TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK,
OR INJURY TO PER S O N S , OB SERVE THE
FOLLOWING:
a. Use this unit only in a manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
b. Before servicing or cleaning unit, switch power off
at service pa n e l a n d l o c k service pan e l
disconnecting means to prevent power from being
switched o n a c c i dentally . W h e n the servic e
disconnecting means cannot be locked, securely
fa sten a war ning device, such as a tag, to th e
service panel.
1. Read your owner’s manual carefully and keep it for
future reference.
2. Be car eful of the f a n and blade s when clean ing,
painting, or working near the fan. Always turn off the
power to the ceiling fan before servicing.
3. Do not put anything into the fan blades while they are
turning.
4. Do not operate reversing switch until fan blades have
come to a complete stop.
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off
at the fuse box before wiring, and do not operate fan
without blades.
2. All wiring m ust be in accordance wit h the N ati ona l
Electri c a l Code “A N S I /NFPA 70 - 2 0 14” an d Local
Electrical Codes. Use the National Electrical Code if
Lo cal Codes d o not exis t. The ce iling fan must be
grounded as a precaution against possible electrical
shock. Elect r i c a l in s t a l l ation shoul d be made or
approved by a licensed electrician.
!
Section Page
11. Installing the Glass Shades and Light Bulbs . . . . . . . . .17
3. The outlet box and joist must be securely mounted
and capable of reliably supporting at least 50 pounds.
Use only U.L. outlet boxes listed as “Acceptable for
Fan Support of 22.7 kg. (50 lbs.) or less”, and use the
mounting sc r e w s provid e d w i t h the outlet bo x .
Most outlet boxes commonly used for support of light
fixtures are not acceptable for fan support and may
need to be replaced. Consult a qualified electrician if
in doubt.
4. The downrod furnished with the fan provides the
minimum recommended floor to fan blade clearance
for an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least
7 feet from the floor to prevent accidental contact with
the fan blades.
6. Follow the recommended instructions for the proper
method of wiring your ceiling fan. If you do not know
enough about electrical wiring, have your fan installed
by a licensed electrician.
WARNING: To reduce the risk of electrical shock, this
fan mu s t be install e d with an is o l a t ing wa l l
control/switch.
NOTE: The CF711 fan is suitable for use with solid-state
speed controls.
WARNING: To avoid fire, shock or injury, do not use an
Emerson or any other brand of control not specifically
approved for this fan.
WARNING: This product is designed to use only those
parts supplied with this product and/or any accessories
designated specifically for use this product by Emerson
Electric Co. Substitution of parts or accessories not
designated for use with this product by Emerson could
result in personal injury or property damage.
WARNING: To reduce the risk of personal injury, do not
bend the blade flange when installing the blade flanges,
balancing the blades or cleaning the fan. Do not insert
foreign objects in between rotating fan blades.
NOTE: All setscrews must be checked and re-tightened
where necessary before installation.
DATE CODE:
The date code of this fan may be found on the box, stamped in ink on a white label. You should
record this data above and keep it in a safe place for future use.
U.L. Model No.: 42-ANT & 52-ANT
2
Page 3
1. Unpacking Instructions
G
F
H
I
E
C
B
A
D
1
2
3
7
8
4
5
6
9
WARNING
Do not install or use fan if any part is damaged or
missing. Call Toll-Free:
!
1-800-654-3545
WARNING
This product is des ign ed to use o nly tho se part s
supplied with this product and/or any accessories
designated specifically for use with this product by
Emerson E l e c tric Co. S u b s titutio n o f p arts or
accessories not designated for use with this product
by Emerson Electric Co. could result in personal injury
or property damage.
!
1.1
Open ca r t on cont a ining f a n . Remov e top hal f o f
styrofoam unit. Remove parts and check to see that you
have received the following parts:
NOTE: If you are uncertain of part description, refer
to exploded view illustration.
NOTE: Place the parts from the loose parts bags in
a small container to keep them from being lost.
If a n y p a rts a re m issi n g, c a ll 1 -800 - 654- 3 545
for replacement parts before proceeding.
PACKAGE CONTENTS
Part Description Quantity
A Fan Motor Assembly 1
B Ceiling Cover 1
C Switch Housing Cover 1
D Blade Flanges 5
E Fan Blades 5
F Hanger Bracket 1
G Hanger Ball / Downrod Assembly 1
H Glass Shades (3 or 4)
Remove the fan housing assembly from the protective
plastic bag. Turn the upper styrofoam pad over and
carefully place the fan motor assembly into the recess
in the pad with the top of the motor facing up.
