Emerson ASCO 336 Technical Specifications

SUGGESTED SPECIFICATION
Low Voltage (600V) Generator Paralleling Switchboard
1.1 Scope
A. The intent of this specification is to provide power control for the parallel operation of __
generator units (up to 4) rated ___ KW at __ power factor, ___ volts, 3 phase, __ wire, [50 | 60] Hertz. [If they are all different KW’s, list them separately.] All components and testing specified or required for a complete operable system shall be included.
1.2 Application Codes and Standards
A. UL 891 – Switchboards B. ISO 9001:2008 – Requirements of a Quality Management System
1.3 Manufacturer’s Qualifications
for
Automatic Transfer Switches, Bypass Switches, Paralleling Switchboards and Switchgear, Monitoring and Control shall be supplied by ASCO. The equipment described, as a minimum, shall meet all of the requirements specified in this section. The equipment shall be the product of a manufacturer who has produced paralleling electrical equipment for a period of no less than 50 years. The manufacturer must provide integral electrical and mechanical design, fabrication and construction services for all cubicle structures, formed and punched bus bar, and control panel assemblies. Comprehensive documentation detailing electrical and mechanical designs shall be available upon request. The manufacturer must be certified under ISO 9001.
1.4 Order Management
Management of orders shall be assigned to personnel employed and trained specifically and exclusively for project management; the use of field service representatives, design engineers or sales representatives for order management purposes shall not be acceptable. Each order shall be managed by both a factory-based project manager and a factory-direct field-based project manager.
1.5 Documentation
A. Submittals for approval shall include the following:
ASCO Power Technologies, Florham Park, New Jersey 07932. 800-800-ASCO www.EmersonNetworkPower.com/ASCO
8-2014 1 Publication 3279
B. [Optional: One complete set of as-installed, engine and switchboard interconnect
C. Electronic docu mentation shall include:
1.6 Testing
The equipment shall be fully assembled for factory testing. Testing shall include, but not be
1. Elevation drawings with shipping splits identified and estimated weights.
2. Outline drawings showing conduit entry areas and anchoring information.
3. Single line diagram.
4. User Manual (including description of operation).
5. Complete bill of material listing items by manufacturer’s name, part number and
description.
drawings, and material summary shall be provided following installation.]
1. Complete Drawings, Layouts and Schematics.
2. Material Summary.
3. Component Instruction.
4. User Manual (including Description of Operation).
5. Installation Manual.
limited to three phase 5A secondary injection testing of the current circuits. The Closed Transition Transfer Switch mechanisms supplied shall be electrically and mechanically tested. A narrative of the system operation shall be provided and shall be utilized when testing the equipment. A certified factory test report shall be furnished to verify system testing if requested.
1.7 Warranty and Service
A. Manufacturer shall warrant the equipment for eighteen months subject to terms and
conditions of manufacturer’s current warranty publication.
B. Manufacturer shall have an established network of service centers capable of servicing
the equipment.
C. Service representatives shall be on call 24 hours a day, 365 days a year. Personnel shall
be factory trained and certified in the maintenance and repair of the specified equipment.
D. Post-warranty service contracts shall be made available to the owner by the manufacturer
to provide scheduled maintenance and/or emergency repair of the equipment.
1.8 General Requirements
A. Switchboard Enclosure
ASCO Power Technologies, Florham Park, New Jersey 07932. 800-800-ASCO www.EmersonNetworkPower.com/ASCO
8-2014 2 Publication 3279
1. Structure. The enclosure shall be free-standing and floor supported, with front and/or
rear access as specified. An adequate number of anchor bolt holes shall be designed to place the base in direct contact with the foundation when bolted. The flatness of the floor surface upon which the equipment is installed shall deviate no more than
0.125 inches per 10 feet in any direction. All doors shall be formed from sheet stock, provided with sufficient hinges to support the door, and able to swing open more than 90 degrees. Front doors shall be supplied with a lockable handle. Rear doors, if applicable, shall be supplied. All door locks shall be keyed alike, with one key supplied for each lock. All panel covers shall be formed type, and secured with screws as necessary. The sheet steel used for the finished assembly shall be degreased and thoroughly cleaned through a minimum five stage aqueous process. The finish shall be ANSI-61, light gray, electrostatically charged powder paint over a phosphate coating, at an average of 2.0 mils thick. Finish shall be suitable for indoor and outdoor environments, enclosure Type as specified.
2. Bus. Distribution main bus shall be silver plated copper and have a maximum
current density of 1000 amperes per square inch. Main bus shall be rated for [1200 | 3000 | 4000] amperes and braced appropriately.
3. Wiring. Control wiring shall be UL 1015 rated for 600 volt. Current transformer
wiring terminations, where applicable, shall be ring type; shorting terminal blocks shall be included where applicable. Control wires shall include identification every eight (8) inches or less, permanently marked with wire designations. These designations shall include the device and connection point where the wire is terminated. All wire markings shall be permanent and not noticeably fade or smudge. Low level signal circuits shall be separated and provided with shielded wire to minimize electromagnetic interference. Shielded wire shall be grounded at one point. Ethernet cabling shall be unshielded category 5 or higher. Wires shall be placed in wire duct or harnessed, and shall be supported to prevent sagging or breakage from weight or vibration. Communication cables and current transformer circuits shall be hard wired.
ASCO Power Technologies, Florham Park, New Jersey 07932. 800-800-ASCO www.EmersonNetworkPower.com/ASCO
8-2014 3 Publication 3279