TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK,
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a. Use this unit only in a manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
b. Before servicing or cleaning unit, switch power off at
service panel and lock service panel disconnecting
means to prevent power from being switched on
accidentally. When the service disconnecting means
cannot be locked, securely fasten a warning device,
such as a tag, to the service panel.
1. Read your owner’s manual carefully and keep it for future
reference.
2. Be careful of the fan and blades when cleaning, painting,
or working near the fan. Always turn off the power to the
ceiling fan before servicing.
3. Do not put anything into the fan blades while they are
turning.
4. Do not operate reversing switch until fan blades have
come to a complete stop.
3. The outlet box and joist must be securely mounted and
capable of reliably supporting at least 50 pounds. Use
only U.L. outlet boxes listed as “Acceptable for Fan
Support of 22.7kg. (50 lbs.) or less”, and use the
mounting screws provided with the outlet box. Most
outlet boxes commonly used for support of light fixtures
are not acceptable for fan support and may need to be
replaced. Consult a qualified electrician if in doubt.
4. The downrod furnished with the fan provides the
minimum recommended floor to fan blade clearance for
an 8 foot ceiling.
5. The fan must be mounted with the fan blades at least
7 feet from the floor to prevent accidental contact with
the fan blades.
6. Follow the recommended instructions for the proper
method of wiring your ceiling fan. If you do not know
enough about electrical wiring, have your fan installed by
a licensed electrician.
NOTE: This fan is suitable for use with solid-state speed
controls.
NOTE: All setscrews must be checked and re-tightened
where necessary before installation.
WARNING
!
Additional Safety Instructions for Installation
1. To avoid possible shock, be sure electricity is turned off
at the fuse box before wiring, and do not operate fan
without blades.
2. All wiring must be in accordance with the National
Electrical Code “ANSI/NFPA 70-2014” and Local
Electrical Codes. Use the National Electrical Code if
Local Codes do not exist. The ceiling fan must be
grounded as a precaution against possible electrical
shock. Electrical installation should be made or
approved by a licensed electrician.
U.L. Model No.: CF500
To reduce the risk of electrical shock, this fan must be
installed with an isolating wall control/switch.
To reduce the risk of fire or electrical shock, this fan
should only be used with fan speed control, Model No.
SW46/U.L. Model No. UDC9020, manufactured by Rhine
Electric Co., Ltd.
This product is designed to use only those parts supplied
with this product and/or any accessories designated
specifically for use this product by Emerson Electric Co.
Substitution of parts or accessories not designated for
use with this product by Emerson could result in
personal injury or property damage.
To reduce the risk of personal injury, do not bend the
blade flange when installing the blade flanges, balancing
the blades or cleaning the fan. Do not insert foreign
objects in between rotating fan blades.
2
1. Unpacking Instructions
B
D
E
F
H
A
G
I
0
4
3
2
1
J
C
10
7
4
3
2
1
6
5
8
9
WARNING
Do not install or use fan if any part is damaged or
missing. Call Toll-Free:
!
1-800-654-3545
WARNING
This product is designed to use only those parts supplied
with this product and/or any accessories designated
specifically for use with this product by Emerson Electric
Co. Substitution of parts or accessories not designated
for use with this product by Emerson Electric Co. could
result in personal injury or property damage.
!
1.1
Check to see that you have received the following parts:
NOTE: If you are uncertain of part description, refer to
exploded view illustration.