Please contact 1-800-654-3545 for further assistance
3
U.L. Model No.: 42-ANT & 52-ANT
emersonfans.com
Page 4
1. Unpacking Instructions (Continued)
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
Tools Needed for Assembly
One Phillips head screwdriver One stepladder
One 1/4” blade screwdriver One wire stripper
Three wire connectors (supplied)
Four 13W E26 medium base bulbs CFL (CF711) (
Three 13W E26 medium base bulbs CFL (CF710) (supplied)
supplied)
Materials
Wiring outlet box and box connectors must be of type
required by the local code. The minimum wire would be
a 3-conductor (2-wire with ground) of following size:
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
2. Electrical Requirements
WARNING
efore assembling your ceiling fan, refer to section on
B
proper method of wiring your fan (page 11). If you feel
you do not h a v e e n o ugh wirin g k n o w ledge or
experience, have your fan i nst all ed by a licensed
electrician.
!
Controls Sold Separately
SW46 Wall Control and SW90 Wall Control (both sold
separately) may be used with this PRO Series Ceiling
Fan. Controls are recommended for indoor use only.
Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.
WARNING
To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable for
Fan Support of 22.7 kg. (50 lbs.) or less”, and use
screws supplied with outlet box. Most outlet boxes
commonly used for support of light fixtures are not
acceptab l e f o r f a n s u p p o rt a nd may need to be
replaced. Consult a qualified electrician if in doubt.
WARNING
Turning off wall switch is not suffi cient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the c e i l ing f a n must be p r o p erly g r o u nded a s a
precaution against possible electrical shock.
!
!
The outlet box must be securely anchored and capable
of withstanding a load of at least 50 pounds.
If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time and
remove the existing light fixture.
WARNING
To avoid fire or shock, follow all wiring instructions
carefully.
Any e l e c t r ical w o r k no t desc r i b e d in t h e se
instructions should be done or approved by a licensed
electrician.
Plea s e call Eme r s on tech n ica l su p port at
1-800-654-3545 if you have any questions about
installation and operation of this ceiling fan.
!
U.L. Model No.: 42-ANT & 52-ANT
4
Page 5
IMPORTANT
THREE 42"
MOTOR LEADS
CEILING
COVER
HANGER
BALL/3.5"
DOWNROD
ASSEMBLY
THREE 42"
MOTOR LEADS
our c eili n g fa n is d esig n ed t o be i nsta l led e ithe r in t he s t and a rd m a nner , or i n th e
Y
close-to-the-ceiling manner. Using the standard method, the hanger ball/downrod assembly will suspend
the fan several inches below the ceiling cover. Using the close-to-the-ceiling method, the ceiling cover
installs directly on the fan motor housing, thus mounting the fan 3-1/2 inches closer to the ceiling than the
standard method. In no case should the fan blades be lower than seven feet above the floor. Depending
n your desired mounting method, proceed to “INSTALLING HANGER BALL/DOWNROD ASSEMBLY” for
o
standard mounting, or to “INSTALLING CEILING COVER ON FAN MOTOR HOUSING” for close-to-theceiling mounting.
3. Installing the Hanger Ball/Downrod Assembly
(For Standard Mounting)
3.1
Pass the 42” motor leads through the opening in the
ceiling cover.
Be sure the cover is oriented correctly (Figure 1).
3.2
Separate, untwist and unkink the three motor leads.
Route the motor leads through the hanger ball/downrod
assembly (Figure 2).
Figure 1
Figure 2
emersonfans.com
Please contact 1-800-654-3545 for further assistance
5
U.L. Model No.: 42-ANT & 52-ANT
Page 6
3. Installing the Hanger Ball/Downrod Assembly
DOWNROD
C
LEVIS
PIN
HAIRPIN
CLIP
MOTOR
COUPLING
HAIRPIN
C
LIP
CLEVIS
P
IN
LOOSEN
SETSCREWS (2)
MOTOR
COUPLING
HANGER BALL/
DOWNROD
ASSEMBLY
RETIGHTEN
SETSCREW
RETIGHTEN
SETSCREW
(For Standard Mounting) (Continued)
3.3
Loosen the two setscrews in the motor coupling.
Place the hanger ball/downrod assembly into the motor
coupling, aligning the clevis pin holes in the downrod
with the holes in the motor coupling (Figure 3).
The clevis pin must go through the holes in the motor
coupling and the holes in the downrod.
Be sure to push the straight leg of the hairpin clip
through the hole near the end of the clevis pin until the
curved portion of the hairpin clip snaps around the
clevis pin.
The hairpin clip must be properly installed to prevent
the clevis pin from working loose.
Pull on the hanger ball to make sure the clevis pin is
properly installed.
WARNING
It is critical that the clevis pin in the motor coupling is
properly installed. Failure to verify that the pin is
properly installed could result in the fan falling.
!
