBZ 764127-ORB
19 Flange (set of 5) 764091-AP 764091-CK 764091-GBZ 764091-ORB
20 Wall Control,Transmitter 6-Speed 764088 764088 764088 764088
21 Control, Receiver 764087 764087 764087 764087
Owner's Manual BP7427-2 BP7427-2 BP7427-2 BP7427-2
Before discarding packaging material, be certain all
parts have been removed.
HOW TO ORDER REPAIR PARTS
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION:
• PART NUMBER • PART DESCRIPTION
• NAME OF ITEM • MODEL NUMBER
For repair parts, phone 1-800-654-3545.
Page 20
Part No. F40BP74270002 Printed in China 10/11 Form No. BP7427-2
Air Comfort Products
DIVISION OF EMERSON ELECTRIC CO.
8100 W. Florissant • St. Louis, MO 63136
LIMITED WARRANTY
What The Warranty Covers:
This warranty covers the motor and the other components and accessories of your Emerson ceiling fan against all defects in workmanship and materials. You must be the original purchaser or user of the product to be covered.
What The Period Of Coverage Is:
As it applies to the motor, this warranty will last for the lifetime of your ceiling fan. All other components and accessories are covered by this warranty for one year from the date you purchased your ceiling fan. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE WITH RESPECT TO COMPONENTS AND ACCESSORIES IS ALSO LIMITED TO ONE YEAR.
What Will Emerson Electric Co. Do To Correct Problems:
Emerson Electric Co. will replace a defective Emerson Air Comfort Ceiling Fan motor, blade, component or other accessory at no charge to you. If repair of the motor or blades is not practical or possible within a reasonable time and no replacement can be provided, Emerson will refund the actual purchase price of your fan. WE WILL SHIP THE REPAIRED PRODUCT OR
REPLACEMENT TO YOU AT NO CHARGE, BUT YOU ARE RESPONSIBLE FOR ALL COSTS OR REMOVAL, REINSTALLATION AND SHIPPING OF THE PRODUCT TO EMERSON ELECTRIC CO.
How Can You Get Service:
YOU MUST HAVE PROOF OF YOUR PURCHASE OF THE CEILING FAN TO OBTAIN LIMITED WARRANTY SERVICE. KEEP YOUR RECEIPT OR OTHER PROOF OF PURCHASE. You can return the product to our factory or to your nearest authorized service center.
• To return the product to the factory, obtain a return authorization and service identification tag by writing to Air Comfort Products, Division of Emerson Electric Electric Co., 8100 W. Florissant Ave., St. Louis, MO 63136. Include all model numbers shown on the product with your request.
• To return the product to an authorized service center, call 1-800-654-3545 for the address of the nearest authorized service center.
You will be responsible for all insurance, freight or other transportation charges to our factory or authorized service center. Your Emerson Air Comfort Ceiling Fan should be properly packed to avoid damage in transit since we will not be responsible for any such damage.
What Is Not Covered:
The glass globes and light bulbs of your ceiling fan are not covered by this warranty. This warranty also does not cover any defects, malfunctions or failures caused by:
• Repairs by persons not authorized by Emerson Electric Co.,
• Use of parts or accessories not authorized by Emerson Electric Co.,
• Mishandling, improper installation, modifications or damage to your ceiling fan while in your possession, or
• Unreasonable use, misuse, abuse, including failing to do reasonable and necessary maintenance, and normal wear and tear.
Additionally, this warranty and any implied warranty of merchantability or fitness for a particular purpose are voided when:
• The original purchaser or user ceases to own the product, or
• The fan is moved from its original point of installation.
This warranty is only valid within the 50 states of the United States and the District of Columbia. No other written or oral warranties apply, and no employee, agent, dealer or other person is authorized to give any warranties on behalf of Emerson Electric Co.
REPAIR, REPLACEMENT OR A REFUND ARE THE EXCLUSIVE REMEDIES AVAILABLE UNDER THIS WARRANTY AND EMERSON IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND, INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGES. Incidental damages include but are not limited to such damages as loss of time and loss of use. Consequential damages include but are not limited to the cost of repairing or replacing other property which was damaged if this product does not work properly.
How State Law Relates To The Warranty:
Some states do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion or limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
ETL Model No.: CF788
Loading...