HARDWARE CONTENTS
PACKAGE CONTENTS
Part Description Quantity
A Fan Motor Assembly 1
B Hanger Bracket 1
C Hanger Ball / 4.5” Downrod 1
D Ceiling Canopy 1
E Motor Coupler Cover 1
F Fan Blade Flanges 5
G SW46 Wall Control 1
H Switch Housing Adapter 1
I Switch Housing Cover 1
J Fan Blades 5
Part Description Quantity
1 Threaded Studs, #8-32 x 1-1/4” 2
2 Lockwashers, External Tooth, #8 2
3 Knurled Knobs, #8-32 2
4 Clevis Pin 1
5 Hairpin Clip 1
6 Wire Connectors 4
7 Washer Head Screws #10-24 x 9/32” 16
8 Round Head Screw with Lockwasher
1/4-20 x 9/16” (Spare) 1
9 Flat Head Screw #8-32 x 5/16” (Spare) 1
10 Blade Balance Kit 1
NOTE: The loose parts are individually packaged for
ease of installation. Place the parts from the loose
parts bags in a small container to keep them from
being lost. If any parts are missing, contact your local
retailer or catalog outlet for replacement before
proceeding.
1.2
Re move the fan assembly from the protectiv e
plastic bag. Place the fan assembly into the upper foam
pad with the top of the motor facing up.
The upper foam pad serves as a holder for the fan during
the first stages of assembly.
emersonfans.com
Please contact 1-800-654-3545 for further assistance
3
U.L. Model No.: CF500
1. Unpacking Instructions (Continued)
This Manual Is Designed to Make it as Easy as Possible for You to Assemble,
Install, Operate and Maintain Your Ceiling Fan
our Emerson Ceiling Fan comes supplied with a Fan Wall
Tools Needed for Assembly
One Phillips head screwdriver One stepladder
One 1/4” blade screwdriver One wire stripper
Materials
Wiring outlet box and box connectors must be of type
required by the local code. The minimum wire would be a
3-conductor (2-wire with ground) of following size:
Installed Wire Length Wire Size A.W.G.
Up to 50 ft. 14
50-100 ft. 12
Y
Control. This system allows you to regulate your ceiling fan
speed.
This Emerson Ceiling Fan may be used with the following
ac cessories : RCFP /RC188 Receiver and SR4 01/
SR600/SR650 Remote Control and SW650 Wall Control.
WARNING
Before assembling your ceiling fan, refer to section on
proper method of wiring your fan (page 12). If you feel
you do not have enough wiring knowledge or experience,
have your fan installed by a licensed electrician.
!
2. Electrical Requirements
Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and capable of
withstanding a load of at least 50 pounds.
WARNING
To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable for
Fan Support of 22.7kg. (50 lbs.) or less”, and use screws
supplied with outlet box. Most outlet boxes commonly
used for support of light fixtures are not acceptable for
fan support and may need to be replaced. Consult a
qualified electrician if in doubt.
WARNING
Turning off wall switch is not sufficient. To avoid possible
electrical shock, be sure electricity is turned off at the
main fuse box before wiring. All wiring must be in
accordance with National and Local codes and the ceiling
fan must be properly grounded as a precaution against
possible electrical shock.
!
!
If your fan is to replace an existing ceiling light fixture, turn
electricity off at the main fuse box at this time and remove
the existing light fixture.
WARNING
To avoid fire or shock, follow all wiring instructions
carefully.
Any electrical work not described in these
instructions should be done or approved by a licensed
electrician.
Pl ease ca ll Emer son tec hnical support at
1- 800-654-3 545 if you have any qu estions about
installation and operation of this ceiling fan.
!
U.L. Model No.: CF500
4
3. Ceiling Fan Assembly
#10-24 x 9/32" WASHER
HEAD SCREW
FAN BLADE FLANGE
FA N
BLADE
1/4-20 x 9/16" ROUND
HEAD SCREWS WITH
LOCKWASHERS
(2 per blade / flange
BLADE/ FLANGE ASSEMBLY
MOTOR HUB
3.1
NOTE: Intermixing blades and flanges between fans
an cause excessive wobble. Keep blades and flanges
c
in original sets of five.
lace the fan blade on the fan blade flange (Figure 1).
P
Tighten the #10-24 x 9/32” washer head screw to secure
(supplied in parts bag) the fan blade and fan blade flange
(Figure 1).
Repeat this procedure for the other four fan blade flanges
and fan blades.