3.4
While pulling up on the hanger ball, retighten the two
setscrews (previously loosened) in the motor coupling
to secure the hanger ball/downrod assembly into place
(Figure 4).
NOTE: The setscrews must be properly installed as
described above, or fan wobble could result.
WARNING
It is critical that the setscrews are securely tightened.
Fa i lure t o verify that t h e setsc r ews are properl y
installed could result in the fan falling.
!
NOTE : For h a ngin g inst r ucti o ns us i ng
Ha n ger Ball/Down r od Assembly, S e e Page 11,
Sec t i o n 6. Hanging the Ceiling Fan (Sta n d a r d
Method Using Hanger Ball/Downrod).
Figure 3
Figure 4
U.L. Model No.: 42-ANT & 52-ANT
6
Page 7
3. Installing the Hanger Ball/Downrod Assembly
HANGER BALL/
DOWNROD
ASSEMBLY
6 to 9
INCHES
(For Standard Mounting) (Continued)
3.5
The fan comes with blue, black and white leads that are
42” long.
Measure up approximately 6 to 9-inches above top of
hanger ball/downrod assembly (Figure 5).
Cut off excess leads and strip back insulation 1/2-inch
from end of leads.
Figure 5
emersonfans.com
Please contact 1-800-654-3545 for further assistance
7
U.L. Model No.: 42-ANT & 52-ANT
Page 8
4. Installing the Ceiling Cover on the Fan Motor
M
OTOR
HOUSING
SCREWS (3)
MOTOR
HOUSING
REMOVE SCREWS (3)
RUBBER
GASKET
MOTOR
HOUSING
RUBBER GASKET
LARGE HOLES (3)
RUBBER GASKET
SMALL HOLES (3)
INSTALL
RUBBER
GASKET
Housing (For Close-to-the-Ceiling Mounting)
4.1
emove three motor housing screws (every other
R
screw as illustrated) from the top of the motor housing
(Figure 6).
Retain the three motor housing screws for future use.
4.2
Position the rubber gasket (supplied in parts bag) on
the motor housing.
The three small holes in the gasket should center over
the holes in the motor housing where the three screws
were previously removed (Figure 7).
The three large holes in the gasket should center over
the three screws still installed in the motor housing.
ently pry the decorative cap from the ceiling cover
G
(Figure 8).
4.4
Align the holes in the ceiling cover with the holes in the
motor housing and secure using the three screws
previously removed in Step 4.1 (Figure 9).
Figure 8
NOTE: For hanging instructions using Close-to-theCeiling Method, See Page 12, Section 7. Hanging
the Ceiling Fan (Close-to-the-Ceiling Method with
Ceiling Cover Installed on the Motor Housing).
4.5
The fan comes with blue, black and white leads that are
42” long.
Measure up approximately 6 to 9-inches above the
motor coupling (Figure 10).
Cut off excess leads and strip back insulation 1/2-inch
from ends of leads.
Figure 9
Figure 10
emersonfans.com
Please contact 1-800-654-3545 for further assistance
9
U.L. Model No.: 42-ANT & 52-ANT
Page 10
5. How to Hang Your Ceiling Fan
FLOOR
7'
MIN.
CEILING
HANGER BRACKET
LOOSEN TWO
SCREWS
(SUPPLIED
WITH OUTLET BOX)
OUTLET BOX
SLIDE THE HANGER BRACKET
ONTO THE OUTLET BOX
SCREWS, THROUGH THE
T-SLOT
T-SLOT
WARNING
The fan must be hung with at least 7' of clearance from
floor to blades (Figure 11).
WARNING
The outlet box and joist must be securely mounted and
capable of supporting at least 50 lbs. Use only a U.L.
outlet box listed as “Acceptable for Fan Support of
22.7 kg. (50 lbs.) or less”.
WARNING
To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable for
Fan Support of 22.7 kg. (50 lbs.) or less”, and use
screws supplied with outlet box. Most outlet boxes
commonly used for support of light fixtures are not
acceptab l e f o r f a n s u p p o rt a nd may need to be
replaced. Consult a qualified electrician if in doubt.
!
!
!
Figure 11
5.1
Unscrew (but do not remove) the two mounting screws
in the outlet box (Figure 12).
Position the hanger bracket on the outlet box so that
the T-slots in the hanger bracket are aligned with the
outlet box screws.
WARNING
Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the c e i l ing f a n must be p r o p erly g r o u nded a s a
precaution against possible electrical shock.
!
Figure 12
U.L. Model No.: 42-ANT & 52-ANT
10
Page 11
5. How to Hang Your Ceiling Fan(Continued)
HANGER BRACKET
HOOK
SECURELY
TIGHTEN
SCREWS
(one on each side)
CEILING
HANGER
BRACKET
HOOK
TAB
GROOVE
HANGER BALL
NOTE: CEILING COVER, SUPPLY
WIRES AND FAN WIRES OMITTED
FOR CLARITY.
