Emerson ASCO 185SE Technical Specifications

SUGGESTED SPECIFICATION
Optional Standby Power Generator Systems
PART 1 GENERAL
1.01 Scope
A. Furnish and install automatic transfer switches (ATS) with number of poles,
amperage, voltage, and withstand and close-on current ratings as shown on the plans. Each automatic transfer shall consist of an inherently double throw power transfer switch unit and a microprocessor controller, interconnected to provide complete automatic operation. All transfer switches and controllers shall be the product of the same manufacturer.
B. Furnish an enclosure for the ATS that is for service entry. It shall provide all of the
proper disconnecting, protection, grounding and bonding required for service entrance equipment.
1.02 Acceptable Manufacturers
Service Entrance Automatic transfer switches shall be ASCO Series 185SE. Any alternate shall be submitted in writing at least 10 days prior to bid. Each alternate bid must list any deviations from the specification.
1.03 Codes and Standards
The automatic transfer switches and controls shall conform to the requirements of:
A. UL 1008 - Standard for Automatic Transfer Switches
for
B. CSA – Listed to CSA 22.2
C. NFPA 70 - National Electrical Code
D. International Standards Organization ISO 9001: 2000 E. UL 508 Industrial Control Equipment F. IEC 947-6-1 Automatic Transfer Switches G. NEMA Standard ICS 10 Standard for Automatic Transfer Switches
ASCO Power Technologies, Florham Park, New Jersey 07932 800-937-ASCO www.ascopower.com
01-2009
1 Publication 3208
PART 2 PRODUCTS
2.01 Mechanically Held Transfer Switch A. The transfer switch unit shall be electrically operated and mechanically held. The
electrical operator shall be a momentarily energized, single-solenoid mechanism. Main operators which include overcurrent disconnect devices, or linear motors shall not be acceptable. The switch shall be mechanically interlocked to ensure only two possible positions, normal or emergency.
B. The switch shall be positively locked and unaffected by momentary outages so that
contact pressure is maintained at a constant value and temperature rise at the contacts is minimized for maximum reliability and operating life.
C. All main contacts shall be silver alloy composition. D. Inspection of all contacts shall be possible from the front of the switch without
disassembly of operating linkages and without disconnection of power conductors. A manual operating handle shall be provided for maintenance purposes. The handle shall permit the operator to manually stop the contacts at any point throughout their entire travel to inspect and service the contacts when required.
E. Designs utilizing components of molded-case circuit breakers, contactors, or parts
thereof which are not intended for continuous duty, repetitive switching or transfer between two active power sources are not acceptable.
F. Where neutral conductors are to be solidly connected, a neutral terminal plate with
fully-rated AL-CU pressure connectors shall be provided.
2.02 Microprocessor Controller with Membrane Interface Panel A. The controller shall direct the operation of the transfer switch. The controller's
sensing and logic shall be controlled by a built-in microprocessor for maximum reliability and minimum maintenance. The controller shall be connected to the transfer switch by an interconnecting wiring harness. The harness shall include a keyed disconnect plug to enable the controller to be disconnected from the transfer switch for routine maintenance.
B. The controller shall be self contained and be mounted separate from the transfer
switch unit for safety and ease of maintenance. Sensing and control logic shall be provided on a printed circuit board.
C. The controller shall meet or exceed the requirements for Electromagnetic
Compatibility (EMC) as follows:
1. IEC 1000-4-2 (1995) – Electrostatic Discharge Immunity
2. IEC 1000-4-3 (1995) – Radiated EM Field Immunity
3. IEC 1000-4-4 (1995) – Electrical Fast Transient Immunity
4. IEC 1000-4-5 (1995) – Surge Immunity
5. IEC 1000-4-6 (1995) – Conducted RF Disturbance Immunity
6. EN 55011 – Radiated and Conducted Emissions
7. EMC Directive 93/68/ECC CISPR Class A
ASCO Power Technologies, Florham Park, New Jersey 07932 800-937-ASCO www.ascopower.com
01-2009 2 Publication xxxx