Make sure all the #10-24 x 9/32” washer head screws are
tighten securely to the fan blade and flange.
3.2
Loosely attach one blade/flange assembly to the motor
hub by securing the two 1/4-20 x 9/16” round head screws
with lockwashers (Figure 2).
Repeat this procedure for the other four blade/flange
assemblies.
Securely tighten all the 1/4-20 x 9/16” round head screws
with lockwashers to the motor hub at this time.
NOTE: Take care not to scratch fan housing when
installing blades.
A spare 1/4-20 x 9/16” round head screw with lockwasher
supplied in parts bag, if needed.
Figure 1
WARNING
To reduce the risk of personal injury, do not bend the
blade flange when installing the blade flanges,
balancing the blades or cleaning the fan. Do not insert
foreign objects in between rotating fan blades.
!
5
Figure 2
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: CF500
3. Ceiling Fan Assembly (Continued)
SWITCH HOUSING COVER
#8-32 x 5/16" FLAT
HEAD SCREWS (3)
FI N I A L
SWITCH HOUSING ADAPTER
ROTATE ADAPTER
CLOCKWISE
#8-32 x 3/8"
ROUND HEAD SCREW
WITH LOCKWASHER
SWITCH HOUSING
ADAPTER
3.3
Remove one #8-32 x 3/8” round head screw with
lockwasher from the motor hub and retain for later use.
Loosen the other two #8-32 x 3/8” round head screw with
ockwasher on the motor hub for the installation of the switch
l
housing adapter.
Place the motor hub connectors through the center hole of
the switch housing adapter.
Place the switch housing adapter onto the motor hub,
aligning the three screw holes (Figure 3).
Rotate the switch housing adapter key hole slots clockwise
to engage both loosened screws (Figure 3).
Reinstall the previous removed #8-32 x 3/8” round head
screw with lockwasher.
Secure the switch housing to the motor hub by tightening the
three switch housing screws.
Figure 3
3.4
Tuck all the wires and wire connectors into the switch
housing adapter.
Remove the three #8-32 x 5/16” flat head screws from the
switch housing adapter and retain for the installation of the
switch housing cover.
Align the three screw holes of the switch housing cover
onto the switch housing adapter (Figure 4).
Reinstall the previous removed #8-32 x 5/16” flat head
screws.
Secure the switch housing cover to the switch housing
adapter by tightening the three switch housing screws
(Figure 4).
A spare #8-32 x 5/16” flat head screw supplied in parts bag,
if needed.
The finial may be removed for use with an Emerson light kit.
Figure 4
U.L. Model No.: CF500
6
3. Ceiling Fan Assembly(Continued)
4.5" DOWNROD
THREE 80" MOTOR
LEADS (UNTWISTED)
MOTOR
COUP L I N G
4.5"
DOWNROD
LOOSEN
PHILLIPS HEAD
SET SCREWS (2)
PHILLIPS HEAD SET SCREW (LOOSENED)
HANGER BALL
4
.5" DOWNROD
P
IN
G
REEN GROUND WIRE
3.5
Carefully turn the partially assembled fan right side up and
place on the styrofoam carton, in preparation for final
nstallation.
i
Remove the hanger ball by loosening the Phillips head set
crew in the hanger ball until the ball falls freely down the
s
downrod (Figure 5).
Remove the pin from the downrod, then remove the
hanger ball (Figure 5).
Retain the pin and hanger ball for reinstallation in
Step 3.11.
3.6
Separate, untwist and unkink the three 80” motor leads.
Route the three 80” black, blue, and white motor leads
through the downrod (Figure 6).
Figure 5
3.7
Loosen the two Phillips head set screws in the motor
coupler for installation of the downrod (Figure 7).
Seat the downrod in the motor coupler (Figure 7).
Rotate and align the downrod holes with all the holes in the
motor coupler (Figure 7).
7
Figure 6
Figure 7
emersonfans.com
Please contact 1-800-654-3545 for further assistance
U.L. Model No.: CF500
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.