5.2
NOTE: The hanger bracket must be mounted flush
with the ceiling in order for the ceiling cover to
nstall properly. If necessary, use leveling washers
i
(not supp lied) between the outle t box and the
hanger bracket.
Slide the hanger bracket onto the outlet box screws.
Center the bracket over the outlet box a n d t h e n
securely tighten the screws (Figure 13).
WARNING
Hanger bracket must seat firmly against outlet box. If
th e out let box is recesse d, us e lev eling wash ers
between the hanger bracket and the outlet box until
the bracket is flush with the ceiling. If bracket and/or
outlet box are not securely attached, the fan could
wobble or fall.
!
6. Hanging the Ceiling Fan
(Standard Method Using Hanger Ball/Downrod)
6.1
Carefully lift the fan assembly and seat the hanger ball
in the hanger bracket (Figure 14).
The tab on the hanger bracket must seat in the groove
in the hanger ball.
Figure 13
WARNING
Failure to seat tab in groove could cause damage to
electrical wires and possible shock or fire hazard.
WARNING
To avoid fire or shock, do not pinch wires between the
hanger ball/downrod assembly and hanger bracket.
!
!
11
Figure 14
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: 42-ANT & 52-ANT
Page 12
7. Hanging the Ceiling Fan
HANGERBRACKET
HOOK
HOOK ON HANGER BRACKET MUST PASS THROUGH SCREW HOLE
IN CEILING COVER, INSIDE OF BRACKET TO OUTSIDE OF BRACKET
CEILING
COVER
(Close-to-the-Ceiling Method with
Ceiling Cover Installed on the Motor Housing)
7.1
arefully lift the fan assembly up to the hanger bracket.
C
Pass the hook on the hanger bracket (Figur e 15)
through one of the screw holes (not the slots) in the
ceiling cover (Figure 15).
The hook must pass from the inside of the ceiling cover
to the outside. The hook will hold the fan assembly
while connecting the wiring.
WARNING
The hook must pass through the screw hole in the
ceiling cover from the inside to the outside. Any other
hanging method may cause the hook to break and the
fan to fall.
!
Figure 15
U.L. Model No.: 42-ANT & 52-ANT
12
Page 13
8. How to Wire Your Ceiling Fan
G
ROUND
CONDUCTOR
S
UPPLY
LISTED WIRE
CONNECTOR
GREEN WIRE
(GROUND)
FROM
HANGER
BRACKET
GREEN WIRE
(GROUND) FROM
HANGER BALL
LISTED WIRE
CONNECTOR
SUPPLY WHITE
(NEUTRAL)
FAN MOTOR
WHITE WIRE
The following instructions show that the Hanger Ball/Downrod Assembly and the Close-To-The-Ceiling
Assembly wiring instructions are the same.
8.1
If you feel that you do not have enough electrical
wiring knowledge or experience, have your fan
installed by a licensed electrician.
WARNING
Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is turned
off at the main fuse box before wiring. All wiring must
be in accordance with National and Local codes and
the c e i l ing f a n must be p r o p erly g r o u nded a s a
precaution against possible electrical shock.
Connect the green grounding lead from the hanger ball
and the green grounding lead from the hanger bracket
to the grounding conductor of supply (this may be a
bare wire o r wire wit h g reen col o r ed insul a t i on)
(Fig u re 1 6 ). S ecur e ly c onne c t wi r es u sing wire
connectors supplied.
NOTE: When wiring the ceiling fan for close-to-theceiling mounting, there will be no green grounding
lead from the hanger ball.
!
Hanger Ball/Downrod Assembly Shown
Figure 16
WARNING
To avoid possible electrical shock, be sure electricity
is turned off at the main fuse box before wiring.
NOTE: If you are not sure if the outlet box is grounded,
contact a licensed electrician for advice, as it must be
grounded for safe operation.
!
8.2
Securely connect the fan motor white wire to the supply
white (neutral) wire using wire connector supplied
(Figure 17).
Hanger Ball/Downrod Assembly Shown
Figure 17
Please contact 1-800-654-3545 for further assistance
13
emersonfans.com
U.L. Model No.: 42-ANT & 52-ANT
Page 14
8. How to Wire Your Ceiling Fan (Continued)
LISTED WIRE
CONNECTOR
FAN MOTOR
BLACK FAN
WIRE
BLUE
FAN
WIRE
SUPPLY
BLACK
(HOT)
TWO BLACK WIRES
AND ONE BLUE WIRE
WHITE WIRES
GREEN WIRES
8.3
Securely connect the fan motor black wire and blue
wire to the supply black (hot) wire using wire connector
supplied (Figure 18).
