Emerson B NG Instruction Manual

Appuyez su
r
le bouton vert
pour mise en
Instruction Manual
/Rok
Patnáctka
/
NTB0704
April 2012 - Rev. 04
Type B NG
V
Conform PED art 3.3 Conforme DESP art 3.3
DESCRIPTION
TYPE B NG REGULATOR
The type B NG i s a two -stage pressure reducin g regulator with an automatic safety device to avoid outlet over-pressure (relief valve venting to atmos­phere) or stopping the gas fl ow in the event of an abnormal drop in inlet or outlet pressure or an excess fl ow condition. Rearming is manual by using the push-button and depending on models (B6 version only) a valve may be associated. A removable vent fi lter is situated in the inlet connec tion, and a vent screen (see sche­matic, item V). The underground model is treated for anti-corrosion and is painted.
Maximum allowable pressure: 5 bar
Operating temperature: -20 / 60°C
Certain conditions apply for usage outside these ranges.
INSTALLATION
CAUTION
• To be used with clean, dry and non-corrosive gas.
• All regulators, except for un derground version, must be protected from direct contact of water and corrosive atmosphere du e to construction materials base with zinc, copper and aluminium (cabinet installation recommended).
• Recommended installation positions : inlet and/ or outlet in vertical position.
• To avoid: vent facing upwards, without protector or connector, in humid conditions (risk of water penetration due to rain or condensation).
Volumn
Gas Type Density Weight kg/m3 B6 B10
Manufactured gas (n)m3/h
• Butane air 1.20 1.552 11 4 7
• Propane air 1.15 1.487 11 4 7
Natural gas (n)m3/h
• Group L 0.64 0.827 27 6 10
• Group H 0.61 0.789 21 6 10
LP-gas kg/h
• Propane 1.56 2.017 37 7.2 12
Before connecting :
• Do not weld the inlet and outlet connections with the regulator in place.
• Remove the protective capsules from the inlet and outlet connections.
• Ensure that the pipeline is perfectly clean.
• Place the O-ring(s), (according to model) greasing is recommended.
Connection
• Respect the gas fl ow direction indicated on the regulator body.
• Respect the tightening torques by using a dyna­mometric wrench (inlet with tight shutoff metal = 40 Nm, others according to O-ring used).
WARNING
Do not re-orientate the regulator after tight­ening connections, under no circumstances should the r egulator be put under any geo­metr ical or dimen sional cons ecutive for ce between inlet and outlet sides.
When connecting the vent (residential areas, underground) the diameter used should not be inferior to 10 mm and should not be obstructed.
COMMISSIONING OR REARMING
Close the downstream valve (if exis tent). Open the upstream valve. Press on the green button for a few seconds, then release. Open the downstream valve (if existent).
Pressure Setpoint
Pds (mbar)
Nominal Flow
1