Emerson Bettis Q-Series, Bettis QC4124VDC, Bettis QC42115VAC, Bettis QC43230VAC Installation Manual

Installation Guide Bettis Q-Series
DOC.IG.BQC41.1 Rev. 3 August 2018
Bettis Integrated Control Modules
QC41 24VDC QC42 115VAC QC43 230VAC
Bettis Q-Series Installation Guide
August 2018 DOC.IG.BQC41.1 Rev. 3
1 Applicable Control modules:
QC41 - 24VDC - Weather Proof
- Explosion Proof / Flame proof QC42 - 115VAC - Weather Proof
- Explosion Proof / Flame proof QC43 - 230VAC - Weather Proof
- Explosion Proof / Flame proof
Note:
Both executions can be equipped with one or two pilot valves: * One pilot valve is default and suitable for normal
operation of double acting or spring return actuators.
* Two pilot valves are required for Fail in Last
Position function on double acting actuators.
The enclosures of both Weather Proof and Explosion Proof / Flame proof modules, have a IP66 or NEMA 4X, ingress protected rating.
2 Before starting
* Actuator must be isolated both pneumatically
and electrically before any (dis)assembly is begun.
* Installation, adjustment, putting into service,
use, assembly, disassembly and maintenance of the control module must be done by qualified personnel.
* Be sure that the actuator is correctly mounted
before connecting air supply and electrical wiring (see Installation & Operation Manual Bettis Q-Series Valve Actuator, DOC.IOM.BQ.E)
* Check the module label for the right execution
(see figure 2.2)
* Check the type of actuator: single or double
acting (see figure 2.2).
* For mechanical installation of the module see
installation instruction leaflet DOC.QC4.MTI.1, as shipped with the module.
2.1 Intended use
The Bettis Q-Series actuator is an integrated concept for the automation of quarter turn valves, dampers or other quarter turn applications. It consists of two basic parts (see figure 2.1):
1. Pneumatic actuator
2. Control Module The control module allows operation of the actuator and supplies position feedback signals.
Fig. 2.1 Check proper mounting before connecting air
supply and electrical wiring.
2
Control Module Type Label = 24VDC
QC41..WP.. = Weather Proof QC41..Px.. = Explosion-/Flame proof
115VAC
QC42..WP.. = Weather Proof QC42..Px.. = Explosion-/Flame proof
230VAC
QC43..WP.. = Weather Proof QC43..Px.. = Explosion-/Flame proof
Actuator Type Label = QS xxxx = Single acting (Spring Return) QD xxxx = Double acting
Fig. 2.2 Identification
Installation Guide Bettis Q-Series
DOC.IG.BQC41.1 Rev. 3 August 2018
2.2 Mechanical alignment and mounting of the control module
The control module is equipped with an alignment­edge on top of the module. This allows easy alignment and mounting of the control module on to the actuator housing.
Procedure: (see figure 2.3)
1. First take care that both mating faces from the
actuator and control module are clean and free of dirt.
2. Check if the module has the required function
3. Remove the transparent film from the control
module.
4. Ensure seals are placed correctly.
5. Level the screws with the surface.
6. Place the alignment-edge (1) of the control
module at the top of the pneumatic interface.
7. Flip the module down taking care that the IPT
Probe (see fig 5; nr.2) on the actuator fits in the mating hole on the control module and loosely place the screws.
8. Tighten screws according force in sequence.
Tightening moments
The Control Module should be fastened by using an Allen key and applying the following tightening moments:
- Allen Key No 5: 6.1 to 6.6 Nm (54 - 58.4
In.lbs)
Alignment-edge
Alignment-edge
IPT probe
Fig. 2.3 Alignment and mounting of control
module to actuator
3
Bettis Q-Series Installation Guide
August 2018 DOC.IG.BQC41.1 Rev. 3
3 Pneumatic connections
IMPORTANT
1 The actuator/valve combination can move
after connecting the air supply.
2 Ensure that the QC4x control modules are
mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
3 Check that the maximum supply pressure
P
= 8bar/116Psi
max
4 Be sure that the minimum required supply
pressure for the application is available at the actuator.
5 Take appropriate measures to prevent
condensation or moisture to entering the actuator or the control module. Condensation or moisture can damage these components and can result in failures.
6 The exhaust ports Ra and Rb on the module
(see figure 3.1) are shipped from the factory with transport protection.
* If ingress protection IP66 or NEMA 4X is
required, appropriate connections must be used in exhaust ports Ra & Rb.
3.1 Operating media :
* Air or inert gasses. * Air filtered at 50 micron. * Dew point 10 K below operating temperature. * For subzero applications take appropriate
measures.
3.2 Single acting (spring return) or Double acting actuator :
1 Remove the transport sticker from the air supply
(Ps).
2 Connect air supply to port (Ps).
Single acting
Control Module cover
Double acting
Fig. 3.1 Pneumatic connections
Ra
Ps 1/4” BSP or 1/4” NPT
Ra
Rb
Ps 1/4” BSP or 1/4” NPT
4
Installation Guide Bettis Q-Series
DOC.IG.BQC41.1 Rev. 3 August 2018
4 Electric Connections
The conventional Control Module contains a pilot valve for controlling the actuator and switches for position feedback.