8.4
After connections have been made, turn leads upward
and carefully push leads into the outlet box, with the
white and green leads on one side of the outlet box and
blac k le a ds o n t h e o t her sid e of the out l et b ox
(Figure 19).
Hanger Ball/Downrod Assembly Shown
Figure 18
Hanger Ball/Downrod Assembly Shown
WARNING
Check to see that all connections are tight, including
ground, and that no bare wire is visible at the wire
connectors, except for the ground wire. Do not operate
fan until blades are in place. Noise and fan damage
could result.
!
Figure 19
U.L. Model No.: 42-ANT & 52-ANT
14
Page 15
9. Installing the Ceiling Cover
REMOVE LEFT
SCREW AND
LOCKWASHER
ON EACH SIDE
LOOSEN THE RIGHT
SCREW/LOCKWASHER
ON EACH SIDE
CLOSE-TO-THE-CEILING ASSEMBLY
REINSALL LEFT
SCREW AND
LOCKWASHER
ON EACH SIDE
HANGER BRACKET
CEILING COVER
HANGER BALL/DOWNROD ASSEMBLY
CEILING COVER
HANGER
BRACKET
REINSALL LEFT
SCREW AND
LOCKWASHER
ON EACH SIDE
9.1
Remove the left screw and lockwasher from each side
of the hanger bracket (Figure 20) and loosen the other
wo screws.
t
NOTE: When installing the ceiling fan using the
lose-to-the-ceiling method, carefully lift the fan
c
assembly from the hook on the hanger bracket and
proceed as follows.
9.2
Lift the ceiling cover up to the hanger bracket. Engage
the slots in the ceiling cover with the loosened screws
in the bracket and turn the cover counterclockwise
(Figure 21).
Be sure that the lockwashers are between the screw
heads and the ceiling cover.
Install the other two screws and lockwashers; tighten all
screws securely.
Hanger Ball/Downrod Assembly Shown
Figure 20
WARNING
To avoid possible fire or shock, make sure that the
electrical wires are completely inside the outlet box
and not pinched between the ceiling cover and the
ceiling.
!
15
Figure 21
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: 42-ANT & 52-ANT
Page 16
RUBBER GROMMETS
BLADE FLANGE
ALIGNMENT
POST
M5 x 6 WASHER
HEAD BLADE SCREW (3)
FAN BLADE
10.1
CAPTIVE
SCREW (2)
BLADE
FLANGE
ALIGNMENT
SLOT
MOTOR HUB
CHAIN
COUPLER
WOODEN
PENDANT
3-SPEED
SWITCH
PULL CHAIN
LIGHT
FIXTURE
PULL CHAIN
WOODEN
PENDANT
10. Installing the Fan Blades
WARNING
To reduce the risk of personal injury, do not bend the
blade flanges when installing the flanges, balancing
the blades, or cleaning the fan. Do not insert foreign
objects between rotating fan blades.
!
Make sure the three rubber grommets are firmly seated
on each of the blade flanges.
Then mount the blade flanges to the fan blades using
three M5 x 6 washer head blade screws per blade
(Figure 22).
10.2
Mount one blade assembly to the motor hub by mating
the alignment post (Figure 23) of the flange with one of
the alignment slots in the motor hub (Figure 23).
Then tighten the two captive screws in the flange to
secure the flange to the motor hub.
Repe a t t his pr o cedu r e for the ot h er fou r b l ade
assemblies. Make sure all screws are tightened.
Figure 22
Spare captive screw provided in parts bag if needed.
10.3
Cut the speed control switch pull chain and the light
switch pull chain to the desired lengths.
Connect the wood pendants (supplied) to the pull
chains by sliding the pendants (small hole first) onto the
pull chains.
Then attach the chain couplings (supplied) to the end of
the chains and allow the pendants to fall down over the
couplings (Figure 24).
U.L. Model No.: 42-ANT & 52-ANT
Figure 23
Figure 24
16
Page 17
11. Installing the Glass Shades and Light Bulbs
RETAINING
CLIP
SQUEEZE
RETAINING
CLIPS
TOGETHER
AND SLIDE
ON GLASS
SHADE
GLASS
SHADE
13W E26 MEDIUM
BASE BULB CFL
(3 or 4)
SWITCH
HOUSING
LIGHT
FIXTURE
SCREW (3)
LIGHT BULBS
PREVIOUSLY
REMOVED
LIGHT
FIXTURE
REMOVE THE TWO
WIRE CONNECTORS
TO DISCONNECT
WIRES FROM LIGHT
FIXTURE AND THE
SWITCH HOUSING
SWITCH
HOUSING
11.1
To install the glass shade, squeeze the retaining clips
towards the bulb socket and slide on the glass shade
(Figure 25). The spring clips will seat the shade and
secure it in place.
Install a 13W E26 medium base bulb CFL in each of
the light fitter sockets (Figure 25).
To remove the shade, first remove the light bulb from
the socket, then simply pull the shade off using a
twisting motion.
12. Removal of the Light Fixture
Figure 25
12.1
NOTE: In some instances it may be desirable to
install the ceiling fan without the light fixture. If this
is the case, proceed as follows. (You may want to
keep the light fixture for possible future use.)
Light bulbs and glass shades removed.
Remove the three switch housing screws securing the
light fixture (Figure 26).
Retain the three switch housing screws for future use.
12.2
Disconnect the two wire connectors that are securing
the light fixture wires to the swi tch housing wires
(Figure 27).
Retain the wire connectors for future use.
Figure 26
17
Figure 27
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: 42-ANT & 52-ANT
Page 18
12. Removal of the Light Fixture (Continued)
RECONNECT THE TWO
SWITCH HOUSING WIRES
WITH THE PREVIOUSLY
REMOVED WIRE
CONNECTORS
SWITCH
HOUSING
SWITCH HOUSING
COVER
SWITCH HOUSING
TUCK WIRES AND
CONNECTORS INSIDE
SWITCH HOUSING
SWITCH HOUSING
SWITCH HOUSING
COVER
SCREW (3)
SWITCH HOUSING
COVER PLUG SCREW
12.3
Reconnect the two switch housin g wires with the
previously removed wire connectors (Figure 28).
12.4
Tu c k t he wires and connec t o rs inside the switch
housing (Figure 29).
Figure 28
12.5
Replace the switch housing cover using the previously
removed three switch housing screws (Figure 30).
Place the switch housing cover plug screw into the
bottom of the switch housing cover (Figure 30).
WARNING
To avoid possible fire or shock, do not pinch wires
between the switch housing and the switch housing
cover.
!
Figure 29
Figure 30
U.L. Model No.: 42-ANT & 52-ANT
18
Page 19
13. Using Your Ceiling Fan
REVERSING
SWITCH
CHAIN
COUPLER
WOODEN PENDANT
3-SPEED
SWITCH
PULL CHAIN
LIGHT
FIXTURE
PULL CHAIN
WOODEN
PENDANT
13.1
Restore electrical power to the outlet box by turning the
electricity on at the main fuse box.
Check the operation of the fan by gently pulling on the
light switch pull chain.
Your fan is shipped from the factory with the reversing
switch positioned to circulate air downward. If airflow is
desired in opposite direction, turn the fan off and wait
for the blades to stop turning, then slide the reversing
switch to the opposite position, and turn the fan on
again. (Figure 31).
The fan blades will turn in the opposite direction and
reverse the airflow.
Reverse Switch Information
Season Rotation Direction Switch Position
Summer Counter-Clockwise Up
Winter Clockwise Down
Figure 31
13.2
Your fan mod e l is eq u ipp e d wi th a 4- p osit i on,
3-speed pull chain switch (Figure 32). The operating
sequence is as follows:
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: 42-ANT & 52-ANT
Page 22
16. Accessories
eiling Fan/Light Controls (see store or catalog).
C
WARNING
!
Downrod Extension Kits (see store or catalog).
This product is des ign ed to use o nly tho se part s
WARNING
The use of any other control not specifically approved
for this fan could result in fire, shock and personal
njury.
i
!
supplied with this product and/or any accessories
designated specifically for use with this product by
Emerson E l e c tric Co. S u b s titutio n o f p arts or
accessories not designated for use with this product
y Emerson Electric Co. could result in personal injury
b
or property damage.
17. Trouble Shooting
WARNING: FOR YOUR OWN SAFETY TURN OFF POWER AT FUSE BOX OR CIRCUIT BREAKER BEFORE
!
TROUBLE SHOOTING YOUR FAN.
TROUBLE
1.Fan will not start. 1.Fuse or circuit breaker blown. 1. Check main and branch circuit fuses or circuit breakers.
2. Loose power line connections to the fan, 2. Check line wire connections to fan and switch wire
or loose switch wire connections in the connections in the switch housing.
switch housing.
WARNING: Make sure main power is turned off.
3. Reversing switch in neutral position. 3. Make sure reversing switch position is all the way to one
side.
2.Fan sounds noisy. 1. Blades not attached to fan. 1. Attach blades to fan before operating.
2. Screws securing fan blade flanges to 2. Check to make sure the screws which attach the fan
motor hub are loose. flanges to the motor hub are tight.