WARNING:
* If the Control Module is used in a manner not
specified by the manufacturer, the protection provided by the equipment may be impaired.
* For electrical safety the marked protective
conductor terminal inside or outside the Control Module housing shall be connected to earth.
* If required, mount earth wire (1) between top
(2) and stainless steel washer (3) of earth wire connection (see figure 4.2).
* To fulfill the electrical safety regulations
according IEC 61010-1, a switch and circuit­breaker shall be included in the building installation. It is advised to indicate the location of the circuit breaker by means of a label on or nearby the installed Bettis Q-Series modules. The disconnection switch or circuit breaker shall disconnect all current-carrying conductors.
* Heat resistant cable and cable glands shall be
used, suitable for temperatures of at least 80°C
* Use and mount cable glands as required by
national or local legislation.
* If IP66 or NEMA 4X ingress protection is
required, then the electrical entries must be fitted with devices rated IP66 or NEMA 4X.
Electrical safety requirements:
Use In- and outdoor.
Altitude
Maximum rela­tive humidity
Mains supply fluctuation Over voltage category
Pollution degree 2 (3 when the cover remains closed) Temperature see table 4.1
Operating full power available up to 2000 meter (6000 feet). 80% for temperatures up to 31°C (87.8°F) decreasing linearly to 50% relative humidity at 40°C (104°F).
up to ±10% of nominal voltage
II
Caution! :
Risk of electric shock
* Installation, adjustment, putting into service,
use, assembly, disassembly and maintenance of the control module is strictly reserved to qualified personnel.
* Do not attempt to install or repair any electric
device without shutting off incoming power.
Terminals
Lockable Module cover
Electrical entries:
3/4”NPT or M25
1/2”NPT or M20
Switch terminals
Control Module Type Label
Pilot valve terminals
Option: Manual control
Option: Additional manual control for “Fail in Last Position”
Fig. 4.1 Terminal connections behind cover.
Fig. 4.2 Earth wire connection
5
Bettis Q-Series Installation Guide
August 2018 DOC.IG.BQC41.1 Rev. 3
4.1 Bettis Q-Series QC4x modules Hazardous Area instructions
IMPORTANT
All installation, inspection, maintenance and
repair of the equipment should be performed by suitably trained personnel.
The Control Modules must not be used in
atmospheres that contains acetone, ethyl acetate or acetic acid vapors.
4.1.1 ATEX/IECEx Intended use
The Control Modules QC4x..P5.. of the Bettis Q-Series pneumatic actuator is a Group II category 2 (ATEX) equipment with protection level Gb, Db (IECEx) and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapors, mists or by air/dusts are likely to occur. The pneumatic actuator part, together with the pneumatic module part of the Bettis Q-Series pneumatic actuators is a Group II category 2 equipment and intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapors, mists or by air/dusts are likely to occur. Therefore it may be used in hazardous area classified Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
Control Module Type Label =
QC41·MP5MSA1·0040UQP000
Pneumatic action Switch cartridge
Fig. 4.4 Switch cartridge and pneumatic action identification
4.1.2 Hazardous area Special safety instructions
for safe use
1. For ATEX, all installation, inspection,
maintenance and repair must be done by suitably trained personnel. For information refer to EN60079-14, EN60079-17, EN60079-19.
2. Substitution of component may impair
suitability for Zone 2 Increased Safety.
3. Do not open cover of terminal compartment
when an explosive atmosphere is present.
4. Cleaning this housing by rubbing should be done in a non-hazardous area,
5. Potential electrostatic charging hazard, clean only with a damp cloth - danger of propagating discharge.
6. The apparatus shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid flow of dust is avoided.
7. All grounding and bonding installation requirements must be addressed.
8. The cable entry device and the closing elements of unused apertures must be of a certified flameproof type, suitable for the conditions of use and correctly installed.
9 Blind plugs or cable gland shall be engaged
into the cable entries minimal 5.5 threads for M20x1.5 entries and minimal 5 threads for NPT entries.
10. Certified Ex t cable glands shall be use in a dust environment.
11. Heat resistant cable and cable glands shall be used, suitable for temperatures of at least 80°C
12. The maximum temperature of the supply air must stay below the maximum ambient temperature as marked on the control module (see table 4.1).
13. The maximum temperature of the base actuator must stay below the maximum ambient temperature as marked on the control module (see table 4.1).
14. Contact your local Emerson representative for information on the dimensions of the flame proof joints.
15.Precaution shall be taken to avoid danger of ignition due to electrostatic charges on the marking plate of the enclosure.
4.1.3 FM Special safety instructions
1. Metric entries are not allowed. Metric entries are for IECEx or ATEX installations only.
2. Wiring must be done according NEC 500.
Note:
This product is only intended for use in large-scale fixed installations excluded from the scope of Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS 2).
6
Loading...
+ 14 hidden pages