3. Wire connectors inside switch housing 3. Check to make sure wire connectors in switch housing
rattling. are not rattling against each other or against the interior
wall of the switch housing.
WARNING: Make sure main power is turned off.
4. Motor noise caused by solid-state variable 4. Some fan motors are sensitive to signals from Solid speed control. State variable speed controls. If Solid-State Control
is used and motor noise results choose an alternative
control method.
5. Screws holding blades to flanges are loose. 5. Tighten screws securely.
3.Fan wobbles 1. Setscrews in motor coupling are loose. 1. Tighten both setscrews securely in the motor coupling.
excessively. 2. Setscrew in hanger ball/downrod assembly 2. Tighten the setscrew in the hanger ball/downrod
is loose. assembly.
3. Screws securing fan blade flanges to 3. Check to be sure screws which attach the fan blade
motor are loose. flanges to the motor are tight.
4. Fan blade flanges not seated properly. 4. Check to be sure the fan blade flanges seat firmly and
uniformly to the surface of the motor.
5. Hanger bracket and/or ceiling outlet box 5. Tighten the hanger bracket screws to the outlet box,
is not securely fastened. and/or secure outlet box.
6. Fan blades out of balance. 6. Interchanging an adjacent (side-by-side) blade pair can
redistribute the weight and result in smoother operation.
PROBAB LE CAUSE SUGGESTED REMEDY
PROBAB LE
!
!
U.L. Model No.: 42-ANT & 52-ANT
22
Page 23
Emerson Air Comfort Ceiling Fan Limited Warranty
What The Limited Warranty Covers:
This limited warranty is offered by Air Comfort Products division of Emerson Electric Co. ("Emerson" "we" or "us") located at the address stated below to the original
retail purchaser ("you" or "your") of an Emerson Air Comfort Ceiling Fan product ("Emerson Ceiling Fan") and covers the motor and the other components and
accessories of the Emerson Ceiling Fan against all defects in workmanship and materials.
What The Period Of Coverage Is:
This limited warranty will cover the Emerson Ceiling Fan motor for the expected lifetime of your Emerson Ceiling Fan (when operated in accordance with your Owner's
Manual or other instructions provided by Emerson to you with the Emerson Ceiling Fan). All other components and accessories of the Emerson Ceiling Fan are covered
by this limited warranty for a period of one (1) year from its date of original retail purchase. ANY IMPLIED WARRANTY, INCLUDING WITHOUT LIMITATION, ANY
IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT IS AVAILABLE TO YOU UNDER THE LAWS OF YOUR STATE OR
PROVINCE SHALL COVER THE MOTOR FOR THE EXPECTED LIFETIME OF THE MOTOR (SUBJECT TO PROPER USE), AND FOR ONE YEAR WITH RESPECT TO
COMPONENTS AND ACCESSORIES.
No Other Express or Implied Warranty Applies:
THE LIMITED WARRANTIES PROVIDED ABOVE ARE THE SOLE AND EXCLUSIVE WARRANTIES PROVIDED BY EMERSON TO YOU FOR YOUR EMERSON CEILING
FAN, AND ARE IN LIEU OF ALL OTHER WARRANTIES, WRITTEN OR ORAL, EXPRESS OR IMPLIED, WHETHER ARISING BY OPERATION OF LAW OR OTHERWISE,
WHETHER OR NOT THE PURPOSE HAS BEEN DISCLOSED AND WHETHER OR NOT THE EMERSON CEILING FAN HAS BEEN SPECIFICALLY DESIGNED OR
MANUFACTURED FOR YOUR USE OR PURPOSE. EMERSON HEREBY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE FOR COMPONENTS AND ACCESSORIES AS OF THE EXPIRATION OF
THE ONE YEAR WARRANTY PERIOD FOR SUCH COMPONENTS AND ACCESSORIES. IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE FOR THE MOTOR PORTION OF THE EMERSON CEILING FAN ARE LIKEWISE DISCLAIMED BY EMERSON AT SUCH TIME THAT THE
EXPECTED LIFETIME OF THE EMERSON CEILING FAN UNDER NORMAL USAGE HAS BEEN REACHED. EXCLUSIONS OR LIMITATIONS OF IMPLIED WARRANTIES
MAY VARY FROM STATE TO STATE AND PROVINCE TO PROVINCE SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU.
What We Will Do To Correct Problems:
If during the one (1) year warranty period the motor or any component or accessory of your Emerson Ceiling Fan is defective in materials or workmanship, or if during
the expected lifetime of the Emerson Ceiling Fan (when used in accordance with the User Manual or other instructions) the motor is defective in materials or
workmanship, you must contact Emerson during the applicable warranty period. If the defect is covered by warranty, Emerson will repair or replace the defective
motor, component or other accessory at no charge to you. If repair of the motor, component or accessory is not practical or possible within a reasonable time and no
replacement Emerson Ceiling Fan can be provided, Emerson will refund to you the actual purchase price of your Emerson Ceiling Fan. We will ship the repaired or the
replacement Emerson Ceiling Fan to you at no charge, but you are responsible for all costs of removal and reinstallation of your Emerson Ceiling Fan.
How You Can Receive Warranty Service:
You must be the original retail purchaser and have proof of your purchase of the Emerson Ceiling Fan to obtain your remedy under this limited warranty. You can
return your Emerson Ceiling Fan to your place of purchase, or you can call Emerson Customer Service at 1-800-237-6511 to obtain a return authorization and service
identification tag. In order for us to confirm that your Emerson Ceiling Fan is still under warranty, please retain your receipt or other proof of purchase and have that
information readily available when returning your Emerson Ceiling Fan to your place of purchase, or upon calling Emerson Customer Service. If you call Emerson
Customer Service, prior to your call please be prepared to provide all model numbers shown on your Emerson Ceiling Fan. Once we have processed your return
authorization request, we will provide you with a postage paid return label which should be affixed to the Emerson Ceiling Fan package you ship to the address listed at
the end of this limited warranty. The return label will be sent to the mailing address you provide to us by phone.
What Is Not Covered:
This limited warranty does not extend to and expressly excludes:
• The glass globes and light bulbs of your Emerson Ceiling Fan,
• Loss or damage to the motor or any component or accessory caused by normal wear and tear, rather than due to defects in materials or workmanship,
• Loss or damage resulting from conditions beyond our reasonable control, including without limitation, repairs not made at our factory or authorized service center,
use of parts or accessories not provided to you as part of this warranty by our factory or authorized service center, mishandling, unreasonable use, misuse, abuse,
modifications or other damage caused by you or a third party to your Emerson Ceiling Fan while not in our possession,
• Loss or damage resulting from improper installation, or other failure to comply with instructions in your Owner's Manual.
This limited warranty is deemed null and void upon the occurrence of either of the following events:
• You cease to own the Emerson Ceiling Fan product, or
• The Emerson Ceiling Fan is moved from its original point of installation.
This limited warranty is only valid within the 50 United States, the District of Columbia, and Canada. No other written or oral warranties apply, and no employee, agent,
dealer or other person is authorized to give any warranties on behalf of Air Comfort Products or Emerson Electric Co.
Limitation of Liability
REPAIR, REPLACEMENT OR A REFUND ARE THE EXCLUSIVE REMEDIES AVAILABLE TO YOU UNDER THIS LIMITED WARRANTY. TO THE EXTENT PERMITTED BY
LAW, IN NO EVENT SHALL EMERSON OR ANY EMERSON AUTHORIZED DEALER BE LIABLE FOR ANY INCIDENTAL, SPECIAL, INDIRECT, OR CONSEQUENTIAL
DAMAGES, INCLUDING ANY ECONOMIC LOSS, WHETHER RESULTING FROM NONPERFORMANCE, USE, MISUSE OR INABILITY TO USE THE EMERSON CEILING
FAN OR FOR THE NEGLIGENCE OF EMERSON OR AN EMERSON AUTHORIZED DEALER. EMERSON SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN
PERFORMANCE AND IN NO EVENT, REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTION (WHETHER BASED IN CONTRACT, INFRINGEMENT,
NEGLIGENCE, STRICT LIABILITY, OTHER TORT OR OTHERWISE), SHALL EMERSON'S OR ANY EMERSON AUTHORIZED AGENT'S LIABILITY TO YOU OR ANY
INDIVIDUAL USING THE EMERSON CEILING FAN EXCEED THE PRICE PAID BY THE ORIGINAL OWNER FOR THE EMERSON CEILING FAN. The term "consequential
damages" shall include, but not be limited to, loss of anticipated profits, business interruption, loss of use or revenue, cost of capital or loss or damage to property or
equipment.
How State and Provincial Law Relates To The Warranty:
Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages so the above exclusion or limitation may not apply to you.
This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
23
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: 42-ANT & 52-ANT
Page 24
Air Comfort Products
DIVISION OF EMERSON ELECTRIC CO.
8100 W. Florissant • St. Louis, MO63136
Questions, problems, missing parts: Before returning to the store call
Emerson Electric Customer Service
8 a.m. - 6 p.m., Eastern, Monday-Friday
1-800-654-3545
www.emersonfans.com
Retain this manual for future use.
Part No. F40BP72580009 Form No. BP7258-9
Revision: 150605 U.L. Model No.: 42-ANT & 52-ANT
Printed in China
06/15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.